  4. Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX

Boiler burner management interface · BACnet points list

Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the TS-1100 touchscreen: 130 objects (66 AI, 6 AO, 58 BI), all polled. Binary inputs show the BMS connection, boiler available, pump status and the LMV and RWF input/output states plus annunciator inputs; six outputs set LMV and RWF remote mode, remote setpoint and remote output; analog inputs give LMV phase, actuator positions, output, setpoint/actual value, flame signal and lockout history.

This page lists 130 BACnet objects for the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Equipment
Boiler burner management interface
Equipment type
Boilers & water heaters
BACnet objects
130 (6 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen
Source document
BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a · TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv
Download CSV 130 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX

Integration in brief

Set LMV remote mode (AO 59), then write the remote setpoint W3 (AO 60) in auto or the remote output (AO 61) in remote-on mode. Read boiler available, LMV phase, output and alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 59LMV remote modeLMV remote modeCommand
AO 60LMV remote setpoint (W3) (remote mode auto)Remote setpoint W3 (auto)Command
AO 61LMV remote output (remote mode on)Remote output (remote on)Command
BI 3Boiler availableBoiler availableRead
BI 7LMV controller on/offLMV controller onRead
AI 65LMV phaseLMV phaseRead
AI 74LMV current outputLMV current outputRead
AI 77LMV flame signalFlame signalRead
BI 20LMV alarmLMV alarmRead
BI 1Active connection from BMSBMS connection activeRead

Network setup

Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

130 of 130 shown
Type
Binary
Access
Show
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet Points List
DescriptionStates
BImin1Active connection from BMSModbus 100001Read
BI2RWF remote disableModbus 100002Read
BImin3Boiler availableModbus 100003Read
BI4Boiler circulating pump run statusModbus 100004Read
BI5Boiler circulating pump timed alarm statusModbus 100005Read
BI6LMV current type of fuelModbus 100006Read
BImin7LMV controller on/offModbus 100007Read
BI8LMV fan contactor contact (LMV5...)Modbus 100008Read
BI9LMV fuel selection oil (LMV5...)Modbus 100009Read
BI10LMV fuel selection gas (LMV5...)Modbus 100010Read
BI11LMV oil max pressure switch (LMV5...)Modbus 100011Read
BI12LMV oil min pressure switch (LMV5...)Modbus 100012Read
BI13LMV valve proving pressure switch (LMV5...)Modbus 100013Read
BI14LMV safety loopModbus 100014Read
BI15LMV gas min pressure switchModbus 100015Read
BI16LMV gas max pressure switchModbus 100016Read
BI17LMV LPModbus 100017Read
BI18LMV start release oilModbus 100018Read
BI19LMV heavy oil immediate releaseModbus 100019Read
BImin20LMV alarmModbus 100020Read
BI21LMV ignitionModbus 100021Read
BI22LMV start signal / DW valve (LMV5...)Modbus 100022Read
BI23LMV fanModbus 100023Read
BI24LMV oil pump / magnetic coupling (LMV5...)Modbus 100024Read
BI25LMV fuel valve SV oil (LMV5...)Modbus 100025Read
BI26LMV fuel valve V1 oil (LMV5...)Modbus 100026Read
BI27LMV fuel valve V2 oil (LMV5...)Modbus 100027Read
BI28LMV fuel valve V3 oil (LMV5...)Modbus 100028Read
BI29LMV fuel valve SV gas (LMV5...)Modbus 100029Read
BI30LMV fuel valve V1 (gas LMV5...)Modbus 100030Read
BI31LMV fuel valve V2 (gas LMV5...)Modbus 100031Read
BI32LMV fuel valve V3 (gas LMV5...)Modbus 100032Read
BI33LMV local/remote modeModbus 100033Read
BI34LMV5... lockout history current fuel selectedModbus 100034Read
BI35LMV5... error history current fuel selectedModbus 100035Read
BI36RWF40 management system thermostat overrideModbus 100036Read
BI37RWF40 binary input 2 closedModbus 100037Read
BI38RWF40 thermostat function activeModbus 100038Read
BI39RWF40 limit comparator activeModbus 100039Read
BI40RWF40 not optioned or RWF55Modbus 100040Read
BI41RWF40 feedwater binary input 2 closedModbus 100041Read
BI42RWF40 feedwater high waterModbus 100042Read
BI43RWF40 feedwater low waterModbus 100043Read
BI44RWF40 feedwater not optioned or RWF55Modbus 100044Read
BI45EA annunciation input 1Modbus 100045Read
BI46EA annunciation input 2Modbus 100046Read
BI47EA annunciation input 3Modbus 100047Read
BI48EA annunciation input 4Modbus 100048Read
BI49EA annunciation input 5Modbus 100049Read
BI50EA annunciation input 6Modbus 100050Read
BI51EA annunciation input 7Modbus 100051Read
BI52EA annunciation input 8Modbus 100052Read
BI53EA annunciation input 9Modbus 100053Read
BI54EA annunciation input 10Modbus 100054Read
BI55EA annunciation input 11Modbus 100055Read
BI56EA annunciation input 12Modbus 100056Read
BI57EA annunciation input 13Modbus 100057Read
BI58EA not optionedModbus 100058Read
AOmin59LMV remote modeModbus 400001Command
AOmin60LMV remote setpoint (W3) (remote mode auto)Modbus 400002Command
AOmin61LMV remote output (remote mode on)Modbus 400003Command
AO62RWF remote modeModbus 400004Command
AO63RWF remote setpointModbus 400005Command
AO64RWF remote outputModbus 400007Command
AImin65LMV phaseModbus 400009Read
AI66LMV position of currently active fuel actuatorModbus 400010Read
AI67LMV position of gas actuator (LMV5...)Modbus 400011Read
AI68LMV position of oil actuator (LMV5...)Modbus 400012Read
AI69LMV position of air actuatorModbus 400013Read
AI70LMV position of auxiliary actuator 1 (LMV5...)Modbus 400014Read
AI71LMV position of auxiliary actuator 2 (LMV5...)Modbus 400015Read
AI72LMV position of auxiliary actuator 3 (LMV5...)Modbus 400016Read
AI73LMV manipulated variable for var speed drive (LMV5...)Modbus 400017Read
AImin74LMV current outputModbus 400018Read
AI75LMV current setpoint / temperature / pressure (LMV5...)Modbus 400019Read
AI76LMV actual value / temperature / pressure (LMV5...)Modbus 400020Read
AImin77LMV flame signalModbus 400021Read
AI78LMV current fuel throughput (LMV5...)Modbus 400022Read
AI79LMV current O2 value (LMV52...)Modbus 400023Read
AI80LMV startup counter totalModbus 400024Read
AI81LMV hours run total (LMV5...)Modbus 400026Read
AI82LMV supply air temperature (LMV52...)Modbus 400028Read
AI83LMV flue gas temperature (LMV52...)Modbus 400029Read
AI84LMV combustion efficiency (LMV52...)Modbus 400030Read
AI85LMV local setpoint W1 (LMV5...)Modbus 400031Read
AI86LMV local setpoint W2 (LMV5...)Modbus 400032Read
AI87LMV fuel volume gas (LMV5...)Modbus 400033Read
AI88LMV fuel volume oil (LMV5...)Modbus 400035Read
AI89LMV5... lockout history current error codeModbus 400037Read
AI90LMV5... lockout history current diagnostic codeModbus 400038Read
AI91LMV5... lockout history current error classModbus 400039Read
AI92LMV5... lockout history current error phaseModbus 400040Read
AI93LMV5... lockout history current outputModbus 400041Read
AI94LMV5... lockout history current date - year(two digit)Modbus 400042Read
AI95LMV5... lockout history current date - monthModbus 400043Read
AI96LMV5... lockout history current date - dayModbus 400044Read
AI97LMV5... lockout history current time - hoursModbus 400045Read
AI98LMV5... lockout history current time - minutesModbus 400046Read
AI99LMV5... lockout history current time - secondsModbus 400047Read
AI100LMV5... lockout history current startup counter totalModbus 400048Read
AI101LMV5... lockout history current hours run totalModbus 400050Read
AI102LMV5... error history current error codeModbus 400052Read
AI103LMV5... error history current diagnostic codeModbus 400053Read
AI104LMV5... error history current error classModbus 400054Read
AI105LMV5... error history current error phaseModbus 400055Read
AI106LMV5... error history current outputModbus 400056Read
AI107LMV5... error history current startup counter totalModbus 400057Read
AI108RWF actual temperature / pressure (E1)Modbus 400059Read
AI109RWF actual (E2)Modbus 400061Read
AI110RWF actual temperature (E3)Modbus 400063Read
AI111RWF current setpointModbus 400065Read
AI112RWF local setpoint (SP1)Modbus 400067Read
AI113RWF local setpoint (SP2)Modbus 400069Read
AI114RWF feedwater actual temperature /pressure (E1)Modbus 400071Read
AI115RWF feedwater actual (E2)Modbus 400073Read
AI116RWF feedwater current setpointModbus 400075Read
AI117RWF feedwater local setpoint (SP1)Modbus 400077Read
AI118EA temperature outputModbus 400079Read
AI119EA configurable analog input 1Modbus 400080Read
AI120EA configurable analog input 2Modbus 400081Read
AI121EA configurable analog input 3Modbus 400082Read
AI122EA configurable analog input 4Modbus 400083Read
AI123EA configurable RTD input 1Modbus 400084Read
AI124EA configurable RTD input 2Modbus 400085Read
AI125EA configurable RTD input 3Modbus 400086Read
AI126EA valve outputModbus 400087Read
AI127EA totalized analog input 1Modbus 400088Read
AI128EA totalized analog input 2Modbus 400090Read
AI129EA totalized analog input 3Modbus 400092Read
AI130EA totalized analog input 4Modbus 400094Read
Object ID lookup: Contemporary Controls BASgatewayLX Siemens TS-1100 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX

How many BACnet points does the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX have?

This list has 130 BACnet objects: 66 analog inputs, 6 analog outputs, 58 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet points are writable?

6 of the 130 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a (TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/TS1100TouchS_RTU_LMV3_LMV5_RWF.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX?

Start with AO 59 LMV remote mode (LMV remote mode); AO 60 LMV remote setpoint (W3) (remote mode auto) (Remote setpoint W3 (auto)); AO 61 LMV remote output (remote mode on) (Remote output (remote on)); BI 3 Boiler available (Boiler available); BI 7 LMV controller on/off (LMV controller on); AI 65 LMV phase (LMV phase); AI 74 LMV current output (LMV current output); AI 77 LMV flame signal (Flame signal); BI 20 LMV alarm (LMV alarm); BI 1 Active connection from BMS (BMS connection active).

How do I check these points on the real Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a · TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.