- Home
- BACnet points lists
- Contemporary Controls
- Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Combined heat and power (CHP) module · BACnet points list
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Tecogen InVerde Ultra 100: 277 objects (158 AI, 93 BI, 26 BO), but only 20 polled by default: the ready/startup/run/shutdown LEDs plus battery voltage, rpm, voltages, currents, power per leg and frequency. The rest of the map (engine and inverter analog values, alarm bits, relay outputs and start/stop/reset flags) is in the profile unpolled.
This page lists 277 BACnet objects for the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Tecogen InVerde Ultra 100 CHP via BASgatewayLX
- Equipment
- Combined heat and power (CHP) module
- Equipment type
- Other equipment
- BACnet objects
- 277 (26 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Read the Run and Ready LEDs, average power and voltage. Start/stop and alarm reset flags (BO 24-26) exist but are unpolled; check the Tecogen register document before writing them.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 19 | Run LED | Run LED (unit running) | Command |
| BO 17 | Ready LED | Ready LED | Command |
| BO 20 | Shutdown LED | Shutdown LED | Command |
| AI 196 | Average Power (X 10) | Average power (x10) | Read |
| AI 188 | Average voltage (V) | Average voltage, V | Read |
| AI 192 | Average current (A) | Average current | Read |
| AI 197 | Frequency (Hz X 10) | Frequency (Hz x10) | Read |
| AI 182 | RPM | Engine rpm | Read |
| BO 21 | Alarm LED | Alarm LED | Command |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- LED and relay states are Binary Outputs (coils) in this profile; reading them is safe, writing them is not.
- Several values are scaled by 10 as the names say.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 1 | Fuel valve step command | Modbus 000001; not polled by default | Command | ||
| BO | 2 | Fuel valve open command | Modbus 000002; not polled by default | Command | ||
| BO | 3 | O2 sensor 1 heater | Modbus 000003; not polled by default | Command | ||
| BO | 4 | O2 sensor 2 heater | Modbus 000004; not polled by default | Command | ||
| BO | 5 | Gas / Ignition relay | Modbus 000005; not polled by default | Command | ||
| BO | 6 | Engine starter relay | Modbus 000006; not polled by default | Command | ||
| BO | 7 | Pump relay | Modbus 000007; not polled by default | Command | ||
| BO | 8 | Contactor relay | Modbus 000008; not polled by default | Command | ||
| BO | 9 | Alarm relay | Modbus 000009; not polled by default | Command | ||
| BO | 10 | Radiator fan output | Modbus 000010; not polled by default | Command | ||
| BO | 11 | Inverter wakeup | Modbus 000011; not polled by default | Command | ||
| BO | 12 | Hourmeter | Modbus 000012; not polled by default | Command | ||
| BO | 13 | EFLH meter | Modbus 000013; not polled by default | Command | ||
| BO | 14 | Unit started | Modbus 000014; not polled by default | Command | ||
| BO | 15 | Load shed | Modbus 000015; not polled by default | Command | ||
| BO | 16 | Customer output | Modbus 000016; not polled by default | Command | ||
| BOmin | 17 | Ready LED | Modbus 000017 | Command | ||
| BO | 18 | Startup LED | Modbus 000018 | Command | ||
| BOmin | 19 | Run LED | Modbus 000019 | Command | ||
| BOmin | 20 | Shutdown LED | Modbus 000020 | Command | ||
| BOmin | 21 | Alarm LED | Modbus 000021; not polled by default | Command | ||
| BO | 22 | Start LED | Modbus 000022; not polled by default | Command | ||
| BO | 23 | Stop LED | Modbus 000023; not polled by default | Command | ||
| BO | 24 | Start flag | Modbus 000024; not polled by default | Command | ||
| BO | 25 | Network start flag | Modbus 000025; not polled by default | Command | ||
| BO | 26 | Alarm reset flag | Modbus 000026; not polled by default | Command | ||
| BI | 27 | High water pressure switch | Modbus 100001; not polled by default | Read | ||
| BI | 28 | Low water pressure switch | Modbus 100002; not polled by default | Read | ||
| BI | 29 | Low oil pressure switch | Modbus 100003; not polled by default | Read | ||
| BI | 30 | Low oil level switch | Modbus 100004; not polled by default | Read | ||
| BI | 31 | Ignition power verify | Modbus 100005; not polled by default | Read | ||
| BI | 32 | Emergency stop verify | Modbus 100006; not polled by default | Read | ||
| BI | 33 | Protective relay input | Modbus 100007; not polled by default | Read | ||
| BI | 34 | Customer run switch | Modbus 100008; not polled by default | Read | ||
| BI | 35 | Standby run input | Modbus 100009; not polled by default | Read | ||
| BI | 36 | Temperature control mode | Modbus 100010; not polled by default | Read | ||
| BI | 37 | Counter 1 | Modbus 100013; not polled by default | Read | ||
| BI | 38 | Counter 2 | Modbus 100014; not polled by default | Read | ||
| BI | 39 | Counter 3 | Modbus 100015; not polled by default | Read | ||
| BI | 40 | Counter 4 | Modbus 100016; not polled by default | Read | ||
| BI | 41 | Dip switch settings S1-1 | Modbus 100017; not polled by default | Read | ||
| BI | 42 | Dip switch settings S1-2 | Modbus 100018; not polled by default | Read | ||
| BI | 43 | Dip switch settings S1-3 | Modbus 100019; not polled by default | Read | ||
| BI | 44 | Dip switch settings S1-4 | Modbus 100020; not polled by default | Read | ||
| BI | 45 | Dip switch settings S1-5 | Modbus 100021; not polled by default | Read | ||
| BI | 46 | Dip switch settings S1-6 | Modbus 100022; not polled by default | Read | ||
| BI | 47 | Dip switch settings S1-7 | Modbus 100023; not polled by default | Read | ||
| BI | 48 | Dip switch settings S1-8 | Modbus 100024; not polled by default | Read | ||
| BI | 49 | Dip switch settings S2-1 | Modbus 100025; not polled by default | Read | ||
| BI | 50 | Dip switch settings S2-2 | Modbus 100026; not polled by default | Read | ||
| BI | 51 | Dip switch settings S2-3 | Modbus 100027; not polled by default | Read | ||
| BI | 52 | Dip switch settings S2-4 | Modbus 100028; not polled by default | Read | ||
| BI | 53 | Dip switch settings S2-5 | Modbus 100029; not polled by default | Read | ||
| BI | 54 | Dip switch settings S2-6 | Modbus 100030; not polled by default | Read | ||
| BI | 55 | Dip switch settings S2-7 | Modbus 100031; not polled by default | Read | ||
| BI | 56 | Dip switch settings S2-8 | Modbus 100032; not polled by default | Read | ||
| BI | 57 | Dip switch settings S3-1 | Modbus 100033; not polled by default | Read | ||
| BI | 58 | Dip switch settings S3-2 | Modbus 100034; not polled by default | Read | ||
| BI | 59 | Dip switch settings S3-3 | Modbus 100035; not polled by default | Read | ||
| BI | 60 | Dip switch settings S3-4 | Modbus 100036; not polled by default | Read | ||
| BI | 61 | Dip switch settings S3-5 | Modbus 100037; not polled by default | Read | ||
| BI | 62 | Dip switch settings S3-6 | Modbus 100038; not polled by default | Read | ||
| BI | 63 | Dip switch settings S3-7 | Modbus 100039; not polled by default | Read | ||
| BI | 64 | Dip switch settings S3-8 | Modbus 100040; not polled by default | Read | ||
| BI | 65 | Dip switch settings S4-1 | Modbus 100041; not polled by default | Read | ||
| BI | 66 | Dip switch settings S4-2 | Modbus 100042; not polled by default | Read | ||
| BI | 67 | Dip switch settings S4-3 | Modbus 100043; not polled by default | Read | ||
| BI | 68 | Dip switch settings S4-4 | Modbus 100044; not polled by default | Read | ||
| BI | 69 | Dip switch settings S4-5 | Modbus 100045; not polled by default | Read | ||
| BI | 70 | Dip switch settings S4-6 | Modbus 100046; not polled by default | Read | ||
| BI | 71 | Dip switch settings S4-7 | Modbus 100047; not polled by default | Read | ||
| BI | 72 | Dip switch settings S4-8 | Modbus 100048; not polled by default | Read | ||
| BI | 73 | Dip switch settings S5-1 | Modbus 100049; not polled by default | Read | ||
| BI | 74 | Dip switch settings S5-2 | Modbus 100050; not polled by default | Read | ||
| BI | 75 | Dip switch settings S5-3 | Modbus 100051; not polled by default | Read | ||
| BI | 76 | Dip switch settings S5-4 | Modbus 100052; not polled by default | Read | ||
| BI | 77 | Dip switch settings S5-5 | Modbus 100053; not polled by default | Read | ||
| BI | 78 | Dip switch settings S5-6 | Modbus 100054; not polled by default | Read | ||
| BI | 79 | Dip switch settings S5-7 | Modbus 100055; not polled by default | Read | ||
| BI | 80 | Dip switch settings S5-8 | Modbus 100056; not polled by default | Read | ||
| BI | 81 | Dip switch settings S6-1 | Modbus 100057; not polled by default | Read | ||
| BI | 82 | Dip switch settings S6-2 | Modbus 100058; not polled by default | Read | ||
| BI | 83 | Dip switch settings S6-3 | Modbus 100059; not polled by default | Read | ||
| BI | 84 | Dip switch settings S6-4 | Modbus 100060; not polled by default | Read | ||
| BI | 85 | Dip switch settings S6-5 | Modbus 100061; not polled by default | Read | ||
| BI | 86 | Dip switch settings S6-6 | Modbus 100062; not polled by default | Read | ||
| BI | 87 | Dip switch settings S6-7 | Modbus 100063; not polled by default | Read | ||
| BI | 88 | Dip switch settings S6-8 | Modbus 100064; not polled by default | Read | ||
| BI | 89 | Dip switch settings S7-1 | Modbus 100065; not polled by default | Read | ||
| BI | 90 | Dip switch settings S7-2 | Modbus 100066; not polled by default | Read | ||
| BI | 91 | Dip switch settings S7-3 | Modbus 100067; not polled by default | Read | ||
| BI | 92 | Dip switch settings S7-4 | Modbus 100068; not polled by default | Read | ||
| BI | 93 | Dip switch settings S7-5 | Modbus 100069; not polled by default | Read | ||
| BI | 94 | Dip switch settings S7-6 | Modbus 100070; not polled by default | Read | ||
| BI | 95 | Dip switch settings S7-7 | Modbus 100071; not polled by default | Read | ||
| BI | 96 | Dip switch settings S7-8 | Modbus 100072; not polled by default | Read | ||
| BI | 97 | Dip switch settings S8-1 | Modbus 100073; not polled by default | Read | ||
| BI | 98 | Dip switch settings S8-2 | Modbus 100074; not polled by default | Read | ||
| BI | 99 | Dip switch settings S8-3 | Modbus 100075; not polled by default | Read | ||
| BI | 100 | Dip switch settings S8-4 | Modbus 100076; not polled by default | Read | ||
| BI | 101 | Dip switch settings S8-5 | Modbus 100077; not polled by default | Read | ||
| BI | 102 | Dip switch settings S8-6 | Modbus 100078; not polled by default | Read | ||
| BI | 103 | Dip switch settings S8-7 | Modbus 100079; not polled by default | Read | ||
| BI | 104 | Dip switch settings S8-8 | Modbus 100080; not polled by default | Read | ||
| BI | 105 | PCS overload | Modbus 100082; not polled by default | Read | ||
| BI | 106 | PCS PLL OK | Modbus 100087; not polled by default | Read | ||
| BI | 107 | PCS AC line OK | Modbus 100088; not polled by default | Read | ||
| BI | 108 | PCS MG mode | Modbus 100089; not polled by default | Read | ||
| BI | 109 | PCS GT mode | Modbus 100090; not polled by default | Read | ||
| BI | 110 | PCS receive error | Modbus 100095; not polled by default | Read | ||
| BI | 111 | PCS system fault | Modbus 100096; not polled by default | Read | ||
| BI | 112 | MG feeder mode | Modbus 100097; not polled by default | Read | ||
| BI | 113 | MG e voltage OK | Modbus 100098; not polled by default | Read | ||
| BI | 114 | MG e frequency OK | Modbus 100099; not polled by default | Read | ||
| BI | 115 | MG PLL enable | Modbus 100100; not polled by default | Read | ||
| BI | 116 | MG PLL OK | Modbus 100101; not polled by default | Read | ||
| BI | 117 | MG PLL fault | Modbus 100102; not polled by default | Read | ||
| BI | 118 | MG voltage low | Modbus 100103; not polled by default | Read | ||
| BI | 119 | MG contactor fault | Modbus 100104; not polled by default | Read | ||
| AI | 120 | Day of week (0 - 7 Sunday = 0) | Modbus 400001; not polled by default | days | Read | |
| AI | 121 | Year (0 - 99) | Modbus 400002; not polled by default | years | Read | |
| AI | 122 | Month (1 - 12) | Modbus 400003; not polled by default | months | Read | |
| AI | 123 | Date (1 - 31) | Modbus 400004; not polled by default | days | Read | |
| AI | 124 | Hour (0 - 23) | Modbus 400005; not polled by default | h | Read | |
| AI | 125 | Minute (0 - 59) | Modbus 400006; not polled by default | min | Read | |
| AI | 126 | Second (0 - 59) | Modbus 400007; not polled by default | s | Read | |
| AI | 127 | Hundredth of second (0 - 99) | Modbus 400008; not polled by default | 1/100 s | Read | |
| AI | 128 | Permanent power setpoint (kW X 10) | Modbus 400009; not polled by default | kW | Read | |
| AI | 129 | Permanent Temperature setpoint (°F X 10) | Modbus 400010; not polled by default | °F | Read | |
| AI | 130 | Inverter Operation Command | Modbus 400011; not polled by default | Read | ||
| AI | 131 | Inverter Control Mode Command | Modbus 400012; not polled by default | Read | ||
| AI | 132 | Inverter Readback Command | Modbus 400013; not polled by default | Read | ||
| AI | 133 | Inverter Current Set | Modbus 400014; not polled by default | Read | ||
| AI | 134 | Microgrid Operating Mode Command | Modbus 400015; not polled by default | Read | ||
| AI | 135 | Microgrid Voltage Command (0.1V/Bit) | Modbus 400016; not polled by default | V | Read | |
| AI | 136 | Microgrid Output Power Command (0.1kW/Bit) | Modbus 400017; not polled by default | kW | Read | |
| AI | 137 | Microgrid Feeder Power Command (0.1kW/Bit) | Modbus 400018; not polled by default | kW | Read | |
| AI | 138 | Microgrid Q Vs E Droop Command (0.01V/kVA/Bit) | Modbus 400019; not polled by default | Read | ||
| AI | 139 | Microgrid Q Max Command (0.1kVA/Bit) | Modbus 400020; not polled by default | kVA | Read | |
| AI | 140 | Microgrid P Vs Frequency Droop Command (0.00001V/Hz/Bit) | Modbus 400021; not polled by default | Read | ||
| AI | 141 | Microgrid Max Power Command (0.1kW/bit) | Modbus 400022; not polled by default | kW | Read | |
| AI | 142 | Microgrid Min Power Command (0.1kW/bit) | Modbus 400023; not polled by default | kW | Read | |
| AI | 143 | Microgrid Feeder Pow Vs Freq Drop Command (0.00001V/Hz/Bit) | Modbus 400024; not polled by default | Read | ||
| AI | 144 | Microgrid Frequency Command (0.01Hz/Bit) | Modbus 400025; not polled by default | Hz | Read | |
| AI | 145 | Inverter Readback Command | Modbus 400026; not polled by default | Read | ||
| AI | 146 | Setting For Overfrequency 1 (Hz X 10) | Modbus 400027; not polled by default | Hz | Read | |
| AI | 147 | Setting For Underfrequency (Hz X 10) | Modbus 400028; not polled by default | Hz | Read | |
| AI | 148 | Delay For Overfrequency 1 (cycles) | Modbus 400029; not polled by default | Read | ||
| AI | 149 | Delay For Underfrequency 1 (cycles) | Modbus 400030; not polled by default | Read | ||
| AI | 150 | Setting For Overfrequency 2 (Hz X 10) | Modbus 400031; not polled by default | Hz | Read | |
| AI | 151 | Setting For Underfrequency (Hz X 10) | Modbus 400032; not polled by default | Hz | Read | |
| AI | 152 | Delay For Overfrequency 2 (cycles) | Modbus 400033; not polled by default | Read | ||
| AI | 153 | Delay For Underfrequency 2 (cycles) | Modbus 400034; not polled by default | Read | ||
| AI | 154 | Setting For Overvoltage 1 (V) | Modbus 400035; not polled by default | V | Read | |
| AI | 155 | Setting For Undervoltage 1 (V) | Modbus 400036; not polled by default | V | Read | |
| AI | 156 | Delay For Overvoltage 1 (cycles) | Modbus 400037; not polled by default | Read | ||
| AI | 157 | Delay For Undervoltage 1 (cycles) | Modbus 400038; not polled by default | Read | ||
| AI | 158 | Setting For Overvoltage 2 (V) | Modbus 400039; not polled by default | V | Read | |
| AI | 159 | Setting For Undervoltage 2 (V) | Modbus 400040; not polled by default | V | Read | |
| AI | 160 | Delay For Overvoltage 2 (cycles) | Modbus 400041; not polled by default | Read | ||
| AI | 161 | Delay For Undervoltage 2 (cycles) | Modbus 400042; not polled by default | Read | ||
| AI | 162 | Grid-Tie Reconnect Delay (msec) | Modbus 400043; not polled by default | ms | Read | |
| AI | 163 | Sensitivity For Anti-Islanding | Modbus 400044; not polled by default | Read | ||
| AI | 164 | GT Settings Readback Command | Modbus 400045; not polled by default | Read | ||
| AI | 165 | Day of week (0 - 7 Sunday = 0) | Modbus 300001; not polled by default | days | Read | |
| AI | 166 | Year (0 - 99) | Modbus 300002; not polled by default | years | Read | |
| AI | 167 | Month (1 - 12) | Modbus 300003; not polled by default | months | Read | |
| AI | 168 | Date (1 - 31) | Modbus 300004; not polled by default | days | Read | |
| AI | 169 | Hour (0 - 23) | Modbus 300005; not polled by default | h | Read | |
| AI | 170 | Minute (0 - 59) | Modbus 300006; not polled by default | min | Read | |
| AI | 171 | Second (0 - 59) | Modbus 300007; not polled by default | s | Read | |
| AI | 172 | Hundredth of second (0 - 99) | Modbus 300008; not polled by default | 1/100 s | Read | |
| AI | 173 | Operating mode | Modbus 300009; not polled by default | Read | ||
| AI | 174 | Active alarm number | Modbus 300010; not polled by default | Read | ||
| AI | 175 | Active prealarm number | Modbus 300011; not polled by default | Read | ||
| AI | 176 | Active runback number | Modbus 300012; not polled by default | Read | ||
| AI | 177 | Present power setpoint (kW X 10) | Modbus 300013; not polled by default | kW | Read | |
| AI | 178 | Permanent Temperature setpoint (°F X 10) | Modbus 300014; not polled by default | °F | Read | |
| AI | 179 | Logic voltage (mV) | Modbus 300015; not polled by default | mV | Read | |
| AI | 180 | Analog voltage (mV) | Modbus 300016 | mV | Read | |
| AI | 181 | Battery voltage (mV) | Modbus 300017 | mV | Read | |
| AImin | 182 | RPM | Modbus 300018 | rpm | Read | |
| AI | 183 | Total starts | Modbus 300019; not polled by default | Read | ||
| AI | 184 | Total hourmeter (hours) | Modbus 300020; not polled by default | h | Read | |
| AI | 185 | V1 voltage (V) | Modbus 300021 | V | Read | |
| AI | 186 | V2 voltage (V) | Modbus 300022 | V | Read | |
| AI | 187 | V3 voltage (V) | Modbus 300023 | V | Read | |
| AImin | 188 | Average voltage (V) | Modbus 300024 | V | Read | |
| AI | 189 | C1 current (A) | Modbus 300025 | V | Read | |
| AI | 190 | C2 current (A) | Modbus 300026 | V | Read | |
| AI | 191 | C3 current (A) | Modbus 300027 | V | Read | |
| AImin | 192 | Average current (A) | Modbus 300028 | V | Read | |
| AI | 193 | Power Leg 1 (X 10) | Modbus 300029 | Read | ||
| AI | 194 | Power Leg 2 (X 10) | Modbus 300030 | Read | ||
| AI | 195 | Power Leg 3 (X 10) | Modbus 300031 | Read | ||
| AImin | 196 | Average Power (X 10) | Modbus 300032 | Read | ||
| AImin | 197 | Frequency (Hz X 10) | Modbus 300033 | Hz | Read | |
| AI | 198 | Generator inlet temperature (°F X 10) | Modbus 300034; not polled by default | °F | Read | |
| AI | 199 | Generator outlet temperature (°F X 10) | Modbus 300035; not polled by default | °F | Read | |
| AI | 200 | Water inlet temperature (°F X 10) | Modbus 300036; not polled by default | °F | Read | |
| AI | 201 | Water outlet temperature (°F X 10) | Modbus 300037; not polled by default | °F | Read | |
| AI | 202 | Coolant temperature (°F X 10) | Modbus 300038; not polled by default | °F | Read | |
| AI | 203 | Oil temperature (°F X 10) | Modbus 300039; not polled by default | °F | Read | |
| AI | 204 | Enclosure temperature (°F X 10) | Modbus 300040; not polled by default | °F | Read | |
| AI | 205 | Exhaust temperature (°F X 10) | Modbus 300041; not polled by default | °F | Read | |
| AI | 206 | Customer 1 temperature (°F X 10) | Modbus 300042; not polled by default | °F | Read | |
| AI | 207 | Customer 2 temperature (°F X 10) | Modbus 300043; not polled by default | °F | Read | |
| AI | 208 | Customer 3 temperature (°F X 10) | Modbus 300044; not polled by default | °F | Read | |
| AI | 209 | Customer 4 temperature (°F X 10) | Modbus 300045; not polled by default | °F | Read | |
| AI | 210 | Customer 5 temperature (°F X 10) | Modbus 300046; not polled by default | °F | Read | |
| AI | 211 | Customer 6 temperature (°F X 10) | Modbus 300047; not polled by default | °F | Read | |
| AI | 212 | Customer 7 temperature (°F X 10) | Modbus 300048; not polled by default | °F | Read | |
| AI | 213 | SKiiP temperature (°F X 10) | Modbus 300049; not polled by default | °F | Read | |
| AI | 214 | Catalyst outlet temperature (°F) | Modbus 300050; not polled by default | °F | Read | |
| AI | 215 | Catalyst inlet temperature (°F) | Modbus 300051; not polled by default | °F | Read | |
| AI | 216 | TecoNET output coils as word | Modbus 300052; not polled by default | Read | ||
| AI | 217 | TecoNET input coils as word | Modbus 300053; not polled by default | Read | ||
| AI | 218 | O2 sensor (mV) | Modbus 300054; not polled by default | mV | Read | |
| AI | 219 | Long-term block learn | Modbus 300055; not polled by default | Read | ||
| AI | 220 | Short-term block learn | Modbus 300056; not polled by default | Read | ||
| AI | 221 | Fuel valve position (%) | Modbus 300057; not polled by default | % | Read | |
| AI | 222 | Manifold absolute pressure inches of Hg X 10 | Modbus 300058; not polled by default | inHg | Read | |
| AI | 223 | Barometric absolute pressure inches of Hg X 10 | Modbus 300059; not polled by default | inHg | Read | |
| AI | 224 | Customer voltage input 1 | Modbus 300060; not polled by default | Read | ||
| AI | 225 | Customer voltage input 2 | Modbus 300061; not polled by default | Read | ||
| AI | 226 | Customer voltage input 3 | Modbus 300062; not polled by default | Read | ||
| AI | 227 | Customer voltage input 4 | Modbus 300063; not polled by default | Read | ||
| AI | 228 | Customer voltage input 5 | Modbus 300064; not polled by default | Read | ||
| AI | 229 | Customer voltage input 6 | Modbus 300065; not polled by default | Read | ||
| AI | 230 | Counter 1 | Modbus 300066; not polled by default | Read | ||
| AI | 231 | Counter 2 | Modbus 300067; not polled by default | Read | ||
| AI | 232 | Counter 3 | Modbus 300068; not polled by default | Read | ||
| AI | 233 | Counter 4 | Modbus 300069; not polled by default | Read | ||
| AI | 234 | Total energy (MW-hr) | Modbus 300070; not polled by default | MWh | Read | |
| AI | 235 | Total heat (MMBTU) | Modbus 300071; not polled by default | MBtu | Read | |
| AI | 236 | Inverter State | Modbus 300072; not polled by default | Read | ||
| AI | 237 | Inverter Status | Modbus 300073; not polled by default | Read | ||
| AI | 238 | Inverter Faults | Modbus 300074; not polled by default | Read | ||
| AI | 239 | Micogrid State | Modbus 300075; not polled by default | Read | ||
| AI | 240 | Micogrid Status | Modbus 300076; not polled by default | Read | ||
| AI | 241 | Micogrid Faults | Modbus 300077; not polled by default | Read | ||
| AI | 242 | Micogrid VLoop | Modbus 300078; not polled by default | Read | ||
| AI | 243 | Inverter DC Voltage | Modbus 300079; not polled by default | V | Read | |
| AI | 244 | Inverter Voltage Phase A | Modbus 300080; not polled by default | V | Read | |
| AI | 245 | Inverter Current Phase A | Modbus 300081; not polled by default | A | Read | |
| AI | 246 | Inverter kW Phase A X 10 | Modbus 300082; not polled by default | kW | Read | |
| AI | 247 | Inverter kVA Phase A X 10 | Modbus 300083; not polled by default | kW | Read | |
| AI | 248 | Inverter Voltage Phase B | Modbus 300084; not polled by default | V | Read | |
| AI | 249 | Inverter Current Phase B | Modbus 300085; not polled by default | A | Read | |
| AI | 250 | Inverter kW Phase B X 10 | Modbus 300086; not polled by default | kW | Read | |
| AI | 251 | Inverter kVA Phase B X 10 | Modbus 300087; not polled by default | kVA | Read | |
| AI | 252 | Inverter Voltage Phase C | Modbus 300088; not polled by default | V | Read | |
| AI | 253 | Inverter Current Phase C | Modbus 300089; not polled by default | A | Read | |
| AI | 254 | Inverter kW Phase C X 10 | Modbus 300090; not polled by default | kW | Read | |
| AI | 255 | Inverter kVA Phase C X 10 | Modbus 300091; not polled by default | kVA | Read | |
| AI | 256 | Inverter Skiip Temperature | Modbus 300092; not polled by default | Read | ||
| AI | 257 | Inverter Debug 1 | Modbus 300093; not polled by default | Read | ||
| AI | 258 | Inverter Debug 2 | Modbus 300094; not polled by default | Read | ||
| AI | 259 | Inverter Debug 3 | Modbus 300095; not polled by default | Read | ||
| AI | 260 | Line Voltage Phase A | Modbus 300096; not polled by default | V | Read | |
| AI | 261 | Line Voltage Phase B | Modbus 300097; not polled by default | V | Read | |
| AI | 262 | Line Voltage Phase C | Modbus 300098; not polled by default | V | Read | |
| AI | 263 | Inverter Power X 10 | Modbus 300099; not polled by default | Read | ||
| AI | 264 | Inverter Power Percent X 10 | Modbus 300100; not polled by default | Read | ||
| AI | 265 | Inverter Current Sum Of Mean | Modbus 300101; not polled by default | Read | ||
| AI | 266 | Micogrid Current D (0.1A/Bit) | Modbus 300102; not polled by default | A | Read | |
| AI | 267 | Micogrid Current Q (0.1A/Bit) | Modbus 300103; not polled by default | A | Read | |
| AI | 268 | Micogrid Voltage D (0.1V/Bit) | Modbus 300104; not polled by default | V | Read | |
| AI | 269 | Micogrid Voltage Q (0.1V/Bit) | Modbus 300105; not polled by default | V | Read | |
| AI | 270 | Micogrid P (0.1kW/Bit) | Modbus 300106; not polled by default | kW | Read | |
| AI | 271 | Micogrid Q (0.1kVA/Bit) | Modbus 300107; not polled by default | kVA | Read | |
| AI | 272 | Micogrid F (0.1kW/Bit) | Modbus 300108; not polled by default | kW | Read | |
| AI | 273 | Micogrid E0 (0.1V/Bit) | Modbus 300109; not polled by default | V | Read | |
| AI | 274 | Micogrid Feeder Current D (0.1A/Bit) | Modbus 300110; not polled by default | A | Read | |
| AI | 275 | Micogrid Feeder Current Q (0.1A/Bit) | Modbus 300111; not polled by default | A | Read | |
| AI | 276 | Micogrid E Out (0.1V.bit) | Modbus 300112; not polled by default | V | Read | |
| AI | 277 | Micogrid Frequency (0.01Hz/bit) | Modbus 300113; not polled by default | Hz | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Tecogen InVerde 100 point IDs by name
BO1Fuel valve step commandBO2Fuel valve open commandBO3O2 sensor 1 heaterBO4O2 sensor 2 heaterBO5Gas / Ignition relayBO6Engine starter relayBO7Pump relayBO8Contactor relayBO9Alarm relayBO10Radiator fan outputBO11Inverter wakeupBO12HourmeterBO13EFLH meterBO14Unit startedBO15Load shedBO16Customer outputBO17Ready LEDBO18Startup LEDBO19Run LEDBO20Shutdown LEDBO21Alarm LEDBO22Start LEDBO23Stop LEDBO24Start flagBO25Network start flagBO26Alarm reset flagBI27High water pressure switchBI28Low water pressure switchBI29Low oil pressure switchBI30Low oil level switchBI31Ignition power verifyBI32Emergency stop verifyBI33Protective relay inputBI34Customer run switchBI35Standby run inputBI36Temperature control modeBI37Counter 1BI38Counter 2BI39Counter 3BI40Counter 4BI41Dip switch settings S1-1BI42Dip switch settings S1-2BI43Dip switch settings S1-3BI44Dip switch settings S1-4BI45Dip switch settings S1-5BI46Dip switch settings S1-6BI47Dip switch settings S1-7BI48Dip switch settings S1-8BI49Dip switch settings S2-1BI50Dip switch settings S2-2BI51Dip switch settings S2-3BI52Dip switch settings S2-4BI53Dip switch settings S2-5BI54Dip switch settings S2-6BI55Dip switch settings S2-7BI56Dip switch settings S2-8BI57Dip switch settings S3-1BI58Dip switch settings S3-2BI59Dip switch settings S3-3BI60Dip switch settings S3-4BI61Dip switch settings S3-5BI62Dip switch settings S3-6BI63Dip switch settings S3-7BI64Dip switch settings S3-8BI65Dip switch settings S4-1BI66Dip switch settings S4-2BI67Dip switch settings S4-3BI68Dip switch settings S4-4BI69Dip switch settings S4-5BI70Dip switch settings S4-6BI71Dip switch settings S4-7BI72Dip switch settings S4-8BI73Dip switch settings S5-1BI74Dip switch settings S5-2BI75Dip switch settings S5-3BI76Dip switch settings S5-4BI77Dip switch settings S5-5BI78Dip switch settings S5-6BI79Dip switch settings S5-7BI80Dip switch settings S5-8BI81Dip switch settings S6-1BI82Dip switch settings S6-2BI83Dip switch settings S6-3BI84Dip switch settings S6-4BI85Dip switch settings S6-5BI86Dip switch settings S6-6BI87Dip switch settings S6-7BI88Dip switch settings S6-8BI89Dip switch settings S7-1BI90Dip switch settings S7-2BI91Dip switch settings S7-3BI92Dip switch settings S7-4BI93Dip switch settings S7-5BI94Dip switch settings S7-6BI95Dip switch settings S7-7BI96Dip switch settings S7-8BI97Dip switch settings S8-1BI98Dip switch settings S8-2BI99Dip switch settings S8-3BI100Dip switch settings S8-4BI101Dip switch settings S8-5BI102Dip switch settings S8-6BI103Dip switch settings S8-7BI104Dip switch settings S8-8BI105PCS overloadBI106PCS PLL OKBI107PCS AC line OKBI108PCS MG modeBI109PCS GT modeBI110PCS receive errorBI111PCS system faultBI112MG feeder modeBI113MG e voltage OKBI114MG e frequency OKBI115MG PLL enableBI116MG PLL OKBI117MG PLL faultBI118MG voltage lowBI119MG contactor faultAI120Day of week (0 - 7 Sunday = 0)AI121Year (0 - 99)AI122Month (1 - 12)AI123Date (1 - 31)AI124Hour (0 - 23)AI125Minute (0 - 59)AI126Second (0 - 59)AI127Hundredth of second (0 - 99)AI128Permanent power setpoint (kW X 10)AI129Permanent Temperature setpoint (°F X 10)AI130Inverter Operation CommandAI131Inverter Control Mode CommandAI132Inverter Readback CommandAI133Inverter Current SetAI134Microgrid Operating Mode CommandAI135Microgrid Voltage Command (0.1V/Bit)AI136Microgrid Output Power Command (0.1kW/Bit)AI137Microgrid Feeder Power Command (0.1kW/Bit)AI138Microgrid Q Vs E Droop Command (0.01V/kVA/Bit)AI139Microgrid Q Max Command (0.1kVA/Bit)AI140Microgrid P Vs Frequency Droop Command (0.00001V/Hz/Bit)AI141Microgrid Max Power Command (0.1kW/bit)AI142Microgrid Min Power Command (0.1kW/bit)AI143Microgrid Feeder Pow Vs Freq Drop Command (0.00001V/Hz/Bit)AI144Microgrid Frequency Command (0.01Hz/Bit)AI145Inverter Readback CommandAI146Setting For Overfrequency 1 (Hz X 10)AI147Setting For Underfrequency (Hz X 10)AI148Delay For Overfrequency 1 (cycles)AI149Delay For Underfrequency 1 (cycles)AI150Setting For Overfrequency 2 (Hz X 10)AI151Setting For Underfrequency (Hz X 10)AI152Delay For Overfrequency 2 (cycles)AI153Delay For Underfrequency 2 (cycles)AI154Setting For Overvoltage 1 (V)AI155Setting For Undervoltage 1 (V)AI156Delay For Overvoltage 1 (cycles)AI157Delay For Undervoltage 1 (cycles)AI158Setting For Overvoltage 2 (V)AI159Setting For Undervoltage 2 (V)AI160Delay For Overvoltage 2 (cycles)AI161Delay For Undervoltage 2 (cycles)AI162Grid-Tie Reconnect Delay (msec)AI163Sensitivity For Anti-IslandingAI164GT Settings Readback CommandAI165Day of week (0 - 7 Sunday = 0)AI166Year (0 - 99)AI167Month (1 - 12)AI168Date (1 - 31)AI169Hour (0 - 23)AI170Minute (0 - 59)AI171Second (0 - 59)AI172Hundredth of second (0 - 99)AI173Operating modeAI174Active alarm numberAI175Active prealarm numberAI176Active runback numberAI177Present power setpoint (kW X 10)AI178Permanent Temperature setpoint (°F X 10)AI179Logic voltage (mV)AI180Analog voltage (mV)AI181Battery voltage (mV)AI182RPMAI183Total startsAI184Total hourmeter (hours)AI185V1 voltage (V)AI186V2 voltage (V)AI187V3 voltage (V)AI188Average voltage (V)AI189C1 current (A)AI190C2 current (A)AI191C3 current (A)AI192Average current (A)AI193Power Leg 1 (X 10)AI194Power Leg 2 (X 10)AI195Power Leg 3 (X 10)AI196Average Power (X 10)AI197Frequency (Hz X 10)AI198Generator inlet temperature (°F X 10)AI199Generator outlet temperature (°F X 10)AI200Water inlet temperature (°F X 10)AI201Water outlet temperature (°F X 10)AI202Coolant temperature (°F X 10)AI203Oil temperature (°F X 10)AI204Enclosure temperature (°F X 10)AI205Exhaust temperature (°F X 10)AI206Customer 1 temperature (°F X 10)AI207Customer 2 temperature (°F X 10)AI208Customer 3 temperature (°F X 10)AI209Customer 4 temperature (°F X 10)AI210Customer 5 temperature (°F X 10)AI211Customer 6 temperature (°F X 10)AI212Customer 7 temperature (°F X 10)AI213SKiiP temperature (°F X 10)AI214Catalyst outlet temperature (°F)AI215Catalyst inlet temperature (°F)AI216TecoNET output coils as wordAI217TecoNET input coils as wordAI218O2 sensor (mV)AI219Long-term block learnAI220Short-term block learnAI221Fuel valve position (%)AI222Manifold absolute pressure inches of Hg X 10AI223Barometric absolute pressure inches of Hg X 10AI224Customer voltage input 1AI225Customer voltage input 2AI226Customer voltage input 3AI227Customer voltage input 4AI228Customer voltage input 5AI229Customer voltage input 6AI230Counter 1AI231Counter 2AI232Counter 3AI233Counter 4AI234Total energy (MW-hr)AI235Total heat (MMBTU)AI236Inverter StateAI237Inverter StatusAI238Inverter FaultsAI239Micogrid StateAI240Micogrid StatusAI241Micogrid FaultsAI242Micogrid VLoopAI243Inverter DC VoltageAI244Inverter Voltage Phase AAI245Inverter Current Phase AAI246Inverter kW Phase A X 10AI247Inverter kVA Phase A X 10AI248Inverter Voltage Phase BAI249Inverter Current Phase BAI250Inverter kW Phase B X 10AI251Inverter kVA Phase B X 10AI252Inverter Voltage Phase CAI253Inverter Current Phase CAI254Inverter kW Phase C X 10AI255Inverter kVA Phase C X 10AI256Inverter Skiip TemperatureAI257Inverter Debug 1AI258Inverter Debug 2AI259Inverter Debug 3AI260Line Voltage Phase AAI261Line Voltage Phase BAI262Line Voltage Phase CAI263Inverter Power X 10AI264Inverter Power Percent X 10AI265Inverter Current Sum Of MeanAI266Micogrid Current D (0.1A/Bit)AI267Micogrid Current Q (0.1A/Bit)AI268Micogrid Voltage D (0.1V/Bit)AI269Micogrid Voltage Q (0.1V/Bit)AI270Micogrid P (0.1kW/Bit)AI271Micogrid Q (0.1kVA/Bit)AI272Micogrid F (0.1kW/Bit)AI273Micogrid E0 (0.1V/Bit)AI274Micogrid Feeder Current D (0.1A/Bit)AI275Micogrid Feeder Current Q (0.1A/Bit)AI276Micogrid E Out (0.1V.bit)AI277Micogrid Frequency (0.01Hz/bit)
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile TECOGEN_INV_100_a_LX.csv; the profile maps the registers in the InVerde 100 Modbus register list (https://www.ccontrols.com/support/dp/TecogenINV-100.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 20 of the 277 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Counter 1; Counter 2; Counter 3...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tecogen InVerde Ultra 100 CHP via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
How many BACnet points does the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX have?
This list has 277 BACnet objects: 158 analog inputs, 93 binary inputs, 26 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet points are writable?
26 of the 277 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile TECOGEN_INV_100_a (TECOGEN_INV_100_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/TECOGEN_INV_100.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX?
Start with BO 19 Run LED (Run LED (unit running)); BO 17 Ready LED (Ready LED); BO 20 Shutdown LED (Shutdown LED); AI 196 Average Power (X 10) (Average power (x10)); AI 188 Average voltage (V) (Average voltage, V); AI 192 Average current (A) (Average current); AI 197 Frequency (Hz X 10) (Frequency (Hz x10)); AI 182 RPM (Engine rpm); BO 21 Alarm LED (Alarm LED).
How do I check these points on the real Tecogen InVerde Ultra 100 CHP via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile TECOGEN_INV_100_a · TECOGEN_INV_100_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.