- PVI Industries TempTrac water heater control via BASgatewayLX
Water heater controller · BACnet points list
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the PVI TempTrac: 123 objects (106 AI, 17 BI), all polled. Most analog inputs are the control's parameters (setpoints 1-5, differentials, limits, delays, outdoor reset and weekly setback); the live values are the three probe temperatures and states, the 4-20 mA modulation output, relay states and alarm bits.
This page lists 123 BACnet objects for the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- PVI Industries TempTrac water heater control via BASgatewayLX
- Equipment
- Water heater controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 123 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- TempTrac, PVI TempTrac, PVI water heater Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
Read probe 1 temperature against set point 1, the modulation output and relay 1, and watch the alarm bits. Every object is read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 100 | Probe 1 temperature | Probe 1 (tank) temperature | Read |
| AI 1 | Set point1 | Set point 1 | Read |
| AI 106 | Modulation rate output (4 to 20mA) | Modulation output, % | Read |
| BI 107 | Status of Relay 1 | Relay 1 (heat) on | Read |
| BI 114 | High Temperature Alarm beep Flash yellow HA=2 | High temperature alarm | Read |
| BI 113 | Low Temperature Alarm beep Flash Yellow LA= 1 | Low temperature alarm | Read |
| BI 115 | Probe 1 error open or shorted Drops call for | Probe 1 error | Read |
| BI 118 | ALARM 1 (stops heating) Input 1 | Alarm 1 (input 1, stops heating) | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Probe temperatures carry no units in the profile; AI 42 shows the configured temperature unit.
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Set point1 | Modbus 400769 | Read | ||
| AI | 2 | Set point2 | Modbus 400770 | Read | ||
| AI | 3 | Set point3 | Modbus 400771 | Read | ||
| AI | 4 | Set point5 Set point 3 alternate | Modbus 400772 | °F | Read | |
| AI | 5 | Differential for St1 | Modbus 400773 | °F | Read | |
| AI | 6 | Minimum set point1 | Modbus 400774 | °F | Read | |
| AI | 7 | Maximum set point1 | Modbus 400775 | °F | Read | |
| AI | 8 | Anti-short cycle delay for output 1 | Modbus 400776 | Read | ||
| AI | 9 | Configuration of St2: dependent on St1 or independent | Modbus 400777 | Read | ||
| AI | 10 | Differential for St2 | Modbus 400778 | °F | Read | |
| AI | 11 | Minimum set point2 | Modbus 400779 | °F | Read | |
| AI | 12 | Maximum set point2 | Modbus 400780 | °F | Read | |
| AI | 13 | Anti-short cycle delay for output 2 | Modbus 400781 | Read | ||
| AI | 14 | Configuration of St3: dependent on St1 or independent | Modbus 400782 | Read | ||
| AI | 15 | Differential for set point 3 St3 | Modbus 400783 | °F | Read | |
| AI | 16 | Minimum set point 3 St3 | Modbus 400784 | °F | Read | |
| AI | 17 | Maximum set point 3 St3 | Modbus 400785 | °F | Read | |
| AI | 18 | Anti-short cycle delay for output 3 | Modbus 400786 | Read | ||
| AI | 19 | Probe selection for output 3 | Modbus 400787 | Read | ||
| AI | 20 | Set point shift for output 3 enable disable | Modbus 400788 | Read | ||
| AI | 21 | Differential for set point 5 | Modbus 400789 | °F | Read | |
| AI | 22 | Anti-short cycle delay for output 3 alternate set point | Modbus 400790 | Read | ||
| AI | 23 | Time delay between the St3 to St5 set point shift | Modbus 400791 | Read | ||
| AI | 24 | Configuration of St4: dependent on St1 or independent | Modbus 400792 | Read | ||
| AI | 25 | Analogue output set point | Modbus 400793 | °F | Read | |
| AI | 26 | Analogue output band width | Modbus 400794 | °F | Read | |
| AI | 27 | Outlet temperature threshold for forcing analog out | Modbus 400795 | °F | Read | |
| AI | 28 | Differential for restart working of analog output | Modbus 400796 | °F | Read | |
| AI | 29 | Anti-short cycle delay for output 4 | Modbus 400797 | Read | ||
| AI | 30 | Analog output percentage (nu=101) | Modbus 400798 | Read | ||
| AI | 31 | Analog output percentage with fault probe 1 | Modbus 400799 | Read | ||
| AI | 32 | Outdoor temperature threshold for dynamic reset of St1 | Modbus 400800 | °F | Read | |
| AI | 33 | Outdoor temperature band width | Modbus 400801 | °F | Read | |
| AI | 34 | Maximum shift of St1 | Modbus 400802 | °F | Read | |
| AI | 35 | Outdoor temperature threshold to open all the loads | Modbus 400803 | °F | Read | |
| AI | 36 | Differential for restart working of controller | Modbus 400804 | °F | Read | |
| AI | 37 | Digital input 1 polarity | Modbus 400805 | Read | ||
| AI | 38 | Digital input 2 polarity | Modbus 400806 | Read | ||
| AI | 39 | Digital input 2 alarm delay | Modbus 400807 | Read | ||
| AI | 40 | Digital input 3 polarity | Modbus 400808 | Read | ||
| AI | 41 | Digital input 3 alarm delay | Modbus 400809 | Read | ||
| AI | 42 | Temperature measurement unit | Modbus 400810 | Read | ||
| AI | 43 | Resolution (integer/decimal point) only for °C | Modbus 400811 | Read | ||
| AI | 44 | Default showing for display #2 Top (red) | Modbus 400812 | Read | ||
| AI | 45 | Default showing for display #1 Bottom (Yellow) | Modbus 400813 | Read | ||
| AI | 46 | Temp alarms configuration: dependent on St1 or independent | Modbus 400814 | Read | ||
| AI | 47 | minimum temperature alarm for Pb1 Alarm LA Flash Only | Modbus 400815 | °F | Read | |
| AI | 48 | MAXIMUM temperature alarm for Pb1 Alarm HA Flash only | Modbus 400816 | °F | Read | |
| AI | 49 | Differential for temperature alarm recovery | Modbus 400817 | °F | Read | |
| AI | 50 | Temperature alarm delay | Modbus 400818 | Read | ||
| AI | 51 | Delay of temperature alarm at start up 1 = 10 min | Modbus 400819 | Read | ||
| AI | 52 | First probe calibration | Modbus 400820 | °F | Read | |
| AI | 53 | Second probe presence | Modbus 400821 | Read | ||
| AI | 54 | Second probe calibration | Modbus 400822 | °F | Read | |
| AI | 55 | Third probe presence | Modbus 400823 | Read | ||
| AI | 56 | Third probe calibration | Modbus 400824 | °F | Read | |
| AI | 57 | Current hour | Modbus 400825 | Read | ||
| AI | 58 | Current minute | Modbus 400826 | Read | ||
| AI | 59 | Current day | Modbus 400827 | Read | ||
| AI | 60 | Energy saving start on Sunday | Modbus 400828 | Read | ||
| AI | 61 | Energy saving stop on Sunday | Modbus 400829 | Read | ||
| AI | 62 | Set back temperature on Sunday | Modbus 400830 | °F | Read | |
| AI | 63 | Energy saving start on Monday | Modbus 400831 | Read | ||
| AI | 64 | Energy saving stop on Monday | Modbus 400832 | Read | ||
| AI | 65 | Set back temperature on Monday | Modbus 400833 | °F | Read | |
| AI | 66 | Energy saving start on Tuesday | Modbus 400834 | Read | ||
| AI | 67 | Energy saving stop on Tuesday | Modbus 400835 | Read | ||
| AI | 68 | Set back temperature on Tuesday | Modbus 400836 | °F | Read | |
| AI | 69 | Energy saving start on Wednesday | Modbus 400837 | Read | ||
| AI | 70 | Energy saving stop on Wednesday | Modbus 400838 | Read | ||
| AI | 71 | Set back temperature on Wednesday | Modbus 400839 | °F | Read | |
| AI | 72 | Energy saving start on Thursday | Modbus 400840 | Read | ||
| AI | 73 | Energy saving stop on Thursday | Modbus 400841 | Read | ||
| AI | 74 | Set back temperature on Thursday | Modbus 400842 | °F | Read | |
| AI | 75 | Energy saving start on Friday | Modbus 400843 | Read | ||
| AI | 76 | Energy saving stop on Friday | Modbus 400844 | Read | ||
| AI | 77 | Set back temperature on Friday | Modbus 400845 | °F | Read | |
| AI | 78 | Energy saving start on Saturday | Modbus 400846 | Read | ||
| AI | 79 | Energy saving stop on Saturday | Modbus 400847 | Read | ||
| AI | 80 | Set back temperature on Saturday | Modbus 400848 | °F | Read | |
| AI | 81 | working hours actual of relay 1 | Modbus 400849 | h | Read | |
| AI | 82 | working hours actual of relay 2 | Modbus 400850 | h | Read | |
| AI | 83 | working hours actual of relay 3 | Modbus 400851 | h | Read | |
| AI | 84 | working hours limit of relay 1 Nn1 Alarm when reached | Modbus 400852 | Read | ||
| AI | 85 | working hours limit of relay 2 Nn2 Alarm when reached | Modbus 400853 | Read | ||
| AI | 86 | working hours limit of relay 3 Nn3 Alarm when reached | Modbus 400854 | Read | ||
| AI | 87 | The output 1 force ON / OFF or Temperature regulation | Modbus 400855 | Read | ||
| AI | 88 | The output 2 force ON / OFF or Temperature regulation | Modbus 400856 | Read | ||
| AI | 89 | The output 3 force ON / OFF or Temperature regulaton | Modbus 400857 | Read | ||
| AI | 90 | Serial address | Modbus 400858 | Read | ||
| AI | 91 | Parameter map code always = 1 | Modbus 400859 | Read | ||
| AI | 92 | Software release 5 = V0.5 3 = V0.3 | Modbus 400860 | Read | ||
| AI | 93 | Analog output when Digital Input 1 is activated | Modbus 400861 | mA | Read | |
| AI | 94 | Analog out at i1S extra time if Digital In 1 is not activated | Modbus 400862 | s | Read | |
| AI | 95 | Digital Input 1 Alarm Delay | Modbus 400863 | min | Read | |
| AI | 96 | If Yes Digital Input 1 will function as Alarm. | Modbus 400864 | Read | ||
| AI | 97 | Digital Input 2 will function only when Output 1 is energized | Modbus 400865 | Read | ||
| AI | 98 | Digital Input 3 will function only when Output 1 is energized | Modbus 400866 | Read | ||
| AI | 99 | Output 2 function: either temp relay or alarm relay | Modbus 400867 | Read | ||
| AImin | 100 | Probe 1 temperature | Modbus 400257 | Read | ||
| AI | 101 | Probe 1 Information/Status Normal=512 or Fault=515 | Modbus 400258 | Read | ||
| AI | 102 | Probe 2 temperature | Modbus 400259 | Read | ||
| AI | 103 | Probe 2 Information/Status Normal=512 or Fault=515 | Modbus 400260 | Read | ||
| AI | 104 | Probe 3 temperature | Modbus 400261 | Read | ||
| AI | 105 | Probe 3 Information/Status Normal=512 or Fault=515 | Modbus 400262 | Read | ||
| AImin | 106 | Modulation rate output (4 to 20mA) | Modbus 400263 | % | Read | |
| BImin | 107 | Status of Relay 1 | Modbus 402050 bit 0 | Read | ||
| BI | 108 | Status of Relay 2 | Modbus 402050 bit 1 | Read | ||
| BI | 109 | Status of Relay 3 | Modbus 402050 bit 2 | Read | ||
| BI | 110 | Input 3 Alarm buz ALMMB Flashes HP= 4096 | Modbus 403329 bit 12 | Read | ||
| BI | 111 | Input 2 Alarm buz Flashes LP= 4096 | Modbus 403329 bit 12 | Read | ||
| BI | 112 | Input 2 3 buz Flashed HP LP= 4096 | Modbus 403329 bit 12 | Read | ||
| BImin | 113 | Low Temperature Alarm beep Flash Yellow LA= 1 | Modbus 403329 bit 0 | Read | ||
| BImin | 114 | High Temperature Alarm beep Flash yellow HA=2 | Modbus 403329 bit 1 | Read | ||
| BImin | 115 | Probe 1 error open or shorted Drops call for | Modbus 403329 bit 2 | Read | ||
| BI | 116 | Probe 2 error open or shorted Flashing red | Modbus 403329 bit 8 | Read | ||
| BI | 117 | Probe 3 error open or shorted Flashing red | Modbus 403329 bit 9 | Read | ||
| BImin | 118 | ALARM 1 (stops heating) Input 1 | Modbus 403329 bit 10 | Read | ||
| BI | 119 | ALARM 2 (Lockout stops heating) Input 2 | Modbus 403329 bit 11 | Read | ||
| BI | 120 | ALARM 3 (Lockout stops heating) Input 3 | Modbus 403329 bit 12 | Read | ||
| BI | 121 | Maintenance Relay1 beep Flash Nn1 | Modbus 403329 bit 13 | Read | ||
| BI | 122 | Maintenance Relay2 beep Flash Nn2 | Modbus 403329 bit 14 | Read | ||
| BI | 123 | Maintenance Relay3 beep Flash Nn3 | Modbus 403329 bit 15 | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX PVI TempTrac point IDs by name
AI1Set point1AI2Set point2AI3Set point3AI4Set point5 Set point 3 alternateAI5Differential for St1AI6Minimum set point1AI7Maximum set point1AI8Anti-short cycle delay for output 1AI9Configuration of St2: dependent on St1 or independentAI10Differential for St2AI11Minimum set point2AI12Maximum set point2AI13Anti-short cycle delay for output 2AI14Configuration of St3: dependent on St1 or independentAI15Differential for set point 3 St3AI16Minimum set point 3 St3AI17Maximum set point 3 St3AI18Anti-short cycle delay for output 3AI19Probe selection for output 3AI20Set point shift for output 3 enable disableAI21Differential for set point 5AI22Anti-short cycle delay for output 3 alternate set pointAI23Time delay between the St3 to St5 set point shiftAI24Configuration of St4: dependent on St1 or independentAI25Analogue output set pointAI26Analogue output band widthAI27Outlet temperature threshold for forcing analog outAI28Differential for restart working of analog outputAI29Anti-short cycle delay for output 4AI30Analog output percentage (nu=101)AI31Analog output percentage with fault probe 1AI32Outdoor temperature threshold for dynamic reset of St1AI33Outdoor temperature band widthAI34Maximum shift of St1AI35Outdoor temperature threshold to open all the loadsAI36Differential for restart working of controllerAI37Digital input 1 polarityAI38Digital input 2 polarityAI39Digital input 2 alarm delayAI40Digital input 3 polarityAI41Digital input 3 alarm delayAI42Temperature measurement unitAI43Resolution (integer/decimal point) only for °CAI44Default showing for display #2 Top (red)AI45Default showing for display #1 Bottom (Yellow)AI46Temp alarms configuration: dependent on St1 or independentAI47minimum temperature alarm for Pb1 Alarm LA Flash OnlyAI48MAXIMUM temperature alarm for Pb1 Alarm HA Flash onlyAI49Differential for temperature alarm recoveryAI50Temperature alarm delayAI51Delay of temperature alarm at start up 1 = 10 minAI52First probe calibrationAI53Second probe presenceAI54Second probe calibrationAI55Third probe presenceAI56Third probe calibrationAI57Current hourAI58Current minuteAI59Current dayAI60Energy saving start on SundayAI61Energy saving stop on SundayAI62Set back temperature on SundayAI63Energy saving start on MondayAI64Energy saving stop on MondayAI65Set back temperature on MondayAI66Energy saving start on TuesdayAI67Energy saving stop on TuesdayAI68Set back temperature on TuesdayAI69Energy saving start on WednesdayAI70Energy saving stop on WednesdayAI71Set back temperature on WednesdayAI72Energy saving start on ThursdayAI73Energy saving stop on ThursdayAI74Set back temperature on ThursdayAI75Energy saving start on FridayAI76Energy saving stop on FridayAI77Set back temperature on FridayAI78Energy saving start on SaturdayAI79Energy saving stop on SaturdayAI80Set back temperature on SaturdayAI81working hours actual of relay 1AI82working hours actual of relay 2AI83working hours actual of relay 3AI84working hours limit of relay 1 Nn1 Alarm when reachedAI85working hours limit of relay 2 Nn2 Alarm when reachedAI86working hours limit of relay 3 Nn3 Alarm when reachedAI87The output 1 force ON / OFF or Temperature regulationAI88The output 2 force ON / OFF or Temperature regulationAI89The output 3 force ON / OFF or Temperature regulatonAI90Serial addressAI91Parameter map code always = 1AI92Software release 5 = V0.5 3 = V0.3AI93Analog output when Digital Input 1 is activatedAI94Analog out at i1S extra time if Digital In 1 is not activatedAI95Digital Input 1 Alarm DelayAI96If Yes Digital Input 1 will function as Alarm.AI97Digital Input 2 will function only when Output 1 is energizedAI98Digital Input 3 will function only when Output 1 is energizedAI99Output 2 function: either temp relay or alarm relayAI100Probe 1 temperatureAI101Probe 1 Information/Status Normal=512 or Fault=515AI102Probe 2 temperatureAI103Probe 2 Information/Status Normal=512 or Fault=515AI104Probe 3 temperatureAI105Probe 3 Information/Status Normal=512 or Fault=515AI106Modulation rate output (4 to 20mA)BI107Status of Relay 1BI108Status of Relay 2BI109Status of Relay 3BI110Input 3 Alarm buz ALMMB Flashes HP= 4096BI111Input 2 Alarm buz Flashes LP= 4096BI112Input 2 3 buz Flashed HP LP= 4096BI113Low Temperature Alarm beep Flash Yellow LA= 1BI114High Temperature Alarm beep Flash yellow HA=2BI115Probe 1 error open or shorted Drops call forBI116Probe 2 error open or shorted Flashing redBI117Probe 3 error open or shorted Flashing redBI118ALARM 1 (stops heating) Input 1BI119ALARM 2 (Lockout stops heating) Input 2BI120ALARM 3 (Lockout stops heating) Input 3BI121Maintenance Relay1 beep Flash Nn1BI122Maintenance Relay2 beep Flash Nn2BI123Maintenance Relay3 beep Flash Nn3
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile PVI_Ind_TempTrac_Water_Heater_a_LX.csv; the profile maps the registers in the TempTrac Modbus register list (https://www.ccontrols.com/support/dp/PV500-42.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- All 123 rows are flagged for polling in the profile, so every object is served to BACnet once the profile is loaded.
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PVI Industries TempTrac water heater control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
How many BACnet points does the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX have?
This list has 123 BACnet objects: 106 analog inputs, 17 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile PVI_Industries_TempTrac_Water_Heater_a (PVI_Ind_TempTrac_Water_Heater_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/PVI_Ind_TempTrac_Water_Heater.zip.
What are the minimum BACnet points to integrate the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX?
Start with AI 100 Probe 1 temperature (Probe 1 (tank) temperature); AI 1 Set point1 (Set point 1); AI 106 Modulation rate output (4 to 20mA) (Modulation output, %); BI 107 Status of Relay 1 (Relay 1 (heat) on); BI 114 High Temperature Alarm beep Flash yellow HA=2 (High temperature alarm); BI 113 Low Temperature Alarm beep Flash Yellow LA= 1 (Low temperature alarm); BI 115 Probe 1 error open or shorted Drops call for (Probe 1 error); BI 118 ALARM 1 (stops heating) Input 1 (Alarm 1 (input 1, stops heating)).
How do I check these points on the real PVI Industries TempTrac water heater control via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile PVI_Industries_TempTrac_Water_Heater_a · PVI_Ind_TempTrac_Water_Heater_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.