- Home
- BACnet points lists
- Contemporary Controls
- Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Lighting control panel (remote-operated breakers) · BACnet points list
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Pow-R-Command panel: 464 objects (64 AI, 208 BI, 192 BO), 320 polled by default. For up to 64 breakers it has a writable peer coil (BO) plus read-only command, feedback and alarm coil bits; further unpolled bits and registers cover condition codes, schedules, input override timers and load egress timers.
This page lists 464 BACnet objects for the Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX — 192 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
- Equipment
- Lighting control panel (remote-operated breakers)
- Equipment type
- Other equipment
- BACnet objects
- 464 (192 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Write the peer coil for each breaker you switch and read its feedback coil; watch the alarm coils.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Peer Coils Breaker 01 | Breaker 01 peer coil (writable) | Command |
| BI 193 | Feedback Coils Breaker 01 | Breaker 01 feedback (state) | Read |
| BI 289 | Alarm Coils Breaker 01 | Breaker 01 alarm | Read |
| BO 2 | Peer Coils Breaker 02 | Breaker 02 peer coil (writable) | Command |
| BI 194 | Feedback Coils Breaker 02 | Breaker 02 feedback (state) | Read |
| BI 290 | Alarm Coils Breaker 02 | Breaker 02 alarm | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Check the Pow-R-Command documentation for how peer coils interact with the panel's own schedules before the BMS takes over a breaker.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Peer Coils Breaker 01 | Modbus 000001 | Command | ||
| BOmin | 2 | Peer Coils Breaker 02 | Modbus 000002 | Command | ||
| BO | 3 | Peer Coils Breaker 03 | Modbus 000003 | Command | ||
| BO | 4 | Peer Coils Breaker 04 | Modbus 000004 | Command | ||
| BO | 5 | Peer Coils Breaker 05 | Modbus 000005 | Command | ||
| BO | 6 | Peer Coils Breaker 06 | Modbus 000006 | Command | ||
| BO | 7 | Peer Coils Breaker 07 | Modbus 000007 | Command | ||
| BO | 8 | Peer Coils Breaker 08 | Modbus 000008 | Command | ||
| BO | 9 | Peer Coils Breaker 09 | Modbus 000009 | Command | ||
| BO | 10 | Peer Coils Breaker 10 | Modbus 000010 | Command | ||
| BO | 11 | Peer Coils Breaker 11 | Modbus 000011 | Command | ||
| BO | 12 | Peer Coils Breaker 12 | Modbus 000012 | Command | ||
| BO | 13 | Peer Coils Breaker 13 | Modbus 000013 | Command | ||
| BO | 14 | Peer Coils Breaker 14 | Modbus 000014 | Command | ||
| BO | 15 | Peer Coils Breaker 15 | Modbus 000015 | Command | ||
| BO | 16 | Peer Coils Breaker 16 | Modbus 000016 | Command | ||
| BO | 17 | Peer Coils Breaker 17 | Modbus 000017 | Command | ||
| BO | 18 | Peer Coils Breaker 18 | Modbus 000018 | Command | ||
| BO | 19 | Peer Coils Breaker 19 | Modbus 000019 | Command | ||
| BO | 20 | Peer Coils Breaker 20 | Modbus 000020 | Command | ||
| BO | 21 | Peer Coils Breaker 21 | Modbus 000021 | Command | ||
| BO | 22 | Peer Coils Breaker 22 | Modbus 000022 | Command | ||
| BO | 23 | Peer Coils Breaker 23 | Modbus 000023 | Command | ||
| BO | 24 | Peer Coils Breaker 24 | Modbus 000024 | Command | ||
| BO | 25 | Peer Coils Breaker 25 | Modbus 000025 | Command | ||
| BO | 26 | Peer Coils Breaker 26 | Modbus 000026 | Command | ||
| BO | 27 | Peer Coils Breaker 27 | Modbus 000027 | Command | ||
| BO | 28 | Peer Coils Breaker 28 | Modbus 000028 | Command | ||
| BO | 29 | Peer Coils Breaker 29 | Modbus 000029 | Command | ||
| BO | 30 | Peer Coils Breaker 30 | Modbus 000030 | Command | ||
| BO | 31 | Peer Coils Breaker 31 | Modbus 000031 | Command | ||
| BO | 32 | Peer Coils Breaker 32 | Modbus 000032 | Command | ||
| BO | 33 | Peer Coils Breaker 33 | Modbus 000033 | Command | ||
| BO | 34 | Peer Coils Breaker 34 | Modbus 000034 | Command | ||
| BO | 35 | Peer Coils Breaker 35 | Modbus 000035 | Command | ||
| BO | 36 | Peer Coils Breaker 36 | Modbus 000036 | Command | ||
| BO | 37 | Peer Coils Breaker 37 | Modbus 000037 | Command | ||
| BO | 38 | Peer Coils Breaker 38 | Modbus 000038 | Command | ||
| BO | 39 | Peer Coils Breaker 39 | Modbus 000039 | Command | ||
| BO | 40 | Peer Coils Breaker 40 | Modbus 000040 | Command | ||
| BO | 41 | Peer Coils Breaker 41 | Modbus 000041 | Command | ||
| BO | 42 | Peer Coils Breaker 42 | Modbus 000042 | Command | ||
| BO | 43 | Peer Coils Breaker 43 | Modbus 000043 | Command | ||
| BO | 44 | Peer Coils Breaker 44 | Modbus 000044 | Command | ||
| BO | 45 | Peer Coils Breaker 45 | Modbus 000045 | Command | ||
| BO | 46 | Peer Coils Breaker 46 | Modbus 000046 | Command | ||
| BO | 47 | Peer Coils Breaker 47 | Modbus 000047 | Command | ||
| BO | 48 | Peer Coils Breaker 48 | Modbus 000048 | Command | ||
| BO | 49 | Peer Flags General Purpose Flags 01 | Modbus 000049 | Command | ||
| BO | 50 | Peer Flags General Purpose Flags 02 | Modbus 000050 | Command | ||
| BO | 51 | Peer Flags General Purpose Flags 03 | Modbus 000051 | Command | ||
| BO | 52 | Peer Flags General Purpose Flags 04 | Modbus 000052 | Command | ||
| BO | 53 | Peer Flags General Purpose Flags 05 | Modbus 000053 | Command | ||
| BO | 54 | Peer Flags General Purpose Flags 06 | Modbus 000054 | Command | ||
| BO | 55 | Peer Flags General Purpose Flags 07 | Modbus 000055 | Command | ||
| BO | 56 | Peer Flags General Purpose Flags 08 | Modbus 000056 | Command | ||
| BO | 57 | Peer Flags General Purpose Flags 09 | Modbus 000057 | Command | ||
| BO | 58 | Peer Flags General Purpose Flags 10 | Modbus 000058 | Command | ||
| BO | 59 | Peer Flags General Purpose Flags 11 | Modbus 000059 | Command | ||
| BO | 60 | Peer Flags General Purpose Flags 12 | Modbus 000060 | Command | ||
| BO | 61 | Peer Flags General Purpose Flags 13 | Modbus 000061 | Command | ||
| BO | 62 | Peer Flags General Purpose Flags 14 | Modbus 000062 | Command | ||
| BO | 63 | Peer Flags General Purpose Flags 15 | Modbus 000063 | Command | ||
| BO | 64 | Peer Flags General Purpose Flags 16 | Modbus 000064 | Command | ||
| BO | 65 | Priority Coils Breaker 01 | Modbus 000065 | Command | ||
| BO | 66 | Priority Coils Breaker 02 | Modbus 000066 | Command | ||
| BO | 67 | Priority Coils Breaker 03 | Modbus 000067 | Command | ||
| BO | 68 | Priority Coils Breaker 04 | Modbus 000068 | Command | ||
| BO | 69 | Priority Coils Breaker 05 | Modbus 000069 | Command | ||
| BO | 70 | Priority Coils Breaker 06 | Modbus 000070 | Command | ||
| BO | 71 | Priority Coils Breaker 07 | Modbus 000071 | Command | ||
| BO | 72 | Priority Coils Breaker 08 | Modbus 000072 | Command | ||
| BO | 73 | Priority Coils Breaker 09 | Modbus 000073 | Command | ||
| BO | 74 | Priority Coils Breaker 10 | Modbus 000074 | Command | ||
| BO | 75 | Priority Coils Breaker 11 | Modbus 000075 | Command | ||
| BO | 76 | Priority Coils Breaker 12 | Modbus 000076 | Command | ||
| BO | 77 | Priority Coils Breaker 13 | Modbus 000077 | Command | ||
| BO | 78 | Priority Coils Breaker 14 | Modbus 000078 | Command | ||
| BO | 79 | Priority Coils Breaker 15 | Modbus 000079 | Command | ||
| BO | 80 | Priority Coils Breaker 16 | Modbus 000080 | Command | ||
| BO | 81 | Priority Coils Breaker 17 | Modbus 000081 | Command | ||
| BO | 82 | Priority Coils Breaker 18 | Modbus 000082 | Command | ||
| BO | 83 | Priority Coils Breaker 19 | Modbus 000083 | Command | ||
| BO | 84 | Priority Coils Breaker 20 | Modbus 000084 | Command | ||
| BO | 85 | Priority Coils Breaker 21 | Modbus 000085 | Command | ||
| BO | 86 | Priority Coils Breaker 22 | Modbus 000086 | Command | ||
| BO | 87 | Priority Coils Breaker 23 | Modbus 000087 | Command | ||
| BO | 88 | Priority Coils Breaker 24 | Modbus 000088 | Command | ||
| BO | 89 | Priority Coils Breaker 25 | Modbus 000089 | Command | ||
| BO | 90 | Priority Coils Breaker 26 | Modbus 000090 | Command | ||
| BO | 91 | Priority Coils Breaker 27 | Modbus 000091 | Command | ||
| BO | 92 | Priority Coils Breaker 28 | Modbus 000092 | Command | ||
| BO | 93 | Priority Coils Breaker 29 | Modbus 000093 | Command | ||
| BO | 94 | Priority Coils Breaker 30 | Modbus 000094 | Command | ||
| BO | 95 | Priority Coils Breaker 31 | Modbus 000095 | Command | ||
| BO | 96 | Priority Coils Breaker 32 | Modbus 000096 | Command | ||
| BO | 97 | Priority Coils Breaker 33 | Modbus 000097 | Command | ||
| BO | 98 | Priority Coils Breaker 34 | Modbus 000098 | Command | ||
| BO | 99 | Priority Coils Breaker 35 | Modbus 000099 | Command | ||
| BO | 100 | Priority Coils Breaker 36 | Modbus 000100 | Command | ||
| BO | 101 | Priority Coils Breaker 37 | Modbus 000101 | Command | ||
| BO | 102 | Priority Coils Breaker 38 | Modbus 000102 | Command | ||
| BO | 103 | Priority Coils Breaker 39 | Modbus 000103 | Command | ||
| BO | 104 | Priority Coils Breaker 40 | Modbus 000104 | Command | ||
| BO | 105 | Priority Coils Breaker 41 | Modbus 000105 | Command | ||
| BO | 106 | Priority Coils Breaker 42 | Modbus 000106 | Command | ||
| BO | 107 | Priority Coils Breaker 43 | Modbus 000107 | Command | ||
| BO | 108 | Priority Coils Breaker 44 | Modbus 000108 | Command | ||
| BO | 109 | Priority Coils Breaker 45 | Modbus 000109 | Command | ||
| BO | 110 | Priority Coils Breaker 46 | Modbus 000110 | Command | ||
| BO | 111 | Priority Coils Breaker 47 | Modbus 000111 | Command | ||
| BO | 112 | Priority Coils Breaker 48 | Modbus 000112 | Command | ||
| BO | 113 | Service Coils Breaker 01 | Modbus 000129 | Command | ||
| BO | 114 | Service Coils Breaker 02 | Modbus 000130 | Command | ||
| BO | 115 | Service Coils Breaker 03 | Modbus 000131 | Command | ||
| BO | 116 | Service Coils Breaker 04 | Modbus 000132 | Command | ||
| BO | 117 | Service Coils Breaker 05 | Modbus 000133 | Command | ||
| BO | 118 | Service Coils Breaker 06 | Modbus 000134 | Command | ||
| BO | 119 | Service Coils Breaker 07 | Modbus 000135 | Command | ||
| BO | 120 | Service Coils Breaker 08 | Modbus 000136 | Command | ||
| BO | 121 | Service Coils Breaker 09 | Modbus 000137 | Command | ||
| BO | 122 | Service Coils Breaker 10 | Modbus 000138 | Command | ||
| BO | 123 | Service Coils Breaker 11 | Modbus 000139 | Command | ||
| BO | 124 | Service Coils Breaker 12 | Modbus 000140 | Command | ||
| BO | 125 | Service Coils Breaker 13 | Modbus 000141 | Command | ||
| BO | 126 | Service Coils Breaker 14 | Modbus 000142 | Command | ||
| BO | 127 | Service Coils Breaker 15 | Modbus 000143 | Command | ||
| BO | 128 | Service Coils Breaker 16 | Modbus 000144 | Command | ||
| BO | 129 | Service Coils Breaker 17 | Modbus 000145 | Command | ||
| BO | 130 | Service Coils Breaker 18 | Modbus 000146 | Command | ||
| BO | 131 | Service Coils Breaker 19 | Modbus 000147 | Command | ||
| BO | 132 | Service Coils Breaker 20 | Modbus 000148 | Command | ||
| BO | 133 | Service Coils Breaker 21 | Modbus 000149 | Command | ||
| BO | 134 | Service Coils Breaker 22 | Modbus 000150 | Command | ||
| BO | 135 | Service Coils Breaker 23 | Modbus 000151 | Command | ||
| BO | 136 | Service Coils Breaker 24 | Modbus 000152 | Command | ||
| BO | 137 | Service Coils Breaker 25 | Modbus 000153 | Command | ||
| BO | 138 | Service Coils Breaker 26 | Modbus 000154 | Command | ||
| BO | 139 | Service Coils Breaker 27 | Modbus 000155 | Command | ||
| BO | 140 | Service Coils Breaker 28 | Modbus 000156 | Command | ||
| BO | 141 | Service Coils Breaker 29 | Modbus 000157 | Command | ||
| BO | 142 | Service Coils Breaker 30 | Modbus 000158 | Command | ||
| BO | 143 | Service Coils Breaker 31 | Modbus 000159 | Command | ||
| BO | 144 | Service Coils Breaker 32 | Modbus 000160 | Command | ||
| BO | 145 | Service Coils Breaker 33 | Modbus 000161 | Command | ||
| BO | 146 | Service Coils Breaker 34 | Modbus 000162 | Command | ||
| BO | 147 | Service Coils Breaker 35 | Modbus 000163 | Command | ||
| BO | 148 | Service Coils Breaker 36 | Modbus 000164 | Command | ||
| BO | 149 | Service Coils Breaker 37 | Modbus 000165 | Command | ||
| BO | 150 | Service Coils Breaker 38 | Modbus 000166 | Command | ||
| BO | 151 | Service Coils Breaker 39 | Modbus 000167 | Command | ||
| BO | 152 | Service Coils Breaker 40 | Modbus 000168 | Command | ||
| BO | 153 | Service Coils Breaker 41 | Modbus 000169 | Command | ||
| BO | 154 | Service Coils Breaker 42 | Modbus 000170 | Command | ||
| BO | 155 | Service Coils Breaker 43 | Modbus 000171 | Command | ||
| BO | 156 | Service Coils Breaker 44 | Modbus 000172 | Command | ||
| BO | 157 | Service Coils Breaker 45 | Modbus 000173 | Command | ||
| BO | 158 | Service Coils Breaker 46 | Modbus 000174 | Command | ||
| BO | 159 | Service Coils Breaker 47 | Modbus 000175 | Command | ||
| BO | 160 | Service Coils Breaker 48 | Modbus 000176 | Command | ||
| BO | 161 | Group Coils A | Modbus 000193 | Command | ||
| BO | 162 | Group Coils B | Modbus 000194 | Command | ||
| BO | 163 | Group Coils C | Modbus 000195 | Command | ||
| BO | 164 | Group Coils D | Modbus 000196 | Command | ||
| BO | 165 | Group Coils E | Modbus 000197 | Command | ||
| BO | 166 | Group Coils F | Modbus 000198 | Command | ||
| BO | 167 | Group Coils G | Modbus 000199 | Command | ||
| BO | 168 | Group Coils H | Modbus 000200 | Command | ||
| BO | 169 | Group Coils I | Modbus 000201 | Command | ||
| BO | 170 | Group Coils J | Modbus 000202 | Command | ||
| BO | 171 | Group Coils K | Modbus 000203 | Command | ||
| BO | 172 | Group Coils L | Modbus 000204 | Command | ||
| BO | 173 | Group Coils M | Modbus 000205 | Command | ||
| BO | 174 | Group Coils N | Modbus 000206 | Command | ||
| BO | 175 | Group Coils O | Modbus 000207 | Command | ||
| BO | 176 | Group Coils P | Modbus 000208 | Command | ||
| BO | 177 | Input Changed Monitors SW 09 | Modbus 000209; not polled by default | Command | ||
| BO | 178 | Input Changed Monitors SW 10 | Modbus 000210; not polled by default | Command | ||
| BO | 179 | Input Changed Monitors SW 11 | Modbus 000211; not polled by default | Command | ||
| BO | 180 | Input Changed Monitors SW 12 | Modbus 000212; not polled by default | Command | ||
| BO | 181 | Input Changed Monitors SW 13 | Modbus 000213; not polled by default | Command | ||
| BO | 182 | Input Changed Monitors SW 14 | Modbus 000214; not polled by default | Command | ||
| BO | 183 | Input Changed Monitors SW 15 | Modbus 000215; not polled by default | Command | ||
| BO | 184 | Input Changed Monitors SW 16 | Modbus 000216; not polled by default | Command | ||
| BO | 185 | Input Changed Monitors SW 01 | Modbus 000217; not polled by default | Command | ||
| BO | 186 | Input Changed Monitors SW 02 | Modbus 000218; not polled by default | Command | ||
| BO | 187 | Input Changed Monitors SW 03 | Modbus 000219; not polled by default | Command | ||
| BO | 188 | Input Changed Monitors SW 04 | Modbus 000220; not polled by default | Command | ||
| BO | 189 | Input Changed Monitors SW 05 | Modbus 000221; not polled by default | Command | ||
| BO | 190 | Input Changed Monitors SW 06 | Modbus 000222; not polled by default | Command | ||
| BO | 191 | Input Changed Monitors SW 07 | Modbus 000223; not polled by default | Command | ||
| BO | 192 | Input Changed Monitors SW 08 | Modbus 000224; not polled by default | Command | ||
| BImin | 193 | Feedback Coils Breaker 01 | Modbus 100001 | Read | ||
| BImin | 194 | Feedback Coils Breaker 02 | Modbus 100002 | Read | ||
| BI | 195 | Feedback Coils Breaker 03 | Modbus 100003 | Read | ||
| BI | 196 | Feedback Coils Breaker 04 | Modbus 100004 | Read | ||
| BI | 197 | Feedback Coils Breaker 05 | Modbus 100005 | Read | ||
| BI | 198 | Feedback Coils Breaker 06 | Modbus 100006 | Read | ||
| BI | 199 | Feedback Coils Breaker 07 | Modbus 100007 | Read | ||
| BI | 200 | Feedback Coils Breaker 08 | Modbus 100008 | Read | ||
| BI | 201 | Feedback Coils Breaker 09 | Modbus 100009 | Read | ||
| BI | 202 | Feedback Coils Breaker 10 | Modbus 100010 | Read | ||
| BI | 203 | Feedback Coils Breaker 11 | Modbus 100011 | Read | ||
| BI | 204 | Feedback Coils Breaker 12 | Modbus 100012 | Read | ||
| BI | 205 | Feedback Coils Breaker 13 | Modbus 100013 | Read | ||
| BI | 206 | Feedback Coils Breaker 14 | Modbus 100014 | Read | ||
| BI | 207 | Feedback Coils Breaker 15 | Modbus 100015 | Read | ||
| BI | 208 | Feedback Coils Breaker 16 | Modbus 100016 | Read | ||
| BI | 209 | Feedback Coils Breaker 17 | Modbus 100017 | Read | ||
| BI | 210 | Feedback Coils Breaker 18 | Modbus 100018 | Read | ||
| BI | 211 | Feedback Coils Breaker 19 | Modbus 100019 | Read | ||
| BI | 212 | Feedback Coils Breaker 20 | Modbus 100020 | Read | ||
| BI | 213 | Feedback Coils Breaker 21 | Modbus 100021 | Read | ||
| BI | 214 | Feedback Coils Breaker 22 | Modbus 100022 | Read | ||
| BI | 215 | Feedback Coils Breaker 23 | Modbus 100023 | Read | ||
| BI | 216 | Feedback Coils Breaker 24 | Modbus 100024 | Read | ||
| BI | 217 | Feedback Coils Breaker 25 | Modbus 100025 | Read | ||
| BI | 218 | Feedback Coils Breaker 26 | Modbus 100026 | Read | ||
| BI | 219 | Feedback Coils Breaker 27 | Modbus 100027 | Read | ||
| BI | 220 | Feedback Coils Breaker 28 | Modbus 100028 | Read | ||
| BI | 221 | Feedback Coils Breaker 29 | Modbus 100029 | Read | ||
| BI | 222 | Feedback Coils Breaker 30 | Modbus 100030 | Read | ||
| BI | 223 | Feedback Coils Breaker 31 | Modbus 100031 | Read | ||
| BI | 224 | Feedback Coils Breaker 32 | Modbus 100032 | Read | ||
| BI | 225 | Feedback Coils Breaker 33 | Modbus 100033 | Read | ||
| BI | 226 | Feedback Coils Breaker 34 | Modbus 100034 | Read | ||
| BI | 227 | Feedback Coils Breaker 35 | Modbus 100035 | Read | ||
| BI | 228 | Feedback Coils Breaker 36 | Modbus 100036 | Read | ||
| BI | 229 | Feedback Coils Breaker 37 | Modbus 100037 | Read | ||
| BI | 230 | Feedback Coils Breaker 38 | Modbus 100038 | Read | ||
| BI | 231 | Feedback Coils Breaker 39 | Modbus 100039 | Read | ||
| BI | 232 | Feedback Coils Breaker 40 | Modbus 100040 | Read | ||
| BI | 233 | Feedback Coils Breaker 41 | Modbus 100041 | Read | ||
| BI | 234 | Feedback Coils Breaker 42 | Modbus 100042 | Read | ||
| BI | 235 | Feedback Coils Breaker 43 | Modbus 100043 | Read | ||
| BI | 236 | Feedback Coils Breaker 44 | Modbus 100044 | Read | ||
| BI | 237 | Feedback Coils Breaker 45 | Modbus 100045 | Read | ||
| BI | 238 | Feedback Coils Breaker 46 | Modbus 100046 | Read | ||
| BI | 239 | Feedback Coils Breaker 47 | Modbus 100047 | Read | ||
| BI | 240 | Feedback Coils Breaker 48 | Modbus 100048 | Read | ||
| BI | 241 | Command Coils Breaker 01 | Modbus 100065 | Read | ||
| BI | 242 | Command Coils Breaker 02 | Modbus 100066 | Read | ||
| BI | 243 | Command Coils Breaker 03 | Modbus 100067 | Read | ||
| BI | 244 | Command Coils Breaker 04 | Modbus 100068 | Read | ||
| BI | 245 | Command Coils Breaker 05 | Modbus 100069 | Read | ||
| BI | 246 | Command Coils Breaker 06 | Modbus 100070 | Read | ||
| BI | 247 | Command Coils Breaker 07 | Modbus 100071 | Read | ||
| BI | 248 | Command Coils Breaker 08 | Modbus 100072 | Read | ||
| BI | 249 | Command Coils Breaker 09 | Modbus 100073 | Read | ||
| BI | 250 | Command Coils Breaker 10 | Modbus 100074 | Read | ||
| BI | 251 | Command Coils Breaker 11 | Modbus 100075 | Read | ||
| BI | 252 | Command Coils Breaker 12 | Modbus 100076 | Read | ||
| BI | 253 | Command Coils Breaker 13 | Modbus 100077 | Read | ||
| BI | 254 | Command Coils Breaker 14 | Modbus 100078 | Read | ||
| BI | 255 | Command Coils Breaker 15 | Modbus 100079 | Read | ||
| BI | 256 | Command Coils Breaker 16 | Modbus 100080 | Read | ||
| BI | 257 | Command Coils Breaker 17 | Modbus 100081 | Read | ||
| BI | 258 | Command Coils Breaker 18 | Modbus 100082 | Read | ||
| BI | 259 | Command Coils Breaker 19 | Modbus 100083 | Read | ||
| BI | 260 | Command Coils Breaker 20 | Modbus 100084 | Read | ||
| BI | 261 | Command Coils Breaker 21 | Modbus 100085 | Read | ||
| BI | 262 | Command Coils Breaker 22 | Modbus 100086 | Read | ||
| BI | 263 | Command Coils Breaker 23 | Modbus 100087 | Read | ||
| BI | 264 | Command Coils Breaker 24 | Modbus 100088 | Read | ||
| BI | 265 | Command Coils Breaker 25 | Modbus 100089 | Read | ||
| BI | 266 | Command Coils Breaker 26 | Modbus 100090 | Read | ||
| BI | 267 | Command Coils Breaker 27 | Modbus 100091 | Read | ||
| BI | 268 | Command Coils Breaker 28 | Modbus 100092 | Read | ||
| BI | 269 | Command Coils Breaker 29 | Modbus 100093 | Read | ||
| BI | 270 | Command Coils Breaker 30 | Modbus 100094 | Read | ||
| BI | 271 | Command Coils Breaker 31 | Modbus 100095 | Read | ||
| BI | 272 | Command Coils Breaker 32 | Modbus 100096 | Read | ||
| BI | 273 | Command Coils Breaker 33 | Modbus 100097 | Read | ||
| BI | 274 | Command Coils Breaker 34 | Modbus 100098 | Read | ||
| BI | 275 | Command Coils Breaker 35 | Modbus 100099 | Read | ||
| BI | 276 | Command Coils Breaker 36 | Modbus 100100 | Read | ||
| BI | 277 | Command Coils Breaker 37 | Modbus 100101 | Read | ||
| BI | 278 | Command Coils Breaker 38 | Modbus 100102 | Read | ||
| BI | 279 | Command Coils Breaker 39 | Modbus 100103 | Read | ||
| BI | 280 | Command Coils Breaker 40 | Modbus 100104 | Read | ||
| BI | 281 | Command Coils Breaker 41 | Modbus 100105 | Read | ||
| BI | 282 | Command Coils Breaker 42 | Modbus 100106 | Read | ||
| BI | 283 | Command Coils Breaker 43 | Modbus 100107 | Read | ||
| BI | 284 | Command Coils Breaker 44 | Modbus 100108 | Read | ||
| BI | 285 | Command Coils Breaker 45 | Modbus 100109 | Read | ||
| BI | 286 | Command Coils Breaker 46 | Modbus 100110 | Read | ||
| BI | 287 | Command Coils Breaker 47 | Modbus 100111 | Read | ||
| BI | 288 | Command Coils Breaker 48 | Modbus 100112 | Read | ||
| BImin | 289 | Alarm Coils Breaker 01 | Modbus 100129 | Read | ||
| BImin | 290 | Alarm Coils Breaker 02 | Modbus 100130 | Read | ||
| BI | 291 | Alarm Coils Breaker 03 | Modbus 100131 | Read | ||
| BI | 292 | Alarm Coils Breaker 04 | Modbus 100132 | Read | ||
| BI | 293 | Alarm Coils Breaker 05 | Modbus 100133 | Read | ||
| BI | 294 | Alarm Coils Breaker 06 | Modbus 100134 | Read | ||
| BI | 295 | Alarm Coils Breaker 07 | Modbus 100135 | Read | ||
| BI | 296 | Alarm Coils Breaker 08 | Modbus 100136 | Read | ||
| BI | 297 | Alarm Coils Breaker 09 | Modbus 100137 | Read | ||
| BI | 298 | Alarm Coils Breaker 10 | Modbus 100138 | Read | ||
| BI | 299 | Alarm Coils Breaker 11 | Modbus 100139 | Read | ||
| BI | 300 | Alarm Coils Breaker 12 | Modbus 100140 | Read | ||
| BI | 301 | Alarm Coils Breaker 13 | Modbus 100141 | Read | ||
| BI | 302 | Alarm Coils Breaker 14 | Modbus 100142 | Read | ||
| BI | 303 | Alarm Coils Breaker 15 | Modbus 100143 | Read | ||
| BI | 304 | Alarm Coils Breaker 16 | Modbus 100144 | Read | ||
| BI | 305 | Alarm Coils Breaker 17 | Modbus 100145 | Read | ||
| BI | 306 | Alarm Coils Breaker 18 | Modbus 100146 | Read | ||
| BI | 307 | Alarm Coils Breaker 19 | Modbus 100147 | Read | ||
| BI | 308 | Alarm Coils Breaker 20 | Modbus 100148 | Read | ||
| BI | 309 | Alarm Coils Breaker 21 | Modbus 100149 | Read | ||
| BI | 310 | Alarm Coils Breaker 22 | Modbus 100150 | Read | ||
| BI | 311 | Alarm Coils Breaker 23 | Modbus 100151 | Read | ||
| BI | 312 | Alarm Coils Breaker 24 | Modbus 100152 | Read | ||
| BI | 313 | Alarm Coils Breaker 25 | Modbus 100153 | Read | ||
| BI | 314 | Alarm Coils Breaker 26 | Modbus 100154 | Read | ||
| BI | 315 | Alarm Coils Breaker 27 | Modbus 100155 | Read | ||
| BI | 316 | Alarm Coils Breaker 28 | Modbus 100156 | Read | ||
| BI | 317 | Alarm Coils Breaker 29 | Modbus 100157 | Read | ||
| BI | 318 | Alarm Coils Breaker 30 | Modbus 100158 | Read | ||
| BI | 319 | Alarm Coils Breaker 31 | Modbus 100159 | Read | ||
| BI | 320 | Alarm Coils Breaker 32 | Modbus 100160 | Read | ||
| BI | 321 | Alarm Coils Breaker 33 | Modbus 100161 | Read | ||
| BI | 322 | Alarm Coils Breaker 34 | Modbus 100162 | Read | ||
| BI | 323 | Alarm Coils Breaker 35 | Modbus 100163 | Read | ||
| BI | 324 | Alarm Coils Breaker 36 | Modbus 100164 | Read | ||
| BI | 325 | Alarm Coils Breaker 37 | Modbus 100165 | Read | ||
| BI | 326 | Alarm Coils Breaker 38 | Modbus 100166 | Read | ||
| BI | 327 | Alarm Coils Breaker 39 | Modbus 100167 | Read | ||
| BI | 328 | Alarm Coils Breaker 40 | Modbus 100168 | Read | ||
| BI | 329 | Alarm Coils Breaker 41 | Modbus 100169 | Read | ||
| BI | 330 | Alarm Coils Breaker 42 | Modbus 100170 | Read | ||
| BI | 331 | Alarm Coils Breaker 43 | Modbus 100171 | Read | ||
| BI | 332 | Alarm Coils Breaker 44 | Modbus 100172 | Read | ||
| BI | 333 | Alarm Coils Breaker 45 | Modbus 100173 | Read | ||
| BI | 334 | Alarm Coils Breaker 46 | Modbus 100174 | Read | ||
| BI | 335 | Alarm Coils Breaker 47 | Modbus 100175 | Read | ||
| BI | 336 | Alarm Coils Breaker 48 | Modbus 100176 | Read | ||
| BI | 337 | Switch Inout Monitors SW 09 | Modbus 100193; not polled by default | Read | ||
| BI | 338 | Switch Inout Monitors SW 10 | Modbus 100194; not polled by default | Read | ||
| BI | 339 | Switch Inout Monitors SW 11 | Modbus 100195; not polled by default | Read | ||
| BI | 340 | Switch Inout Monitors SW 12 | Modbus 100196; not polled by default | Read | ||
| BI | 341 | Switch Inout Monitors SW 13 | Modbus 100197; not polled by default | Read | ||
| BI | 342 | Switch Inout Monitors SW 14 | Modbus 100198; not polled by default | Read | ||
| BI | 343 | Switch Inout Monitors SW 15 | Modbus 100199; not polled by default | Read | ||
| BI | 344 | Switch Inout Monitors SW 16 | Modbus 100200; not polled by default | Read | ||
| BI | 345 | Switch Inout Monitors SW 01 | Modbus 100201; not polled by default | Read | ||
| BI | 346 | Switch Inout Monitors SW 02 | Modbus 100202; not polled by default | Read | ||
| BI | 347 | Switch Inout Monitors SW 03 | Modbus 100203; not polled by default | Read | ||
| BI | 348 | Switch Inout Monitors SW 04 | Modbus 100204; not polled by default | Read | ||
| BI | 349 | Switch Inout Monitors SW 05 | Modbus 100205; not polled by default | Read | ||
| BI | 350 | Switch Inout Monitors SW 06 | Modbus 100206; not polled by default | Read | ||
| BI | 351 | Switch Inout Monitors SW 07 | Modbus 100207; not polled by default | Read | ||
| BI | 352 | Switch Inout Monitors SW 08 | Modbus 100208; not polled by default | Read | ||
| BI | 353 | Condition Codes Pad 1 | Modbus 100225; not polled by default | Read | ||
| BI | 354 | Condition Codes Pad 2 | Modbus 100226; not polled by default | Read | ||
| BI | 355 | Condition Codes Pad 3 | Modbus 100227; not polled by default | Read | ||
| BI | 356 | Condition Codes Pad 4 | Modbus 100228; not polled by default | Read | ||
| BI | 357 | Condition Codes Pad 5 | Modbus 100229; not polled by default | Read | ||
| BI | 358 | Condition Codes Pad 6 | Modbus 100230; not polled by default | Read | ||
| BI | 359 | Condition Codes Pad 7 | Modbus 100231; not polled by default | Read | ||
| BI | 360 | Condition Codes Pad 8 | Modbus 100232; not polled by default | Read | ||
| BI | 361 | Condition Code 232 | Modbus 100233; not polled by default | Read | ||
| BI | 362 | Condition Code 233 | Modbus 100234; not polled by default | Read | ||
| BI | 363 | Condition Code 234 | Modbus 100235; not polled by default | Read | ||
| BI | 364 | Condition Code 235 | Modbus 100236; not polled by default | Read | ||
| BI | 365 | Condition Code 236 | Modbus 100237; not polled by default | Read | ||
| BI | 366 | Condition Code 237 | Modbus 100238; not polled by default | Read | ||
| BI | 367 | Condition Code 238 | Modbus 100239; not polled by default | Read | ||
| BI | 368 | Condition Code 239 | Modbus 100240; not polled by default | Read | ||
| BI | 369 | Schedule Active 01 | Modbus 100241; not polled by default | Read | ||
| BI | 370 | Schedule Active 02 | Modbus 100242; not polled by default | Read | ||
| BI | 371 | Schedule Active 03 | Modbus 100243; not polled by default | Read | ||
| BI | 372 | Schedule Active 04 | Modbus 100244; not polled by default | Read | ||
| BI | 373 | Schedule Active 05 | Modbus 100245; not polled by default | Read | ||
| BI | 374 | Schedule Active 06 | Modbus 100246; not polled by default | Read | ||
| BI | 375 | Schedule Active 07 | Modbus 100247; not polled by default | Read | ||
| BI | 376 | Schedule Active 08 | Modbus 100248; not polled by default | Read | ||
| BI | 377 | Schedule Active 09 | Modbus 100249; not polled by default | Read | ||
| BI | 378 | Schedule Active 10 | Modbus 100250; not polled by default | Read | ||
| BI | 379 | Schedule Active 11 | Modbus 100251; not polled by default | Read | ||
| BI | 380 | Schedule Active 12 | Modbus 100252; not polled by default | Read | ||
| BI | 381 | Schedule Active 13 | Modbus 100253; not polled by default | Read | ||
| BI | 382 | Schedule Active 14 | Modbus 100254; not polled by default | Read | ||
| BI | 383 | Schedule Active 15 | Modbus 100255; not polled by default | Read | ||
| BI | 384 | Schedule Active 16 | Modbus 100256; not polled by default | Read | ||
| BI | 385 | Schedule Active 17 | Modbus 100257; not polled by default | Read | ||
| BI | 386 | Schedule Active 18 | Modbus 100258; not polled by default | Read | ||
| BI | 387 | Schedule Active 19 | Modbus 100259; not polled by default | Read | ||
| BI | 388 | Schedule Active 20 | Modbus 100260; not polled by default | Read | ||
| BI | 389 | Schedule Active 21 | Modbus 100261; not polled by default | Read | ||
| BI | 390 | Schedule Active 22 | Modbus 100262; not polled by default | Read | ||
| BI | 391 | Schedule Active 23 | Modbus 100263; not polled by default | Read | ||
| BI | 392 | Schedule Active 24 | Modbus 100264; not polled by default | Read | ||
| BI | 393 | Schedule Active 25 | Modbus 100265; not polled by default | Read | ||
| BI | 394 | Schedule Active 26 | Modbus 100266; not polled by default | Read | ||
| BI | 395 | Schedule Active 27 | Modbus 100267; not polled by default | Read | ||
| BI | 396 | Schedule Active 28 | Modbus 100268; not polled by default | Read | ||
| BI | 397 | Schedule Active 29 | Modbus 100269; not polled by default | Read | ||
| BI | 398 | Schedule Active 30 | Modbus 100270; not polled by default | Read | ||
| BI | 399 | Schedule Active 31 | Modbus 100271; not polled by default | Read | ||
| BI | 400 | Schedule Active 32 | Modbus 100272; not polled by default | Read | ||
| AI | 401 | Input 01 Override Timer | Modbus 300001; not polled by default | Read | ||
| AI | 402 | Input 02 Override Timer | Modbus 300002; not polled by default | Read | ||
| AI | 403 | Input 03 Override Timer | Modbus 300003; not polled by default | Read | ||
| AI | 404 | Input 04 Override Timer | Modbus 300004; not polled by default | Read | ||
| AI | 405 | Input 05 Override Timer | Modbus 300005; not polled by default | Read | ||
| AI | 406 | Input 06 Override Timer | Modbus 300006; not polled by default | Read | ||
| AI | 407 | Input 07 Override Timer | Modbus 300007; not polled by default | Read | ||
| AI | 408 | Input 08 Override Timer | Modbus 300008; not polled by default | Read | ||
| AI | 409 | Input 09 Override Timer | Modbus 300009; not polled by default | Read | ||
| AI | 410 | Input 10 Override Timer | Modbus 300010; not polled by default | Read | ||
| AI | 411 | Input 11 Override Timer | Modbus 300011; not polled by default | Read | ||
| AI | 412 | Input 12 Override Timer | Modbus 300012; not polled by default | Read | ||
| AI | 413 | Input 13 Override Timer | Modbus 300013; not polled by default | Read | ||
| AI | 414 | Input 14 Override Timer | Modbus 300014; not polled by default | Read | ||
| AI | 415 | Input 15 Override Timer | Modbus 300015; not polled by default | Read | ||
| AI | 416 | Input 16 Override Timer | Modbus 300016; not polled by default | Read | ||
| AI | 417 | Load 1 Wink Delay (Off Timer)__Load 1 Egress Timer | Modbus 300017; not polled by default | Read | ||
| AI | 418 | Load 02 Egress Timer | Modbus 300018; not polled by default | Read | ||
| AI | 419 | Load 03 Egress Timer | Modbus 300019; not polled by default | Read | ||
| AI | 420 | Load 04 Egress Timer | Modbus 300020; not polled by default | Read | ||
| AI | 421 | Load 05 Egress Timer | Modbus 300021; not polled by default | Read | ||
| AI | 422 | Load 06 Egress Timer | Modbus 300022; not polled by default | Read | ||
| AI | 423 | Load 07 Egress Timer | Modbus 300023; not polled by default | Read | ||
| AI | 424 | Load 08 Egress Timer | Modbus 300024; not polled by default | Read | ||
| AI | 425 | Load 09 Egress Timer | Modbus 300025; not polled by default | Read | ||
| AI | 426 | Load 10 Egress Timer | Modbus 300026; not polled by default | Read | ||
| AI | 427 | Load 11 Egress Timer | Modbus 300027; not polled by default | Read | ||
| AI | 428 | Load 12 Egress Timer | Modbus 300028; not polled by default | Read | ||
| AI | 429 | Load 13 Egress Timer | Modbus 300029; not polled by default | Read | ||
| AI | 430 | Load 14 Egress Timer | Modbus 300030; not polled by default | Read | ||
| AI | 431 | Load 15 Egress Timer | Modbus 300031; not polled by default | Read | ||
| AI | 432 | Load 16 Egress Timer | Modbus 300032; not polled by default | Read | ||
| AI | 433 | Load 17 Egress Timer | Modbus 300033; not polled by default | Read | ||
| AI | 434 | Load 18 Egress Timer | Modbus 300034; not polled by default | Read | ||
| AI | 435 | Load 19 Egress Timer | Modbus 300035; not polled by default | Read | ||
| AI | 436 | Load 20 Egress Timer | Modbus 300036; not polled by default | Read | ||
| AI | 437 | Load 21 Egress Timer | Modbus 300037; not polled by default | Read | ||
| AI | 438 | Load 22 Egress Timer | Modbus 300038; not polled by default | Read | ||
| AI | 439 | Load 23 Egress Timer | Modbus 300039; not polled by default | Read | ||
| AI | 440 | Load 24 Egress Timer | Modbus 300040; not polled by default | Read | ||
| AI | 441 | Load 25 Egress Timer | Modbus 300041; not polled by default | Read | ||
| AI | 442 | Load 26 Egress Timer | Modbus 300042; not polled by default | Read | ||
| AI | 443 | Load 27 Egress Timer | Modbus 300043; not polled by default | Read | ||
| AI | 444 | Load 28 Egress Timer | Modbus 300044; not polled by default | Read | ||
| AI | 445 | Load 29 Egress Timer | Modbus 300045; not polled by default | Read | ||
| AI | 446 | Load 30 Egress Timer | Modbus 300046; not polled by default | Read | ||
| AI | 447 | Load 31 Egress Timer | Modbus 300047; not polled by default | Read | ||
| AI | 448 | Load 32 Egress Timer | Modbus 300048; not polled by default | Read | ||
| AI | 449 | Load 33 Egress Timer | Modbus 300049; not polled by default | Read | ||
| AI | 450 | Load 34 Egress Timer | Modbus 300050; not polled by default | Read | ||
| AI | 451 | Load 35 Egress Timer | Modbus 300051; not polled by default | Read | ||
| AI | 452 | Load 36 Egress Timer | Modbus 300052; not polled by default | Read | ||
| AI | 453 | Load 37 Egress Timer | Modbus 300053; not polled by default | Read | ||
| AI | 454 | Load 38 Egress Timer | Modbus 300054; not polled by default | Read | ||
| AI | 455 | Load 39 Egress Timer | Modbus 300055; not polled by default | Read | ||
| AI | 456 | Load 40 Egress Timer | Modbus 300056; not polled by default | Read | ||
| AI | 457 | Load 41 Egress Timer | Modbus 300057; not polled by default | Read | ||
| AI | 458 | Load 42 Egress Timer | Modbus 300058; not polled by default | Read | ||
| AI | 459 | Load 43 Egress Timer | Modbus 300059; not polled by default | Read | ||
| AI | 460 | Load 44 Egress Timer | Modbus 300060; not polled by default | Read | ||
| AI | 461 | Load 45 Egress Timer | Modbus 300061; not polled by default | Read | ||
| AI | 462 | Load 46 Egress Timer | Modbus 300062; not polled by default | Read | ||
| AI | 463 | Load 47 Egress Timer | Modbus 300063; not polled by default | Read | ||
| AI | 464 | Load 48 Egress Timer | Modbus 300064; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Eaton Pow-R-Command point IDs by name
BO1Peer Coils Breaker 01BO2Peer Coils Breaker 02BO3Peer Coils Breaker 03BO4Peer Coils Breaker 04BO5Peer Coils Breaker 05BO6Peer Coils Breaker 06BO7Peer Coils Breaker 07BO8Peer Coils Breaker 08BO9Peer Coils Breaker 09BO10Peer Coils Breaker 10BO11Peer Coils Breaker 11BO12Peer Coils Breaker 12BO13Peer Coils Breaker 13BO14Peer Coils Breaker 14BO15Peer Coils Breaker 15BO16Peer Coils Breaker 16BO17Peer Coils Breaker 17BO18Peer Coils Breaker 18BO19Peer Coils Breaker 19BO20Peer Coils Breaker 20BO21Peer Coils Breaker 21BO22Peer Coils Breaker 22BO23Peer Coils Breaker 23BO24Peer Coils Breaker 24BO25Peer Coils Breaker 25BO26Peer Coils Breaker 26BO27Peer Coils Breaker 27BO28Peer Coils Breaker 28BO29Peer Coils Breaker 29BO30Peer Coils Breaker 30BO31Peer Coils Breaker 31BO32Peer Coils Breaker 32BO33Peer Coils Breaker 33BO34Peer Coils Breaker 34BO35Peer Coils Breaker 35BO36Peer Coils Breaker 36BO37Peer Coils Breaker 37BO38Peer Coils Breaker 38BO39Peer Coils Breaker 39BO40Peer Coils Breaker 40BO41Peer Coils Breaker 41BO42Peer Coils Breaker 42BO43Peer Coils Breaker 43BO44Peer Coils Breaker 44BO45Peer Coils Breaker 45BO46Peer Coils Breaker 46BO47Peer Coils Breaker 47BO48Peer Coils Breaker 48BO49Peer Flags General Purpose Flags 01BO50Peer Flags General Purpose Flags 02BO51Peer Flags General Purpose Flags 03BO52Peer Flags General Purpose Flags 04BO53Peer Flags General Purpose Flags 05BO54Peer Flags General Purpose Flags 06BO55Peer Flags General Purpose Flags 07BO56Peer Flags General Purpose Flags 08BO57Peer Flags General Purpose Flags 09BO58Peer Flags General Purpose Flags 10BO59Peer Flags General Purpose Flags 11BO60Peer Flags General Purpose Flags 12BO61Peer Flags General Purpose Flags 13BO62Peer Flags General Purpose Flags 14BO63Peer Flags General Purpose Flags 15BO64Peer Flags General Purpose Flags 16BO65Priority Coils Breaker 01BO66Priority Coils Breaker 02BO67Priority Coils Breaker 03BO68Priority Coils Breaker 04BO69Priority Coils Breaker 05BO70Priority Coils Breaker 06BO71Priority Coils Breaker 07BO72Priority Coils Breaker 08BO73Priority Coils Breaker 09BO74Priority Coils Breaker 10BO75Priority Coils Breaker 11BO76Priority Coils Breaker 12BO77Priority Coils Breaker 13BO78Priority Coils Breaker 14BO79Priority Coils Breaker 15BO80Priority Coils Breaker 16BO81Priority Coils Breaker 17BO82Priority Coils Breaker 18BO83Priority Coils Breaker 19BO84Priority Coils Breaker 20BO85Priority Coils Breaker 21BO86Priority Coils Breaker 22BO87Priority Coils Breaker 23BO88Priority Coils Breaker 24BO89Priority Coils Breaker 25BO90Priority Coils Breaker 26BO91Priority Coils Breaker 27BO92Priority Coils Breaker 28BO93Priority Coils Breaker 29BO94Priority Coils Breaker 30BO95Priority Coils Breaker 31BO96Priority Coils Breaker 32BO97Priority Coils Breaker 33BO98Priority Coils Breaker 34BO99Priority Coils Breaker 35BO100Priority Coils Breaker 36BO101Priority Coils Breaker 37BO102Priority Coils Breaker 38BO103Priority Coils Breaker 39BO104Priority Coils Breaker 40BO105Priority Coils Breaker 41BO106Priority Coils Breaker 42BO107Priority Coils Breaker 43BO108Priority Coils Breaker 44BO109Priority Coils Breaker 45BO110Priority Coils Breaker 46BO111Priority Coils Breaker 47BO112Priority Coils Breaker 48BO113Service Coils Breaker 01BO114Service Coils Breaker 02BO115Service Coils Breaker 03BO116Service Coils Breaker 04BO117Service Coils Breaker 05BO118Service Coils Breaker 06BO119Service Coils Breaker 07BO120Service Coils Breaker 08BO121Service Coils Breaker 09BO122Service Coils Breaker 10BO123Service Coils Breaker 11BO124Service Coils Breaker 12BO125Service Coils Breaker 13BO126Service Coils Breaker 14BO127Service Coils Breaker 15BO128Service Coils Breaker 16BO129Service Coils Breaker 17BO130Service Coils Breaker 18BO131Service Coils Breaker 19BO132Service Coils Breaker 20BO133Service Coils Breaker 21BO134Service Coils Breaker 22BO135Service Coils Breaker 23BO136Service Coils Breaker 24BO137Service Coils Breaker 25BO138Service Coils Breaker 26BO139Service Coils Breaker 27BO140Service Coils Breaker 28BO141Service Coils Breaker 29BO142Service Coils Breaker 30BO143Service Coils Breaker 31BO144Service Coils Breaker 32BO145Service Coils Breaker 33BO146Service Coils Breaker 34BO147Service Coils Breaker 35BO148Service Coils Breaker 36BO149Service Coils Breaker 37BO150Service Coils Breaker 38BO151Service Coils Breaker 39BO152Service Coils Breaker 40BO153Service Coils Breaker 41BO154Service Coils Breaker 42BO155Service Coils Breaker 43BO156Service Coils Breaker 44BO157Service Coils Breaker 45BO158Service Coils Breaker 46BO159Service Coils Breaker 47BO160Service Coils Breaker 48BO161Group Coils ABO162Group Coils BBO163Group Coils CBO164Group Coils DBO165Group Coils EBO166Group Coils FBO167Group Coils GBO168Group Coils HBO169Group Coils IBO170Group Coils JBO171Group Coils KBO172Group Coils LBO173Group Coils MBO174Group Coils NBO175Group Coils OBO176Group Coils PBO177Input Changed Monitors SW 09BO178Input Changed Monitors SW 10BO179Input Changed Monitors SW 11BO180Input Changed Monitors SW 12BO181Input Changed Monitors SW 13BO182Input Changed Monitors SW 14BO183Input Changed Monitors SW 15BO184Input Changed Monitors SW 16BO185Input Changed Monitors SW 01BO186Input Changed Monitors SW 02BO187Input Changed Monitors SW 03BO188Input Changed Monitors SW 04BO189Input Changed Monitors SW 05BO190Input Changed Monitors SW 06BO191Input Changed Monitors SW 07BO192Input Changed Monitors SW 08BI193Feedback Coils Breaker 01BI194Feedback Coils Breaker 02BI195Feedback Coils Breaker 03BI196Feedback Coils Breaker 04BI197Feedback Coils Breaker 05BI198Feedback Coils Breaker 06BI199Feedback Coils Breaker 07BI200Feedback Coils Breaker 08BI201Feedback Coils Breaker 09BI202Feedback Coils Breaker 10BI203Feedback Coils Breaker 11BI204Feedback Coils Breaker 12BI205Feedback Coils Breaker 13BI206Feedback Coils Breaker 14BI207Feedback Coils Breaker 15BI208Feedback Coils Breaker 16BI209Feedback Coils Breaker 17BI210Feedback Coils Breaker 18BI211Feedback Coils Breaker 19BI212Feedback Coils Breaker 20BI213Feedback Coils Breaker 21BI214Feedback Coils Breaker 22BI215Feedback Coils Breaker 23BI216Feedback Coils Breaker 24BI217Feedback Coils Breaker 25BI218Feedback Coils Breaker 26BI219Feedback Coils Breaker 27BI220Feedback Coils Breaker 28BI221Feedback Coils Breaker 29BI222Feedback Coils Breaker 30BI223Feedback Coils Breaker 31BI224Feedback Coils Breaker 32BI225Feedback Coils Breaker 33BI226Feedback Coils Breaker 34BI227Feedback Coils Breaker 35BI228Feedback Coils Breaker 36BI229Feedback Coils Breaker 37BI230Feedback Coils Breaker 38BI231Feedback Coils Breaker 39BI232Feedback Coils Breaker 40BI233Feedback Coils Breaker 41BI234Feedback Coils Breaker 42BI235Feedback Coils Breaker 43BI236Feedback Coils Breaker 44BI237Feedback Coils Breaker 45BI238Feedback Coils Breaker 46BI239Feedback Coils Breaker 47BI240Feedback Coils Breaker 48BI241Command Coils Breaker 01BI242Command Coils Breaker 02BI243Command Coils Breaker 03BI244Command Coils Breaker 04BI245Command Coils Breaker 05BI246Command Coils Breaker 06BI247Command Coils Breaker 07BI248Command Coils Breaker 08BI249Command Coils Breaker 09BI250Command Coils Breaker 10BI251Command Coils Breaker 11BI252Command Coils Breaker 12BI253Command Coils Breaker 13BI254Command Coils Breaker 14BI255Command Coils Breaker 15BI256Command Coils Breaker 16BI257Command Coils Breaker 17BI258Command Coils Breaker 18BI259Command Coils Breaker 19BI260Command Coils Breaker 20BI261Command Coils Breaker 21BI262Command Coils Breaker 22BI263Command Coils Breaker 23BI264Command Coils Breaker 24BI265Command Coils Breaker 25BI266Command Coils Breaker 26BI267Command Coils Breaker 27BI268Command Coils Breaker 28BI269Command Coils Breaker 29BI270Command Coils Breaker 30BI271Command Coils Breaker 31BI272Command Coils Breaker 32BI273Command Coils Breaker 33BI274Command Coils Breaker 34BI275Command Coils Breaker 35BI276Command Coils Breaker 36BI277Command Coils Breaker 37BI278Command Coils Breaker 38BI279Command Coils Breaker 39BI280Command Coils Breaker 40BI281Command Coils Breaker 41BI282Command Coils Breaker 42BI283Command Coils Breaker 43BI284Command Coils Breaker 44BI285Command Coils Breaker 45BI286Command Coils Breaker 46BI287Command Coils Breaker 47BI288Command Coils Breaker 48BI289Alarm Coils Breaker 01BI290Alarm Coils Breaker 02BI291Alarm Coils Breaker 03BI292Alarm Coils Breaker 04BI293Alarm Coils Breaker 05BI294Alarm Coils Breaker 06BI295Alarm Coils Breaker 07BI296Alarm Coils Breaker 08BI297Alarm Coils Breaker 09BI298Alarm Coils Breaker 10BI299Alarm Coils Breaker 11BI300Alarm Coils Breaker 12BI301Alarm Coils Breaker 13BI302Alarm Coils Breaker 14BI303Alarm Coils Breaker 15BI304Alarm Coils Breaker 16BI305Alarm Coils Breaker 17BI306Alarm Coils Breaker 18BI307Alarm Coils Breaker 19BI308Alarm Coils Breaker 20BI309Alarm Coils Breaker 21BI310Alarm Coils Breaker 22BI311Alarm Coils Breaker 23BI312Alarm Coils Breaker 24BI313Alarm Coils Breaker 25BI314Alarm Coils Breaker 26BI315Alarm Coils Breaker 27BI316Alarm Coils Breaker 28BI317Alarm Coils Breaker 29BI318Alarm Coils Breaker 30BI319Alarm Coils Breaker 31BI320Alarm Coils Breaker 32BI321Alarm Coils Breaker 33BI322Alarm Coils Breaker 34BI323Alarm Coils Breaker 35BI324Alarm Coils Breaker 36BI325Alarm Coils Breaker 37BI326Alarm Coils Breaker 38BI327Alarm Coils Breaker 39BI328Alarm Coils Breaker 40BI329Alarm Coils Breaker 41BI330Alarm Coils Breaker 42BI331Alarm Coils Breaker 43BI332Alarm Coils Breaker 44BI333Alarm Coils Breaker 45BI334Alarm Coils Breaker 46BI335Alarm Coils Breaker 47BI336Alarm Coils Breaker 48BI337Switch Inout Monitors SW 09BI338Switch Inout Monitors SW 10BI339Switch Inout Monitors SW 11BI340Switch Inout Monitors SW 12BI341Switch Inout Monitors SW 13BI342Switch Inout Monitors SW 14BI343Switch Inout Monitors SW 15BI344Switch Inout Monitors SW 16BI345Switch Inout Monitors SW 01BI346Switch Inout Monitors SW 02BI347Switch Inout Monitors SW 03BI348Switch Inout Monitors SW 04BI349Switch Inout Monitors SW 05BI350Switch Inout Monitors SW 06BI351Switch Inout Monitors SW 07BI352Switch Inout Monitors SW 08BI353Condition Codes Pad 1BI354Condition Codes Pad 2BI355Condition Codes Pad 3BI356Condition Codes Pad 4BI357Condition Codes Pad 5BI358Condition Codes Pad 6BI359Condition Codes Pad 7BI360Condition Codes Pad 8BI361Condition Code 232BI362Condition Code 233BI363Condition Code 234BI364Condition Code 235BI365Condition Code 236BI366Condition Code 237BI367Condition Code 238BI368Condition Code 239BI369Schedule Active 01BI370Schedule Active 02BI371Schedule Active 03BI372Schedule Active 04BI373Schedule Active 05BI374Schedule Active 06BI375Schedule Active 07BI376Schedule Active 08BI377Schedule Active 09BI378Schedule Active 10BI379Schedule Active 11BI380Schedule Active 12BI381Schedule Active 13BI382Schedule Active 14BI383Schedule Active 15BI384Schedule Active 16BI385Schedule Active 17BI386Schedule Active 18BI387Schedule Active 19BI388Schedule Active 20BI389Schedule Active 21BI390Schedule Active 22BI391Schedule Active 23BI392Schedule Active 24BI393Schedule Active 25BI394Schedule Active 26BI395Schedule Active 27BI396Schedule Active 28BI397Schedule Active 29BI398Schedule Active 30BI399Schedule Active 31BI400Schedule Active 32AI401Input 01 Override TimerAI402Input 02 Override TimerAI403Input 03 Override TimerAI404Input 04 Override TimerAI405Input 05 Override TimerAI406Input 06 Override TimerAI407Input 07 Override TimerAI408Input 08 Override TimerAI409Input 09 Override TimerAI410Input 10 Override TimerAI411Input 11 Override TimerAI412Input 12 Override TimerAI413Input 13 Override TimerAI414Input 14 Override TimerAI415Input 15 Override TimerAI416Input 16 Override TimerAI417Load 1 Wink Delay (Off Timer)__Load 1 Egress TimerAI418Load 02 Egress TimerAI419Load 03 Egress TimerAI420Load 04 Egress TimerAI421Load 05 Egress TimerAI422Load 06 Egress TimerAI423Load 07 Egress TimerAI424Load 08 Egress TimerAI425Load 09 Egress TimerAI426Load 10 Egress TimerAI427Load 11 Egress TimerAI428Load 12 Egress TimerAI429Load 13 Egress TimerAI430Load 14 Egress TimerAI431Load 15 Egress TimerAI432Load 16 Egress TimerAI433Load 17 Egress TimerAI434Load 18 Egress TimerAI435Load 19 Egress TimerAI436Load 20 Egress TimerAI437Load 21 Egress TimerAI438Load 22 Egress TimerAI439Load 23 Egress TimerAI440Load 24 Egress TimerAI441Load 25 Egress TimerAI442Load 26 Egress TimerAI443Load 27 Egress TimerAI444Load 28 Egress TimerAI445Load 29 Egress TimerAI446Load 30 Egress TimerAI447Load 31 Egress TimerAI448Load 32 Egress TimerAI449Load 33 Egress TimerAI450Load 34 Egress TimerAI451Load 35 Egress TimerAI452Load 36 Egress TimerAI453Load 37 Egress TimerAI454Load 38 Egress TimerAI455Load 39 Egress TimerAI456Load 40 Egress TimerAI457Load 41 Egress TimerAI458Load 42 Egress TimerAI459Load 43 Egress TimerAI460Load 44 Egress TimerAI461Load 45 Egress TimerAI462Load 46 Egress TimerAI463Load 47 Egress TimerAI464Load 48 Egress Timer
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Eaton_Pow_R_Command_PRC100_MOD100_a_LX.csv; the profile maps the registers in the Pow-R-Command Modbus register list (https://www.ccontrols.com/support/dp/IL01412015E.PDF).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 320 of the 464 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Breakers 03-64 follow the same pattern as 01 and 02: peer coil BO n, feedback coil BI 192+n, alarm coil BI 288+n.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
How many BACnet points does the Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX have?
This list has 464 BACnet objects: 64 analog inputs, 208 binary inputs, 192 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX BACnet points are writable?
192 of the 464 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Eaton_Pow_R_Command_PRC100_MOD100_a (Eaton_Pow_R_Command_PRC100_MOD100_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Eaton_Pow_R_Command_PRC100_MOD10.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX?
Start with BO 1 Peer Coils Breaker 01 (Breaker 01 peer coil (writable)); BI 193 Feedback Coils Breaker 01 (Breaker 01 feedback (state)); BI 289 Alarm Coils Breaker 01 (Breaker 01 alarm); BO 2 Peer Coils Breaker 02 (Breaker 02 peer coil (writable)); BI 194 Feedback Coils Breaker 02 (Breaker 02 feedback (state)); BI 290 Alarm Coils Breaker 02 (Breaker 02 alarm).
How do I check these points on the real Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Eaton_Pow_R_Command_PRC100_MOD100_a · Eaton_Pow_R_Command_PRC100_MOD100_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.