Power and energy meter · BACnet points list
Contemporary Controls GE EPM 6000 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the GE EPM 6000: 262 Analog Inputs, 37 polled by default. Polled values are total watts, VARs and VA, phase voltages and currents, PF, frequency, neutral current, energy and the averages; the long tail of per-phase, THD and min/max values is unpolled.
This page lists 262 BACnet objects for the Contemporary Controls GE EPM 6000 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- GE EPM 6000 via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 262 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- EPM 6000, EPM6000, GE Multilin EPM 6000
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls GE EPM 6000 via BASgatewayLX
Map total watts (3-phase), delivered energy (Wh) and received energy (Wh) first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 31 | Watts 3-Ph total | Total watts (3-phase) | Read |
| AI 50 | W-hours Delivered | Delivered energy (Wh) | Read |
| AI 49 | W-hours Received | Received energy (Wh) | Read |
| AI 37 | Volts A-B | Voltage A-B | Read |
| AI 40 | Amps A | Current A | Read |
| AI 46 | Power Factor 3-Ph total | Total power factor | Read |
| AI 47 | Frequency | Frequency | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls GE EPM 6000 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Meter Name 1 ASCII | Modbus 400001; not polled by default | Read | ||
| AI | 2 | Meter Name 2 ASCII | Modbus 400002; not polled by default | Read | ||
| AI | 3 | Meter Name 3 ASCII | Modbus 400003; not polled by default | Read | ||
| AI | 4 | Meter Name 4 ASCII | Modbus 400004; not polled by default | Read | ||
| AI | 5 | Meter Name 5 ASCII | Modbus 400005; not polled by default | Read | ||
| AI | 6 | Meter Name 6 ASCII | Modbus 400006; not polled by default | Read | ||
| AI | 7 | Meter Name 7 ASCII | Modbus 400007; not polled by default | Read | ||
| AI | 8 | Meter Name 8 ASCII | Modbus 400008; not polled by default | Read | ||
| AI | 9 | Meter Serial Number1 ASCII ASCII | Modbus 400009; not polled by default | Read | ||
| AI | 10 | Meter Serial Number2 ASCII ASCII | Modbus 400010; not polled by default | Read | ||
| AI | 11 | Meter Serial Number3 ASCII ASCII | Modbus 400011; not polled by default | Read | ||
| AI | 12 | Meter Serial Number4 ASCII ASCII | Modbus 400012; not polled by default | Read | ||
| AI | 13 | Meter Serial Number5 ASCII ASCII | Modbus 400013; not polled by default | Read | ||
| AI | 14 | Meter Serial Number6 ASCII ASCII | Modbus 400014; not polled by default | Read | ||
| AI | 15 | Meter Serial Number7 ASCII ASCII | Modbus 400015; not polled by default | Read | ||
| AI | 16 | Meter Serial Number8 ASCII ASCII | Modbus 400016; not polled by default | Read | ||
| AI | 17 | Meter Type | Modbus 400017; not polled by default | Read | ||
| AI | 18 | Firmware Version1 ASCII | Modbus 400018; not polled by default | Read | ||
| AI | 19 | Firmware Version2 ASCII | Modbus 400019; not polled by default | Read | ||
| AI | 20 | Map Version | Modbus 400020; not polled by default | Read | ||
| AI | 21 | Meter Configuration | Modbus 400021; not polled by default | Read | ||
| AI | 22 | ASIC Version | Modbus 400022; not polled by default | Read | ||
| AI | 23 | GE Part Number1 ASCII ASCII | Modbus 400040; not polled by default | Read | ||
| AI | 24 | GE Part Number2 ASCII ASCII | Modbus 400041; not polled by default | Read | ||
| AI | 25 | GE Part Number3 ASCII ASCII | Modbus 400042; not polled by default | Read | ||
| AI | 26 | GE Part Number4 ASCII ASCII | Modbus 400043; not polled by default | Read | ||
| AI | 27 | GE Part Number5 ASCII ASCII | Modbus 400044; not polled by default | Read | ||
| AI | 28 | GE Part Number6 ASCII ASCII | Modbus 400045; not polled by default | Read | ||
| AI | 29 | GE Part Number7 ASCII ASCII | Modbus 400046; not polled by default | Read | ||
| AI | 30 | GE Part Number8 ASCII ASCII | Modbus 400047; not polled by default | Read | ||
| AImin | 31 | Watts 3-Ph total | Modbus 400900 | W | Read | |
| AI | 32 | VARs 3-Ph total | Modbus 400902 | VAR | Read | |
| AI | 33 | VAs 3-Ph total | Modbus 400904 | VA | Read | |
| AI | 34 | Volts A-N | Modbus 401000 | V | Read | |
| AI | 35 | Volts B-N | Modbus 401002 | V | Read | |
| AI | 36 | Volts C-N | Modbus 401004 | V | Read | |
| AImin | 37 | Volts A-B | Modbus 401006 | V | Read | |
| AI | 38 | Volts B-C | Modbus 401008 | V | Read | |
| AI | 39 | Volts C-A | Modbus 401010 | V | Read | |
| AImin | 40 | Amps A | Modbus 401012 | A | Read | |
| AI | 41 | Amps B | Modbus 401014 | A | Read | |
| AI | 42 | Amps C | Modbus 401016 | A | Read | |
| AI | 43 | Watts 3-Ph total | Modbus 401018 | W | Read | |
| AI | 44 | VARs 3-Ph total | Modbus 401020 | VAR | Read | |
| AI | 45 | VAs 3-Ph total | Modbus 401022 | VA | Read | |
| AImin | 46 | Power Factor 3-Ph total | Modbus 401024 | Read | ||
| AImin | 47 | Frequency | Modbus 401026 | Hz | Read | |
| AI | 48 | Neutral Current | Modbus 401028 | A | Read | |
| AImin | 49 | W-hours Received | Modbus 401100 | Wh | Read | |
| AImin | 50 | W-hours Delivered | Modbus 401102 | Wh | Read | |
| AI | 51 | W-hours Net | Modbus 401104 | Wh | Read | |
| AI | 52 | W-hours Total | Modbus 401106 | Wh | Read | |
| AI | 53 | VAR-hours Positive | Modbus 401108 | Read | ||
| AI | 54 | VAR-hours Negative | Modbus 401110 | Read | ||
| AI | 55 | VAR-hours Net | Modbus 401112 | Read | ||
| AI | 56 | VAR-hours Total | Modbus 401114 | Read | ||
| AI | 57 | VA-hours Total | Modbus 401116 | Read | ||
| AI | 58 | Amps A Average | Modbus 402000 | A | Read | |
| AI | 59 | Amps B Average | Modbus 402002 | A | Read | |
| AI | 60 | Amps C Average | Modbus 402004 | A | Read | |
| AI | 61 | Positive Watts 3-Ph Average | Modbus 402006 | W | Read | |
| AI | 62 | Positive VARs 3-Ph Average | Modbus 402008 | VAR | Read | |
| AI | 63 | Negative Watts 3-Ph Average | Modbus 402010 | W | Read | |
| AI | 64 | Negative VARs 3-Ph Average | Modbus 402012 | VAR | Read | |
| AI | 65 | VAs 3-Ph Average | Modbus 402014 | VA | Read | |
| AI | 66 | Positive PF 3-Ph Average | Modbus 402016 | Read | ||
| AI | 67 | Negative PF 3-PF Average | Modbus 402018 | Read | ||
| AI | 68 | Volts A-N Minimum | Modbus 403000; not polled by default | V | Read | |
| AI | 69 | Volts B-N Minimum | Modbus 403002; not polled by default | V | Read | |
| AI | 70 | Volts C-N Minimum | Modbus 403004; not polled by default | V | Read | |
| AI | 71 | Volts A-B Minimum | Modbus 403006; not polled by default | V | Read | |
| AI | 72 | Volts B-C Minimum | Modbus 403008; not polled by default | V | Read | |
| AI | 73 | Volts C-A Minimum | Modbus 403010; not polled by default | V | Read | |
| AI | 74 | Amps A Minimum Avg Demand | Modbus 403012; not polled by default | A | Read | |
| AI | 75 | Amps B Minimum Avg Demand | Modbus 403014; not polled by default | A | Read | |
| AI | 76 | Amps C Minimum Avg Demand | Modbus 403016; not polled by default | A | Read | |
| AI | 77 | Positive Watts 3-Ph Minimum Avg Demand | Modbus 403018; not polled by default | W | Read | |
| AI | 78 | Positive VARs 3-Ph Minimum Avg Demand | Modbus 403020; not polled by default | VAR | Read | |
| AI | 79 | Negative Watts 3-Ph Minimum Avg Demand | Modbus 403022; not polled by default | W | Read | |
| AI | 80 | Negative VARs 3-Ph Minimum Avg Demand | Modbus 403024; not polled by default | VAR | Read | |
| AI | 81 | VAs 3-Ph Minimum Avg Demand | Modbus 403026; not polled by default | VA | Read | |
| AI | 82 | Positive Power Factor 3-Ph Minimum Avg Demand | Modbus 403028; not polled by default | Read | ||
| AI | 83 | Negative Power Factor 3-Ph Minimum Avg Demand | Modbus 403030; not polled by default | Read | ||
| AI | 84 | Frequency Minimum | Modbus 403032; not polled by default | Hz | Read | |
| AI | 85 | Volts A-N Maximum | Modbus 403100; not polled by default | V | Read | |
| AI | 86 | Volts B-N Maximum | Modbus 403102; not polled by default | V | Read | |
| AI | 87 | Volts C-N Maximum | Modbus 403104; not polled by default | V | Read | |
| AI | 88 | Volts A-B Maximum | Modbus 403106; not polled by default | V | Read | |
| AI | 89 | Volts B-C Maximum | Modbus 403108; not polled by default | V | Read | |
| AI | 90 | Volts C-A Maximum | Modbus 403110; not polled by default | V | Read | |
| AI | 91 | Amps A Maximum Avg Demand | Modbus 403112; not polled by default | A | Read | |
| AI | 92 | Amps B Maximum Avg Demand | Modbus 403114; not polled by default | A | Read | |
| AI | 93 | Amps C Maximum Avg Demand | Modbus 403116; not polled by default | A | Read | |
| AI | 94 | Positive Watts 3-Ph Maximum Avg Demand | Modbus 403118; not polled by default | W | Read | |
| AI | 95 | Positive VARs 3-Ph Maximum Avg Demand | Modbus 403120; not polled by default | VAR | Read | |
| AI | 96 | Negative Watts 3-Ph Maximum Avg Demand | Modbus 403122; not polled by default | W | Read | |
| AI | 97 | Negative VARs 3-Ph Maximum Avg Demand | Modbus 403124; not polled by default | VAR | Read | |
| AI | 98 | VAs 3-Ph Maximum Avg Demand | Modbus 403126; not polled by default | VA | Read | |
| AI | 99 | Positive Power Factor 3-Ph Maximum Avg Demand | Modbus 403128; not polled by default | Read | ||
| AI | 100 | Negative Power Factor 3-Ph Maximum Avg Demand | Modbus 403130; not polled by default | Read | ||
| AI | 101 | Frequency Maximum | Modbus 403132; not polled by default | Hz | Read | |
| AI | 102 | Volts A-N %THD | Modbus 404000; not polled by default | ° | Read | |
| AI | 103 | Volts B-N %THD | Modbus 404001; not polled by default | ° | Read | |
| AI | 104 | Volts C-N %THD | Modbus 404002; not polled by default | ° | Read | |
| AI | 105 | Amps A %THD | Modbus 404003; not polled by default | ° | Read | |
| AI | 106 | Amps B %THD | Modbus 404004; not polled by default | ° | Read | |
| AI | 107 | Amps C %THD | Modbus 404005; not polled by default | ° | Read | |
| AI | 108 | Phase A Current 0th harmonic magnitude | Modbus 404006; not polled by default | % | Read | |
| AI | 109 | Phase A Current 1st harmonic magnitude | Modbus 404007; not polled by default | Read | ||
| AI | 110 | Phase A Current 2nd harmonic magnitude | Modbus 404008; not polled by default | Read | ||
| AI | 111 | Phase A Current 3rd harmonic magnitude | Modbus 404009; not polled by default | Read | ||
| AI | 112 | Phase A Current 4th harmonic magnitude | Modbus 404010; not polled by default | Read | ||
| AI | 113 | Phase A Current 5th harmonic magnitude | Modbus 404011; not polled by default | Read | ||
| AI | 114 | Phase A Current 6th harmonic magnitude | Modbus 404012; not polled by default | Read | ||
| AI | 115 | Phase A Current 7th harmonic magnitude | Modbus 404013; not polled by default | Read | ||
| AI | 116 | Phase A Voltage 0th harmonic magnitude | Modbus 404014; not polled by default | Read | ||
| AI | 117 | Phase A Voltage 1st harmonic magnitude | Modbus 404015; not polled by default | Read | ||
| AI | 118 | Phase A Voltage 2nd harmonic magnitude | Modbus 404016; not polled by default | Read | ||
| AI | 119 | Phase A Voltage 3rd harmonic magnitude | Modbus 404017; not polled by default | Read | ||
| AI | 120 | Phase B Current 0th harmonic magnitude | Modbus 404018; not polled by default | Read | ||
| AI | 121 | Phase B Current 1st harmonic magnitude | Modbus 404019; not polled by default | Read | ||
| AI | 122 | Phase B Current 2nd harmonic magnitude | Modbus 404020; not polled by default | Read | ||
| AI | 123 | Phase B Current 3rd harmonic magnitude | Modbus 404021; not polled by default | Read | ||
| AI | 124 | Phase B Current 4th harmonic magnitude | Modbus 404022; not polled by default | Read | ||
| AI | 125 | Phase B Current 5th harmonic magnitude | Modbus 404023; not polled by default | Read | ||
| AI | 126 | Phase B Current 6th harmonic magnitude | Modbus 404024; not polled by default | Read | ||
| AI | 127 | Phase B Current 7th harmonic magnitude | Modbus 404025; not polled by default | Read | ||
| AI | 128 | Phase B Voltage 0th harmonic magnitude | Modbus 404026; not polled by default | Read | ||
| AI | 129 | Phase B Voltage 1st harmonic magnitude | Modbus 404027; not polled by default | Read | ||
| AI | 130 | Phase B Voltage 2nd harmonic magnitude | Modbus 404028; not polled by default | Read | ||
| AI | 131 | Phase B Voltage 3rd harmonic magnitude | Modbus 404029; not polled by default | Read | ||
| AI | 132 | Phase C Current 0th harmonic magnitude | Modbus 404030; not polled by default | Read | ||
| AI | 133 | Phase C Current 1st harmonic magnitude | Modbus 404031; not polled by default | Read | ||
| AI | 134 | Phase C Current 2nd harmonic magnitude | Modbus 404032; not polled by default | Read | ||
| AI | 135 | Phase C Current 3rd harmonic magnitude | Modbus 404033; not polled by default | Read | ||
| AI | 136 | Phase C Current 4th harmonic magnitude | Modbus 404034; not polled by default | Read | ||
| AI | 137 | Phase C Current 5th harmonic magnitude | Modbus 404035; not polled by default | Read | ||
| AI | 138 | Phase C Current 6th harmonic magnitude | Modbus 404036; not polled by default | Read | ||
| AI | 139 | Phase C Current 7th harmonic magnitude | Modbus 404037; not polled by default | Read | ||
| AI | 140 | Phase C Voltage 0th harmonic magnitude | Modbus 404038; not polled by default | Read | ||
| AI | 141 | Phase C Voltage 1st harmonic magnitude | Modbus 404039; not polled by default | Read | ||
| AI | 142 | Phase C Voltage 2nd harmonic magnitude | Modbus 404040; not polled by default | Read | ||
| AI | 143 | Phase C Voltage 3rd harmonic magnitude | Modbus 404041; not polled by default | Read | ||
| AI | 144 | Phase A Current | Modbus 404100; not polled by default | ° | Read | |
| AI | 145 | Phase B Current | Modbus 404101; not polled by default | ° | Read | |
| AI | 146 | Phase C Current | Modbus 404102; not polled by default | ° | Read | |
| AI | 147 | Angle Volts A-B | Modbus 404103; not polled by default | ° | Read | |
| AI | 148 | Angle Volts B-C | Modbus 404104; not polled by default | ° | Read | |
| AI | 149 | Angle Volts C-A | Modbus 404105; not polled by default | ° | Read | |
| AI | 150 | Meter Status | Modbus 405000; not polled by default | Read | ||
| AI | 151 | Limits Status7 | Modbus 405001; not polled by default | Read | ||
| AI | 152 | T ime Since Reset | Modbus 405002; not polled by default | ms | Read | |
| AI | 153 | Reset Max/Min Blocks | Modbus 420000; not polled by default | Read | ||
| AI | 154 | Reset Energy Accumulators | Modbus 420001; not polled by default | Read | ||
| AI | 155 | Initiate Programmable Settings Update | Modbus 422000; not polled by default | Read | ||
| AI | 156 | Terminate Programmable Settings Update3 | Modbus 422001; not polled by default | Read | ||
| AI | 157 | Calculate Programmable Settings Checksum3 | Modbus 422002; not polled by default | Read | ||
| AI | 158 | Programmable Settings Checksum3 | Modbus 422003; not polled by default | Read | ||
| AI | 159 | Write New Password3 | Modbus 422004; not polled by default | Read | ||
| AI | 160 | Initiate Meter Firmware Reprogramming | Modbus 423000; not polled by default | Read | ||
| AI | 161 | Force Meter Restart | Modbus 425000; not polled by default | Read | ||
| AI | 162 | Perform a Secure Operation 1 | Modbus 426000; not polled by default | Read | ||
| AI | 163 | Perform a Secure Operation 2 | Modbus 426001; not polled by default | Read | ||
| AI | 164 | Perform a Secure Operation 3 | Modbus 426002; not polled by default | Read | ||
| AI | 165 | Perform a Secure Operation 4 | Modbus 426003; not polled by default | Read | ||
| AI | 166 | Perform a Secure Operation 5 | Modbus 426004; not polled by default | Read | ||
| AI | 167 | Perform a Secure Operation 6 | Modbus 426005; not polled by default | Read | ||
| AI | 168 | Perform a Secure Operation 7 | Modbus 426006; not polled by default | Read | ||
| AI | 169 | Perform a Secure Operation 8 | Modbus 426007; not polled by default | Read | ||
| AI | 170 | Perform a Secure Operation 9 | Modbus 426008; not polled by default | Read | ||
| AI | 171 | Perform a Secure Operation 10 | Modbus 426009; not polled by default | Read | ||
| AI | 172 | Perform a Secure Operation 11 | Modbus 426010; not polled by default | Read | ||
| AI | 173 | Perform a Secure Operation 12 | Modbus 426011; not polled by default | Read | ||
| AI | 174 | CT multiplier denominator | Modbus 430000; not polled by default | Read | ||
| AI | 175 | CT numerator | Modbus 430001; not polled by default | Read | ||
| AI | 176 | PT numerator | Modbus 430002; not polled by default | Read | ||
| AI | 177 | PT denominator | Modbus 430003; not polled by default | Read | ||
| AI | 178 | PT multiplier hookup | Modbus 430004; not polled by default | Read | ||
| AI | 179 | Averaging Method | Modbus 430005; not polled by default | Read | ||
| AI | 180 | Power Energy Format | Modbus 430006; not polled by default | Read | ||
| AI | 181 | Operating Mode Screen Enables | Modbus 430007; not polled by default | Read | ||
| AI | 182 | User Settings Flags | Modbus 430015; not polled by default | Read | ||
| AI | 183 | Full Scale Current (for load % bargraph) | Modbus 430016; not polled by default | Read | ||
| AI | 184 | Meter Designation 1 ASCII 1 ASCII | Modbus 430017; not polled by default | Read | ||
| AI | 185 | Meter Designation 2 ASCII 2 ASCII | Modbus 430018; not polled by default | Read | ||
| AI | 186 | Meter Designation 3 ASCII 3 ASCII | Modbus 430019; not polled by default | Read | ||
| AI | 187 | Meter Designation 4 ASCII 4 ASCII | Modbus 430020; not polled by default | Read | ||
| AI | 188 | Meter Designation 5 ASCII 5 ASCII | Modbus 430021; not polled by default | Read | ||
| AI | 189 | Meter Designation 6 ASCII 6 ASCII | Modbus 430022; not polled by default | Read | ||
| AI | 190 | Meter Designation 7 ASCII 7 ASCII | Modbus 430023; not polled by default | Read | ||
| AI | 191 | Meter Designation 8 ASCII 8 ASCII | Modbus 430024; not polled by default | Read | ||
| AI | 192 | COM1 setup | Modbus 430025; not polled by default | Read | ||
| AI | 193 | COM2 setup | Modbus 430026; not polled by default | Read | ||
| AI | 194 | COM2 address | Modbus 430027; not polled by default | Read | ||
| AI | 195 | Limit #1 Identifier | Modbus 430028; not polled by default | Read | ||
| AI | 196 | Limit #1 Out High Setpoint | Modbus 430029; not polled by default | % | Read | |
| AI | 197 | Limit #1 In High Threshold | Modbus 430030; not polled by default | % | Read | |
| AI | 198 | Limit #1 Out Low Setpoint | Modbus 430031; not polled by default | % | Read | |
| AI | 199 | Limit #1 In Low Threshold | Modbus 430032; not polled by default | % | Read | |
| AI | 200 | Limit #2 (a) | Modbus 430033; not polled by default | Read | ||
| AI | 201 | Limit #2 (b) | Modbus 430034; not polled by default | Read | ||
| AI | 202 | Limit #2 (c) | Modbus 430035; not polled by default | Read | ||
| AI | 203 | Limit #2 (d) | Modbus 430036; not polled by default | Read | ||
| AI | 204 | Limit #2 (c) | Modbus 430037; not polled by default | Read | ||
| AI | 205 | Limit #3 (a) | Modbus 430038; not polled by default | Read | ||
| AI | 206 | Limit #3 (b) | Modbus 430039; not polled by default | Read | ||
| AI | 207 | Limit #3 (c) | Modbus 430040; not polled by default | Read | ||
| AI | 208 | Limit #3 (d) | Modbus 430041; not polled by default | Read | ||
| AI | 209 | Limit #3 (c) | Modbus 430042; not polled by default | Read | ||
| AI | 210 | Limit #4 (a) | Modbus 430043; not polled by default | Read | ||
| AI | 211 | Limit #4 (b) | Modbus 430044; not polled by default | Read | ||
| AI | 212 | Limit #4 (c) | Modbus 430045; not polled by default | Read | ||
| AI | 213 | Limit #4 (d) | Modbus 430046; not polled by default | Read | ||
| AI | 214 | Limit #4 (c) | Modbus 430047; not polled by default | Read | ||
| AI | 215 | Limit #5 (a) | Modbus 430048; not polled by default | Read | ||
| AI | 216 | Limit #5 (b) | Modbus 430049; not polled by default | Read | ||
| AI | 217 | Limit #5 (c) | Modbus 430050; not polled by default | Read | ||
| AI | 218 | Limit #5 (d) | Modbus 430051; not polled by default | Read | ||
| AI | 219 | Limit #5 (c) | Modbus 430052; not polled by default | Read | ||
| AI | 220 | Limit #6 (a) | Modbus 430053; not polled by default | Read | ||
| AI | 221 | Limit #6 (b) | Modbus 430054; not polled by default | Read | ||
| AI | 222 | Limit #6 (c) | Modbus 430055; not polled by default | Read | ||
| AI | 223 | Limit #6 (d) | Modbus 430056; not polled by default | Read | ||
| AI | 224 | Limit #6 (c) | Modbus 430057; not polled by default | Read | ||
| AI | 225 | Limit #7 (a) | Modbus 430058; not polled by default | Read | ||
| AI | 226 | Limit #7 (b) | Modbus 430059; not polled by default | Read | ||
| AI | 227 | Limit #7 (c) | Modbus 430060; not polled by default | Read | ||
| AI | 228 | Limit #7 (d) | Modbus 430061; not polled by default | Read | ||
| AI | 229 | Limit #7 (c) | Modbus 430062; not polled by default | Read | ||
| AI | 230 | Limit #8 (a) | Modbus 430063; not polled by default | Read | ||
| AI | 231 | Limit #8 (b) | Modbus 430064; not polled by default | Read | ||
| AI | 232 | Limit #8 (c) | Modbus 430065; not polled by default | Read | ||
| AI | 233 | Limit #8 (d) | Modbus 430066; not polled by default | Read | ||
| AI | 234 | Limit #8 (c) | Modbus 430067; not polled by default | Read | ||
| AI | 235 | System Sanity Indicator | Modbus 440001; not polled by default | Read | ||
| AI | 236 | Volts A-N | Modbus 440002; not polled by default | V | Read | |
| AI | 237 | Volts B-N | Modbus 440003; not polled by default | V | Read | |
| AI | 238 | Volts C-N | Modbus 440004; not polled by default | V | Read | |
| AI | 239 | Amps A | Modbus 440005; not polled by default | A | Read | |
| AI | 240 | Amps B | Modbus 440006; not polled by default | A | Read | |
| AI | 241 | Amps C | Modbus 440007; not polled by default | A | Read | |
| AI | 242 | Watts 3-Ph total | Modbus 440008; not polled by default | W | Read | |
| AI | 243 | VARs 3-Ph total | Modbus 440009; not polled by default | VAR | Read | |
| AI | 244 | VAs 3-Ph total | Modbus 440010; not polled by default | VA | Read | |
| AI | 245 | Power Factor 3-Ph total | Modbus 440011; not polled by default | Read | ||
| AI | 246 | Frequency | Modbus 440012; not polled by default | Hz | Read | |
| AI | 247 | Volts A-B | Modbus 440013; not polled by default | V | Read | |
| AI | 248 | Volts B-C | Modbus 440014; not polled by default | V | Read | |
| AI | 249 | Volts C-A | Modbus 440015; not polled by default | V | Read | |
| AI | 250 | CT numerator | Modbus 440016; not polled by default | Read | ||
| AI | 251 | CT multiplier | Modbus 440017; not polled by default | Read | ||
| AI | 252 | CT denominator | Modbus 440018; not polled by default | Read | ||
| AI | 253 | PT numerator | Modbus 440019; not polled by default | Read | ||
| AI | 254 | PT multiplier | Modbus 440020; not polled by default | Read | ||
| AI | 255 | PT denominator | Modbus 440021; not polled by default | Read | ||
| AI | 256 | W-hours Positive | Modbus 440022; not polled by default | Wh | Read | |
| AI | 257 | W-hours Negative | Modbus 440024; not polled by default | Wh | Read | |
| AI | 258 | VAR-hours Positive | Modbus 440026; not polled by default | Read | ||
| AI | 259 | VAR-hours Negative | Modbus 440028; not polled by default | Read | ||
| AI | 260 | VA-hours | Modbus 440030; not polled by default | Read | ||
| AI | 261 | Neutral Current | Modbus 440032; not polled by default | A | Read | |
| AI | 262 | Reset Energy Accumulators | Modbus 440100; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX GE EPM 6000 point IDs by name
AI1Meter Name 1 ASCIIAI2Meter Name 2 ASCIIAI3Meter Name 3 ASCIIAI4Meter Name 4 ASCIIAI5Meter Name 5 ASCIIAI6Meter Name 6 ASCIIAI7Meter Name 7 ASCIIAI8Meter Name 8 ASCIIAI9Meter Serial Number1 ASCII ASCIIAI10Meter Serial Number2 ASCII ASCIIAI11Meter Serial Number3 ASCII ASCIIAI12Meter Serial Number4 ASCII ASCIIAI13Meter Serial Number5 ASCII ASCIIAI14Meter Serial Number6 ASCII ASCIIAI15Meter Serial Number7 ASCII ASCIIAI16Meter Serial Number8 ASCII ASCIIAI17Meter TypeAI18Firmware Version1 ASCIIAI19Firmware Version2 ASCIIAI20Map VersionAI21Meter ConfigurationAI22ASIC VersionAI23GE Part Number1 ASCII ASCIIAI24GE Part Number2 ASCII ASCIIAI25GE Part Number3 ASCII ASCIIAI26GE Part Number4 ASCII ASCIIAI27GE Part Number5 ASCII ASCIIAI28GE Part Number6 ASCII ASCIIAI29GE Part Number7 ASCII ASCIIAI30GE Part Number8 ASCII ASCIIAI31Watts 3-Ph totalAI32VARs 3-Ph totalAI33VAs 3-Ph totalAI34Volts A-NAI35Volts B-NAI36Volts C-NAI37Volts A-BAI38Volts B-CAI39Volts C-AAI40Amps AAI41Amps BAI42Amps CAI43Watts 3-Ph totalAI44VARs 3-Ph totalAI45VAs 3-Ph totalAI46Power Factor 3-Ph totalAI47FrequencyAI48Neutral CurrentAI49W-hours ReceivedAI50W-hours DeliveredAI51W-hours NetAI52W-hours TotalAI53VAR-hours PositiveAI54VAR-hours NegativeAI55VAR-hours NetAI56VAR-hours TotalAI57VA-hours TotalAI58Amps A AverageAI59Amps B AverageAI60Amps C AverageAI61Positive Watts 3-Ph AverageAI62Positive VARs 3-Ph AverageAI63Negative Watts 3-Ph AverageAI64Negative VARs 3-Ph AverageAI65VAs 3-Ph AverageAI66Positive PF 3-Ph AverageAI67Negative PF 3-PF AverageAI68Volts A-N MinimumAI69Volts B-N MinimumAI70Volts C-N MinimumAI71Volts A-B MinimumAI72Volts B-C MinimumAI73Volts C-A MinimumAI74Amps A Minimum Avg DemandAI75Amps B Minimum Avg DemandAI76Amps C Minimum Avg DemandAI77Positive Watts 3-Ph Minimum Avg DemandAI78Positive VARs 3-Ph Minimum Avg DemandAI79Negative Watts 3-Ph Minimum Avg DemandAI80Negative VARs 3-Ph Minimum Avg DemandAI81VAs 3-Ph Minimum Avg DemandAI82Positive Power Factor 3-Ph Minimum Avg DemandAI83Negative Power Factor 3-Ph Minimum Avg DemandAI84Frequency MinimumAI85Volts A-N MaximumAI86Volts B-N MaximumAI87Volts C-N MaximumAI88Volts A-B MaximumAI89Volts B-C MaximumAI90Volts C-A MaximumAI91Amps A Maximum Avg DemandAI92Amps B Maximum Avg DemandAI93Amps C Maximum Avg DemandAI94Positive Watts 3-Ph Maximum Avg DemandAI95Positive VARs 3-Ph Maximum Avg DemandAI96Negative Watts 3-Ph Maximum Avg DemandAI97Negative VARs 3-Ph Maximum Avg DemandAI98VAs 3-Ph Maximum Avg DemandAI99Positive Power Factor 3-Ph Maximum Avg DemandAI100Negative Power Factor 3-Ph Maximum Avg DemandAI101Frequency MaximumAI102Volts A-N %THDAI103Volts B-N %THDAI104Volts C-N %THDAI105Amps A %THDAI106Amps B %THDAI107Amps C %THDAI108Phase A Current 0th harmonic magnitudeAI109Phase A Current 1st harmonic magnitudeAI110Phase A Current 2nd harmonic magnitudeAI111Phase A Current 3rd harmonic magnitudeAI112Phase A Current 4th harmonic magnitudeAI113Phase A Current 5th harmonic magnitudeAI114Phase A Current 6th harmonic magnitudeAI115Phase A Current 7th harmonic magnitudeAI116Phase A Voltage 0th harmonic magnitudeAI117Phase A Voltage 1st harmonic magnitudeAI118Phase A Voltage 2nd harmonic magnitudeAI119Phase A Voltage 3rd harmonic magnitudeAI120Phase B Current 0th harmonic magnitudeAI121Phase B Current 1st harmonic magnitudeAI122Phase B Current 2nd harmonic magnitudeAI123Phase B Current 3rd harmonic magnitudeAI124Phase B Current 4th harmonic magnitudeAI125Phase B Current 5th harmonic magnitudeAI126Phase B Current 6th harmonic magnitudeAI127Phase B Current 7th harmonic magnitudeAI128Phase B Voltage 0th harmonic magnitudeAI129Phase B Voltage 1st harmonic magnitudeAI130Phase B Voltage 2nd harmonic magnitudeAI131Phase B Voltage 3rd harmonic magnitudeAI132Phase C Current 0th harmonic magnitudeAI133Phase C Current 1st harmonic magnitudeAI134Phase C Current 2nd harmonic magnitudeAI135Phase C Current 3rd harmonic magnitudeAI136Phase C Current 4th harmonic magnitudeAI137Phase C Current 5th harmonic magnitudeAI138Phase C Current 6th harmonic magnitudeAI139Phase C Current 7th harmonic magnitudeAI140Phase C Voltage 0th harmonic magnitudeAI141Phase C Voltage 1st harmonic magnitudeAI142Phase C Voltage 2nd harmonic magnitudeAI143Phase C Voltage 3rd harmonic magnitudeAI144Phase A CurrentAI145Phase B CurrentAI146Phase C CurrentAI147Angle Volts A-BAI148Angle Volts B-CAI149Angle Volts C-AAI150Meter StatusAI151Limits Status7AI152T ime Since ResetAI153Reset Max/Min BlocksAI154Reset Energy AccumulatorsAI155Initiate Programmable Settings UpdateAI156Terminate Programmable Settings Update3AI157Calculate Programmable Settings Checksum3AI158Programmable Settings Checksum3AI159Write New Password3AI160Initiate Meter Firmware ReprogrammingAI161Force Meter RestartAI162Perform a Secure Operation 1AI163Perform a Secure Operation 2AI164Perform a Secure Operation 3AI165Perform a Secure Operation 4AI166Perform a Secure Operation 5AI167Perform a Secure Operation 6AI168Perform a Secure Operation 7AI169Perform a Secure Operation 8AI170Perform a Secure Operation 9AI171Perform a Secure Operation 10AI172Perform a Secure Operation 11AI173Perform a Secure Operation 12AI174CT multiplier denominatorAI175CT numeratorAI176PT numeratorAI177PT denominatorAI178PT multiplier hookupAI179Averaging MethodAI180Power Energy FormatAI181Operating Mode Screen EnablesAI182User Settings FlagsAI183Full Scale Current (for load % bargraph)AI184Meter Designation 1 ASCII 1 ASCIIAI185Meter Designation 2 ASCII 2 ASCIIAI186Meter Designation 3 ASCII 3 ASCIIAI187Meter Designation 4 ASCII 4 ASCIIAI188Meter Designation 5 ASCII 5 ASCIIAI189Meter Designation 6 ASCII 6 ASCIIAI190Meter Designation 7 ASCII 7 ASCIIAI191Meter Designation 8 ASCII 8 ASCIIAI192COM1 setupAI193COM2 setupAI194COM2 addressAI195Limit #1 IdentifierAI196Limit #1 Out High SetpointAI197Limit #1 In High ThresholdAI198Limit #1 Out Low SetpointAI199Limit #1 In Low ThresholdAI200Limit #2 (a)AI201Limit #2 (b)AI202Limit #2 (c)AI203Limit #2 (d)AI204Limit #2 (c)AI205Limit #3 (a)AI206Limit #3 (b)AI207Limit #3 (c)AI208Limit #3 (d)AI209Limit #3 (c)AI210Limit #4 (a)AI211Limit #4 (b)AI212Limit #4 (c)AI213Limit #4 (d)AI214Limit #4 (c)AI215Limit #5 (a)AI216Limit #5 (b)AI217Limit #5 (c)AI218Limit #5 (d)AI219Limit #5 (c)AI220Limit #6 (a)AI221Limit #6 (b)AI222Limit #6 (c)AI223Limit #6 (d)AI224Limit #6 (c)AI225Limit #7 (a)AI226Limit #7 (b)AI227Limit #7 (c)AI228Limit #7 (d)AI229Limit #7 (c)AI230Limit #8 (a)AI231Limit #8 (b)AI232Limit #8 (c)AI233Limit #8 (d)AI234Limit #8 (c)AI235System Sanity IndicatorAI236Volts A-NAI237Volts B-NAI238Volts C-NAI239Amps AAI240Amps BAI241Amps CAI242Watts 3-Ph totalAI243VARs 3-Ph totalAI244VAs 3-Ph totalAI245Power Factor 3-Ph totalAI246FrequencyAI247Volts A-BAI248Volts B-CAI249Volts C-AAI250CT numeratorAI251CT multiplierAI252CT denominatorAI253PT numeratorAI254PT multiplierAI255PT denominatorAI256W-hours PositiveAI257W-hours NegativeAI258VAR-hours PositiveAI259VAR-hours NegativeAI260VA-hoursAI261Neutral CurrentAI262Reset Energy Accumulators
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile GE_EPM6000_PowerMeter_a_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/GEK-106558D.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 37 of the 262 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Watts 3-Ph total; VARs 3-Ph total; VAs 3-Ph total...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE EPM 6000 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls GE EPM 6000 via BASgatewayLX
How many BACnet points does the Contemporary Controls GE EPM 6000 via BASgatewayLX have?
This list has 262 BACnet objects: 262 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls GE EPM 6000 via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls GE EPM 6000 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile GE_EPM6000_PowerMeter_a (GE_EPM6000_PowerMeter_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/GE_EPM6000_PowerMeter.zip.
What are the minimum BACnet points to integrate the Contemporary Controls GE EPM 6000 via BASgatewayLX?
Start with AI 31 Watts 3-Ph total (Total watts (3-phase)); AI 50 W-hours Delivered (Delivered energy (Wh)); AI 49 W-hours Received (Received energy (Wh)); AI 37 Volts A-B (Voltage A-B); AI 40 Amps A (Current A); AI 46 Power Factor 3-Ph total (Total power factor); AI 47 Frequency (Frequency).
How do I check these points on the real GE EPM 6000 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile GE_EPM6000_PowerMeter_a · GE_EPM6000_PowerMeter_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.