- Home
- BACnet points lists
- Contemporary Controls
- Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boiler burner management interface · BACnet points list
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the TS-1100 touchscreen: 130 objects (66 AI, 6 AO, 58 BI), all polled. Binary inputs show the BMS connection, boiler available, pump status and the LMV and RWF input/output states plus annunciator inputs; six outputs set LMV and RWF remote mode, remote setpoint and remote output; analog inputs give LMV phase, actuator positions, output, setpoint/actual value, flame signal and lockout history.
This page lists 130 BACnet objects for the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
- Equipment
- Boiler burner management interface
- Equipment type
- Boilers & water heaters
- BACnet objects
- 130 (6 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Set LMV remote mode (AO 59), then write the remote setpoint W3 (AO 60) in auto or the remote output (AO 61) in remote-on mode. Read boiler available, LMV phase, output and alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 59 | LMV remote mode | LMV remote mode | Command |
| AO 60 | LMV remote setpoint (W3) (remote mode auto) | Remote setpoint W3 (auto) | Command |
| AO 61 | LMV remote output (remote mode on) | Remote output (remote on) | Command |
| BI 3 | Boiler available | Boiler available | Read |
| BI 7 | LMV controller on/off | LMV controller on | Read |
| AI 65 | LMV phase | LMV phase | Read |
| AI 74 | LMV current output | LMV current output | Read |
| AI 77 | LMV flame signal | Flame signal | Read |
| BI 20 | LMV alarm | LMV alarm | Read |
| BI 1 | Active connection from BMS | BMS connection active | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | Active connection from BMS | Modbus 100001 | Read | ||
| BI | 2 | RWF remote disable | Modbus 100002 | Read | ||
| BImin | 3 | Boiler available | Modbus 100003 | Read | ||
| BI | 4 | Boiler circulating pump run status | Modbus 100004 | Read | ||
| BI | 5 | Boiler circulating pump timed alarm status | Modbus 100005 | Read | ||
| BI | 6 | LMV current type of fuel | Modbus 100006 | Read | ||
| BImin | 7 | LMV controller on/off | Modbus 100007 | Read | ||
| BI | 8 | LMV fan contactor contact (LMV5...) | Modbus 100008 | Read | ||
| BI | 9 | LMV fuel selection oil (LMV5...) | Modbus 100009 | Read | ||
| BI | 10 | LMV fuel selection gas (LMV5...) | Modbus 100010 | Read | ||
| BI | 11 | LMV oil max pressure switch (LMV5...) | Modbus 100011 | Read | ||
| BI | 12 | LMV oil min pressure switch (LMV5...) | Modbus 100012 | Read | ||
| BI | 13 | LMV valve proving pressure switch (LMV5...) | Modbus 100013 | Read | ||
| BI | 14 | LMV safety loop | Modbus 100014 | Read | ||
| BI | 15 | LMV gas min pressure switch | Modbus 100015 | Read | ||
| BI | 16 | LMV gas max pressure switch | Modbus 100016 | Read | ||
| BI | 17 | LMV LP | Modbus 100017 | Read | ||
| BI | 18 | LMV start release oil | Modbus 100018 | Read | ||
| BI | 19 | LMV heavy oil immediate release | Modbus 100019 | Read | ||
| BImin | 20 | LMV alarm | Modbus 100020 | Read | ||
| BI | 21 | LMV ignition | Modbus 100021 | Read | ||
| BI | 22 | LMV start signal / DW valve (LMV5...) | Modbus 100022 | Read | ||
| BI | 23 | LMV fan | Modbus 100023 | Read | ||
| BI | 24 | LMV oil pump / magnetic coupling (LMV5...) | Modbus 100024 | Read | ||
| BI | 25 | LMV fuel valve SV oil (LMV5...) | Modbus 100025 | Read | ||
| BI | 26 | LMV fuel valve V1 oil (LMV5...) | Modbus 100026 | Read | ||
| BI | 27 | LMV fuel valve V2 oil (LMV5...) | Modbus 100027 | Read | ||
| BI | 28 | LMV fuel valve V3 oil (LMV5...) | Modbus 100028 | Read | ||
| BI | 29 | LMV fuel valve SV gas (LMV5...) | Modbus 100029 | Read | ||
| BI | 30 | LMV fuel valve V1 (gas LMV5...) | Modbus 100030 | Read | ||
| BI | 31 | LMV fuel valve V2 (gas LMV5...) | Modbus 100031 | Read | ||
| BI | 32 | LMV fuel valve V3 (gas LMV5...) | Modbus 100032 | Read | ||
| BI | 33 | LMV local/remote mode | Modbus 100033 | Read | ||
| BI | 34 | LMV5... lockout history current fuel selected | Modbus 100034 | Read | ||
| BI | 35 | LMV5... error history current fuel selected | Modbus 100035 | Read | ||
| BI | 36 | RWF40 management system thermostat override | Modbus 100036 | Read | ||
| BI | 37 | RWF40 binary input 2 closed | Modbus 100037 | Read | ||
| BI | 38 | RWF40 thermostat function active | Modbus 100038 | Read | ||
| BI | 39 | RWF40 limit comparator active | Modbus 100039 | Read | ||
| BI | 40 | RWF40 not optioned or RWF55 | Modbus 100040 | Read | ||
| BI | 41 | RWF40 feedwater binary input 2 closed | Modbus 100041 | Read | ||
| BI | 42 | RWF40 feedwater high water | Modbus 100042 | Read | ||
| BI | 43 | RWF40 feedwater low water | Modbus 100043 | Read | ||
| BI | 44 | RWF40 feedwater not optioned or RWF55 | Modbus 100044 | Read | ||
| BI | 45 | EA annunciation input 1 | Modbus 100045 | Read | ||
| BI | 46 | EA annunciation input 2 | Modbus 100046 | Read | ||
| BI | 47 | EA annunciation input 3 | Modbus 100047 | Read | ||
| BI | 48 | EA annunciation input 4 | Modbus 100048 | Read | ||
| BI | 49 | EA annunciation input 5 | Modbus 100049 | Read | ||
| BI | 50 | EA annunciation input 6 | Modbus 100050 | Read | ||
| BI | 51 | EA annunciation input 7 | Modbus 100051 | Read | ||
| BI | 52 | EA annunciation input 8 | Modbus 100052 | Read | ||
| BI | 53 | EA annunciation input 9 | Modbus 100053 | Read | ||
| BI | 54 | EA annunciation input 10 | Modbus 100054 | Read | ||
| BI | 55 | EA annunciation input 11 | Modbus 100055 | Read | ||
| BI | 56 | EA annunciation input 12 | Modbus 100056 | Read | ||
| BI | 57 | EA annunciation input 13 | Modbus 100057 | Read | ||
| BI | 58 | EA not optioned | Modbus 100058 | Read | ||
| AOmin | 59 | LMV remote mode | Modbus 400001 | Command | ||
| AOmin | 60 | LMV remote setpoint (W3) (remote mode auto) | Modbus 400002 | Command | ||
| AOmin | 61 | LMV remote output (remote mode on) | Modbus 400003 | Command | ||
| AO | 62 | RWF remote mode | Modbus 400004 | Command | ||
| AO | 63 | RWF remote setpoint | Modbus 400005 | Command | ||
| AO | 64 | RWF remote output | Modbus 400007 | Command | ||
| AImin | 65 | LMV phase | Modbus 400009 | Read | ||
| AI | 66 | LMV position of currently active fuel actuator | Modbus 400010 | Read | ||
| AI | 67 | LMV position of gas actuator (LMV5...) | Modbus 400011 | Read | ||
| AI | 68 | LMV position of oil actuator (LMV5...) | Modbus 400012 | Read | ||
| AI | 69 | LMV position of air actuator | Modbus 400013 | Read | ||
| AI | 70 | LMV position of auxiliary actuator 1 (LMV5...) | Modbus 400014 | Read | ||
| AI | 71 | LMV position of auxiliary actuator 2 (LMV5...) | Modbus 400015 | Read | ||
| AI | 72 | LMV position of auxiliary actuator 3 (LMV5...) | Modbus 400016 | Read | ||
| AI | 73 | LMV manipulated variable for var speed drive (LMV5...) | Modbus 400017 | Read | ||
| AImin | 74 | LMV current output | Modbus 400018 | Read | ||
| AI | 75 | LMV current setpoint / temperature / pressure (LMV5...) | Modbus 400019 | Read | ||
| AI | 76 | LMV actual value / temperature / pressure (LMV5...) | Modbus 400020 | Read | ||
| AImin | 77 | LMV flame signal | Modbus 400021 | Read | ||
| AI | 78 | LMV current fuel throughput (LMV5...) | Modbus 400022 | Read | ||
| AI | 79 | LMV current O2 value (LMV52...) | Modbus 400023 | Read | ||
| AI | 80 | LMV startup counter total | Modbus 400024 | Read | ||
| AI | 81 | LMV hours run total (LMV5...) | Modbus 400026 | Read | ||
| AI | 82 | LMV supply air temperature (LMV52...) | Modbus 400028 | Read | ||
| AI | 83 | LMV flue gas temperature (LMV52...) | Modbus 400029 | Read | ||
| AI | 84 | LMV combustion efficiency (LMV52...) | Modbus 400030 | Read | ||
| AI | 85 | LMV local setpoint W1 (LMV5...) | Modbus 400031 | Read | ||
| AI | 86 | LMV local setpoint W2 (LMV5...) | Modbus 400032 | Read | ||
| AI | 87 | LMV fuel volume gas (LMV5...) | Modbus 400033 | Read | ||
| AI | 88 | LMV fuel volume oil (LMV5...) | Modbus 400035 | Read | ||
| AI | 89 | LMV5... lockout history current error code | Modbus 400037 | Read | ||
| AI | 90 | LMV5... lockout history current diagnostic code | Modbus 400038 | Read | ||
| AI | 91 | LMV5... lockout history current error class | Modbus 400039 | Read | ||
| AI | 92 | LMV5... lockout history current error phase | Modbus 400040 | Read | ||
| AI | 93 | LMV5... lockout history current output | Modbus 400041 | Read | ||
| AI | 94 | LMV5... lockout history current date - year(two digit) | Modbus 400042 | Read | ||
| AI | 95 | LMV5... lockout history current date - month | Modbus 400043 | Read | ||
| AI | 96 | LMV5... lockout history current date - day | Modbus 400044 | Read | ||
| AI | 97 | LMV5... lockout history current time - hours | Modbus 400045 | Read | ||
| AI | 98 | LMV5... lockout history current time - minutes | Modbus 400046 | Read | ||
| AI | 99 | LMV5... lockout history current time - seconds | Modbus 400047 | Read | ||
| AI | 100 | LMV5... lockout history current startup counter total | Modbus 400048 | Read | ||
| AI | 101 | LMV5... lockout history current hours run total | Modbus 400050 | Read | ||
| AI | 102 | LMV5... error history current error code | Modbus 400052 | Read | ||
| AI | 103 | LMV5... error history current diagnostic code | Modbus 400053 | Read | ||
| AI | 104 | LMV5... error history current error class | Modbus 400054 | Read | ||
| AI | 105 | LMV5... error history current error phase | Modbus 400055 | Read | ||
| AI | 106 | LMV5... error history current output | Modbus 400056 | Read | ||
| AI | 107 | LMV5... error history current startup counter total | Modbus 400057 | Read | ||
| AI | 108 | RWF actual temperature / pressure (E1) | Modbus 400059 | Read | ||
| AI | 109 | RWF actual (E2) | Modbus 400061 | Read | ||
| AI | 110 | RWF actual temperature (E3) | Modbus 400063 | Read | ||
| AI | 111 | RWF current setpoint | Modbus 400065 | Read | ||
| AI | 112 | RWF local setpoint (SP1) | Modbus 400067 | Read | ||
| AI | 113 | RWF local setpoint (SP2) | Modbus 400069 | Read | ||
| AI | 114 | RWF feedwater actual temperature /pressure (E1) | Modbus 400071 | Read | ||
| AI | 115 | RWF feedwater actual (E2) | Modbus 400073 | Read | ||
| AI | 116 | RWF feedwater current setpoint | Modbus 400075 | Read | ||
| AI | 117 | RWF feedwater local setpoint (SP1) | Modbus 400077 | Read | ||
| AI | 118 | EA temperature output | Modbus 400079 | Read | ||
| AI | 119 | EA configurable analog input 1 | Modbus 400080 | Read | ||
| AI | 120 | EA configurable analog input 2 | Modbus 400081 | Read | ||
| AI | 121 | EA configurable analog input 3 | Modbus 400082 | Read | ||
| AI | 122 | EA configurable analog input 4 | Modbus 400083 | Read | ||
| AI | 123 | EA configurable RTD input 1 | Modbus 400084 | Read | ||
| AI | 124 | EA configurable RTD input 2 | Modbus 400085 | Read | ||
| AI | 125 | EA configurable RTD input 3 | Modbus 400086 | Read | ||
| AI | 126 | EA valve output | Modbus 400087 | Read | ||
| AI | 127 | EA totalized analog input 1 | Modbus 400088 | Read | ||
| AI | 128 | EA totalized analog input 2 | Modbus 400090 | Read | ||
| AI | 129 | EA totalized analog input 3 | Modbus 400092 | Read | ||
| AI | 130 | EA totalized analog input 4 | Modbus 400094 | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Siemens TS-1100 point IDs by name
BI1Active connection from BMSBI2RWF remote disableBI3Boiler availableBI4Boiler circulating pump run statusBI5Boiler circulating pump timed alarm statusBI6LMV current type of fuelBI7LMV controller on/offBI8LMV fan contactor contact (LMV5...)BI9LMV fuel selection oil (LMV5...)BI10LMV fuel selection gas (LMV5...)BI11LMV oil max pressure switch (LMV5...)BI12LMV oil min pressure switch (LMV5...)BI13LMV valve proving pressure switch (LMV5...)BI14LMV safety loopBI15LMV gas min pressure switchBI16LMV gas max pressure switchBI17LMV LPBI18LMV start release oilBI19LMV heavy oil immediate releaseBI20LMV alarmBI21LMV ignitionBI22LMV start signal / DW valve (LMV5...)BI23LMV fanBI24LMV oil pump / magnetic coupling (LMV5...)BI25LMV fuel valve SV oil (LMV5...)BI26LMV fuel valve V1 oil (LMV5...)BI27LMV fuel valve V2 oil (LMV5...)BI28LMV fuel valve V3 oil (LMV5...)BI29LMV fuel valve SV gas (LMV5...)BI30LMV fuel valve V1 (gas LMV5...)BI31LMV fuel valve V2 (gas LMV5...)BI32LMV fuel valve V3 (gas LMV5...)BI33LMV local/remote modeBI34LMV5... lockout history current fuel selectedBI35LMV5... error history current fuel selectedBI36RWF40 management system thermostat overrideBI37RWF40 binary input 2 closedBI38RWF40 thermostat function activeBI39RWF40 limit comparator activeBI40RWF40 not optioned or RWF55BI41RWF40 feedwater binary input 2 closedBI42RWF40 feedwater high waterBI43RWF40 feedwater low waterBI44RWF40 feedwater not optioned or RWF55BI45EA annunciation input 1BI46EA annunciation input 2BI47EA annunciation input 3BI48EA annunciation input 4BI49EA annunciation input 5BI50EA annunciation input 6BI51EA annunciation input 7BI52EA annunciation input 8BI53EA annunciation input 9BI54EA annunciation input 10BI55EA annunciation input 11BI56EA annunciation input 12BI57EA annunciation input 13BI58EA not optionedAO59LMV remote modeAO60LMV remote setpoint (W3) (remote mode auto)AO61LMV remote output (remote mode on)AO62RWF remote modeAO63RWF remote setpointAO64RWF remote outputAI65LMV phaseAI66LMV position of currently active fuel actuatorAI67LMV position of gas actuator (LMV5...)AI68LMV position of oil actuator (LMV5...)AI69LMV position of air actuatorAI70LMV position of auxiliary actuator 1 (LMV5...)AI71LMV position of auxiliary actuator 2 (LMV5...)AI72LMV position of auxiliary actuator 3 (LMV5...)AI73LMV manipulated variable for var speed drive (LMV5...)AI74LMV current outputAI75LMV current setpoint / temperature / pressure (LMV5...)AI76LMV actual value / temperature / pressure (LMV5...)AI77LMV flame signalAI78LMV current fuel throughput (LMV5...)AI79LMV current O2 value (LMV52...)AI80LMV startup counter totalAI81LMV hours run total (LMV5...)AI82LMV supply air temperature (LMV52...)AI83LMV flue gas temperature (LMV52...)AI84LMV combustion efficiency (LMV52...)AI85LMV local setpoint W1 (LMV5...)AI86LMV local setpoint W2 (LMV5...)AI87LMV fuel volume gas (LMV5...)AI88LMV fuel volume oil (LMV5...)AI89LMV5... lockout history current error codeAI90LMV5... lockout history current diagnostic codeAI91LMV5... lockout history current error classAI92LMV5... lockout history current error phaseAI93LMV5... lockout history current outputAI94LMV5... lockout history current date - year(two digit)AI95LMV5... lockout history current date - monthAI96LMV5... lockout history current date - dayAI97LMV5... lockout history current time - hoursAI98LMV5... lockout history current time - minutesAI99LMV5... lockout history current time - secondsAI100LMV5... lockout history current startup counter totalAI101LMV5... lockout history current hours run totalAI102LMV5... error history current error codeAI103LMV5... error history current diagnostic codeAI104LMV5... error history current error classAI105LMV5... error history current error phaseAI106LMV5... error history current outputAI107LMV5... error history current startup counter totalAI108RWF actual temperature / pressure (E1)AI109RWF actual (E2)AI110RWF actual temperature (E3)AI111RWF current setpointAI112RWF local setpoint (SP1)AI113RWF local setpoint (SP2)AI114RWF feedwater actual temperature /pressure (E1)AI115RWF feedwater actual (E2)AI116RWF feedwater current setpointAI117RWF feedwater local setpoint (SP1)AI118EA temperature outputAI119EA configurable analog input 1AI120EA configurable analog input 2AI121EA configurable analog input 3AI122EA configurable analog input 4AI123EA configurable RTD input 1AI124EA configurable RTD input 2AI125EA configurable RTD input 3AI126EA valve outputAI127EA totalized analog input 1AI128EA totalized analog input 2AI129EA totalized analog input 3AI130EA totalized analog input 4
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv; the profile maps the registers in the TS-1100 Modbus RTU point list (https://www.ccontrols.com/support/dp/TS-1100_Installation_Instructions.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- All 130 rows are flagged for polling in the profile, so every object is served to BACnet once the profile is loaded.
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
How many BACnet points does the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX have?
This list has 130 BACnet objects: 66 analog inputs, 6 analog outputs, 58 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet points are writable?
6 of the 130 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a (TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/TS1100TouchS_RTU_LMV3_LMV5_RWF.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX?
Start with AO 59 LMV remote mode (LMV remote mode); AO 60 LMV remote setpoint (W3) (remote mode auto) (Remote setpoint W3 (auto)); AO 61 LMV remote output (remote mode on) (Remote output (remote on)); BI 3 Boiler available (Boiler available); BI 7 LMV controller on/off (LMV controller on); AI 65 LMV phase (LMV phase); AI 74 LMV current output (LMV current output); AI 77 LMV flame signal (Flame signal); BI 20 LMV alarm (LMV alarm); BI 1 Active connection from BMS (BMS connection active).
How do I check these points on the real Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile TS1100TouchS_RTU_LMV3_LMV5_RWF_a · TS1100TouchS_RTU_LMV3_LMV5_RWF_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.