Combined heat and power (CHP) module · BACnet points list

Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Tecogen InVerde Ultra 100: 277 objects (158 AI, 93 BI, 26 BO), but only 20 polled by default: the ready/startup/run/shutdown LEDs plus battery voltage, rpm, voltages, currents, power per leg and frequency. The rest of the map (engine and inverter analog values, alarm bits, relay outputs and start/stop/reset flags) is in the profile unpolled.

This page lists 277 BACnet objects for the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Equipment
Combined heat and power (CHP) module
Equipment type
Other equipment
BACnet objects
277 (26 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus
Source document
BASgatewayLX Modbus device profile TECOGEN_INV_100_a · TECOGEN_INV_100_a_LX.csv
Download CSV 277 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX

Integration in brief

Read the Run and Ready LEDs, average power and voltage. Start/stop and alarm reset flags (BO 24-26) exist but are unpolled; check the Tecogen register document before writing them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 19Run LEDRun LED (unit running)Command
BO 17Ready LEDReady LEDCommand
BO 20Shutdown LEDShutdown LEDCommand
AI 196Average Power (X 10)Average power (x10)Read
AI 188Average voltage (V)Average voltage, VRead
AI 192Average current (A)Average currentRead
AI 197Frequency (Hz X 10)Frequency (Hz x10)Read
AI 182RPMEngine rpmRead
BO 21Alarm LEDAlarm LEDCommand

Network setup

Watch out for

Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

277 of 277 shown
Type
Analog
Access
Show
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet Points List
DescriptionStates
BO1Fuel valve step commandModbus 000001; not polled by defaultCommand
BO2Fuel valve open commandModbus 000002; not polled by defaultCommand
BO3O2 sensor 1 heaterModbus 000003; not polled by defaultCommand
BO4O2 sensor 2 heaterModbus 000004; not polled by defaultCommand
BO5Gas / Ignition relayModbus 000005; not polled by defaultCommand
BO6Engine starter relayModbus 000006; not polled by defaultCommand
BO7Pump relayModbus 000007; not polled by defaultCommand
BO8Contactor relayModbus 000008; not polled by defaultCommand
BO9Alarm relayModbus 000009; not polled by defaultCommand
BO10Radiator fan outputModbus 000010; not polled by defaultCommand
BO11Inverter wakeupModbus 000011; not polled by defaultCommand
BO12HourmeterModbus 000012; not polled by defaultCommand
BO13EFLH meterModbus 000013; not polled by defaultCommand
BO14Unit startedModbus 000014; not polled by defaultCommand
BO15Load shedModbus 000015; not polled by defaultCommand
BO16Customer outputModbus 000016; not polled by defaultCommand
BOmin17Ready LEDModbus 000017Command
BO18Startup LEDModbus 000018Command
BOmin19Run LEDModbus 000019Command
BOmin20Shutdown LEDModbus 000020Command
BOmin21Alarm LEDModbus 000021; not polled by defaultCommand
BO22Start LEDModbus 000022; not polled by defaultCommand
BO23Stop LEDModbus 000023; not polled by defaultCommand
BO24Start flagModbus 000024; not polled by defaultCommand
BO25Network start flagModbus 000025; not polled by defaultCommand
BO26Alarm reset flagModbus 000026; not polled by defaultCommand
BI27High water pressure switchModbus 100001; not polled by defaultRead
BI28Low water pressure switchModbus 100002; not polled by defaultRead
BI29Low oil pressure switchModbus 100003; not polled by defaultRead
BI30Low oil level switchModbus 100004; not polled by defaultRead
BI31Ignition power verifyModbus 100005; not polled by defaultRead
BI32Emergency stop verifyModbus 100006; not polled by defaultRead
BI33Protective relay inputModbus 100007; not polled by defaultRead
BI34Customer run switchModbus 100008; not polled by defaultRead
BI35Standby run inputModbus 100009; not polled by defaultRead
BI36Temperature control modeModbus 100010; not polled by defaultRead
BI37Counter 1Modbus 100013; not polled by defaultRead
BI38Counter 2Modbus 100014; not polled by defaultRead
BI39Counter 3Modbus 100015; not polled by defaultRead
BI40Counter 4Modbus 100016; not polled by defaultRead
BI41Dip switch settings S1-1Modbus 100017; not polled by defaultRead
BI42Dip switch settings S1-2Modbus 100018; not polled by defaultRead
BI43Dip switch settings S1-3Modbus 100019; not polled by defaultRead
BI44Dip switch settings S1-4Modbus 100020; not polled by defaultRead
BI45Dip switch settings S1-5Modbus 100021; not polled by defaultRead
BI46Dip switch settings S1-6Modbus 100022; not polled by defaultRead
BI47Dip switch settings S1-7Modbus 100023; not polled by defaultRead
BI48Dip switch settings S1-8Modbus 100024; not polled by defaultRead
BI49Dip switch settings S2-1Modbus 100025; not polled by defaultRead
BI50Dip switch settings S2-2Modbus 100026; not polled by defaultRead
BI51Dip switch settings S2-3Modbus 100027; not polled by defaultRead
BI52Dip switch settings S2-4Modbus 100028; not polled by defaultRead
BI53Dip switch settings S2-5Modbus 100029; not polled by defaultRead
BI54Dip switch settings S2-6Modbus 100030; not polled by defaultRead
BI55Dip switch settings S2-7Modbus 100031; not polled by defaultRead
BI56Dip switch settings S2-8Modbus 100032; not polled by defaultRead
BI57Dip switch settings S3-1Modbus 100033; not polled by defaultRead
BI58Dip switch settings S3-2Modbus 100034; not polled by defaultRead
BI59Dip switch settings S3-3Modbus 100035; not polled by defaultRead
BI60Dip switch settings S3-4Modbus 100036; not polled by defaultRead
BI61Dip switch settings S3-5Modbus 100037; not polled by defaultRead
BI62Dip switch settings S3-6Modbus 100038; not polled by defaultRead
BI63Dip switch settings S3-7Modbus 100039; not polled by defaultRead
BI64Dip switch settings S3-8Modbus 100040; not polled by defaultRead
BI65Dip switch settings S4-1Modbus 100041; not polled by defaultRead
BI66Dip switch settings S4-2Modbus 100042; not polled by defaultRead
BI67Dip switch settings S4-3Modbus 100043; not polled by defaultRead
BI68Dip switch settings S4-4Modbus 100044; not polled by defaultRead
BI69Dip switch settings S4-5Modbus 100045; not polled by defaultRead
BI70Dip switch settings S4-6Modbus 100046; not polled by defaultRead
BI71Dip switch settings S4-7Modbus 100047; not polled by defaultRead
BI72Dip switch settings S4-8Modbus 100048; not polled by defaultRead
BI73Dip switch settings S5-1Modbus 100049; not polled by defaultRead
BI74Dip switch settings S5-2Modbus 100050; not polled by defaultRead
BI75Dip switch settings S5-3Modbus 100051; not polled by defaultRead
BI76Dip switch settings S5-4Modbus 100052; not polled by defaultRead
BI77Dip switch settings S5-5Modbus 100053; not polled by defaultRead
BI78Dip switch settings S5-6Modbus 100054; not polled by defaultRead
BI79Dip switch settings S5-7Modbus 100055; not polled by defaultRead
BI80Dip switch settings S5-8Modbus 100056; not polled by defaultRead
BI81Dip switch settings S6-1Modbus 100057; not polled by defaultRead
BI82Dip switch settings S6-2Modbus 100058; not polled by defaultRead
BI83Dip switch settings S6-3Modbus 100059; not polled by defaultRead
BI84Dip switch settings S6-4Modbus 100060; not polled by defaultRead
BI85Dip switch settings S6-5Modbus 100061; not polled by defaultRead
BI86Dip switch settings S6-6Modbus 100062; not polled by defaultRead
BI87Dip switch settings S6-7Modbus 100063; not polled by defaultRead
BI88Dip switch settings S6-8Modbus 100064; not polled by defaultRead
BI89Dip switch settings S7-1Modbus 100065; not polled by defaultRead
BI90Dip switch settings S7-2Modbus 100066; not polled by defaultRead
BI91Dip switch settings S7-3Modbus 100067; not polled by defaultRead
BI92Dip switch settings S7-4Modbus 100068; not polled by defaultRead
BI93Dip switch settings S7-5Modbus 100069; not polled by defaultRead
BI94Dip switch settings S7-6Modbus 100070; not polled by defaultRead
BI95Dip switch settings S7-7Modbus 100071; not polled by defaultRead
BI96Dip switch settings S7-8Modbus 100072; not polled by defaultRead
BI97Dip switch settings S8-1Modbus 100073; not polled by defaultRead
BI98Dip switch settings S8-2Modbus 100074; not polled by defaultRead
BI99Dip switch settings S8-3Modbus 100075; not polled by defaultRead
BI100Dip switch settings S8-4Modbus 100076; not polled by defaultRead
BI101Dip switch settings S8-5Modbus 100077; not polled by defaultRead
BI102Dip switch settings S8-6Modbus 100078; not polled by defaultRead
BI103Dip switch settings S8-7Modbus 100079; not polled by defaultRead
BI104Dip switch settings S8-8Modbus 100080; not polled by defaultRead
BI105PCS overloadModbus 100082; not polled by defaultRead
BI106PCS PLL OKModbus 100087; not polled by defaultRead
BI107PCS AC line OKModbus 100088; not polled by defaultRead
BI108PCS MG modeModbus 100089; not polled by defaultRead
BI109PCS GT modeModbus 100090; not polled by defaultRead
BI110PCS receive errorModbus 100095; not polled by defaultRead
BI111PCS system faultModbus 100096; not polled by defaultRead
BI112MG feeder modeModbus 100097; not polled by defaultRead
BI113MG e voltage OKModbus 100098; not polled by defaultRead
BI114MG e frequency OKModbus 100099; not polled by defaultRead
BI115MG PLL enableModbus 100100; not polled by defaultRead
BI116MG PLL OKModbus 100101; not polled by defaultRead
BI117MG PLL faultModbus 100102; not polled by defaultRead
BI118MG voltage lowModbus 100103; not polled by defaultRead
BI119MG contactor faultModbus 100104; not polled by defaultRead
AI120Day of week (0 - 7 Sunday = 0)Modbus 400001; not polled by defaultdaysRead
AI121Year (0 - 99)Modbus 400002; not polled by defaultyearsRead
AI122Month (1 - 12)Modbus 400003; not polled by defaultmonthsRead
AI123Date (1 - 31)Modbus 400004; not polled by defaultdaysRead
AI124Hour (0 - 23)Modbus 400005; not polled by defaulthRead
AI125Minute (0 - 59)Modbus 400006; not polled by defaultminRead
AI126Second (0 - 59)Modbus 400007; not polled by defaultsRead
AI127Hundredth of second (0 - 99)Modbus 400008; not polled by default1/100 sRead
AI128Permanent power setpoint (kW X 10)Modbus 400009; not polled by defaultkWRead
AI129Permanent Temperature setpoint (°F X 10)Modbus 400010; not polled by default°FRead
AI130Inverter Operation CommandModbus 400011; not polled by defaultRead
AI131Inverter Control Mode CommandModbus 400012; not polled by defaultRead
AI132Inverter Readback CommandModbus 400013; not polled by defaultRead
AI133Inverter Current SetModbus 400014; not polled by defaultRead
AI134Microgrid Operating Mode CommandModbus 400015; not polled by defaultRead
AI135Microgrid Voltage Command (0.1V/Bit)Modbus 400016; not polled by defaultVRead
AI136Microgrid Output Power Command (0.1kW/Bit)Modbus 400017; not polled by defaultkWRead
AI137Microgrid Feeder Power Command (0.1kW/Bit)Modbus 400018; not polled by defaultkWRead
AI138Microgrid Q Vs E Droop Command (0.01V/kVA/Bit)Modbus 400019; not polled by defaultRead
AI139Microgrid Q Max Command (0.1kVA/Bit)Modbus 400020; not polled by defaultkVARead
AI140Microgrid P Vs Frequency Droop Command (0.00001V/Hz/Bit)Modbus 400021; not polled by defaultRead
AI141Microgrid Max Power Command (0.1kW/bit)Modbus 400022; not polled by defaultkWRead
AI142Microgrid Min Power Command (0.1kW/bit)Modbus 400023; not polled by defaultkWRead
AI143Microgrid Feeder Pow Vs Freq Drop Command (0.00001V/Hz/Bit)Modbus 400024; not polled by defaultRead
AI144Microgrid Frequency Command (0.01Hz/Bit)Modbus 400025; not polled by defaultHzRead
AI145Inverter Readback CommandModbus 400026; not polled by defaultRead
AI146Setting For Overfrequency 1 (Hz X 10)Modbus 400027; not polled by defaultHzRead
AI147Setting For Underfrequency (Hz X 10)Modbus 400028; not polled by defaultHzRead
AI148Delay For Overfrequency 1 (cycles)Modbus 400029; not polled by defaultRead
AI149Delay For Underfrequency 1 (cycles)Modbus 400030; not polled by defaultRead
AI150Setting For Overfrequency 2 (Hz X 10)Modbus 400031; not polled by defaultHzRead
AI151Setting For Underfrequency (Hz X 10)Modbus 400032; not polled by defaultHzRead
AI152Delay For Overfrequency 2 (cycles)Modbus 400033; not polled by defaultRead
AI153Delay For Underfrequency 2 (cycles)Modbus 400034; not polled by defaultRead
AI154Setting For Overvoltage 1 (V)Modbus 400035; not polled by defaultVRead
AI155Setting For Undervoltage 1 (V)Modbus 400036; not polled by defaultVRead
AI156Delay For Overvoltage 1 (cycles)Modbus 400037; not polled by defaultRead
AI157Delay For Undervoltage 1 (cycles)Modbus 400038; not polled by defaultRead
AI158Setting For Overvoltage 2 (V)Modbus 400039; not polled by defaultVRead
AI159Setting For Undervoltage 2 (V)Modbus 400040; not polled by defaultVRead
AI160Delay For Overvoltage 2 (cycles)Modbus 400041; not polled by defaultRead
AI161Delay For Undervoltage 2 (cycles)Modbus 400042; not polled by defaultRead
AI162Grid-Tie Reconnect Delay (msec)Modbus 400043; not polled by defaultmsRead
AI163Sensitivity For Anti-IslandingModbus 400044; not polled by defaultRead
AI164GT Settings Readback CommandModbus 400045; not polled by defaultRead
AI165Day of week (0 - 7 Sunday = 0)Modbus 300001; not polled by defaultdaysRead
AI166Year (0 - 99)Modbus 300002; not polled by defaultyearsRead
AI167Month (1 - 12)Modbus 300003; not polled by defaultmonthsRead
AI168Date (1 - 31)Modbus 300004; not polled by defaultdaysRead
AI169Hour (0 - 23)Modbus 300005; not polled by defaulthRead
AI170Minute (0 - 59)Modbus 300006; not polled by defaultminRead
AI171Second (0 - 59)Modbus 300007; not polled by defaultsRead
AI172Hundredth of second (0 - 99)Modbus 300008; not polled by default1/100 sRead
AI173Operating modeModbus 300009; not polled by defaultRead
AI174Active alarm numberModbus 300010; not polled by defaultRead
AI175Active prealarm numberModbus 300011; not polled by defaultRead
AI176Active runback numberModbus 300012; not polled by defaultRead
AI177Present power setpoint (kW X 10)Modbus 300013; not polled by defaultkWRead
AI178Permanent Temperature setpoint (°F X 10)Modbus 300014; not polled by default°FRead
AI179Logic voltage (mV)Modbus 300015; not polled by defaultmVRead
AI180Analog voltage (mV)Modbus 300016mVRead
AI181Battery voltage (mV)Modbus 300017mVRead
AImin182RPMModbus 300018rpmRead
AI183Total startsModbus 300019; not polled by defaultRead
AI184Total hourmeter (hours)Modbus 300020; not polled by defaulthRead
AI185V1 voltage (V)Modbus 300021VRead
AI186V2 voltage (V)Modbus 300022VRead
AI187V3 voltage (V)Modbus 300023VRead
AImin188Average voltage (V)Modbus 300024VRead
AI189C1 current (A)Modbus 300025VRead
AI190C2 current (A)Modbus 300026VRead
AI191C3 current (A)Modbus 300027VRead
AImin192Average current (A)Modbus 300028VRead
AI193Power Leg 1 (X 10)Modbus 300029Read
AI194Power Leg 2 (X 10)Modbus 300030Read
AI195Power Leg 3 (X 10)Modbus 300031Read
AImin196Average Power (X 10)Modbus 300032Read
AImin197Frequency (Hz X 10)Modbus 300033HzRead
AI198Generator inlet temperature (°F X 10)Modbus 300034; not polled by default°FRead
AI199Generator outlet temperature (°F X 10)Modbus 300035; not polled by default°FRead
AI200Water inlet temperature (°F X 10)Modbus 300036; not polled by default°FRead
AI201Water outlet temperature (°F X 10)Modbus 300037; not polled by default°FRead
AI202Coolant temperature (°F X 10)Modbus 300038; not polled by default°FRead
AI203Oil temperature (°F X 10)Modbus 300039; not polled by default°FRead
AI204Enclosure temperature (°F X 10)Modbus 300040; not polled by default°FRead
AI205Exhaust temperature (°F X 10)Modbus 300041; not polled by default°FRead
AI206Customer 1 temperature (°F X 10)Modbus 300042; not polled by default°FRead
AI207Customer 2 temperature (°F X 10)Modbus 300043; not polled by default°FRead
AI208Customer 3 temperature (°F X 10)Modbus 300044; not polled by default°FRead
AI209Customer 4 temperature (°F X 10)Modbus 300045; not polled by default°FRead
AI210Customer 5 temperature (°F X 10)Modbus 300046; not polled by default°FRead
AI211Customer 6 temperature (°F X 10)Modbus 300047; not polled by default°FRead
AI212Customer 7 temperature (°F X 10)Modbus 300048; not polled by default°FRead
AI213SKiiP temperature (°F X 10)Modbus 300049; not polled by default°FRead
AI214Catalyst outlet temperature (°F)Modbus 300050; not polled by default°FRead
AI215Catalyst inlet temperature (°F)Modbus 300051; not polled by default°FRead
AI216TecoNET output coils as wordModbus 300052; not polled by defaultRead
AI217TecoNET input coils as wordModbus 300053; not polled by defaultRead
AI218O2 sensor (mV)Modbus 300054; not polled by defaultmVRead
AI219Long-term block learnModbus 300055; not polled by defaultRead
AI220Short-term block learnModbus 300056; not polled by defaultRead
AI221Fuel valve position (%)Modbus 300057; not polled by default%Read
AI222Manifold absolute pressure inches of Hg X 10Modbus 300058; not polled by defaultinHgRead
AI223Barometric absolute pressure inches of Hg X 10Modbus 300059; not polled by defaultinHgRead
AI224Customer voltage input 1Modbus 300060; not polled by defaultRead
AI225Customer voltage input 2Modbus 300061; not polled by defaultRead
AI226Customer voltage input 3Modbus 300062; not polled by defaultRead
AI227Customer voltage input 4Modbus 300063; not polled by defaultRead
AI228Customer voltage input 5Modbus 300064; not polled by defaultRead
AI229Customer voltage input 6Modbus 300065; not polled by defaultRead
AI230Counter 1Modbus 300066; not polled by defaultRead
AI231Counter 2Modbus 300067; not polled by defaultRead
AI232Counter 3Modbus 300068; not polled by defaultRead
AI233Counter 4Modbus 300069; not polled by defaultRead
AI234Total energy (MW-hr)Modbus 300070; not polled by defaultMWhRead
AI235Total heat (MMBTU)Modbus 300071; not polled by defaultMBtuRead
AI236Inverter StateModbus 300072; not polled by defaultRead
AI237Inverter StatusModbus 300073; not polled by defaultRead
AI238Inverter FaultsModbus 300074; not polled by defaultRead
AI239Micogrid StateModbus 300075; not polled by defaultRead
AI240Micogrid StatusModbus 300076; not polled by defaultRead
AI241Micogrid FaultsModbus 300077; not polled by defaultRead
AI242Micogrid VLoopModbus 300078; not polled by defaultRead
AI243Inverter DC VoltageModbus 300079; not polled by defaultVRead
AI244Inverter Voltage Phase AModbus 300080; not polled by defaultVRead
AI245Inverter Current Phase AModbus 300081; not polled by defaultARead
AI246Inverter kW Phase A X 10Modbus 300082; not polled by defaultkWRead
AI247Inverter kVA Phase A X 10Modbus 300083; not polled by defaultkWRead
AI248Inverter Voltage Phase BModbus 300084; not polled by defaultVRead
AI249Inverter Current Phase BModbus 300085; not polled by defaultARead
AI250Inverter kW Phase B X 10Modbus 300086; not polled by defaultkWRead
AI251Inverter kVA Phase B X 10Modbus 300087; not polled by defaultkVARead
AI252Inverter Voltage Phase CModbus 300088; not polled by defaultVRead
AI253Inverter Current Phase CModbus 300089; not polled by defaultARead
AI254Inverter kW Phase C X 10Modbus 300090; not polled by defaultkWRead
AI255Inverter kVA Phase C X 10Modbus 300091; not polled by defaultkVARead
AI256Inverter Skiip TemperatureModbus 300092; not polled by defaultRead
AI257Inverter Debug 1Modbus 300093; not polled by defaultRead
AI258Inverter Debug 2Modbus 300094; not polled by defaultRead
AI259Inverter Debug 3Modbus 300095; not polled by defaultRead
AI260Line Voltage Phase AModbus 300096; not polled by defaultVRead
AI261Line Voltage Phase BModbus 300097; not polled by defaultVRead
AI262Line Voltage Phase CModbus 300098; not polled by defaultVRead
AI263Inverter Power X 10Modbus 300099; not polled by defaultRead
AI264Inverter Power Percent X 10Modbus 300100; not polled by defaultRead
AI265Inverter Current Sum Of MeanModbus 300101; not polled by defaultRead
AI266Micogrid Current D (0.1A/Bit)Modbus 300102; not polled by defaultARead
AI267Micogrid Current Q (0.1A/Bit)Modbus 300103; not polled by defaultARead
AI268Micogrid Voltage D (0.1V/Bit)Modbus 300104; not polled by defaultVRead
AI269Micogrid Voltage Q (0.1V/Bit)Modbus 300105; not polled by defaultVRead
AI270Micogrid P (0.1kW/Bit)Modbus 300106; not polled by defaultkWRead
AI271Micogrid Q (0.1kVA/Bit)Modbus 300107; not polled by defaultkVARead
AI272Micogrid F (0.1kW/Bit)Modbus 300108; not polled by defaultkWRead
AI273Micogrid E0 (0.1V/Bit)Modbus 300109; not polled by defaultVRead
AI274Micogrid Feeder Current D (0.1A/Bit)Modbus 300110; not polled by defaultARead
AI275Micogrid Feeder Current Q (0.1A/Bit)Modbus 300111; not polled by defaultARead
AI276Micogrid E Out (0.1V.bit)Modbus 300112; not polled by defaultVRead
AI277Micogrid Frequency (0.01Hz/bit)Modbus 300113; not polled by defaultHzRead
Object ID lookup: Contemporary Controls BASgatewayLX Tecogen InVerde 100 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Tecogen InVerde Ultra 100 CHP via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX

How many BACnet points does the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX have?

This list has 277 BACnet objects: 158 analog inputs, 93 binary inputs, 26 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet points are writable?

26 of the 277 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile TECOGEN_INV_100_a (TECOGEN_INV_100_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/TECOGEN_INV_100.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX?

Start with BO 19 Run LED (Run LED (unit running)); BO 17 Ready LED (Ready LED); BO 20 Shutdown LED (Shutdown LED); AI 196 Average Power (X 10) (Average power (x10)); AI 188 Average voltage (V) (Average voltage, V); AI 192 Average current (A) (Average current); AI 197 Frequency (Hz X 10) (Frequency (Hz x10)); AI 182 RPM (Engine rpm); BO 21 Alarm LED (Alarm LED).

How do I check these points on the real Tecogen InVerde Ultra 100 CHP via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile TECOGEN_INV_100_a · TECOGEN_INV_100_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.