Boiler burner management (parallel positioning) · BACnet points list
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Fireye PPC4000: 153 Analog Inputs, 43 polled by default. It reads operational state, burner hours and cycles, modulation rate and mode, servo and VFD positions, O2 trim values, sensor readings, the lockout history and the burner control flags.
This page lists 153 BACnet objects for the Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Fireye PPC4000 parallel positioning control via BASgatewayLX
- Equipment
- Boiler burner management (parallel positioning)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 153 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- PPC4000, PPC 4000, Fireye PPC-4000
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Read operational state, modulation rate and the burner control flags; enable the lockout history if you want fault codes. The profile has no writable objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Operational State | Operational state | Read |
| AI 149 | Burner Control On/Off | Burner on/off control state | Read |
| AI 5 | Current Modulation Rate | Current modulation rate | Read |
| AI 6 | Modulation Mode | Modulation mode | Read |
| AI 152 | Burner Control AutoManual | Auto/manual state | Read |
| AI 3 | Burner on minutes | Burner on minutes | Read |
| AI 42 | Lockout History – Current active error number | Current active error number | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- The Burner Control objects (AI 149-153) are inputs in this profile, so they show state only.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Operational State | Modbus 400001 | Read | ||
| AI | 2 | System On Minutes | Modbus 400003 | min | Read | |
| AImin | 3 | Burner on minutes | Modbus 400005 | min | Read | |
| AI | 4 | Completed Burner Cycles | Modbus 400007 | Read | ||
| AImin | 5 | Current Modulation Rate | Modbus 400009 | % | Read | |
| AImin | 6 | Modulation Mode | Modbus 400010 | Read | ||
| AI | 7 | Current internal temperature of the PPC 4000 | Modbus 400011 | Read | ||
| AI | 8 | Current Profile Commission Point | Modbus 400012 | Read | ||
| AI | 9 | Current Calculated C02 value | Modbus 400013 | Read | ||
| AI | 10 | PPC 4000 Model | Modbus 400014; not polled by default | Read | ||
| AI | 11 | Current Selected Profile | Modbus 400015 | Read | ||
| AI | 12 | Total # of commissioned points in current profile | Modbus 400016 | Read | ||
| AI | 13 | Current Profile Commissioned Points Range | Modbus 400017 | Read | ||
| AI | 14 | Current Digital Input values | Modbus 400018 | Read | ||
| AI | 15 | Current VFD 1 position in 1/10th degree | Modbus 400022 | Read | ||
| AI | 16 | Commanded VFD 1 position in 1/10th degree | Modbus 400023 | Read | ||
| AI | 17 | Current VFD 2 position in 1/10th degree | Modbus 400024 | Read | ||
| AI | 18 | Commanded VFD 2 position in 1/10th degree | Modbus 400025 | Read | ||
| AI | 19 | Current running efficiency | Modbus 400026 | % | Read | |
| AI | 20 | Current 02 Target Value in 1/10th % | Modbus 400027 | Read | ||
| AI | 21 | 02 Probe Status (see 02 Probe Manual) | Modbus 400036 | Read | ||
| AI | 22 | 02 Probe Stacl< Temperature (see 02 Probe Manual) | Modbus 400037 | Read | ||
| AI | 23 | 02 Probe Ambient Temperature (see 02 Probe Manual) | Modbus 400038 | Read | ||
| AI | 24 | 02 Probe 02 Level (see 02 Probe Manual) | Modbus 400039 | Read | ||
| AI | 25 | Calibration constant | Modbus 400052; not polled by default | Read | ||
| AI | 26 | Sensor 1 measured raw value | Modbus 400060 | Read | ||
| AI | 27 | Sensor 2 measured raw value | Modbus 400061 | Read | ||
| AI | 28 | Sensor 3 measured raw value | Modbus 400062 | Read | ||
| AI | 29 | Sensor 4 measured raw value | Modbus 400066 | Read | ||
| AI | 30 | Sensor 5 measured raw value | Modbus 400067 | Read | ||
| AI | 31 | Servo 1 current position | Modbus 400080 | Read | ||
| AI | 32 | Servo 2 current position | Modbus 400089 | Read | ||
| AI | 33 | Servo 3 current position | Modbus 400098 | Read | ||
| AI | 34 | Servo 4 current position | Modbus 400107 | Read | ||
| AI | 35 | Servo 5 current position | Modbus 400116 | Read | ||
| AI | 36 | Servo 6 current position | Modbus 400125 | Read | ||
| AI | 37 | Servo 7 current position | Modbus 400134 | Read | ||
| AI | 38 | Servo 8 current position | Modbus 400143 | Read | ||
| AI | 39 | Servo 9 current position | Modbus 400152 | Read | ||
| AI | 40 | Servo 10 current position | Modbus 400161 | Read | ||
| AI | 41 | Lockout History | Modbus 400191; not polled by default | Read | ||
| AImin | 42 | Lockout History – Current active error number | Modbus 400192; not polled by default | Read | ||
| AI | 43 | Lockout History – Total number of errors detected | Modbus 400193; not polled by default | Read | ||
| AI | 44 | Lockout History - Fault 1 | Modbus 400194; not polled by default | Read | ||
| AI | 45 | Lockout History - Fault 1 - Error code | Modbus 400195; not polled by default | Read | ||
| AI | 46 | Lockout History - Fault 1 - Time of Fault Occurrence | Modbus 400196; not polled by default | Read | ||
| AI | 47 | Lockout History - Fault 1 - Date of Fault Occurrence | Modbus 400197; not polled by default | Read | ||
| AI | 48 | Lockout History - Fault 1 - Date of Fault Occurrence | Modbus 400198; not polled by default | Read | ||
| AI | 49 | Lockout History - Fault 1 - Year of Fault Occurrence | Modbus 400199; not polled by default | Read | ||
| AI | 50 | Locl<out History - Fault 2 | Modbus 400200; not polled by default | Read | ||
| AI | 51 | Lockout History - Fault 2 - Error code | Modbus 400201; not polled by default | Read | ||
| AI | 52 | Lockout History - Fault 2 - Time of Fault Occurrence | Modbus 400202; not polled by default | Read | ||
| AI | 53 | Lockout History - Fault 2 - Date of Fault Occurrence | Modbus 400203; not polled by default | Read | ||
| AI | 54 | Lockout History - Fault 2 - Date of Fault Occurrence | Modbus 400204; not polled by default | Read | ||
| AI | 55 | Lockout History - Fault 2 - Year of Fault Occurrence | Modbus 400205; not polled by default | Read | ||
| AI | 56 | Lockout History - Fault 3 | Modbus 400206; not polled by default | Read | ||
| AI | 57 | Lockout History - Fault 3 - Error code | Modbus 400207; not polled by default | Read | ||
| AI | 58 | Lockout History - Fault 3 - Time of Fault Occurrence | Modbus 400208; not polled by default | Read | ||
| AI | 59 | Lockout History - Fault 3 - Date of Fault Occurrence | Modbus 400209; not polled by default | Read | ||
| AI | 60 | Lockout History - Fault 3 - Date of Fault Occurrence | Modbus 400210; not polled by default | Read | ||
| AI | 61 | Lockout History - Fault 3 - Year of Fault Occurrence | Modbus 400211; not polled by default | Read | ||
| AI | 62 | Lockout History - Fault 4 | Modbus 400212; not polled by default | Read | ||
| AI | 63 | Lockout History - Fault 4 - Error code | Modbus 400213; not polled by default | Read | ||
| AI | 64 | Lockout History - Fault 4 - Time of Fault Occurrence | Modbus 400214; not polled by default | Read | ||
| AI | 65 | Lockout History - Fault 4 - Date of Fault Occurrence | Modbus 400215; not polled by default | Read | ||
| AI | 66 | Lockout History - Fault 4 - Date of Fault Occurrence | Modbus 400216; not polled by default | Read | ||
| AI | 67 | Lockout History - Fault 4 - Year of Fault Occurrence | Modbus 400217; not polled by default | Read | ||
| AI | 68 | Lockout History - Fault 5 | Modbus 400218; not polled by default | Read | ||
| AI | 69 | Lockout History - Fault 5 - Error code | Modbus 400219; not polled by default | Read | ||
| AI | 70 | Lockout History - Fault 5 - Time of Fault Occurrence | Modbus 400220; not polled by default | Read | ||
| AI | 71 | Lockout History - Fault 5 - Date of Fault Occurrence | Modbus 400221; not polled by default | Read | ||
| AI | 72 | Lockout History - Fault 5 - Date of Fault Occurrence | Modbus 400222; not polled by default | Read | ||
| AI | 73 | Lockout History - Fault 5 - Year of Fault Occurrence | Modbus 400223; not polled by default | Read | ||
| AI | 74 | Locl<out History - Fault 6 | Modbus 400224; not polled by default | Read | ||
| AI | 75 | Lockout History - Fault 6 - Error code | Modbus 400225; not polled by default | Read | ||
| AI | 76 | Lockout History - Fault 6 - Time of Fault Occurrence | Modbus 400226; not polled by default | Read | ||
| AI | 77 | Lockout History - Fault 6 - Date of Fault Occurrence | Modbus 400227; not polled by default | Read | ||
| AI | 78 | Lockout History - Fault 6 - Date of Fault Occurrence | Modbus 400228; not polled by default | Read | ||
| AI | 79 | Lockout History - Fault 6 - Year of Fault Occurrence | Modbus 400229; not polled by default | Read | ||
| AI | 80 | Lockout History - Fault 7 | Modbus 400230; not polled by default | Read | ||
| AI | 81 | Lockout History - Fault 7 - Error code | Modbus 400231; not polled by default | Read | ||
| AI | 82 | Lockout History - Fault 7 - Time of Fault Occurrence | Modbus 400232; not polled by default | Read | ||
| AI | 83 | Lockout History - Fault 7 - Date of Fault Occurrence | Modbus 400233; not polled by default | Read | ||
| AI | 84 | Lockout History - Fault 7 - Date of Fault Occurrence | Modbus 400234; not polled by default | Read | ||
| AI | 85 | Lockout History - Fault 7 - Year of Fault Occurrence | Modbus 400235; not polled by default | Read | ||
| AI | 86 | Lockout History - Fault 8 | Modbus 400236; not polled by default | Read | ||
| AI | 87 | Lockout History - Fault 8 - Error code | Modbus 400237; not polled by default | Read | ||
| AI | 88 | Lockout History - Fault 8 - Time of Fault Occurrence | Modbus 400238; not polled by default | Read | ||
| AI | 89 | Lockout History - Fault 8 - Date of Fault Occurrence | Modbus 400239; not polled by default | Read | ||
| AI | 90 | Lockout History - Fault 8 - Date of Fault Occurrence | Modbus 400240; not polled by default | Read | ||
| AI | 91 | Lockout History - Fault 8 - Year of Fault Occurrence | Modbus 400241; not polled by default | Read | ||
| AI | 92 | Lockout History - Fault 9 | Modbus 400242; not polled by default | Read | ||
| AI | 93 | Lockout History - Fault 9 - Error code | Modbus 400243; not polled by default | Read | ||
| AI | 94 | Lockout History - Fault 9 - Time of Fault Occurrence | Modbus 400244; not polled by default | Read | ||
| AI | 95 | Lockout History - Fault 9 - Date of Fault Occurrence | Modbus 400245; not polled by default | Read | ||
| AI | 96 | Lockout History - Fault 9 - Date of Fault Occurrence | Modbus 400246; not polled by default | Read | ||
| AI | 97 | Lockout History - Fault 9 - Year of Fault Occurrence | Modbus 400247; not polled by default | Read | ||
| AI | 98 | Locl<out History - Fault 10 | Modbus 400248; not polled by default | Read | ||
| AI | 99 | Lockout History - Fault 10 - Error code | Modbus 400249; not polled by default | Read | ||
| AI | 100 | Lockout History - Fault 10 - Time of Fault | Modbus 400250; not polled by default | Read | ||
| AI | 101 | Occurrence | Modbus 400251; not polled by default | Read | ||
| AI | 102 | Lockout History - Fault 10 - Date of Fault | Modbus 400252; not polled by default | Read | ||
| AI | 103 | Occurrence | Modbus 400253; not polled by default | Read | ||
| AI | 104 | Sensor 1 set point value | Modbus 400265; not polled by default | Read | ||
| AI | 105 | Sensor 1 Cut In value | Modbus 400266; not polled by default | Read | ||
| AI | 106 | Sensor 1 Cut Out value | Modbus 400267; not polled by default | Read | ||
| AI | 107 | Sensor 1 Margin Alarm value | Modbus 400269; not polled by default | Read | ||
| AI | 108 | Sensor 1 Limit Alarm value | Modbus 400270; not polled by default | Read | ||
| AI | 109 | Sensor 2 set point value | Modbus 400273; not polled by default | Read | ||
| AI | 110 | Sensor 2 Cut In value | Modbus 400274; not polled by default | Read | ||
| AI | 111 | Sensor 2 Cut Out value | Modbus 400275; not polled by default | Read | ||
| AI | 112 | Sensor 2 Margin Alarm value | Modbus 400277; not polled by default | Read | ||
| AI | 113 | Sensor 2 Limit Alarm value | Modbus 400278; not polled by default | Read | ||
| AI | 114 | Sensor 3 set point value | Modbus 400281; not polled by default | Read | ||
| AI | 115 | Sensor 3 Cut In value | Modbus 400282; not polled by default | Read | ||
| AI | 116 | Sensor 3 Cut Out value | Modbus 400283; not polled by default | Read | ||
| AI | 117 | Sensor 3 Margin Alarm value | Modbus 400285; not polled by default | Read | ||
| AI | 118 | Sensor 3 Limit Alarm value | Modbus 400286; not polled by default | Read | ||
| AI | 119 | Sensor 4 set point value | Modbus 400289; not polled by default | Read | ||
| AI | 120 | Sensor 4 Cut In value | Modbus 400290; not polled by default | Read | ||
| AI | 121 | Sensor 4 Cut Out value | Modbus 400291; not polled by default | Read | ||
| AI | 122 | Sensor 4 Margin Alarm value | Modbus 400293; not polled by default | Read | ||
| AI | 123 | Sensor 4 Limit Alarm value | Modbus 400294; not polled by default | Read | ||
| AI | 124 | Sensor 5 set point value | Modbus 400297; not polled by default | Read | ||
| AI | 125 | Sensor 5 Cut In value | Modbus 400298; not polled by default | Read | ||
| AI | 126 | Sensor 5 Cut Out value | Modbus 400299; not polled by default | Read | ||
| AI | 127 | Sensor 5 Margin Alarm value | Modbus 400301; not polled by default | Read | ||
| AI | 128 | Sensor 5 Limit Alarm value | Modbus 400302; not polled by default | Read | ||
| AI | 129 | PCV Setpoint string A | Modbus 400347; not polled by default | Read | ||
| AI | 130 | PCV Setpoint string B | Modbus 400348; not polled by default | Read | ||
| AI | 131 | PCV Setpoint string C | Modbus 400349; not polled by default | Read | ||
| AI | 132 | PCV Setpoint string D | Modbus 400350; not polled by default | Read | ||
| AI | 133 | PCV Setpoint string E | Modbus 400351; not polled by default | Read | ||
| AI | 134 | PCV Setpoint string F | Modbus 400352; not polled by default | Read | ||
| AI | 135 | PCV Setpoint string G | Modbus 400353; not polled by default | Read | ||
| AI | 136 | PCV Setpoint string H | Modbus 400354; not polled by default | Read | ||
| AI | 137 | PCV Setpoint string I | Modbus 400355; not polled by default | Read | ||
| AI | 138 | PCV Setpoint string J | Modbus 400356; not polled by default | Read | ||
| AI | 139 | PCV measured value string A | Modbus 400357; not polled by default | Read | ||
| AI | 140 | PCV measured value string B | Modbus 400358; not polled by default | Read | ||
| AI | 141 | PCV measured value string C | Modbus 400359; not polled by default | Read | ||
| AI | 142 | PCV measured value string D | Modbus 400360; not polled by default | Read | ||
| AI | 143 | PCV measured value string E | Modbus 400361; not polled by default | Read | ||
| AI | 144 | PCV measured value string F | Modbus 400362; not polled by default | Read | ||
| AI | 145 | PCV measured value string G | Modbus 400363; not polled by default | Read | ||
| AI | 146 | PCV measured value string H | Modbus 400364; not polled by default | Read | ||
| AI | 147 | PCV measured value string I | Modbus 400365; not polled by default | Read | ||
| AI | 148 | PCV measured value string J | Modbus 400366; not polled by default | Read | ||
| AImin | 149 | Burner Control On/Off | Modbus 401002 | Read | ||
| AI | 150 | Burner Control Low Fire | Modbus 401003 | Read | ||
| AI | 151 | Burner Control Lead Lag | Modbus 401004 | Read | ||
| AImin | 152 | Burner Control AutoManual | Modbus 401005 | Read | ||
| AI | 153 | Manual Modulation Rate | Modbus 401018 | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Fireye PPC4000 point IDs by name
AI1Operational StateAI2System On MinutesAI3Burner on minutesAI4Completed Burner CyclesAI5Current Modulation RateAI6Modulation ModeAI7Current internal temperature of the PPC 4000AI8Current Profile Commission PointAI9Current Calculated C02 valueAI10PPC 4000 ModelAI11Current Selected ProfileAI12Total # of commissioned points in current profileAI13Current Profile Commissioned Points RangeAI14Current Digital Input valuesAI15Current VFD 1 position in 1/10th degreeAI16Commanded VFD 1 position in 1/10th degreeAI17Current VFD 2 position in 1/10th degreeAI18Commanded VFD 2 position in 1/10th degreeAI19Current running efficiencyAI20Current 02 Target Value in 1/10th %AI2102 Probe Status (see 02 Probe Manual)AI2202 Probe Stacl< Temperature (see 02 Probe Manual)AI2302 Probe Ambient Temperature (see 02 Probe Manual)AI2402 Probe 02 Level (see 02 Probe Manual)AI25Calibration constantAI26Sensor 1 measured raw valueAI27Sensor 2 measured raw valueAI28Sensor 3 measured raw valueAI29Sensor 4 measured raw valueAI30Sensor 5 measured raw valueAI31Servo 1 current positionAI32Servo 2 current positionAI33Servo 3 current positionAI34Servo 4 current positionAI35Servo 5 current positionAI36Servo 6 current positionAI37Servo 7 current positionAI38Servo 8 current positionAI39Servo 9 current positionAI40Servo 10 current positionAI41Lockout HistoryAI42Lockout History – Current active error numberAI43Lockout History – Total number of errors detectedAI44Lockout History - Fault 1AI45Lockout History - Fault 1 - Error codeAI46Lockout History - Fault 1 - Time of Fault OccurrenceAI47Lockout History - Fault 1 - Date of Fault OccurrenceAI48Lockout History - Fault 1 - Date of Fault OccurrenceAI49Lockout History - Fault 1 - Year of Fault OccurrenceAI50Locl<out History - Fault 2AI51Lockout History - Fault 2 - Error codeAI52Lockout History - Fault 2 - Time of Fault OccurrenceAI53Lockout History - Fault 2 - Date of Fault OccurrenceAI54Lockout History - Fault 2 - Date of Fault OccurrenceAI55Lockout History - Fault 2 - Year of Fault OccurrenceAI56Lockout History - Fault 3AI57Lockout History - Fault 3 - Error codeAI58Lockout History - Fault 3 - Time of Fault OccurrenceAI59Lockout History - Fault 3 - Date of Fault OccurrenceAI60Lockout History - Fault 3 - Date of Fault OccurrenceAI61Lockout History - Fault 3 - Year of Fault OccurrenceAI62Lockout History - Fault 4AI63Lockout History - Fault 4 - Error codeAI64Lockout History - Fault 4 - Time of Fault OccurrenceAI65Lockout History - Fault 4 - Date of Fault OccurrenceAI66Lockout History - Fault 4 - Date of Fault OccurrenceAI67Lockout History - Fault 4 - Year of Fault OccurrenceAI68Lockout History - Fault 5AI69Lockout History - Fault 5 - Error codeAI70Lockout History - Fault 5 - Time of Fault OccurrenceAI71Lockout History - Fault 5 - Date of Fault OccurrenceAI72Lockout History - Fault 5 - Date of Fault OccurrenceAI73Lockout History - Fault 5 - Year of Fault OccurrenceAI74Locl<out History - Fault 6AI75Lockout History - Fault 6 - Error codeAI76Lockout History - Fault 6 - Time of Fault OccurrenceAI77Lockout History - Fault 6 - Date of Fault OccurrenceAI78Lockout History - Fault 6 - Date of Fault OccurrenceAI79Lockout History - Fault 6 - Year of Fault OccurrenceAI80Lockout History - Fault 7AI81Lockout History - Fault 7 - Error codeAI82Lockout History - Fault 7 - Time of Fault OccurrenceAI83Lockout History - Fault 7 - Date of Fault OccurrenceAI84Lockout History - Fault 7 - Date of Fault OccurrenceAI85Lockout History - Fault 7 - Year of Fault OccurrenceAI86Lockout History - Fault 8AI87Lockout History - Fault 8 - Error codeAI88Lockout History - Fault 8 - Time of Fault OccurrenceAI89Lockout History - Fault 8 - Date of Fault OccurrenceAI90Lockout History - Fault 8 - Date of Fault OccurrenceAI91Lockout History - Fault 8 - Year of Fault OccurrenceAI92Lockout History - Fault 9AI93Lockout History - Fault 9 - Error codeAI94Lockout History - Fault 9 - Time of Fault OccurrenceAI95Lockout History - Fault 9 - Date of Fault OccurrenceAI96Lockout History - Fault 9 - Date of Fault OccurrenceAI97Lockout History - Fault 9 - Year of Fault OccurrenceAI98Locl<out History - Fault 10AI99Lockout History - Fault 10 - Error codeAI100Lockout History - Fault 10 - Time of FaultAI101OccurrenceAI102Lockout History - Fault 10 - Date of FaultAI103OccurrenceAI104Sensor 1 set point valueAI105Sensor 1 Cut In valueAI106Sensor 1 Cut Out valueAI107Sensor 1 Margin Alarm valueAI108Sensor 1 Limit Alarm valueAI109Sensor 2 set point valueAI110Sensor 2 Cut In valueAI111Sensor 2 Cut Out valueAI112Sensor 2 Margin Alarm valueAI113Sensor 2 Limit Alarm valueAI114Sensor 3 set point valueAI115Sensor 3 Cut In valueAI116Sensor 3 Cut Out valueAI117Sensor 3 Margin Alarm valueAI118Sensor 3 Limit Alarm valueAI119Sensor 4 set point valueAI120Sensor 4 Cut In valueAI121Sensor 4 Cut Out valueAI122Sensor 4 Margin Alarm valueAI123Sensor 4 Limit Alarm valueAI124Sensor 5 set point valueAI125Sensor 5 Cut In valueAI126Sensor 5 Cut Out valueAI127Sensor 5 Margin Alarm valueAI128Sensor 5 Limit Alarm valueAI129PCV Setpoint string AAI130PCV Setpoint string BAI131PCV Setpoint string CAI132PCV Setpoint string DAI133PCV Setpoint string EAI134PCV Setpoint string FAI135PCV Setpoint string GAI136PCV Setpoint string HAI137PCV Setpoint string IAI138PCV Setpoint string JAI139PCV measured value string AAI140PCV measured value string BAI141PCV measured value string CAI142PCV measured value string DAI143PCV measured value string EAI144PCV measured value string FAI145PCV measured value string GAI146PCV measured value string HAI147PCV measured value string IAI148PCV measured value string JAI149Burner Control On/OffAI150Burner Control Low FireAI151Burner Control Lead LagAI152Burner Control AutoManualAI153Manual Modulation Rate
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Fireye_PPC4000_a_LX.csv; the profile maps the registers in the PPC4000 Modbus register list (https://www.ccontrols.com/support/dp/MOD-4001.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 43 of the 153 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Lockout History - Fault 1 - Date of Fault Occurrence; Lockout History - Fault 2 - Date of Fault Occurrence; Lockout History - Fault 3 - Date of Fault Occurrence...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Fireye PPC4000 parallel positioning control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
How many BACnet points does the Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX have?
This list has 153 BACnet objects: 153 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Fireye_PPC4000_a (Fireye_PPC4000_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/FireyePPC4000.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX?
Start with AI 1 Operational State (Operational state); AI 149 Burner Control On/Off (Burner on/off control state); AI 5 Current Modulation Rate (Current modulation rate); AI 6 Modulation Mode (Modulation mode); AI 152 Burner Control AutoManual (Auto/manual state); AI 3 Burner on minutes (Burner on minutes); AI 42 Lockout History – Current active error number (Current active error number).
How do I check these points on the real Fireye PPC4000 parallel positioning control via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Fireye_PPC4000_a · Fireye_PPC4000_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.