Water heater controller · BACnet points list

Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the PVI TempTrac: 123 objects (106 AI, 17 BI), all polled. Most analog inputs are the control's parameters (setpoints 1-5, differentials, limits, delays, outdoor reset and weekly setback); the live values are the three probe temperatures and states, the 4-20 mA modulation output, relay states and alarm bits.

This page lists 123 BACnet objects for the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
PVI Industries TempTrac water heater control via BASgatewayLX
Equipment
Water heater controller
Equipment type
Boilers & water heaters
BACnet objects
123 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
TempTrac, PVI TempTrac, PVI water heater Modbus
Source document
BASgatewayLX Modbus device profile PVI_Industries_TempTrac_Water_Heater_a · PVI_Ind_TempTrac_Water_Heater_a_LX.csv
Download CSV 123 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX

Integration in brief

Read probe 1 temperature against set point 1, the modulation output and relay 1, and watch the alarm bits. Every object is read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 100Probe 1 temperatureProbe 1 (tank) temperatureRead
AI 1Set point1Set point 1Read
AI 106Modulation rate output (4 to 20mA)Modulation output, %Read
BI 107Status of Relay 1Relay 1 (heat) onRead
BI 114High Temperature Alarm beep Flash yellow HA=2High temperature alarmRead
BI 113Low Temperature Alarm beep Flash Yellow LA= 1Low temperature alarmRead
BI 115Probe 1 error open or shorted Drops call forProbe 1 errorRead
BI 118ALARM 1 (stops heating) Input 1Alarm 1 (input 1, stops heating)Read

Network setup

Watch out for

Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

123 of 123 shown
Type
AnalogBinary
Show
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Set point1Modbus 400769Read
AI2Set point2Modbus 400770Read
AI3Set point3Modbus 400771Read
AI4Set point5 Set point 3 alternateModbus 400772°FRead
AI5Differential for St1Modbus 400773°FRead
AI6Minimum set point1Modbus 400774°FRead
AI7Maximum set point1Modbus 400775°FRead
AI8Anti-short cycle delay for output 1Modbus 400776Read
AI9Configuration of St2: dependent on St1 or independentModbus 400777Read
AI10Differential for St2Modbus 400778°FRead
AI11Minimum set point2Modbus 400779°FRead
AI12Maximum set point2Modbus 400780°FRead
AI13Anti-short cycle delay for output 2Modbus 400781Read
AI14Configuration of St3: dependent on St1 or independentModbus 400782Read
AI15Differential for set point 3 St3Modbus 400783°FRead
AI16Minimum set point 3 St3Modbus 400784°FRead
AI17Maximum set point 3 St3Modbus 400785°FRead
AI18Anti-short cycle delay for output 3Modbus 400786Read
AI19Probe selection for output 3Modbus 400787Read
AI20Set point shift for output 3 enable disableModbus 400788Read
AI21Differential for set point 5Modbus 400789°FRead
AI22Anti-short cycle delay for output 3 alternate set pointModbus 400790Read
AI23Time delay between the St3 to St5 set point shiftModbus 400791Read
AI24Configuration of St4: dependent on St1 or independentModbus 400792Read
AI25Analogue output set pointModbus 400793°FRead
AI26Analogue output band widthModbus 400794°FRead
AI27Outlet temperature threshold for forcing analog outModbus 400795°FRead
AI28Differential for restart working of analog outputModbus 400796°FRead
AI29Anti-short cycle delay for output 4Modbus 400797Read
AI30Analog output percentage (nu=101)Modbus 400798Read
AI31Analog output percentage with fault probe 1Modbus 400799Read
AI32Outdoor temperature threshold for dynamic reset of St1Modbus 400800°FRead
AI33Outdoor temperature band widthModbus 400801°FRead
AI34Maximum shift of St1Modbus 400802°FRead
AI35Outdoor temperature threshold to open all the loadsModbus 400803°FRead
AI36Differential for restart working of controllerModbus 400804°FRead
AI37Digital input 1 polarityModbus 400805Read
AI38Digital input 2 polarityModbus 400806Read
AI39Digital input 2 alarm delayModbus 400807Read
AI40Digital input 3 polarityModbus 400808Read
AI41Digital input 3 alarm delayModbus 400809Read
AI42Temperature measurement unitModbus 400810Read
AI43Resolution (integer/decimal point) only for °CModbus 400811Read
AI44Default showing for display #2 Top (red)Modbus 400812Read
AI45Default showing for display #1 Bottom (Yellow)Modbus 400813Read
AI46Temp alarms configuration: dependent on St1 or independentModbus 400814Read
AI47minimum temperature alarm for Pb1 Alarm LA Flash OnlyModbus 400815°FRead
AI48MAXIMUM temperature alarm for Pb1 Alarm HA Flash onlyModbus 400816°FRead
AI49Differential for temperature alarm recoveryModbus 400817°FRead
AI50Temperature alarm delayModbus 400818Read
AI51Delay of temperature alarm at start up 1 = 10 minModbus 400819Read
AI52First probe calibrationModbus 400820°FRead
AI53Second probe presenceModbus 400821Read
AI54Second probe calibrationModbus 400822°FRead
AI55Third probe presenceModbus 400823Read
AI56Third probe calibrationModbus 400824°FRead
AI57Current hourModbus 400825Read
AI58Current minuteModbus 400826Read
AI59Current dayModbus 400827Read
AI60Energy saving start on SundayModbus 400828Read
AI61Energy saving stop on SundayModbus 400829Read
AI62Set back temperature on SundayModbus 400830°FRead
AI63Energy saving start on MondayModbus 400831Read
AI64Energy saving stop on MondayModbus 400832Read
AI65Set back temperature on MondayModbus 400833°FRead
AI66Energy saving start on TuesdayModbus 400834Read
AI67Energy saving stop on TuesdayModbus 400835Read
AI68Set back temperature on TuesdayModbus 400836°FRead
AI69Energy saving start on WednesdayModbus 400837Read
AI70Energy saving stop on WednesdayModbus 400838Read
AI71Set back temperature on WednesdayModbus 400839°FRead
AI72Energy saving start on ThursdayModbus 400840Read
AI73Energy saving stop on ThursdayModbus 400841Read
AI74Set back temperature on ThursdayModbus 400842°FRead
AI75Energy saving start on FridayModbus 400843Read
AI76Energy saving stop on FridayModbus 400844Read
AI77Set back temperature on FridayModbus 400845°FRead
AI78Energy saving start on SaturdayModbus 400846Read
AI79Energy saving stop on SaturdayModbus 400847Read
AI80Set back temperature on SaturdayModbus 400848°FRead
AI81working hours actual of relay 1Modbus 400849hRead
AI82working hours actual of relay 2Modbus 400850hRead
AI83working hours actual of relay 3Modbus 400851hRead
AI84working hours limit of relay 1 Nn1 Alarm when reachedModbus 400852Read
AI85working hours limit of relay 2 Nn2 Alarm when reachedModbus 400853Read
AI86working hours limit of relay 3 Nn3 Alarm when reachedModbus 400854Read
AI87The output 1 force ON / OFF or Temperature regulationModbus 400855Read
AI88The output 2 force ON / OFF or Temperature regulationModbus 400856Read
AI89The output 3 force ON / OFF or Temperature regulatonModbus 400857Read
AI90Serial addressModbus 400858Read
AI91Parameter map code always = 1Modbus 400859Read
AI92Software release 5 = V0.5 3 = V0.3Modbus 400860Read
AI93Analog output when Digital Input 1 is activatedModbus 400861mARead
AI94Analog out at i1S extra time if Digital In 1 is not activatedModbus 400862sRead
AI95Digital Input 1 Alarm DelayModbus 400863minRead
AI96If Yes Digital Input 1 will function as Alarm.Modbus 400864Read
AI97Digital Input 2 will function only when Output 1 is energizedModbus 400865Read
AI98Digital Input 3 will function only when Output 1 is energizedModbus 400866Read
AI99Output 2 function: either temp relay or alarm relayModbus 400867Read
AImin100Probe 1 temperatureModbus 400257Read
AI101Probe 1 Information/Status Normal=512 or Fault=515Modbus 400258Read
AI102Probe 2 temperatureModbus 400259Read
AI103Probe 2 Information/Status Normal=512 or Fault=515Modbus 400260Read
AI104Probe 3 temperatureModbus 400261Read
AI105Probe 3 Information/Status Normal=512 or Fault=515Modbus 400262Read
AImin106Modulation rate output (4 to 20mA)Modbus 400263%Read
BImin107Status of Relay 1Modbus 402050 bit 0Read
BI108Status of Relay 2Modbus 402050 bit 1Read
BI109Status of Relay 3Modbus 402050 bit 2Read
BI110Input 3 Alarm buz ALMMB Flashes HP= 4096Modbus 403329 bit 12Read
BI111Input 2 Alarm buz Flashes LP= 4096Modbus 403329 bit 12Read
BI112Input 2 3 buz Flashed HP LP= 4096Modbus 403329 bit 12Read
BImin113Low Temperature Alarm beep Flash Yellow LA= 1Modbus 403329 bit 0Read
BImin114High Temperature Alarm beep Flash yellow HA=2Modbus 403329 bit 1Read
BImin115Probe 1 error open or shorted Drops call forModbus 403329 bit 2Read
BI116Probe 2 error open or shorted Flashing redModbus 403329 bit 8Read
BI117Probe 3 error open or shorted Flashing redModbus 403329 bit 9Read
BImin118ALARM 1 (stops heating) Input 1Modbus 403329 bit 10Read
BI119ALARM 2 (Lockout stops heating) Input 2Modbus 403329 bit 11Read
BI120ALARM 3 (Lockout stops heating) Input 3Modbus 403329 bit 12Read
BI121Maintenance Relay1 beep Flash Nn1Modbus 403329 bit 13Read
BI122Maintenance Relay2 beep Flash Nn2Modbus 403329 bit 14Read
BI123Maintenance Relay3 beep Flash Nn3Modbus 403329 bit 15Read
Object ID lookup: Contemporary Controls BASgatewayLX PVI TempTrac point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PVI Industries TempTrac water heater control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX

How many BACnet points does the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX have?

This list has 123 BACnet objects: 106 analog inputs, 17 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile PVI_Industries_TempTrac_Water_Heater_a (PVI_Ind_TempTrac_Water_Heater_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/PVI_Ind_TempTrac_Water_Heater.zip.

What are the minimum BACnet points to integrate the Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX?

Start with AI 100 Probe 1 temperature (Probe 1 (tank) temperature); AI 1 Set point1 (Set point 1); AI 106 Modulation rate output (4 to 20mA) (Modulation output, %); BI 107 Status of Relay 1 (Relay 1 (heat) on); BI 114 High Temperature Alarm beep Flash yellow HA=2 (High temperature alarm); BI 113 Low Temperature Alarm beep Flash Yellow LA= 1 (Low temperature alarm); BI 115 Probe 1 error open or shorted Drops call for (Probe 1 error); BI 118 ALARM 1 (stops heating) Input 1 (Alarm 1 (input 1, stops heating)).

How do I check these points on the real PVI Industries TempTrac water heater control via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile PVI_Industries_TempTrac_Water_Heater_a · PVI_Ind_TempTrac_Water_Heater_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.