Boiler controller (cascade dependent) · BACnet points list

Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for an ArgusVision boiler set up as a dependent: 47 objects (30 AI, 8 AO, 7 BI, 2 BO), 39 polled by default. Outputs set the Modbus units, CH and DHW setpoints (°F and °C versions), boiler operation and CH/DHW modes; inputs give state, status, error and warning codes, supply, return, DHW, flue and exchanger temperatures, firing rate, flame current, water pressure and counters.

This page lists 47 BACnet objects for the Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Equipment
Boiler controller (cascade dependent)
Equipment type
Boilers & water heaters
BACnet objects
47 (10 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ArgusVision, ebmpapst dependent boiler, Argus boiler control
Source document
BASgatewayLX Modbus device profile DEPENDENT_BOILER_a · DEPENDENT_BOILER_a_LX.csv
Download CSV 47 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX

Integration in brief

Set boiler operation and CH mode, write the CH (and DHW) setpoint in the unit you use, then read state, supply/return temperature and firing rate.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 12Boiler operationBoiler operation commandCommand
AO 14CH modeCH modeCommand
AO 8Boiler CH setpoint FCH setpoint, °FCommand
AO 10Boiler DHW setpoint FDHW setpoint, °FCommand
AI 4StateBoiler stateRead
AI 16Supply temperature FSupply temperature, °FRead
AI 18Return temperature FReturn temperature, °FRead
AI 26Firing RateFiring rateRead
AI 6Error CodeError codeRead
AI 7Warning CodeWarning codeRead

Network setup

Watch out for

Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

47 of 47 shown
Type
Access
Show
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX BACnet Points List
DescriptionStates
BO1Modbus Units C/FModbus 400101 bit 0Command
BO2Modbus Units BAR/PSIModbus 400101 bit 1Command
AI3Device typeModbus 400102Read
AImin4StateModbus 400103Read
AI5StatusModbus 400104Read
AImin6Error CodeModbus 400105Read
AImin7Warning CodeModbus 400106Read
AOmin8Boiler CH setpoint FModbus 400107°FCommand
AO9Boiler CH setpoint CModbus 400107; not polled by default°CCommand
AOmin10Boiler DHW setpoint FModbus 400108°FCommand
AO11Boiler DHW setpoint CModbus 400108; not polled by default°CCommand
AOmin12Boiler operationModbus 400109Command
AO13DHW typeModbus 400110Command
AOmin14CH modeModbus 400111Command
AO15DHW modeModbus 400112Command
AImin16Supply temperature FModbus 400113°FRead
AI17Supply temperature CModbus 400113; not polled by default°CRead
AImin18Return temperature FModbus 400114°FRead
AI19Return temperature CModbus 400114; not polled by default°CRead
AI20DHW temperature FModbus 400115°FRead
AI21DHW temperature CModbus 400115; not polled by default°CRead
AI22Flue gas temperature FModbus 400116°FRead
AI23Flue gas temperature CModbus 400116; not polled by default°CRead
AI24Heat exchanger temperature FModbus 400117°FRead
AI25Heat exchanger temperature CModbus 400117; not polled by default°CRead
AImin26Firing RateModbus 400118%Read
AI27Min Firing RateModbus 400119%Read
AI28Flame currentModbus 400120Read
AI29Water pressure PSIModbus 400121psiRead
AI30Water pressure BARModbus 400121; not polled by defaultbarRead
AI31Analog inModbus 400122VRead
AI32Analog outModbus 400123VRead
BI33Information: Flame SignalModbus 400124 bit 0Read
BI34Information: Water levelModbus 400124 bit 1Read
BI35Information: Low gas pressureModbus 400124 bit 2Read
BI36Information: High gas pressureModbus 400124 bit 3Read
BI37Information: Air pressureModbus 400124 bit 4Read
BI38Information: Blocked flueModbus 400124 bit 5Read
BI39Information: Air damperModbus 400124 bit 6Read
AI40CH pumpModbus 400125%Read
AI41DHW pumpModbus 400126%Read
AI42Ignition count OKModbus 400127Read
AI43Ignition count FailedModbus 400128Read
AI44Flame count FailedModbus 400129Read
AI45Burner High hours / CH HoursModbus 400130hRead
AI46Burner Med hours / DHW HoursModbus 400131hRead
AI47Burner Low hoursModbus 400132hRead
Object ID lookup: Contemporary Controls BASgatewayLX ebm-papst Dependent Boiler point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ebm-papst ArgusVision Dependent Boiler via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX

How many BACnet points does the Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX have?

This list has 47 BACnet objects: 30 analog inputs, 8 analog outputs, 7 binary inputs, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX BACnet points are writable?

10 of the 47 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile DEPENDENT_BOILER_a (DEPENDENT_BOILER_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/DependentBoiler.zip.

What are the minimum BACnet points to integrate the Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX?

Start with AO 12 Boiler operation (Boiler operation command); AO 14 CH mode (CH mode); AO 8 Boiler CH setpoint F (CH setpoint, °F); AO 10 Boiler DHW setpoint F (DHW setpoint, °F); AI 4 State (Boiler state); AI 16 Supply temperature F (Supply temperature, °F); AI 18 Return temperature F (Return temperature, °F); AI 26 Firing Rate (Firing rate); AI 6 Error Code (Error code); AI 7 Warning Code (Warning code).

How do I check these points on the real ebm-papst ArgusVision Dependent Boiler via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile DEPENDENT_BOILER_a · DEPENDENT_BOILER_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.