Water heater controller · BACnet points list

Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the XR10CX: 22 objects (1 AI, 6 AO, 12 BI, 3 BO), all polled. It writes the system setpoint, differential, alarm delays, keypad lock and an on/off for control, and reads probe 1 temperature, the call-for-heat relay, probe errors and high/low/external alarms.

This page lists 22 BACnet objects for the Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
PVI Industries XR10CX controller via BASgatewayLX
Equipment
Water heater controller
Equipment type
Boilers & water heaters
BACnet objects
22 (9 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
XR10CX, Dixell XR10CX, PVI XR10CX Modbus
Source document
BASgatewayLX Modbus device profile PVI_Industries_XR10CX_a · PVI_Industries_XR10CX_a_LX.csv
Download CSV 22 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX

Integration in brief

Write On/Off for Control and the system setpoint, then read probe 1 and the call-for-heat relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 8On Off for ControlControl on/offCommand
AO 7System SetpointSystem setpointCommand
AI 1Probe 1 TemperatureProbe 1 temperatureRead
BI 21Relay Call For HeatRelay calling for heatRead
BI 16High Temperature Alarm Pb1High temperature alarmRead
BI 17Low Temperature Alarm Pb1Low temperature alarmRead
BI 12Probe 1 ErrorProbe 1 errorRead
BI 18Alarm from External inputExternal input alarmRead

Network setup

Watch out for

Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

22 of 22 shown
Type
Access
Show
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Probe 1 TemperatureModbus 400257°FRead
AO2DifferentialModbus 400769Command
AO3Temperature Alarm DelayModbus 400830Command
AO4Temp Alarm Delay at StartupModbus 400831Command
AO5Dig Input Alarm Delay 0-255minModbus 400847Command
AO6Modbus Address 1-247Modbus 400852Command
AOmin7System SetpointModbus 400864Command
BOmin8On Off for ControlModbus 000513Command
BO9Keypad LockModbus 000516Command
BO10Mute Buz and Any-AlarmModbus 000517Command
BI11Digital input Pin 9Modbus 000520Read
BImin12Probe 1 ErrorModbus 000521Read
BI13Probe 2 ErrorModbus 000522Read
BI14Probe 3 ErrorModbus 000523Read
BI15Probe 4 ErrorModbus 000524Read
BImin16High Temperature Alarm Pb1Modbus 000525Read
BImin17Low Temperature Alarm Pb1Modbus 000526Read
BImin18Alarm from External inputModbus 000529Read
BI19EEPROM FailureModbus 000532Read
BI20ANY-Alarm Can be MutedModbus 000538Read
BImin21Relay Call For HeatModbus 000543Read
BI22Buzzer On with Ext or Hi AlarmModbus 000545Read
Object ID lookup: Contemporary Controls BASgatewayLX PVI XR10CX point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PVI Industries XR10CX controller via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX

How many BACnet points does the Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX have?

This list has 22 BACnet objects: 1 analog input, 6 analog outputs, 12 binary inputs, 3 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX BACnet points are writable?

9 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile PVI_Industries_XR10CX_a (PVI_Industries_XR10CX_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/PVI_Industries_XR10CX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX?

Start with BO 8 On Off for Control (Control on/off); AO 7 System Setpoint (System setpoint); AI 1 Probe 1 Temperature (Probe 1 temperature); BI 21 Relay Call For Heat (Relay calling for heat); BI 16 High Temperature Alarm Pb1 (High temperature alarm); BI 17 Low Temperature Alarm Pb1 (Low temperature alarm); BI 12 Probe 1 Error (Probe 1 error); BI 18 Alarm from External input (External input alarm).

How do I check these points on the real PVI Industries XR10CX controller via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile PVI_Industries_XR10CX_a · PVI_Industries_XR10CX_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.