- Home
- BACnet points lists
- Contemporary Controls
- Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Soft starter (motor) · BACnet points list
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Benshaw RB2/RC2/RX2E: 307 objects (234 AI, 61 BI, 12 BO), 100 polled by default. Coils run/stop, reset faults and overloads, select local/remote and ramp, and drive the relays; inputs give ready, running, up-to-speed, alarm, fault and lockout states, input states, each alarm/fault code bit, currents, voltages, kW, kWh and the starter parameters (unpolled).
This page lists 307 BACnet objects for the Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
- Equipment
- Soft starter (motor)
- Equipment type
- Other equipment
- BACnet objects
- 307 (12 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Set Local/Remote to remote, then run/stop by BO 1; read running, up to speed, average current and the alarm/fault/lockout states.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Starter Control Run/Stop | Run (1) / stop (0) | Command |
| BO 4 | Starter Control Local/Remote | Local/remote select | Command |
| BO 2 | Starter Control Fault Reset | Fault reset | Command |
| BI 14 | Starter Status Running | Starter running | Read |
| BI 15 | Starter Status UTS | Up to speed | Read |
| AI 75 | Average Current | Average motor current | Read |
| AI 82 | Average Voltage | Average line voltage | Read |
| BI 16 | Starter Status Alarm | Alarm active | Read |
| BI 17 | Starter Status Fault | Fault active | Read |
| BI 18 | Starter Status Lockout | Lockout active | Read |
Enable & remote start
Starter Control Local/Remote (BO 4) selects whether the network run command is used; check the Benshaw manual for which state is remote.
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Starter Control Run/Stop | Modbus 400020 bit 0 | Command | ||
| BOmin | 2 | Starter Control Fault Reset | Modbus 400020 bit 1 | Command | ||
| BO | 3 | Starter Control Emergency Overload Reset | Modbus 400020 bit 2 | Command | ||
| BOmin | 4 | Starter Control Local/Remote | Modbus 400020 bit 3 | Command | ||
| BO | 5 | Starter Control Heat Disable | Modbus 400020 bit 4 | Command | ||
| BO | 6 | Starter Control Ramp Select | Modbus 400020 bit 5 | Command | ||
| BO | 7 | Starter Control Reserved (Relay 6) | Modbus 400020 bit 10 | Command | ||
| BO | 8 | Starter Control Reserved (Relay 5) | Modbus 400020 bit 11 | Command | ||
| BO | 9 | Starter Control Reserved (Relay 4) | Modbus 400020 bit 12 | Command | ||
| BO | 10 | Starter Control Relay 3 | Modbus 400020 bit 13 | Command | ||
| BO | 11 | Starter Control Relay 2 | Modbus 400020 bit 14 | Command | ||
| BO | 12 | Starter Control Relay 1 | Modbus 400020 bit 15 | Command | ||
| BI | 13 | Starter Status Ready | Modbus 400021 bit 0 | Read | ||
| BImin | 14 | Starter Status Running | Modbus 400021 bit 1 | Read | ||
| BImin | 15 | Starter Status UTS | Modbus 400021 bit 2 | Read | ||
| BImin | 16 | Starter Status Alarm | Modbus 400021 bit 3 | Read | ||
| BImin | 17 | Starter Status Fault | Modbus 400021 bit 4 | Read | ||
| BImin | 18 | Starter Status Lockout | Modbus 400021 bit 5 | Read | ||
| BI | 19 | Input Status Start | Modbus 400022 bit 0 | Read | ||
| BI | 20 | Input Status DI 1 | Modbus 400022 bit 1 | Read | ||
| BI | 21 | Input Status DI 2 | Modbus 400022 bit 2 | Read | ||
| BI | 22 | Input Status DI 3 | Modbus 400022 bit 3 | Read | ||
| BI | 23 | Alarm Status 1 A OL – Motor overload | Modbus 400023 bit 0 | Read | ||
| BI | 24 | Alarm Status 1 A 5 – Reserved (Motor PTC) | Modbus 400023 bit 1 | Read | ||
| BI | 25 | Alarm Status 1 A 6 – Reserved (Stator RTD) | Modbus 400023 bit 2 | Read | ||
| BI | 26 | Alarm Status 1 A 7 – Reserved (Bearing RTD) | Modbus 400023 bit 3 | Read | ||
| BI | 27 | Alarm Status 1 A 8 – Reserved (Other RTD) | Modbus 400023 bit 4 | Read | ||
| BI | 28 | Alarm Status 1 A 10 – Phase rotation not ABC | Modbus 400023 bit 5 | Read | ||
| BI | 29 | Alarm Status 1 A 11 – Phase rotation not CBA | Modbus 400023 bit 6 | Read | ||
| BI | 30 | Alarm Status 1 A 12 – Low Line Frequency | Modbus 400023 bit 7 | Read | ||
| BI | 31 | Alarm Status 1 A 13 – High Line Frequency | Modbus 400023 bit 8 | Read | ||
| BI | 32 | Alarm Status 1 A 14 – Phase rotation not 1PH | Modbus 400023 bit 9 | Read | ||
| BI | 33 | Alarm Status 1 A 15 – Phase rotation not 3PH | Modbus 400023 bit 10 | Read | ||
| BI | 34 | Alarm Status 1 A 21 – Low line L1-L2 | Modbus 400023 bit 11 | Read | ||
| BI | 35 | Alarm Status 1 A 22 – Low line L2-L3 | Modbus 400023 bit 12 | Read | ||
| BI | 36 | Alarm Status 1 A 23 – Low line L3-L1 | Modbus 400023 bit 13 | Read | ||
| BI | 37 | Alarm Status 1 A 24 – High line L1-L2 | Modbus 400023 bit 14 | Read | ||
| BI | 38 | Alarm Status 1 A 25 – High line L2-L3 | Modbus 400023 bit 15 | Read | ||
| BI | 39 | Alarm Status 2 A 26 – High line L3-L1 | Modbus 400024 bit 0 | Read | ||
| BI | 40 | Alarm Status 2 A 27 – Phase loss | Modbus 400024 bit 1 | Read | ||
| BI | 41 | Alarm Status 2 noL – No line | Modbus 400024 bit 2 | Read | ||
| BI | 42 | Alarm Status 2 A 29 – PORT Timeout (reserved) | Modbus 400024 bit 3 | Read | ||
| BI | 43 | Alarm Status 2 A 31 – Overcurrent | Modbus 400024 bit 4 | Read | ||
| BI | 44 | Alarm Status 2 A 34 – Undercurrent | Modbus 400024 bit 5 | Read | ||
| BI | 45 | Alarm Status 2 A 35 – PF Too Leading (reserved) | Modbus 400024 bit 6 | Read | ||
| BI | 46 | Alarm Status 2 A 36 – PF Too Lagging (reserved) | Modbus 400024 bit 7 | Read | ||
| BI | 47 | Alarm Status 2 A 37 – Current imbalance | Modbus 400024 bit 8 | Read | ||
| BI | 48 | Alarm Status 2 A 38 – Ground fault | Modbus 400024 bit 9 | Read | ||
| BI | 49 | Alarm Status 2 A 47 – Stack overtemperature | Modbus 400024 bit 10 | Read | ||
| BI | 50 | Alarm Status 2 53 – Tach Loss (reserved) | Modbus 400024 bit 11 | Read | ||
| BI | 51 | Alarm Status 2 A 60 – DI 1 | Modbus 400024 bit 12 | Read | ||
| BI | 52 | Alarm Status 2 A 61 – DI 2 | Modbus 400024 bit 13 | Read | ||
| BI | 53 | Alarm Status 2 A 62 – DI 3 | Modbus 400024 bit 14 | Read | ||
| BI | 54 | Alarm Status 2 63– Reserved (DI 4) | Modbus 400024 bit 15 | Read | ||
| BI | 55 | Alarm Status 3 A 64 – Reserved (DI 5) | Modbus 400025 bit 0 | Read | ||
| BI | 56 | Alarm Status 3 A 65 – Reserved (DI 6) | Modbus 400025 bit 1 | Read | ||
| BI | 57 | Alarm Status 3 A 66 – Reserved (DI 7) | Modbus 400025 bit 2 | Read | ||
| BI | 58 | Alarm Status 3 A 67 – Reserved (DI 8) | Modbus 400025 bit 3 | Read | ||
| BI | 59 | Alarm Status 3 A 71 – Analog Input #1 Trip | Modbus 400025 bit 4 | Read | ||
| BI | 60 | Lockout Status L OL – Motor overload | Modbus 400026 bit 0 | Read | ||
| BI | 61 | Lockout Status – Reserved - (Motor PTC) | Modbus 400026 bit 1 | Read | ||
| BI | 62 | Lockout Status – Reserved - (RTD Stator) | Modbus 400026 bit 2 | Read | ||
| BI | 63 | Lockout Status – Reserved - (RTD Bearing) | Modbus 400026 bit 3 | Read | ||
| BI | 64 | Lockout Status – Reserved - (RTD Other) | Modbus 400026 bit 4 | Read | ||
| BI | 65 | Lockout Status L rl – Run Interlock | Modbus 400026 bit 5 | Read | ||
| BI | 66 | Lockout Status L dS – Disconnect open | Modbus 400026 bit 6 | Read | ||
| BI | 67 | Lockout Status L Ot – Stack overtemperature | Modbus 400026 bit 7 | Read | ||
| BI | 68 | Lockout Status L CP – Control Power | Modbus 400026 bit 8 | Read | ||
| BI | 69 | Lockout Status Reserved – (RTD Open/Short) | Modbus 400026 bit 9 | Read | ||
| BI | 70 | Lockout Status Reserved – (Time between starts) | Modbus 400026 bit 10 | Read | ||
| BI | 71 | Lockout Status Reserved – (Backspin) | Modbus 400026 bit 11 | Read | ||
| BI | 72 | Lockout Status Reserved – (Starts per hour) | Modbus 400026 bit 12 | Read | ||
| BI | 73 | Lockout Status Reserved – (RTD Comm Loss) | Modbus 400026 bit 13 | Read | ||
| AI | 74 | Present Fault Code | Modbus 400027 | Read | ||
| AImin | 75 | Average Current | Modbus 400028 | A | Read | |
| AI | 76 | L1 Current | Modbus 400029 | A | Read | |
| AI | 77 | L2 Current | Modbus 400030 | A | Read | |
| AI | 78 | L3 Current | Modbus 400031 | A | Read | |
| AI | 79 | Current Imbalance | Modbus 400032 | % | Read | |
| AI | 80 | Residual Ground Fault Current | Modbus 400033 | % | Read | |
| AI | 81 | Reserved | Modbus 400034 | Read | ||
| AImin | 82 | Average Voltage | Modbus 400035 | V | Read | |
| AI | 83 | L1-L2 Voltage | Modbus 400036 | V | Read | |
| AI | 84 | L2-L3 Voltage | Modbus 400037 | V | Read | |
| AI | 85 | L3-L1 Voltage | Modbus 400038 | V | Read | |
| AI | 86 | Motor Overload | Modbus 400039 | % | Read | |
| AI | 87 | Power Factor | Modbus 400040 | PF | Read | |
| AI | 88 | Watts | Modbus 400041 | W | Read | |
| AI | 89 | VA | Modbus 400043 | VA | Read | |
| AI | 90 | vars | Modbus 400045 | VAR | Read | |
| AI | 91 | kW hours | Modbus 400047 | kWh | Read | |
| AI | 92 | Phase Order | Modbus 400049 | Read | ||
| AI | 93 | Line Frequency | Modbus 400050 | Hz | Read | |
| AI | 94 | Analog Input % | Modbus 400051 | % | Read | |
| AI | 95 | Analog Output % | Modbus 400052 | % | Read | |
| AI | 96 | Running Time | Modbus 400053 | h | Read | |
| AI | 97 | Running Time | Modbus 400054 | min | Read | |
| AI | 98 | Starts | Modbus 400055 | Read | ||
| AI | 99 | TruTorque % | Modbus 400056 | % | Read | |
| AI | 100 | Power % | Modbus 400057 | % | Read | |
| AI | 101 | Peak Starting Current | Modbus 400058; not polled by default | A | Read | |
| AI | 102 | Last Starting Duration | Modbus 400059; not polled by default | s | Read | |
| AI | 103 | Motor FLA | Modbus 400101; not polled by default | A | Read | |
| AI | 104 | Motor Service Factor | Modbus 400102; not polled by default | Read | ||
| AI | 105 | Independent Start/Run Motor Overloads | Modbus 400103; not polled by default | Read | ||
| AI | 106 | Motor Overload Running Enable | Modbus 400104; not polled by default | Read | ||
| AI | 107 | Motor Overload Running Class | Modbus 400105; not polled by default | Read | ||
| AI | 108 | Motor Overload Starting Enable | Modbus 400106; not polled by default | Read | ||
| AI | 109 | Motor Overload Starting Class | Modbus 400107; not polled by default | Read | ||
| AI | 110 | Motor Overload Hot/Cold Ratio | Modbus 400108; not polled by default | % | Read | |
| AI | 111 | Motor Overload Cooling Time | Modbus 400109; not polled by default | min | Read | |
| AI | 112 | Local Source | Modbus 400110; not polled by default | Read | ||
| AI | 113 | Remote Source | Modbus 400111; not polled by default | Read | ||
| AI | 114 | Start Mode | Modbus 400112; not polled by default | Read | ||
| AI | 115 | Initial Motor Current 1 | Modbus 400113; not polled by default | % | Read | |
| AI | 116 | Maximum Motor Current 1 | Modbus 400114; not polled by default | % | Read | |
| AI | 117 | Ramp Time 1 | Modbus 400115; not polled by default | s | Read | |
| AI | 118 | Initial Motor Current 2 | Modbus 400116; not polled by default | % | Read | |
| AI | 119 | Maximum Motor Current 2 | Modbus 400117; not polled by default | % | Read | |
| AI | 120 | Ramp Time 2 | Modbus 400118; not polled by default | s | Read | |
| AI | 121 | UTS Time | Modbus 400119; not polled by default | s | Read | |
| AI | 122 | Initial V/T/P | Modbus 400120; not polled by default | % | Read | |
| AI | 123 | Max T/P | Modbus 400121; not polled by default | % | Read | |
| AI | 124 | Stop Mode | Modbus 400122; not polled by default | Read | ||
| AI | 125 | Decel Begin Level | Modbus 400123; not polled by default | % | Read | |
| AI | 126 | Decel End Level | Modbus 400124; not polled by default | % | Read | |
| AI | 127 | Decel Time | Modbus 400125; not polled by default | Read | ||
| AI | 128 | DC Brake Level | Modbus 400126; not polled by default | Read | ||
| AI | 129 | DC Brake Time | Modbus 400127; not polled by default | Read | ||
| AI | 130 | DC Brake Delay | Modbus 400128; not polled by default | Read | ||
| AI | 131 | Kick Enable 1 | Modbus 400129; not polled by default | Read | ||
| AI | 132 | Kick Current Level 1 | Modbus 400130; not polled by default | % | Read | |
| AI | 133 | Kick Time 1 | Modbus 400131; not polled by default | Read | ||
| AI | 134 | Kick Enable 2 | Modbus 400132; not polled by default | Read | ||
| AI | 135 | Kick Current Level 2 | Modbus 400133; not polled by default | % | Read | |
| AI | 136 | Kick Time 2 | Modbus 400134; not polled by default | Read | ||
| AI | 137 | Slow Speed Enable | Modbus 400135; not polled by default | Read | ||
| AI | 138 | Slow Speed | Modbus 400136; not polled by default | % | Read | |
| AI | 139 | Slow Speed Current Level | Modbus 400137; not polled by default | % | Read | |
| AI | 140 | Slow Speed Time Limit Enable | Modbus 400138; not polled by default | Read | ||
| AI | 141 | Slow Speed Time Limit | Modbus 400139; not polled by default | s | Read | |
| AI | 142 | Slow Speed Kick Enable | Modbus 400140; not polled by default | Read | ||
| AI | 143 | Slow Speed Kick Level | Modbus 400141; not polled by default | % | Read | |
| AI | 144 | Slow Speed Kick Time | Modbus 400142; not polled by default | Read | ||
| AI | 145 | Rated RMS Voltage | Modbus 400143; not polled by default | V | Read | |
| AI | 146 | Input Phase Sensitivity | Modbus 400144; not polled by default | Read | ||
| AI | 147 | Motor Rated Power Factor | Modbus 400145; not polled by default | Read | ||
| AI | 148 | Overcurrent Enable | Modbus 400146; not polled by default | Read | ||
| AI | 149 | Overcurrent Level | Modbus 400147; not polled by default | % | Read | |
| AI | 150 | Overcurrent Delay Time Enable | Modbus 400148; not polled by default | Read | ||
| AI | 151 | Overcurrent Delay Time | Modbus 400149; not polled by default | Read | ||
| AI | 152 | Undercurrent Trip Enable | Modbus 400150; not polled by default | Read | ||
| AI | 153 | Undercurrent Trip Level | Modbus 400151; not polled by default | % | Read | |
| AI | 154 | Undercurrent Trip Delay Time Enable | Modbus 400152; not polled by default | Read | ||
| AI | 155 | Undercurrent Trip Delay Time | Modbus 400153; not polled by default | Read | ||
| AI | 156 | Current Imbalance Trip Enable | Modbus 400154; not polled by default | Read | ||
| AI | 157 | Current Imbalance Trip Level | Modbus 400155; not polled by default | % | Read | |
| AI | 158 | Residual Ground Fault Trip Enable | Modbus 400156; not polled by default | Read | ||
| AI | 159 | Residual Ground Fault Trip Level | Modbus 400157; not polled by default | % | Read | |
| AI | 160 | Over Voltage Trip Enable | Modbus 400158; not polled by default | Read | ||
| AI | 161 | Over Voltage Trip Level | Modbus 400159; not polled by default | % | Read | |
| AI | 162 | Under Voltage Trip Enable | Modbus 400160; not polled by default | Read | ||
| AI | 163 | Under Voltage Trip Level | Modbus 400161; not polled by default | % | Read | |
| AI | 164 | Over/Under Voltage Delay Time | Modbus 400162; not polled by default | Read | ||
| AI | 165 | Digital Input Trip Delay Time | Modbus 400163; not polled by default | Read | ||
| AI | 166 | Auto Fault Reset Enable | Modbus 400164; not polled by default | Read | ||
| AI | 167 | Auto Fault Reset Delay Time | Modbus 400165; not polled by default | s | Read | |
| AI | 168 | Auto Fault Reset Count Enable | Modbus 400166; not polled by default | Read | ||
| AI | 169 | Auto Fault Reset Count | Modbus 400167; not polled by default | Read | ||
| AI | 170 | Controlled Fault Stop | Modbus 400168; not polled by default | Read | ||
| AI | 171 | DI 1 Configuration | Modbus 400169; not polled by default | Read | ||
| AI | 172 | DI 2 Configuration | Modbus 400170; not polled by default | Read | ||
| AI | 173 | DI 3 Configuration | Modbus 400171; not polled by default | Read | ||
| AI | 174 | R1 Configuration | Modbus 400172; not polled by default | Read | ||
| AI | 175 | R2 Configuration | Modbus 400173; not polled by default | Read | ||
| AI | 176 | R3 Configuration | Modbus 400174; not polled by default | Read | ||
| AI | 177 | Analog Input Trip Enable | Modbus 400175; not polled by default | Read | ||
| AI | 178 | Analog Input Trip Type | Modbus 400176; not polled by default | Read | ||
| AI | 179 | Analog Input Trip Level | Modbus 400177; not polled by default | % | Read | |
| AI | 180 | Analog Input Trip Delay Time | Modbus 400178; not polled by default | Read | ||
| AI | 181 | Analog Input Span | Modbus 400179; not polled by default | % | Read | |
| AI | 182 | Analog Input Offset | Modbus 400180; not polled by default | % | Read | |
| AI | 183 | Analog Output Function | Modbus 400181; not polled by default | Read | ||
| AI | 184 | Analog Output Span | Modbus 400182; not polled by default | % | Read | |
| AI | 185 | Analog Output Offset | Modbus 400183; not polled by default | % | Read | |
| AI | 186 | Inline Enable | Modbus 400184; not polled by default | Read | ||
| AI | 187 | Inline Delay Time | Modbus 400185; not polled by default | Read | ||
| AI | 188 | Bypass Feedback Time | Modbus 400186; not polled by default | Read | ||
| AI | 189 | Keypad Stop | Modbus 400187; not polled by default | Read | ||
| AI | 190 | Modbus Timeout Enable | Modbus 400188; not polled by default | Read | ||
| AI | 191 | Modbus Timeout | Modbus 400189; not polled by default | s | Read | |
| AI | 192 | CT Ratio (x:1) | Modbus 400190; not polled by default | Read | ||
| AI | 193 | Auto Start | Modbus 400191; not polled by default | Read | ||
| AI | 194 | Energy Saver Enable | Modbus 400192; not polled by default | Read | ||
| AI | 195 | Heater / Anti-Windmill Enable | Modbus 400193; not polled by default | Read | ||
| AI | 196 | Heater / Anti-Windmill Level | Modbus 400194; not polled by default | % | Read | |
| AI | 197 | Starter Type | Modbus 400195; not polled by default | Read | ||
| AI | 198 | LED Display Meter | Modbus 400196; not polled by default | Read | ||
| AI | 199 | LCD Display Meter 1 | Modbus 400197; not polled by default | Read | ||
| AI | 200 | LCD Display Meter 1 | Modbus 400198; not polled by default | Read | ||
| AI | 201 | Misc. Commands | Modbus 400199; not polled by default | Read | ||
| AI | 202 | Bypass Feedback Enable | Modbus 400200; not polled by default | Read | ||
| AI | 203 | Fault Codes 1 | Modbus 400601; not polled by default | Read | ||
| AI | 204 | Fault Codes 2 | Modbus 400602; not polled by default | Read | ||
| AI | 205 | Fault Codes 3 | Modbus 400603; not polled by default | Read | ||
| AI | 206 | Fault Codes 4 | Modbus 400604; not polled by default | Read | ||
| AI | 207 | Fault Codes 5 | Modbus 400605; not polled by default | Read | ||
| AI | 208 | Fault Codes 6 | Modbus 400606; not polled by default | Read | ||
| AI | 209 | Fault Codes 7 | Modbus 400607; not polled by default | Read | ||
| AI | 210 | Fault Codes 8 | Modbus 400608; not polled by default | Read | ||
| AI | 211 | Fault Codes 9 | Modbus 400609; not polled by default | Read | ||
| AI | 212 | System States 1 | Modbus 400611; not polled by default | Read | ||
| AI | 213 | System States 2 | Modbus 400612; not polled by default | Read | ||
| AI | 214 | System States 3 | Modbus 400613; not polled by default | Read | ||
| AI | 215 | System States 4 | Modbus 400614; not polled by default | Read | ||
| AI | 216 | System States 5 | Modbus 400615; not polled by default | Read | ||
| AI | 217 | System States 6 | Modbus 400616; not polled by default | Read | ||
| AI | 218 | System States 7 | Modbus 400617; not polled by default | Read | ||
| AI | 219 | System States 8 | Modbus 400618; not polled by default | Read | ||
| AI | 220 | System States 9 | Modbus 400619; not polled by default | Read | ||
| AI | 221 | L1 Currents 1 | Modbus 400621; not polled by default | A | Read | |
| AI | 222 | L1 Currents 2 | Modbus 400622; not polled by default | A | Read | |
| AI | 223 | L1 Currents 3 | Modbus 400623; not polled by default | A | Read | |
| AI | 224 | L1 Currents 4 | Modbus 400624; not polled by default | A | Read | |
| AI | 225 | L1 Currents 5 | Modbus 400625; not polled by default | A | Read | |
| AI | 226 | L1 Currents 6 | Modbus 400626; not polled by default | A | Read | |
| AI | 227 | L1 Currents 7 | Modbus 400627; not polled by default | A | Read | |
| AI | 228 | L1 Currents 8 | Modbus 400628; not polled by default | A | Read | |
| AI | 229 | L1 Currents 9 | Modbus 400629; not polled by default | A | Read | |
| AI | 230 | L2 Currents 1 | Modbus 400631; not polled by default | A | Read | |
| AI | 231 | L2 Currents 2 | Modbus 400632; not polled by default | A | Read | |
| AI | 232 | L2 Currents 3 | Modbus 400633; not polled by default | A | Read | |
| AI | 233 | L2 Currents 4 | Modbus 400634; not polled by default | A | Read | |
| AI | 234 | L2 Currents 5 | Modbus 400635; not polled by default | A | Read | |
| AI | 235 | L2 Currents 6 | Modbus 400636; not polled by default | A | Read | |
| AI | 236 | L2 Currents 7 | Modbus 400637; not polled by default | A | Read | |
| AI | 237 | L2 Currents 8 | Modbus 400638; not polled by default | A | Read | |
| AI | 238 | L2 Currents 9 | Modbus 400639; not polled by default | A | Read | |
| AI | 239 | L3 Currents 1 | Modbus 400641; not polled by default | A | Read | |
| AI | 240 | L3 Currents 2 | Modbus 400642; not polled by default | A | Read | |
| AI | 241 | L3 Currents 3 | Modbus 400643; not polled by default | A | Read | |
| AI | 242 | L3 Currents 4 | Modbus 400644; not polled by default | A | Read | |
| AI | 243 | L3 Currents 5 | Modbus 400645; not polled by default | A | Read | |
| AI | 244 | L3 Currents 6 | Modbus 400646; not polled by default | A | Read | |
| AI | 245 | L3 Currents 7 | Modbus 400647; not polled by default | A | Read | |
| AI | 246 | L3 Currents 8 | Modbus 400648; not polled by default | A | Read | |
| AI | 247 | L3 Currents 9 | Modbus 400649; not polled by default | A | Read | |
| AI | 248 | L1-L2 Voltages 1 | Modbus 400651; not polled by default | V | Read | |
| AI | 249 | L1-L2 Voltages 2 | Modbus 400652; not polled by default | V | Read | |
| AI | 250 | L1-L2 Voltages 3 | Modbus 400653; not polled by default | V | Read | |
| AI | 251 | L1-L2 Voltages 4 | Modbus 400654; not polled by default | V | Read | |
| AI | 252 | L1-L2 Voltages 5 | Modbus 400655; not polled by default | V | Read | |
| AI | 253 | L1-L2 Voltages 6 | Modbus 400656; not polled by default | V | Read | |
| AI | 254 | L1-L2 Voltages 7 | Modbus 400657; not polled by default | V | Read | |
| AI | 255 | L1-L2 Voltages 8 | Modbus 400658; not polled by default | V | Read | |
| AI | 256 | L1-L2 Voltages 9 | Modbus 400659; not polled by default | V | Read | |
| AI | 257 | L2-L3 Voltages 1 | Modbus 400661; not polled by default | V | Read | |
| AI | 258 | L2-L3 Voltages 2 | Modbus 400662; not polled by default | V | Read | |
| AI | 259 | L2-L3 Voltages 3 | Modbus 400663; not polled by default | V | Read | |
| AI | 260 | L2-L3 Voltages 4 | Modbus 400664; not polled by default | V | Read | |
| AI | 261 | L2-L3 Voltages 5 | Modbus 400665; not polled by default | V | Read | |
| AI | 262 | L2-L3 Voltages 6 | Modbus 400666; not polled by default | V | Read | |
| AI | 263 | L2-L3 Voltages 7 | Modbus 400667; not polled by default | V | Read | |
| AI | 264 | L2-L3 Voltages 8 | Modbus 400668; not polled by default | V | Read | |
| AI | 265 | L2-L3 Voltages 9 | Modbus 400669; not polled by default | V | Read | |
| AI | 266 | L3-L1 Voltages 1 | Modbus 400671; not polled by default | V | Read | |
| AI | 267 | L3-L1 Voltages 2 | Modbus 400672; not polled by default | V | Read | |
| AI | 268 | L3-L1 Voltages 3 | Modbus 400673; not polled by default | V | Read | |
| AI | 269 | L3-L1 Voltages 4 | Modbus 400674; not polled by default | V | Read | |
| AI | 270 | L3-L1 Voltages 5 | Modbus 400675; not polled by default | V | Read | |
| AI | 271 | L3-L1 Voltages 6 | Modbus 400676; not polled by default | V | Read | |
| AI | 272 | L3-L1 Voltages 7 | Modbus 400677; not polled by default | V | Read | |
| AI | 273 | L3-L1 Voltages 8 | Modbus 400678; not polled by default | V | Read | |
| AI | 274 | L3-L1 Voltages 9 | Modbus 400679; not polled by default | V | Read | |
| AI | 275 | Kilowatts 1 | Modbus 400681; not polled by default | kW | Read | |
| AI | 276 | Kilowatts 2 | Modbus 400682; not polled by default | kW | Read | |
| AI | 277 | Kilowatts 3 | Modbus 400683; not polled by default | kW | Read | |
| AI | 278 | Kilowatts 4 | Modbus 400684; not polled by default | kW | Read | |
| AI | 279 | Kilowatts 5 | Modbus 400685; not polled by default | kW | Read | |
| AI | 280 | Kilowatts 6 | Modbus 400686; not polled by default | kW | Read | |
| AI | 281 | Kilowatts 7 | Modbus 400687; not polled by default | kW | Read | |
| AI | 282 | Kilowatts 8 | Modbus 400688; not polled by default | kW | Read | |
| AI | 283 | Kilowatts 9 | Modbus 400689; not polled by default | kW | Read | |
| AI | 284 | Line Periods 1 | Modbus 400691; not polled by default | Read | ||
| AI | 285 | Line Periods 2 | Modbus 400692; not polled by default | Read | ||
| AI | 286 | Line Periods 3 | Modbus 400693; not polled by default | Read | ||
| AI | 287 | Line Periods 4 | Modbus 400694; not polled by default | Read | ||
| AI | 288 | Line Periods 5 | Modbus 400695; not polled by default | Read | ||
| AI | 289 | Line Periods 6 | Modbus 400696; not polled by default | Read | ||
| AI | 290 | Line Periods 7 | Modbus 400697; not polled by default | Read | ||
| AI | 291 | Line Periods 8 | Modbus 400698; not polled by default | Read | ||
| AI | 292 | Line Periods 9 | Modbus 400699; not polled by default | Read | ||
| AI | 293 | Run Time Hours 1 | Modbus 400701; not polled by default | h | Read | |
| AI | 294 | Run Time Hours 2 | Modbus 400702; not polled by default | h | Read | |
| AI | 295 | Run Time Hours 3 | Modbus 400703; not polled by default | h | Read | |
| AI | 296 | Run Time Hours 4 | Modbus 400704; not polled by default | h | Read | |
| AI | 297 | Run Time Hours 5 | Modbus 400705; not polled by default | h | Read | |
| AI | 298 | Run Time Hours 6 | Modbus 400706; not polled by default | h | Read | |
| AI | 299 | Run Time Hours 7 | Modbus 400707; not polled by default | h | Read | |
| AI | 300 | Run Time Hours 8 | Modbus 400708; not polled by default | h | Read | |
| AI | 301 | Run Time Hours 9 | Modbus 400709; not polled by default | h | Read | |
| AI | 302 | Parameter Changed Flag | Modbus 401201; not polled by default | Read | ||
| AI | 303 | Modbus Address | Modbus 401202; not polled by default | Read | ||
| AI | 304 | Baud Rate | Modbus 401203; not polled by default | Read | ||
| AI | 305 | Byte Framing | Modbus 401204; not polled by default | Read | ||
| AI | 306 | Modbus Messages Received | Modbus 401205; not polled by default | Read | ||
| AI | 307 | Scratch | Modbus 401206; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Benshaw RB2/RC2/RX2E point IDs by name
BO1Starter Control Run/StopBO2Starter Control Fault ResetBO3Starter Control Emergency Overload ResetBO4Starter Control Local/RemoteBO5Starter Control Heat DisableBO6Starter Control Ramp SelectBO7Starter Control Reserved (Relay 6)BO8Starter Control Reserved (Relay 5)BO9Starter Control Reserved (Relay 4)BO10Starter Control Relay 3BO11Starter Control Relay 2BO12Starter Control Relay 1BI13Starter Status ReadyBI14Starter Status RunningBI15Starter Status UTSBI16Starter Status AlarmBI17Starter Status FaultBI18Starter Status LockoutBI19Input Status StartBI20Input Status DI 1BI21Input Status DI 2BI22Input Status DI 3BI23Alarm Status 1 A OL – Motor overloadBI24Alarm Status 1 A 5 – Reserved (Motor PTC)BI25Alarm Status 1 A 6 – Reserved (Stator RTD)BI26Alarm Status 1 A 7 – Reserved (Bearing RTD)BI27Alarm Status 1 A 8 – Reserved (Other RTD)BI28Alarm Status 1 A 10 – Phase rotation not ABCBI29Alarm Status 1 A 11 – Phase rotation not CBABI30Alarm Status 1 A 12 – Low Line FrequencyBI31Alarm Status 1 A 13 – High Line FrequencyBI32Alarm Status 1 A 14 – Phase rotation not 1PHBI33Alarm Status 1 A 15 – Phase rotation not 3PHBI34Alarm Status 1 A 21 – Low line L1-L2BI35Alarm Status 1 A 22 – Low line L2-L3BI36Alarm Status 1 A 23 – Low line L3-L1BI37Alarm Status 1 A 24 – High line L1-L2BI38Alarm Status 1 A 25 – High line L2-L3BI39Alarm Status 2 A 26 – High line L3-L1BI40Alarm Status 2 A 27 – Phase lossBI41Alarm Status 2 noL – No lineBI42Alarm Status 2 A 29 – PORT Timeout (reserved)BI43Alarm Status 2 A 31 – OvercurrentBI44Alarm Status 2 A 34 – UndercurrentBI45Alarm Status 2 A 35 – PF Too Leading (reserved)BI46Alarm Status 2 A 36 – PF Too Lagging (reserved)BI47Alarm Status 2 A 37 – Current imbalanceBI48Alarm Status 2 A 38 – Ground faultBI49Alarm Status 2 A 47 – Stack overtemperatureBI50Alarm Status 2 53 – Tach Loss (reserved)BI51Alarm Status 2 A 60 – DI 1BI52Alarm Status 2 A 61 – DI 2BI53Alarm Status 2 A 62 – DI 3BI54Alarm Status 2 63– Reserved (DI 4)BI55Alarm Status 3 A 64 – Reserved (DI 5)BI56Alarm Status 3 A 65 – Reserved (DI 6)BI57Alarm Status 3 A 66 – Reserved (DI 7)BI58Alarm Status 3 A 67 – Reserved (DI 8)BI59Alarm Status 3 A 71 – Analog Input #1 TripBI60Lockout Status L OL – Motor overloadBI61Lockout Status – Reserved - (Motor PTC)BI62Lockout Status – Reserved - (RTD Stator)BI63Lockout Status – Reserved - (RTD Bearing)BI64Lockout Status – Reserved - (RTD Other)BI65Lockout Status L rl – Run InterlockBI66Lockout Status L dS – Disconnect openBI67Lockout Status L Ot – Stack overtemperatureBI68Lockout Status L CP – Control PowerBI69Lockout Status Reserved – (RTD Open/Short)BI70Lockout Status Reserved – (Time between starts)BI71Lockout Status Reserved – (Backspin)BI72Lockout Status Reserved – (Starts per hour)BI73Lockout Status Reserved – (RTD Comm Loss)AI74Present Fault CodeAI75Average CurrentAI76L1 CurrentAI77L2 CurrentAI78L3 CurrentAI79Current ImbalanceAI80Residual Ground Fault CurrentAI81ReservedAI82Average VoltageAI83L1-L2 VoltageAI84L2-L3 VoltageAI85L3-L1 VoltageAI86Motor OverloadAI87Power FactorAI88WattsAI89VAAI90varsAI91kW hoursAI92Phase OrderAI93Line FrequencyAI94Analog Input %AI95Analog Output %AI96Running TimeAI97Running TimeAI98StartsAI99TruTorque %AI100Power %AI101Peak Starting CurrentAI102Last Starting DurationAI103Motor FLAAI104Motor Service FactorAI105Independent Start/Run Motor OverloadsAI106Motor Overload Running EnableAI107Motor Overload Running ClassAI108Motor Overload Starting EnableAI109Motor Overload Starting ClassAI110Motor Overload Hot/Cold RatioAI111Motor Overload Cooling TimeAI112Local SourceAI113Remote SourceAI114Start ModeAI115Initial Motor Current 1AI116Maximum Motor Current 1AI117Ramp Time 1AI118Initial Motor Current 2AI119Maximum Motor Current 2AI120Ramp Time 2AI121UTS TimeAI122Initial V/T/PAI123Max T/PAI124Stop ModeAI125Decel Begin LevelAI126Decel End LevelAI127Decel TimeAI128DC Brake LevelAI129DC Brake TimeAI130DC Brake DelayAI131Kick Enable 1AI132Kick Current Level 1AI133Kick Time 1AI134Kick Enable 2AI135Kick Current Level 2AI136Kick Time 2AI137Slow Speed EnableAI138Slow SpeedAI139Slow Speed Current LevelAI140Slow Speed Time Limit EnableAI141Slow Speed Time LimitAI142Slow Speed Kick EnableAI143Slow Speed Kick LevelAI144Slow Speed Kick TimeAI145Rated RMS VoltageAI146Input Phase SensitivityAI147Motor Rated Power FactorAI148Overcurrent EnableAI149Overcurrent LevelAI150Overcurrent Delay Time EnableAI151Overcurrent Delay TimeAI152Undercurrent Trip EnableAI153Undercurrent Trip LevelAI154Undercurrent Trip Delay Time EnableAI155Undercurrent Trip Delay TimeAI156Current Imbalance Trip EnableAI157Current Imbalance Trip LevelAI158Residual Ground Fault Trip EnableAI159Residual Ground Fault Trip LevelAI160Over Voltage Trip EnableAI161Over Voltage Trip LevelAI162Under Voltage Trip EnableAI163Under Voltage Trip LevelAI164Over/Under Voltage Delay TimeAI165Digital Input Trip Delay TimeAI166Auto Fault Reset EnableAI167Auto Fault Reset Delay TimeAI168Auto Fault Reset Count EnableAI169Auto Fault Reset CountAI170Controlled Fault StopAI171DI 1 ConfigurationAI172DI 2 ConfigurationAI173DI 3 ConfigurationAI174R1 ConfigurationAI175R2 ConfigurationAI176R3 ConfigurationAI177Analog Input Trip EnableAI178Analog Input Trip TypeAI179Analog Input Trip LevelAI180Analog Input Trip Delay TimeAI181Analog Input SpanAI182Analog Input OffsetAI183Analog Output FunctionAI184Analog Output SpanAI185Analog Output OffsetAI186Inline EnableAI187Inline Delay TimeAI188Bypass Feedback TimeAI189Keypad StopAI190Modbus Timeout EnableAI191Modbus TimeoutAI192CT Ratio (x:1)AI193Auto StartAI194Energy Saver EnableAI195Heater / Anti-Windmill EnableAI196Heater / Anti-Windmill LevelAI197Starter TypeAI198LED Display MeterAI199LCD Display Meter 1AI200LCD Display Meter 1AI201Misc. CommandsAI202Bypass Feedback EnableAI203Fault Codes 1AI204Fault Codes 2AI205Fault Codes 3AI206Fault Codes 4AI207Fault Codes 5AI208Fault Codes 6AI209Fault Codes 7AI210Fault Codes 8AI211Fault Codes 9AI212System States 1AI213System States 2AI214System States 3AI215System States 4AI216System States 5AI217System States 6AI218System States 7AI219System States 8AI220System States 9AI221L1 Currents 1AI222L1 Currents 2AI223L1 Currents 3AI224L1 Currents 4AI225L1 Currents 5AI226L1 Currents 6AI227L1 Currents 7AI228L1 Currents 8AI229L1 Currents 9AI230L2 Currents 1AI231L2 Currents 2AI232L2 Currents 3AI233L2 Currents 4AI234L2 Currents 5AI235L2 Currents 6AI236L2 Currents 7AI237L2 Currents 8AI238L2 Currents 9AI239L3 Currents 1AI240L3 Currents 2AI241L3 Currents 3AI242L3 Currents 4AI243L3 Currents 5AI244L3 Currents 6AI245L3 Currents 7AI246L3 Currents 8AI247L3 Currents 9AI248L1-L2 Voltages 1AI249L1-L2 Voltages 2AI250L1-L2 Voltages 3AI251L1-L2 Voltages 4AI252L1-L2 Voltages 5AI253L1-L2 Voltages 6AI254L1-L2 Voltages 7AI255L1-L2 Voltages 8AI256L1-L2 Voltages 9AI257L2-L3 Voltages 1AI258L2-L3 Voltages 2AI259L2-L3 Voltages 3AI260L2-L3 Voltages 4AI261L2-L3 Voltages 5AI262L2-L3 Voltages 6AI263L2-L3 Voltages 7AI264L2-L3 Voltages 8AI265L2-L3 Voltages 9AI266L3-L1 Voltages 1AI267L3-L1 Voltages 2AI268L3-L1 Voltages 3AI269L3-L1 Voltages 4AI270L3-L1 Voltages 5AI271L3-L1 Voltages 6AI272L3-L1 Voltages 7AI273L3-L1 Voltages 8AI274L3-L1 Voltages 9AI275Kilowatts 1AI276Kilowatts 2AI277Kilowatts 3AI278Kilowatts 4AI279Kilowatts 5AI280Kilowatts 6AI281Kilowatts 7AI282Kilowatts 8AI283Kilowatts 9AI284Line Periods 1AI285Line Periods 2AI286Line Periods 3AI287Line Periods 4AI288Line Periods 5AI289Line Periods 6AI290Line Periods 7AI291Line Periods 8AI292Line Periods 9AI293Run Time Hours 1AI294Run Time Hours 2AI295Run Time Hours 3AI296Run Time Hours 4AI297Run Time Hours 5AI298Run Time Hours 6AI299Run Time Hours 7AI300Run Time Hours 8AI301Run Time Hours 9AI302Parameter Changed FlagAI303Modbus AddressAI304Baud RateAI305Byte FramingAI306Modbus Messages ReceivedAI307Scratch
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Benshaw_Redistart_RB2_RC2_RX2E__LX.csv; the profile maps the registers in the Benshaw RediStart Modbus register list (https://www.ccontrols.com/support/dp/Benshaw.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 100 of the 307 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Running Time; LCD Display Meter 1); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
How many BACnet points does the Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX have?
This list has 307 BACnet objects: 234 analog inputs, 61 binary inputs, 12 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX BACnet points are writable?
12 of the 307 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Benshaw_Redistart_RB2_RC2_RX2E_ (Benshaw_Redistart_RB2_RC2_RX2E__LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Benshaw_Redistart_RB2_RC2_RX2E__LX.csv.
What are the minimum BACnet points to integrate the Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX?
Start with BO 1 Starter Control Run/Stop (Run (1) / stop (0)); BO 4 Starter Control Local/Remote (Local/remote select); BO 2 Starter Control Fault Reset (Fault reset); BI 14 Starter Status Running (Starter running); BI 15 Starter Status UTS (Up to speed); AI 75 Average Current (Average motor current); AI 82 Average Voltage (Average line voltage); BI 16 Starter Status Alarm (Alarm active); BI 17 Starter Status Fault (Fault active); BI 18 Starter Status Lockout (Lockout active).
How do I enable BMS control of the Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX?
Starter Control Local/Remote (BO 4) selects whether the network run command is used; check the Benshaw manual for which state is remote.
How do I check these points on the real Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Benshaw_Redistart_RB2_RC2_RX2E_ · Benshaw_Redistart_RB2_RC2_RX2E__LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.