Generator set controller · BACnet points list
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Cat EMCP 4: 570 objects (348 AI, 48 AO, 174 BI), 64 polled by default (generator and bus electrical values, generator bearing and winding temperatures, fuel level, oil, coolant, battery, rpm and hours). Unpolled rows add further engine values, exhaust ports, control switch position and command, the alarm group bits and writable analog/PWM outputs and passwords.
This page lists 570 BACnet objects for the Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Caterpillar EMCP 4 generator set control via BASgatewayLX
- Equipment
- Generator set controller
- Equipment type
- Other equipment
- BACnet objects
- 570 (48 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Read generator kW, voltage, current and frequency plus engine values. Enable the control switch position and the alarm group bits you need; there is no start/stop command in the polled set.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 7 | Generator Total Real Power | Generator total real power | Read |
| AI 1 | Generator Average Line-Line AC RMS Voltage | Average line-line voltage | Read |
| AI 2 | Generator Average AC RMS Current | Average current | Read |
| AI 3 | Generator Average AC RMS Frequency | Generator frequency | Read |
| AI 70 | Engine rpm | Engine speed | Read |
| AI 68 | Engine Coolant Temperature | Coolant temperature | Read |
| AI 67 | Engine Oil Pressure | Oil pressure | Read |
| AI 69 | Battery Voltage | Battery voltage | Read |
| AI 65 | Fuel Level | Fuel level, % | Read |
| AI 119 | Engine Control Switch Position | Engine control switch position | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Password objects (AO 378+) are part of the EMCP security scheme; leave them unpolled.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Generator Average Line-Line AC RMS Voltage | Modbus 400100 | V | Read | |
| AImin | 2 | Generator Average AC RMS Current | Modbus 400101 | A | Read | |
| AImin | 3 | Generator Average AC RMS Frequency | Modbus 400102 | Hz | Read | |
| AI | 4 | Generator Overall Power Factor | Modbus 400103 | PF | Read | |
| AI | 5 | Generator Overall Power Factor Lagging | Modbus 400104 | Read | ||
| AI | 6 | Generator Total Percent kW | Modbus 400105 | % | Read | |
| AImin | 7 | Generator Total Real Power | Modbus 400106 | W | Read | |
| AI | 8 | Generator Phase A Line-Line AC RMS Voltage | Modbus 400108 | V | Read | |
| AI | 9 | Generator Phase B Line-Line AC RMS Voltage | Modbus 400109 | V | Read | |
| AI | 10 | Generator Phase C Line-Line AC RMS Voltage | Modbus 400110 | V | Read | |
| AI | 11 | Generator Phase A AC RMS Current | Modbus 400111 | A | Read | |
| AI | 12 | Generator Phase B AC RMS Current | Modbus 400112 | A | Read | |
| AI | 13 | Generator Phase C AC RMS Current | Modbus 400113 | A | Read | |
| AI | 14 | Generator Phase A Line-Neutral AC RMS Voltage | Modbus 400114 | V | Read | |
| AI | 15 | Generator Phase B Line-Neutral AC RMS Voltage | Modbus 400115 | V | Read | |
| AI | 16 | Generator Phase C Line-Neutral AC RMS Voltage | Modbus 400116 | V | Read | |
| AI | 17 | Generator Phase A Real Power | Modbus 400117 | W | Read | |
| AI | 18 | Generator Phase B Real Power | Modbus 400119 | W | Read | |
| AI | 19 | Generator Phase C Real Power | Modbus 400121 | W | Read | |
| AI | 20 | Generator Phase A Apparent Power | Modbus 400123 | VA | Read | |
| AI | 21 | Generator Phase B Apparent Power | Modbus 400125 | VA | Read | |
| AI | 22 | Generator Phase C Apparent Power | Modbus 400127 | VA | Read | |
| AI | 23 | Generator Phase A Reactive Power | Modbus 400129 | VAR | Read | |
| AI | 24 | Generator Phase B Reactive Power | Modbus 400131 | VAR | Read | |
| AI | 25 | Generator Phase C Reactive Power | Modbus 400133 | VAR | Read | |
| AI | 26 | Generator Phase A Power Factor | Modbus 400135 | PF | Read | |
| AI | 27 | Generator Phase B Power Factor | Modbus 400136 | PF | Read | |
| AI | 28 | Generator Phase C Power Factor | Modbus 400137 | PF | Read | |
| AI | 29 | Generator Total Apparent Power | Modbus 400138 | VA | Read | |
| AI | 30 | Generator Total Percent Apparent Power | Modbus 400140 | % | Read | |
| AI | 31 | Generator Total Reactive Power | Modbus 400141 | VAR | Read | |
| AI | 32 | Generator Total Percent Reactive Power | Modbus 400143 | % | Read | |
| AI | 33 | Generator Total Real Energy Exported | Modbus 400144 | kWh | Read | |
| AI | 34 | Generator Total Reactive Energy Exported | Modbus 400146 | kVARh | Read | |
| AI | 35 | Generator Average Line-Neutral AC RMS Voltage | Modbus 400148 | V | Read | |
| AI | 36 | Generator Front Bearing Temperature from Data Link | Modbus 400149 | °C | Read | |
| AI | 37 | Generator Rear Bearing Temperature from Data Link | Modbus 400150 | °C | Read | |
| AI | 38 | Generator Phase A Winding Temperature from Data Link | Modbus 400151 | °C | Read | |
| AI | 39 | Generator Phase B Winding Temperature from Data Link | Modbus 400152 | °C | Read | |
| AI | 40 | Generator Phase C Winding Temperature from Data Link | Modbus 400153 | °C | Read | |
| AI | 41 | Generator Phase A Power Factor Lagging | Modbus 400159 | Read | ||
| AI | 42 | Generator Phase B Power Factor Lagging | Modbus 400160 | Read | ||
| AI | 43 | Generator Phase C Power Factor Lagging | Modbus 400161 | Read | ||
| AI | 44 | Generator Rear Bearing Temperature from I/O Pin | Modbus 400162 | °C | Read | |
| AI | 45 | Generator Average Line-Line AC RMS Voltage Percent | Modbus 400163 | % | Read | |
| AI | 46 | Bus Average Line-Line AC RMS Voltage | Modbus 400164 | V | Read | |
| AI | 47 | Bus Average AC RMS Frequency | Modbus 400165 | Hz | Read | |
| AI | 48 | Bus Phase A Line-Line AC RMS Voltage | Modbus 400166 | V | Read | |
| AI | 49 | Bus Phase B Line-Line AC RMS Voltage | Modbus 400167 | V | Read | |
| AI | 50 | Bus Phase C Line-Line AC RMS Voltage | Modbus 400168 | V | Read | |
| AI | 51 | Bus Phase A Line-Neutral AC RMS Voltage | Modbus 400169 | V | Read | |
| AI | 52 | Bus Phase B Line-Neutral AC RMS Voltage | Modbus 400170 | V | Read | |
| AI | 53 | Bus Phase C Line-Neutral AC RMS Voltage | Modbus 400171 | V | Read | |
| AI | 54 | Bus Average Line-Neutral AC RMS Voltage | Modbus 400172 | V | Read | |
| AI | 55 | Bus Average Line-Line AC RMS Voltage Percent | Modbus 400173 | % | Read | |
| AI | 56 | Generator Total Percent Current | Modbus 400174 | % | Read | |
| AI | 57 | Utility Total Real Power | Modbus 400175; not polled by default | W | Read | |
| AI | 58 | Utility Total Reactive Power | Modbus 400176; not polled by default | W | Read | |
| AI | 59 | Utility Overall Power Factor | Modbus 400177; not polled by default | PF | Read | |
| AI | 60 | Generator Desired Power Factor | Modbus 400178; not polled by default | PF | Read | |
| AI | 61 | Desired Base Load | Modbus 400179; not polled by default | W | Read | |
| AI | 62 | Load Share Line Total Percent kW | Modbus 400181; not polled by default | % | Read | |
| AI | 63 | Load Share Line Total Percent kVAr | Modbus 400182; not polled by default | % | Read | |
| AI | 64 | Generator Average AC RMS Frequency Percent | Modbus 400183 | % | Read | |
| AImin | 65 | Fuel Level | Modbus 400198 | % | Read | |
| AI | 66 | Engine Oil Temperature | Modbus 400199 | °C | Read | |
| AImin | 67 | Engine Oil Pressure | Modbus 400200 | kPa | Read | |
| AImin | 68 | Engine Coolant Temperature | Modbus 400201 | °C | Read | |
| AImin | 69 | Battery Voltage | Modbus 400202 | Read | ||
| AImin | 70 | Engine rpm | Modbus 400203 | Read | ||
| AI | 71 | Engine Operating Hours | Modbus 400204 | Read | ||
| AI | 72 | Automatic Start/Stop State | Modbus 400206; not polled by default | Read | ||
| AI | 73 | Spare Analog Input Percent | Modbus 400207; not polled by default | Read | ||
| AI | 74 | Spare Analog Input Temperature | Modbus 400208; not polled by default | °C | Read | |
| AI | 75 | Spare Analog Input Pressure | Modbus 400209; not polled by default | kPa | Read | |
| AI | 76 | Service Maintenance Interval Hours Remaining | Modbus 400210; not polled by default | h | Read | |
| AI | 77 | Service Maintenance Interval Days Remaining | Modbus 400212; not polled by default | days | Read | |
| AI | 78 | Number of Crank Attempts | Modbus 400213; not polled by default | Read | ||
| AI | 79 | Number of Successful Starts | Modbus 400215; not polled by default | Read | ||
| AI | 80 | Engine Oil Pressure from Data Link | Modbus 400217; not polled by default | kPa | Read | |
| AI | 81 | Engine Coolant Temperature from Data Link | Modbus 400219; not polled by default | °C | Read | |
| AI | 82 | Cylinder #1 Exhaust Port Temperature from Data Link | Modbus 400221; not polled by default | °C | Read | |
| AI | 83 | Cylinder #2 Exhaust Port Temperature from Data Link | Modbus 400222; not polled by default | °C | Read | |
| AI | 84 | Cylinder #3 Exhaust Port Temperature from Data Link | Modbus 400223; not polled by default | °C | Read | |
| AI | 85 | Cylinder #4 Exhaust Port Temperature from Data Link | Modbus 400224; not polled by default | °C | Read | |
| AI | 86 | Cylinder #5 Exhaust Port Temperature from Data Link | Modbus 400225; not polled by default | °C | Read | |
| AI | 87 | Cylinder #6 Exhaust Port Temperature from Data Link | Modbus 400226; not polled by default | °C | Read | |
| AI | 88 | Cylinder #7 Exhaust Port Temperature from Data Link | Modbus 400227; not polled by default | °C | Read | |
| AI | 89 | Cylinder #8 Exhaust Port Temperature from Data Link | Modbus 400228; not polled by default | °C | Read | |
| AI | 90 | Cylinder #9 Exhaust Port Temperature from Data Link | Modbus 400229; not polled by default | °C | Read | |
| AI | 91 | Cylinder #10 Exhaust Port Temperature from Data Link | Modbus 400230; not polled by default | °C | Read | |
| AI | 92 | Cylinder #11 Exhaust Port Temperature from Data Link | Modbus 400231; not polled by default | °C | Read | |
| AI | 93 | Cylinder #12 Exhaust Port Temperature from Data Link | Modbus 400232; not polled by default | °C | Read | |
| AI | 94 | Cylinder #13 Exhaust Port Temperature from Data Link | Modbus 400233; not polled by default | °C | Read | |
| AI | 95 | Cylinder #14 Exhaust Port Temperature from Data Link | Modbus 400234; not polled by default | °C | Read | |
| AI | 96 | Cylinder #15 Exhaust Port Temperature from Data Link | Modbus 400235; not polled by default | °C | Read | |
| AI | 97 | Cylinder #16 Exhaust Port Temperature from Data Link | Modbus 400236; not polled by default | °C | Read | |
| AI | 98 | Cylinder #17 Exhaust Port Temperature from Data Link | Modbus 400237; not polled by default | °C | Read | |
| AI | 99 | Cylinder #18 Exhaust Port Temperature from Data Link | Modbus 400238; not polled by default | °C | Read | |
| AI | 100 | Cylinder #19 Exhaust Port Temperature from Data Link | Modbus 400239; not polled by default | °C | Read | |
| AI | 101 | Cylinder #20 Exhaust Port Temperature from Data Link | Modbus 400240; not polled by default | °C | Read | |
| AI | 102 | Exhaust Manifold #1 (Left) Temperature | Modbus 400241; not polled by default | °C | Read | |
| AI | 103 | Exhaust Manifold #2 (Right) Temperature from Data Link | Modbus 400242; not polled by default | °C | Read | |
| AI | 104 | Intake Manifold #1 Temperature from Data Link | Modbus 400243; not polled by default | °C | Read | |
| AI | 105 | Intake Manifold #2 Temperature from Data Link | Modbus 400244; not polled by default | °C | Read | |
| AI | 106 | Engine Oil Temperature from Data Link | Modbus 400245; not polled by default | °C | Read | |
| AI | 107 | Engine Fuel Temperature from Data Link | Modbus 400246; not polled by default | °C | Read | |
| AI | 108 | Fuel Pressure from Data Link | Modbus 400247; not polled by default | kPa | Read | |
| AI | 109 | Crankcase Pressure from Data Link | Modbus 400248; not polled by default | kPa | Read | |
| AI | 110 | Boost Pressure from Data Link | Modbus 400249; not polled by default | kPa | Read | |
| AI | 111 | Oil Filter Differential Pressure from Data Link | Modbus 400251; not polled by default | kPa | Read | |
| AI | 112 | Fuel Filter Differential Pressure from Data Link | Modbus 400252; not polled by default | kPa | Read | |
| AI | 113 | Air Filter 1 Differential Pressure from Data Link | Modbus 400253; not polled by default | kPa | Read | |
| AI | 114 | Instantaneous Fuel Consumption from Data Link | Modbus 400256; not polled by default | L/h | Read | |
| AI | 115 | Atmospheric Pressure from Data Link | Modbus 400257; not polled by default | kPa | Read | |
| AI | 116 | Fuel Level | Modbus 400258; not polled by default | % | Read | |
| AI | 117 | Service Maintenance Interval Weeks Remaining | Modbus 400299; not polled by default | weeks | Read | |
| AI | 118 | Bypass Cooldown | Modbus 400300; not polled by default | Read | ||
| AImin | 119 | Engine Control Switch Position | Modbus 400301; not polled by default | Read | ||
| AI | 120 | Engine Control Switch Command | Modbus 400302; not polled by default | Read | ||
| AI | 121 | Lamp Test Command | Modbus 400303; not polled by default | Read | ||
| AI | 122 | Acknowledge All Events Command | Modbus 400304; not polled by default | Read | ||
| AI | 123 | Auto Start/Stop Fuel Control Enabled | Modbus 400307; not polled by default | Read | ||
| AI | 124 | Key Press | Modbus 400310; not polled by default | Read | ||
| AI | 125 | SCR System Check Required Status | Modbus 400319; not polled by default | Read | ||
| AI | 126 | Fuel Unload Pump Active | Modbus 400321; not polled by default | Read | ||
| AI | 127 | Fuel Load Pump Active | Modbus 400322; not polled by default | Read | ||
| AI | 128 | System Event Count | Modbus 400334; not polled by default | Read | ||
| AI | 129 | System Event Lamp Status | Modbus 400335; not polled by default | Read | ||
| AI | 130 | Forced Idle Command Active | Modbus 400337; not polled by default | Read | ||
| AI | 131 | Generator Excitation Field Voltage from Data Link | Modbus 400338; not polled by default | Read | ||
| AI | 132 | Generator Excitation Field Current from Data Link | Modbus 400340; not polled by default | Read | ||
| BI | 133 | Alarm Group 1 Column 1 row 16 | Modbus 400342 bit 15; not polled by default | Read | ||
| BI | 134 | Alarm Group 1 Column 1 row 15 | Modbus 400342 bit 14; not polled by default | Read | ||
| BI | 135 | Alarm Group 1 Column 1 row 14 | Modbus 400342 bit 13; not polled by default | Read | ||
| BI | 136 | Alarm Group 1 Column 1 row 13 | Modbus 400342 bit 12; not polled by default | Read | ||
| BI | 137 | Alarm Group 1 Column 1 row 12 | Modbus 400342 bit 11; not polled by default | Read | ||
| BI | 138 | Alarm Group 1 Column 1 row 11 | Modbus 400342 bit 10; not polled by default | Read | ||
| BI | 139 | Alarm Group 1 Column 1 row 10 | Modbus 400342 bit 9; not polled by default | Read | ||
| BI | 140 | Alarm Group 1 Column 1 row 09 | Modbus 400342 bit 8; not polled by default | Read | ||
| BI | 141 | Alarm Group 1 Column 1 row 08 | Modbus 400342 bit 7; not polled by default | Read | ||
| BI | 142 | Alarm Group 1 Column 1 row 07 | Modbus 400342 bit 6; not polled by default | Read | ||
| BI | 143 | Alarm Group 1 Column 1 row 06 | Modbus 400342 bit 5; not polled by default | Read | ||
| BI | 144 | Alarm Group 1 Column 1 row 05 | Modbus 400342 bit 4; not polled by default | Read | ||
| BI | 145 | Alarm Group 1 Column 1 row 04 | Modbus 400342 bit 3; not polled by default | Read | ||
| BI | 146 | Alarm Group 1 Column 1 row 03 | Modbus 400342 bit 2; not polled by default | Read | ||
| BI | 147 | Alarm Group 1 Column 1 row 02 | Modbus 400342 bit 1; not polled by default | Read | ||
| BI | 148 | Alarm Group 1 Column 1 row 01 | Modbus 400342 bit 0; not polled by default | Read | ||
| BI | 149 | Alarm Group 1 Column 2 row 16 | Modbus 400343 bit 15; not polled by default | Read | ||
| BI | 150 | Alarm Group 1 Column 2 row 15 | Modbus 400343 bit 14; not polled by default | Read | ||
| BI | 151 | Alarm Group 1 Column 2 row 14 | Modbus 400343 bit 13; not polled by default | Read | ||
| BI | 152 | Alarm Group 1 Column 2 row 13 | Modbus 400343 bit 12; not polled by default | Read | ||
| BI | 153 | Alarm Group 1 Column 2 row 12 | Modbus 400343 bit 11; not polled by default | Read | ||
| BI | 154 | Alarm Group 1 Column 2 row 11 | Modbus 400343 bit 10; not polled by default | Read | ||
| BI | 155 | Alarm Group 1 Column 2 row 10 | Modbus 400343 bit 9; not polled by default | Read | ||
| BI | 156 | Alarm Group 1 Column 2 row 09 | Modbus 400343 bit 8; not polled by default | Read | ||
| BI | 157 | Alarm Group 1 Column 2 row 08 | Modbus 400343 bit 7; not polled by default | Read | ||
| BI | 158 | Alarm Group 1 Column 2 row 07 | Modbus 400343 bit 6; not polled by default | Read | ||
| BI | 159 | Alarm Group 1 Column 2 row 06 | Modbus 400343 bit 5; not polled by default | Read | ||
| BI | 160 | Alarm Group 1 Column 2 row 05 | Modbus 400343 bit 4; not polled by default | Read | ||
| BI | 161 | Alarm Group 1 Column 2 row 04 | Modbus 400343 bit 3; not polled by default | Read | ||
| BI | 162 | Alarm Group 1 Column 2 row 03 | Modbus 400343 bit 2; not polled by default | Read | ||
| BI | 163 | Alarm Group 1 Column 2 row 02 | Modbus 400343 bit 1; not polled by default | Read | ||
| BI | 164 | Alarm Group 1 Column 2 row 01 | Modbus 400343 bit 0; not polled by default | Read | ||
| BI | 165 | Alarm Group 1 Horn row 16 | Modbus 400344 bit 15; not polled by default | Read | ||
| BI | 166 | Alarm Group 1 Horn row 15 | Modbus 400344 bit 14; not polled by default | Read | ||
| BI | 167 | Alarm Group 1 Horn row 14 | Modbus 400344 bit 13; not polled by default | Read | ||
| BI | 168 | Alarm Group 1 Horn row 13 | Modbus 400344 bit 12; not polled by default | Read | ||
| BI | 169 | Alarm Group 1 Horn row 12 | Modbus 400344 bit 11; not polled by default | Read | ||
| BI | 170 | Alarm Group 1 Horn row 11 | Modbus 400344 bit 10; not polled by default | Read | ||
| BI | 171 | Alarm Group 1 Horn row 10 | Modbus 400344 bit 9; not polled by default | Read | ||
| BI | 172 | Alarm Group 1 Horn row 09 | Modbus 400344 bit 8; not polled by default | Read | ||
| BI | 173 | Alarm Group 1 Horn row 08 | Modbus 400344 bit 7; not polled by default | Read | ||
| BI | 174 | Alarm Group 1 Horn row 07 | Modbus 400344 bit 6; not polled by default | Read | ||
| BI | 175 | Alarm Group 1 Horn row 06 | Modbus 400344 bit 5; not polled by default | Read | ||
| BI | 176 | Alarm Group 1 Horn row 05 | Modbus 400344 bit 4; not polled by default | Read | ||
| BI | 177 | Alarm Group 1 Horn row 04 | Modbus 400344 bit 3; not polled by default | Read | ||
| BI | 178 | Alarm Group 1 Horn row 03 | Modbus 400344 bit 2; not polled by default | Read | ||
| BI | 179 | Alarm Group 1 Horn row 02 | Modbus 400344 bit 1; not polled by default | Read | ||
| BI | 180 | Alarm Group 1 Horn row 01 | Modbus 400344 bit 0; not polled by default | Read | ||
| BI | 181 | Alarm Group 2 Column 1 row 16 | Modbus 400346 bit 15; not polled by default | Read | ||
| BI | 182 | Alarm Group 2 Column 1 row 15 | Modbus 400346 bit 14; not polled by default | Read | ||
| BI | 183 | Alarm Group 2 Column 1 row 14 | Modbus 400346 bit 13; not polled by default | Read | ||
| BI | 184 | Alarm Group 2 Column 1 row 13 | Modbus 400346 bit 12; not polled by default | Read | ||
| BI | 185 | Alarm Group 2 Column 1 row 12 | Modbus 400346 bit 11; not polled by default | Read | ||
| BI | 186 | Alarm Group 2 Column 1 row 11 | Modbus 400346 bit 10; not polled by default | Read | ||
| BI | 187 | Alarm Group 2 Column 1 row 10 | Modbus 400346 bit 9; not polled by default | Read | ||
| BI | 188 | Alarm Group 2 Column 1 row 09 | Modbus 400346 bit 8; not polled by default | Read | ||
| BI | 189 | Alarm Group 2 Column 1 row 08 | Modbus 400346 bit 7; not polled by default | Read | ||
| BI | 190 | Alarm Group 2 Column 1 row 07 | Modbus 400346 bit 6; not polled by default | Read | ||
| BI | 191 | Alarm Group 2 Column 1 row 06 | Modbus 400346 bit 5; not polled by default | Read | ||
| BI | 192 | Alarm Group 2 Column 1 row 05 | Modbus 400346 bit 4; not polled by default | Read | ||
| BI | 193 | Alarm Group 2 Column 1 row 04 | Modbus 400346 bit 3; not polled by default | Read | ||
| BI | 194 | Alarm Group 2 Column 1 row 03 | Modbus 400346 bit 2; not polled by default | Read | ||
| BI | 195 | Alarm Group 2 Column 1 row 02 | Modbus 400346 bit 1; not polled by default | Read | ||
| BI | 196 | Alarm Group 2 Column 1 row 01 | Modbus 400346 bit 0; not polled by default | Read | ||
| BI | 197 | Alarm Group 2 Column 2 row 16 | Modbus 400347 bit 15; not polled by default | Read | ||
| BI | 198 | Alarm Group 2 Column 2 row 15 | Modbus 400347 bit 14; not polled by default | Read | ||
| BI | 199 | Alarm Group 2 Column 2 row 14 | Modbus 400347 bit 13; not polled by default | Read | ||
| BI | 200 | Alarm Group 2 Column 2 row 13 | Modbus 400347 bit 12; not polled by default | Read | ||
| BI | 201 | Alarm Group 2 Column 2 row 12 | Modbus 400347 bit 11; not polled by default | Read | ||
| BI | 202 | Alarm Group 2 Column 2 row 11 | Modbus 400347 bit 10; not polled by default | Read | ||
| BI | 203 | Alarm Group 2 Column 2 row 10 | Modbus 400347 bit 9; not polled by default | Read | ||
| BI | 204 | Alarm Group 2 Column 2 row 09 | Modbus 400347 bit 8; not polled by default | Read | ||
| BI | 205 | Alarm Group 2 Column 2 row 08 | Modbus 400347 bit 7; not polled by default | Read | ||
| BI | 206 | Alarm Group 2 Column 2 row 07 | Modbus 400347 bit 6; not polled by default | Read | ||
| BI | 207 | Alarm Group 2 Column 2 row 06 | Modbus 400347 bit 5; not polled by default | Read | ||
| BI | 208 | Alarm Group 2 Column 2 row 05 | Modbus 400347 bit 4; not polled by default | Read | ||
| BI | 209 | Alarm Group 2 Column 2 row 04 | Modbus 400347 bit 3; not polled by default | Read | ||
| BI | 210 | Alarm Group 2 Column 2 row 03 | Modbus 400347 bit 2; not polled by default | Read | ||
| BI | 211 | Alarm Group 2 Column 2 row 02 | Modbus 400347 bit 1; not polled by default | Read | ||
| BI | 212 | Alarm Group 2 Column 2 row 01 | Modbus 400347 bit 0; not polled by default | Read | ||
| BI | 213 | Alarm Group 2 Horn row 16 | Modbus 400348 bit 15; not polled by default | Read | ||
| BI | 214 | Alarm Group 2 Horn row 15 | Modbus 400348 bit 14; not polled by default | Read | ||
| BI | 215 | Alarm Group 2 Horn row 14 | Modbus 400348 bit 13; not polled by default | Read | ||
| BI | 216 | Alarm Group 2 Horn row 13 | Modbus 400348 bit 12; not polled by default | Read | ||
| BI | 217 | Alarm Group 2 Horn row 12 | Modbus 400348 bit 11; not polled by default | Read | ||
| BI | 218 | Alarm Group 2 Horn row 11 | Modbus 400348 bit 10; not polled by default | Read | ||
| BI | 219 | Alarm Group 2 Horn row 10 | Modbus 400348 bit 9; not polled by default | Read | ||
| BI | 220 | Alarm Group 2 Horn row 09 | Modbus 400348 bit 8; not polled by default | Read | ||
| BI | 221 | Alarm Group 2 Horn row 08 | Modbus 400348 bit 7; not polled by default | Read | ||
| BI | 222 | Alarm Group 2 Horn row 07 | Modbus 400348 bit 6; not polled by default | Read | ||
| BI | 223 | Alarm Group 2 Horn row 06 | Modbus 400348 bit 5; not polled by default | Read | ||
| BI | 224 | Alarm Group 2 Horn row 05 | Modbus 400348 bit 4; not polled by default | Read | ||
| BI | 225 | Alarm Group 2 Horn row 04 | Modbus 400348 bit 3; not polled by default | Read | ||
| BI | 226 | Alarm Group 2 Horn row 03 | Modbus 400348 bit 2; not polled by default | Read | ||
| BI | 227 | Alarm Group 2 Horn row 02 | Modbus 400348 bit 1; not polled by default | Read | ||
| BI | 228 | Alarm Group 2 Horn row 01 | Modbus 400348 bit 0; not polled by default | Read | ||
| BI | 229 | Alarm Group 3 Col 1 Aftertreatment Shutdown Event | Modbus 400350 bit 15; not polled by default | Read | ||
| BI | 230 | Alarm Group 3 Col 1 High Battery Voltage Shutdown Event Active | Modbus 400350 bit 9; not polled by default | Read | ||
| BI | 231 | Alarm Group 3 Col 1 Low Fuel or Gas Pressure shutdown | Modbus 400350 bit 7; not polled by default | Read | ||
| BI | 232 | Alarm Group 3 Col 1 Low Coolant Level Shutdown | Modbus 400350 bit 6; not polled by default | Read | ||
| BI | 233 | Alarm Group 3 Col 1 Overspeed Shotdown Event | Modbus 400350 bit 5; not polled by default | Read | ||
| BI | 234 | Alarm Group 3 Col 1 Low Oil Pressure Shutdown Event | Modbus 400350 bit 4; not polled by default | Read | ||
| BI | 235 | Alarm Group 3 Col 1 High Coolant Temperature Shutdown | Modbus 400350 bit 2; not polled by default | Read | ||
| BI | 236 | Alarm Group 3 Col 1 Engine Failure to Start Overcrank | Modbus 400350 bit 1; not polled by default | Read | ||
| BI | 237 | Alarm Group 3 Col 1 Emergency Stop Shutdown | Modbus 400350 bit 0; not polled by default | Read | ||
| BI | 238 | Alarm Group 3 Col 2 Aftertreatment Warning Event Active | Modbus 400351 bit 15; not polled by default | Read | ||
| BI | 239 | Alarm Group 3 Col 2 Engine Running Condition Active | Modbus 400351 bit 14; not polled by default | Read | ||
| BI | 240 | Alarm Group 3 Col 2 Emerg Power Syst Sup Load Cond Active | Modbus 400351 bit 13; not polled by default | Read | ||
| BI | 241 | Alarm Group 3 Col 2 Battery Charger AC Failure Event Active | Modbus 400351 bit 12; not polled by default | Read | ||
| BI | 242 | Alarm Group 3 Col 2 Low Cranking Voltage Warning Event Active | Modbus 400351 bit 11; not polled by default | Read | ||
| BI | 243 | Alarm Group 3 Col 2 Low Battery Voltage Warning Event Active | Modbus 400351 bit 10; not polled by default | Read | ||
| BI | 244 | Alarm Group 3 Col 2 High Battery Voltage Warning Event Active | Modbus 400351 bit 9; not polled by default | Read | ||
| BI | 245 | Alarm Group 3 Col 2 Engine Control Sw Not in Auto Event Active | Modbus 400351 bit 8; not polled by default | Read | ||
| BI | 246 | Alarm Group 3 Col 2 Low Fuel Level or Gas Pres Warn Event Act | Modbus 400351 bit 7; not polled by default | Read | ||
| BI | 247 | Alarm Group 3 Col 2 Low Coolant Level Warning Event Active | Modbus 400351 bit 6; not polled by default | Read | ||
| BI | 248 | Alarm Group 3 Col 2 Low Oil Pressure Warning Event Active | Modbus 400351 bit 4; not polled by default | Read | ||
| BI | 249 | Alarm Group 3 Col 2 Low Coolant Temperature Warning Event Active | Modbus 400351 bit 3; not polled by default | Read | ||
| BI | 250 | Alarm Group 3 Col 2 High Coolant Temp Warning Event Active | Modbus 400351 bit 2; not polled by default | Read | ||
| BI | 251 | Alarm Group 3 Col 2 Emergency Stop Diagnostic Event Active | Modbus 400351 bit 0; not polled by default | Read | ||
| BI | 252 | Alarm Group 3 Horn Aftertreatment Event Horn Active | Modbus 400352 bit 15; not polled by default | Read | ||
| BI | 253 | Alarm Group 3 Horn Engine Running Condition Active | Modbus 400352 bit 14; not polled by default | Read | ||
| BI | 254 | Alarm Group 3 Horn Emerg Pwr Syst Supply Load Cond Horn Active | Modbus 400352 bit 13; not polled by default | Read | ||
| BI | 255 | Alarm Group 3 Horn Battery Charger AC Failure Event Horn Active | Modbus 400352 bit 12; not polled by default | Read | ||
| BI | 256 | Alarm Group 3 Horn Low Cranking Voltage Event Horn Active | Modbus 400352 bit 11; not polled by default | Read | ||
| BI | 257 | Alarm Group 3 Horn Low Battery Voltage Event Horn Active | Modbus 400352 bit 10; not polled by default | Read | ||
| BI | 258 | Alarm Group 3 Horn High Battery Voltage Event Horn Active | Modbus 400352 bit 9; not polled by default | Read | ||
| BI | 259 | Alarm Group 3 Horn Eng Cont Sw Not in Auto Event Horn Active | Modbus 400352 bit 8; not polled by default | Read | ||
| BI | 260 | Alarm Group 3 Horn Low Fuel Level or Gasd Press Event Horn Act | Modbus 400352 bit 7; not polled by default | Read | ||
| BI | 261 | Alarm Group 3 Horn Low Coolant Level Event Horn Active | Modbus 400352 bit 6; not polled by default | Read | ||
| BI | 262 | Alarm Group 3 Horn Overspeed Shutdown Event Horn Active | Modbus 400352 bit 5; not polled by default | Read | ||
| BI | 263 | Alarm Group 3 Horn Low Oil Pressure Event Horn Active | Modbus 400352 bit 4; not polled by default | Read | ||
| BI | 264 | Alarm Group 3 Horn Low Coolant Temp Event Horn Active | Modbus 400352 bit 3; not polled by default | Read | ||
| BI | 265 | Alarm Group 3 Horn High Coolant Temperature Event Horn Act | Modbus 400352 bit 2; not polled by default | Read | ||
| BI | 266 | Alarm Group 3 Horn Eng Fail Start Overcrank Shutdn Evt Horn Act | Modbus 400352 bit 1; not polled by default | Read | ||
| BI | 267 | Alarm Group 3 Horn Emerg Stop Shutdown Diagnostic Horn Active | Modbus 400352 bit 0; not polled by default | Read | ||
| BI | 268 | Alarm Group 4 Col 1 Aftertreatment Shutdown Event Active | Modbus 400354 bit 15; not polled by default | Read | ||
| BI | 269 | Alarm Group 4 Col 1 Air Shutdown Damper Closed Event Active | Modbus 400354 bit 14; not polled by default | Read | ||
| BI | 270 | Alarm Group 4 Col 1 High Battery Voltage Shutdown Event Active | Modbus 400354 bit 9; not polled by default | Read | ||
| BI | 271 | Alarm Group 4 Col 1 Low Fuel Level Shutdown Event Active | Modbus 400354 bit 7; not polled by default | Read | ||
| BI | 272 | Alarm Group 4 Col 1 Eventa A Event Active | Modbus 400354 bit 6; not polled by default | Read | ||
| BI | 273 | Alarm Group 4 Col 1 Overspeed Shutdown Event Active | Modbus 400354 bit 5; not polled by default | Read | ||
| BI | 274 | Alarm Group 4 Col 1 Low Oil Pressure Shutdown Event Active | Modbus 400354 bit 4; not polled by default | Read | ||
| BI | 275 | Alarm Group 4 Col 1 High Coolant Temp Shutdown Event Active | Modbus 400354 bit 2; not polled by default | Read | ||
| BI | 276 | Alarm Group 4 Col 1 Eng Fail to Start Overcrank Shutdn Event Act | Modbus 400354 bit 1; not polled by default | Read | ||
| BI | 277 | Alarm Group 4 Col 1 Emergency Stop Shutdown Event Active | Modbus 400354 bit 0; not polled by default | Read | ||
| BI | 278 | Alarm Group 4 Col 2 Aftertreatment Warning Event Active | Modbus 400355 bit 15; not polled by default | Read | ||
| BI | 279 | Alarm Group 4 Col 2 Emerg Powr Sys Supply Load Condition Act | Modbus 400355 bit 13; not polled by default | Read | ||
| BI | 280 | Alarm Group 4 Col 2 Battery Charger AC Failure Event Active | Modbus 400355 bit 12; not polled by default | Read | ||
| BI | 281 | Alarm Group 4 Col 2 Low Cranking Voltage Warning Event Active | Modbus 400355 bit 11; not polled by default | Read | ||
| BI | 282 | Alarm Group 4 Col 2 Low Battery Voltage Warning Event Active | Modbus 400355 bit 10; not polled by default | Read | ||
| BI | 283 | Alarm Group 4 Col 2 High Battery Voltage Warning Event Active | Modbus 400355 bit 9; not polled by default | Read | ||
| BI | 284 | Alarm Group 4 Col 2 Engine Control Switch Not in Auto Event Act | Modbus 400355 bit 8; not polled by default | Read | ||
| BI | 285 | Alarm Group 4 Col 2 Low Fuel Level Warning Event Act | Modbus 400355 bit 7; not polled by default | Read | ||
| BI | 286 | Alarm Group 4 Col 2 Low Coolant Level Warning Event Act | Modbus 400355 bit 6; not polled by default | Read | ||
| BI | 287 | Alarm Group 4 Col 2 Low Oil Pressure Warning Event Act | Modbus 400355 bit 4; not polled by default | Read | ||
| BI | 288 | Alarm Group 4 Col 2 Low Coolant Temp Warning Event Act | Modbus 400355 bit 3; not polled by default | Read | ||
| BI | 289 | Alarm Group 4 Col 2 High Coolant Temp Warning Event Act | Modbus 400355 bit 2; not polled by default | Read | ||
| BI | 290 | Alarm Group 4 Col 2 Emergency Stop Diagnostic Event Act | Modbus 400355 bit 0; not polled by default | Read | ||
| BI | 291 | Alarm Group 4 Horn Aftertreatment Event Horn Active | Modbus 400356 bit 15; not polled by default | Read | ||
| BI | 292 | Alarm Group 4 Horn Air Shutdown Damper Closed Event Horn Act | Modbus 400356 bit 14; not polled by default | Read | ||
| BI | 293 | Alarm Group 4 Horn Emerg Pwr Sys Supply Load Condition Horn Act | Modbus 400356 bit 13; not polled by default | Read | ||
| BI | 294 | Alarm Group 4 Horn Battery Charger AC Failure Event Horn Act | Modbus 400356 bit 12; not polled by default | Read | ||
| BI | 295 | Alarm Group 4 Horn Low Cranking Voltage Event Horn Active | Modbus 400356 bit 11; not polled by default | Read | ||
| BI | 296 | Alarm Group 4 Horn Low Battery Voltage Event Horn Act | Modbus 400356 bit 10; not polled by default | Read | ||
| BI | 297 | Alarm Group 4 Horn = High Battery Voltage Event Horn Act | Modbus 400356 bit 9; not polled by default | Read | ||
| BI | 298 | Alarm Group 4 Horn Engine Control Sw Not in Auto Event Horn Act | Modbus 400356 bit 8; not polled by default | Read | ||
| BI | 299 | Alarm Group 4 Horn Low Fuel Level Event Horn Active | Modbus 400356 bit 7; not polled by default | Read | ||
| BI | 300 | Alarm Group 4 Horn Low Coolant Level Event Horn Act | Modbus 400356 bit 6; not polled by default | Read | ||
| BI | 301 | Alarm Group 4 Horn Overspeed Shutdown Event Horn Act | Modbus 400356 bit 5; not polled by default | Read | ||
| BI | 302 | Alarm Group 4 Horn Low Oil Pressure Event Horn Act | Modbus 400356 bit 4; not polled by default | Read | ||
| BI | 303 | Alarm Group 4 Horn = Low Coolant Temperature Event Horn Active | Modbus 400356 bit 3; not polled by default | Read | ||
| BI | 304 | Alarm Group 4 Horn High Coolant Temperature Event Horn Act | Modbus 400356 bit 2; not polled by default | Read | ||
| BI | 305 | Alarm Grp 4 Horn Eng Fail to Str Overcrank Shutdn Event Horn Act | Modbus 400356 bit 1; not polled by default | Read | ||
| BI | 306 | Alarm Grp 4 Horn Emergency Stop Shutdown Diagnostic Horn Act | Modbus 400356 bit 0; not polled by default | Read | ||
| AI | 307 | Urea Tank Level | Modbus 400377; not polled by default | % | Read | |
| AI | 308 | Aftertreatment #1 SCR Catalyst Reagent Tank #1 Temperature | Modbus 400378; not polled by default | °C | Read | |
| AI | 309 | Urea Injection Air Pressure | Modbus 400379; not polled by default | kPa | Read | |
| AI | 310 | Catalyst Intake Temperature | Modbus 400381; not polled by default | °C | Read | |
| AI | 311 | Aftertreatment 1 SCR Catalyst Exhaust Gas Differential Pressure | Modbus 400382; not polled by default | kPa | Read | |
| AI | 312 | Digital Input #1 Active Status | Modbus 400600; not polled by default | Read | ||
| AI | 313 | Digital Input #2 Active Status | Modbus 400601; not polled by default | Read | ||
| AI | 314 | Digital Input #3 Active Status | Modbus 400602; not polled by default | Read | ||
| AI | 315 | Digital Input #4 Active Status | Modbus 400603; not polled by default | Read | ||
| AI | 316 | Digital Input #5 Active Status | Modbus 400604; not polled by default | Read | ||
| AI | 317 | Digital Input #6 Active Status | Modbus 400605; not polled by default | Read | ||
| AI | 318 | Digital Input #7 Active Status | Modbus 400606; not polled by default | Read | ||
| AI | 319 | Digital Input #8 Active Status | Modbus 400607; not polled by default | Read | ||
| AI | 320 | Isolated Digital Input #1 Active Status | Modbus 400608; not polled by default | Read | ||
| AI | 321 | Isolated Digital Input #2 Active Status | Modbus 400609; not polled by default | Read | ||
| AI | 322 | Isolated Digital Input #3 Active Status | Modbus 400610; not polled by default | Read | ||
| AI | 323 | Isolated Digital Input #4 Active Status | Modbus 400611; not polled by default | Read | ||
| AI | 324 | Dedicated Digital Input #1 (E-Stop) Active Status | Modbus 400612; not polled by default | Read | ||
| AI | 325 | Dedicated Digital Input #2 (Initiate Command) Active Status | Modbus 400613; not polled by default | Read | ||
| AI | 326 | Dedicated Digital Input #3 (Gen CB Aux A) Active Status | Modbus 400614; not polled by default | Read | ||
| AI | 327 | Dedicated Digital Input #4 (Gen CB Aux B) Active Status | Modbus 400615; not polled by default | Read | ||
| AI | 328 | Relay Output #1 Active Status | Modbus 400616; not polled by default | Read | ||
| AI | 329 | Relay Output #2 Active Status | Modbus 400617; not polled by default | Read | ||
| AI | 330 | Relay Output #3 Active Status | Modbus 400618; not polled by default | Read | ||
| AI | 331 | Relay Output #4 Active Status | Modbus 400619; not polled by default | Read | ||
| AI | 332 | Relay Output #5 Active Status | Modbus 400620; not polled by default | Read | ||
| AI | 333 | Relay Output #6 Active Status | Modbus 400621; not polled by default | Read | ||
| AI | 334 | Relay Output #7 Active Status | Modbus 400622; not polled by default | Read | ||
| AI | 335 | Relay Output #8 Active Status | Modbus 400623; not polled by default | Read | ||
| AI | 336 | Digital Output #1 Active Status | Modbus 400624; not polled by default | Read | ||
| AI | 337 | Digital Output #2 Active Status | Modbus 400625; not polled by default | Read | ||
| AI | 338 | Digital Output #3 Active Status | Modbus 400626; not polled by default | Read | ||
| AI | 339 | Digital Output #4 Active Status | Modbus 400627; not polled by default | Read | ||
| AI | 340 | Digital Output #5 Active Status | Modbus 400628; not polled by default | Read | ||
| AI | 341 | Digital Output #6 Active Status | Modbus 400629; not polled by default | Read | ||
| AI | 342 | Digital Output #7 Active Status | Modbus 400630; not polled by default | Read | ||
| AI | 343 | Digital Output #8 Active Status | Modbus 400631; not polled by default | Read | ||
| AI | 344 | Digital Output #9 Active Status | Modbus 400632; not polled by default | Read | ||
| AI | 345 | Digital Output #10 Active Status | Modbus 400633; not polled by default | Read | ||
| AI | 346 | Digital Output #11 Active Status | Modbus 400634; not polled by default | Read | ||
| AI | 347 | Digital Output #12 Active Status | Modbus 400635; not polled by default | Read | ||
| AI | 348 | Digital Output #13 Active Status | Modbus 400636; not polled by default | Read | ||
| AI | 349 | Digital Output #14 Active Status | Modbus 400637; not polled by default | Read | ||
| AI | 350 | Digital Output #15 Active Status | Modbus 400638; not polled by default | Read | ||
| AI | 351 | Digital Output #16 Active Status | Modbus 400639; not polled by default | Read | ||
| AI | 352 | Digital Output #17 Active Status | Modbus 400640; not polled by default | Read | ||
| AI | 353 | Group Start Active Status (DIDI-01) | Modbus 400641; not polled by default | Read | ||
| AI | 354 | Bell Alarm Active Status (DIDI-02) | Modbus 400642; not polled by default | Read | ||
| AI | 355 | Gen CB Trip Command Active Status (DIDI-03) | Modbus 400643; not polled by default | Read | ||
| AI | 356 | Gen CB Close Command Active Status (DIDI-04) | Modbus 400644; not polled by default | Read | ||
| AI | 357 | Arbitration Relay Active Status (DDO-01) | Modbus 400645; not polled by default | Read | ||
| AI | 358 | Gen CB Close Active Status (DDO-02) | Modbus 400646; not polled by default | Read | ||
| AI | 359 | Gen CB Trip Active Status (DDO-03) | Modbus 400647; not polled by default | Read | ||
| AI | 360 | Analog Input #1 Sensor Value | Modbus 400648; not polled by default | Read | ||
| AI | 361 | Analog Input #2 Sensor Value | Modbus 400649; not polled by default | Read | ||
| AI | 362 | Analog Input #3 Sensor Value | Modbus 400650; not polled by default | Read | ||
| AI | 363 | Analog Input #4 Sensor Value | Modbus 400651; not polled by default | Read | ||
| AI | 364 | Analog Input #1 Data Value | Modbus 400652; not polled by default | Read | ||
| AI | 365 | Analog Input #2 Data Value | Modbus 400654; not polled by default | Read | ||
| AI | 366 | Analog Input #3 Data Value | Modbus 400656; not polled by default | Read | ||
| AI | 367 | Analog Input #4 Data Value | Modbus 400658; not polled by default | Read | ||
| AI | 368 | Analog Output #1 Data Value | Modbus 400660; not polled by default | Read | ||
| AI | 369 | Analog Output #2 Data Value | Modbus 400662; not polled by default | Read | ||
| AI | 370 | Analog Output #3 Data Value | Modbus 400664; not polled by default | Read | ||
| AI | 371 | PWM Output #1 Data Value | Modbus 400672; not polled by default | % | Read | |
| AI | 372 | PWM Output #2 Data Value | Modbus 400674; not polled by default | % | Read | |
| AO | 373 | Analog Output #1 Data Command | Modbus 400681; not polled by default | % | Command | |
| AO | 374 | Analog Output #2 Data Command | Modbus 400683; not polled by default | % | Command | |
| AO | 375 | Analog Output #3 Data Command | Modbus 400685; not polled by default | % | Command | |
| AO | 376 | PWM Output #1 Data Command | Modbus 400687; not polled by default | % | Command | |
| AO | 377 | PWM Output #2 Data Command | Modbus 400689; not polled by default | % | Command | |
| AO | 378 | Write Access Password Word 1 | Modbus 400700; not polled by default | Command | ||
| AO | 379 | Write Access Password Word 2 | Modbus 400701; not polled by default | Command | ||
| AO | 380 | Write Access Password Word 3 | Modbus 400702; not polled by default | Command | ||
| AO | 381 | Write Access Password Word 4 | Modbus 400703; not polled by default | Command | ||
| AO | 382 | Write Access Password Word 5 | Modbus 400704; not polled by default | Command | ||
| AO | 383 | Write Access Password Word 6 | Modbus 400705; not polled by default | Command | ||
| AO | 384 | Write Access Password Word 7 | Modbus 400706; not polled by default | Command | ||
| AO | 385 | Write Access Password Word 8 | Modbus 400707; not polled by default | Command | ||
| AO | 386 | Level 1 Password Word 1 | Modbus 400708; not polled by default | Command | ||
| AO | 387 | Level 1 Password Word 2 | Modbus 400709; not polled by default | Command | ||
| AO | 388 | Level 1 Password Word 3 | Modbus 400710; not polled by default | Command | ||
| AO | 389 | Level 1 Password Word 4 | Modbus 400711; not polled by default | Command | ||
| AO | 390 | Level 1 Password Word 5 | Modbus 400712; not polled by default | Command | ||
| AO | 391 | Level 1 Password Word 6 | Modbus 400713; not polled by default | Command | ||
| AO | 392 | Level 1 Password Word 7 | Modbus 400714; not polled by default | Command | ||
| AO | 393 | Level 1 Password Word 8 | Modbus 400715; not polled by default | Command | ||
| AO | 394 | Level 2 Password Word 1 | Modbus 400716; not polled by default | Command | ||
| AO | 395 | Level 2 Password Word 2 | Modbus 400717; not polled by default | Command | ||
| AO | 396 | Level 2 Password Word 3 | Modbus 400718; not polled by default | Command | ||
| AO | 397 | Level 2 Password Word 4 | Modbus 400719; not polled by default | Command | ||
| AO | 398 | Level 2 Password Word 5 | Modbus 400720; not polled by default | Command | ||
| AO | 399 | Level 2 Password Word 6 | Modbus 400721; not polled by default | Command | ||
| AO | 400 | Level 2 Password Word 7 | Modbus 400722; not polled by default | Command | ||
| AO | 401 | Level 2 Password Word 8 | Modbus 400723; not polled by default | Command | ||
| AO | 402 | SCADA Password Word 1 | Modbus 400724; not polled by default | Command | ||
| AO | 403 | SCADA Password Word 2 | Modbus 400725; not polled by default | Command | ||
| AO | 404 | SCADA Password Word 3 | Modbus 400726; not polled by default | Command | ||
| AO | 405 | SCADA Password Word 4 | Modbus 400727; not polled by default | Command | ||
| AO | 406 | SCADA Password Word 5 | Modbus 400728; not polled by default | Command | ||
| AO | 407 | SCADA Password Word 6 | Modbus 400729; not polled by default | Command | ||
| AO | 408 | SCADA Password Word 7 | Modbus 400730; not polled by default | Command | ||
| AO | 409 | SCADA Password Word 8 | Modbus 400731; not polled by default | Command | ||
| AI | 410 | Current Security Level | Modbus 400732; not polled by default | Read | ||
| AO | 411 | Set Security Level | Modbus 400733; not polled by default | Command | ||
| AI | 412 | Level 3 Password Phone In Prompt Word 1 | Modbus 400734; not polled by default | Read | ||
| AI | 413 | Level 3 Password Phone In Prompt Word 2 | Modbus 400735; not polled by default | Read | ||
| AI | 414 | Level 3 Password Phone In Prompt Word 3 | Modbus 400736; not polled by default | Read | ||
| AI | 415 | Level 3 Password Phone In Prompt Word 4 | Modbus 400737; not polled by default | Read | ||
| AI | 416 | Level 3 Password Phone In Prompt Word 5 | Modbus 400738; not polled by default | Read | ||
| AI | 417 | Level 3 Password Phone In Prompt Word 6 | Modbus 400739; not polled by default | Read | ||
| AI | 418 | Level 3 Password Phone In Prompt Word 7 | Modbus 400740; not polled by default | Read | ||
| AI | 419 | Level 3 Password Phone In Prompt Word 8 | Modbus 400741; not polled by default | Read | ||
| AI | 420 | Engine Oil Temperature from I/O Pin | Modbus 400800; not polled by default | °C | Read | |
| AI | 421 | Exhaust Temperature | Modbus 400801; not polled by default | °C | Read | |
| AI | 422 | Left Manifold Exhaust Temperature | Modbus 400802; not polled by default | °C | Read | |
| AI | 423 | Right Manifold Exhaust Temperature from I/O Pin | Modbus 400803; not polled by default | °C | Read | |
| AI | 424 | Fuel Level from I/O Pin | Modbus 400804; not polled by default | % | Read | |
| AI | 425 | External Tank Fuel Level from I/O Pin | Modbus 400805; not polled by default | % | Read | |
| AI | 426 | Engine Oil Level from I/O Pin | Modbus 400806; not polled by default | % | Read | |
| AI | 427 | Engine Coolant Level from I/O Pin | Modbus 400807; not polled by default | % | Read | |
| AI | 428 | Oil Filter Differential Pressure from I/O Pin | Modbus 400809; not polled by default | kPa | Read | |
| AI | 429 | Air Filter 1 Differential Pressure from I/O Pin | Modbus 400810; not polled by default | kPa | Read | |
| AI | 430 | Fuel Filter Differential Pressure from I/O Pin | Modbus 400811; not polled by default | kPa | Read | |
| AI | 431 | Main Tank Urea Level from I/O Pin | Modbus 400812; not polled by default | % | Read | |
| AI | 432 | Real Time Clock Word 1 | Modbus 400900; not polled by default | Read | ||
| AI | 433 | Real Time Clock Word 2 | Modbus 400901; not polled by default | Read | ||
| AI | 434 | Real Time Clock Word 3 | Modbus 400902; not polled by default | Read | ||
| AO | 435 | Update Real Time Clock Command Word 1 | Modbus 400903; not polled by default | Command | ||
| AO | 436 | Update Real Time Clock Command Word 2 | Modbus 400904; not polled by default | Command | ||
| AO | 437 | Update Real Time Clock Command Word 3 | Modbus 400905; not polled by default | Command | ||
| AI | 438 | Log Entry Index | Modbus 401033; not polled by default | Read | ||
| AI | 439 | Log Entry Word 01 | Modbus 401034; not polled by default | Read | ||
| AI | 440 | Log Entry Word 02 | Modbus 401035; not polled by default | Read | ||
| AI | 441 | Log Entry Word 03 | Modbus 401036; not polled by default | Read | ||
| AI | 442 | Log Entry Word 04 | Modbus 401037; not polled by default | Read | ||
| AI | 443 | Log Entry Word 05 | Modbus 401038; not polled by default | Read | ||
| AI | 444 | Log Entry Word 06 | Modbus 401039; not polled by default | Read | ||
| AI | 445 | Log Entry Word 07 | Modbus 401040; not polled by default | Read | ||
| AI | 446 | Log Entry Word 08 | Modbus 401041; not polled by default | Read | ||
| AI | 447 | Log Entry Word 09 | Modbus 401042; not polled by default | Read | ||
| AI | 448 | Log Entry Word 10 | Modbus 401043; not polled by default | Read | ||
| AI | 449 | Log Entry Word 11 | Modbus 401044; not polled by default | Read | ||
| AI | 450 | Log Entry Word 12 | Modbus 401045; not polled by default | Read | ||
| AI | 451 | Log Entry Word 13 | Modbus 401046; not polled by default | Read | ||
| AI | 452 | Log Entry Word 14 | Modbus 401047; not polled by default | Read | ||
| AO | 453 | Reset Event Word 1 | Modbus 401048; not polled by default | Command | ||
| AO | 454 | Reset Event Word 2 | Modbus 401049; not polled by default | Command | ||
| AI | 455 | Cooldown Duration Remaining | Modbus 401054; not polled by default | Read | ||
| AO | 456 | Remote Initiate Command | Modbus 401055; not polled by default | Command | ||
| AO | 457 | Emergency Stop Command | Modbus 401056; not polled by default | Command | ||
| AI | 458 | Desired Genset Output Voltage | Modbus 401057; not polled by default | Read | ||
| AI | 459 | Total Voltage Bias Percent | Modbus 401058; not polled by default | % | Read | |
| AO | 460 | Voltage Bias Percent Increment Command | Modbus 401059; not polled by default | % | Command | |
| AI | 461 | Requested Engine Speed | Modbus 401060; not polled by default | Read | ||
| AI | 462 | Total Speed Bias Percent | Modbus 401061; not polled by default | % | Read | |
| AO | 463 | Speed Bias Percent Increment Command | Modbus 401062; not polled by default | % | Command | |
| AI | 464 | Generator/Bus Phase Difference | Modbus 401064; not polled by default | ° (phase) | Read | |
| AI | 465 | Generator Circuit Breaker Status | Modbus 401065; not polled by default | Read | ||
| AI | 466 | Generator Frequency within Limits | Modbus 401067; not polled by default | Read | ||
| AI | 467 | Generator Voltage within Limits | Modbus 401068; not polled by default | Read | ||
| AI | 468 | Bus Voltage within Limits | Modbus 401069; not polled by default | Read | ||
| AI | 469 | Bus Live Status | Modbus 401070; not polled by default | Read | ||
| AI | 470 | Genset Control Online | Modbus 401090; not polled by default | Read | ||
| AI | 471 | Engine Control Online | Modbus 401091; not polled by default | Read | ||
| AI | 472 | Secondary Engine Control Online | Modbus 401092; not polled by default | Read | ||
| AI | 473 | External I/O #1 Online | Modbus 401093; not polled by default | Read | ||
| AI | 474 | External I/O #2 Online | Modbus 401094; not polled by default | Read | ||
| AI | 475 | External I/O #3 Online | Modbus 401095; not polled by default | Read | ||
| AI | 476 | External I/O #4 Online | Modbus 401096; not polled by default | Read | ||
| AI | 477 | Digital AVR Online | Modbus 401097; not polled by default | Read | ||
| AI | 478 | RTD Module Online | Modbus 401098; not polled by default | Read | ||
| AI | 479 | Thermocouple #1 Online | Modbus 401099; not polled by default | Read | ||
| AI | 480 | Thermocouple #2 Online | Modbus 401100; not polled by default | Read | ||
| AI | 481 | SCR Module Online | Modbus 401103; not polled by default | Read | ||
| AI | 482 | Sync Mode Switch State | Modbus 401108; not polled by default | Read | ||
| AI | 483 | Dead Bus Arbitration State | Modbus 401111; not polled by default | Read | ||
| AI | 484 | Load Sense Load Demand State | Modbus 401120; not polled by default | Read | ||
| AI | 485 | Load Shed Command Active Status | Modbus 401129; not polled by default | Read | ||
| AI | 486 | Load Shed Command Reset | Modbus 401130; not polled by default | Read | ||
| AI | 487 | Primary Data Link Status | Modbus 401140; not polled by default | Read | ||
| AI | 488 | Accessory Data Link Status | Modbus 401141; not polled by default | Read | ||
| AI | 489 | RS-485 SCADA Data Link Status | Modbus 401142; not polled by default | Read | ||
| AI | 490 | TCP/IP SCADA Data Link Status | Modbus 401143; not polled by default | Read | ||
| AI | 491 | RS-485 Annunciator Data Link Status | Modbus 401144; not polled by default | Read | ||
| AI | 492 | Low Idle State from ADEM | Modbus 401263; not polled by default | Read | ||
| AI | 493 | Engine Protection has Shut Down Engine | Modbus 401275; not polled by default | Read | ||
| AI | 494 | Control Serial Number Word 1 | Modbus 401276; not polled by default | Read | ||
| AI | 495 | Control Serial Number Word 2 | Modbus 401277; not polled by default | Read | ||
| AI | 496 | Control Serial Number Word 3 | Modbus 401278; not polled by default | Read | ||
| AI | 497 | Control Serial Number Word 4 | Modbus 401279; not polled by default | Read | ||
| AI | 498 | Control Serial Number Word 5 | Modbus 401280; not polled by default | Read | ||
| AI | 499 | Control Serial Number Word 6 | Modbus 401281; not polled by default | Read | ||
| AI | 500 | Programmable Cycle Timer 1 Output 3 status | Modbus 401487; not polled by default | Read | ||
| AI | 501 | Programmable Cycle Timer 2 Output 3 status | Modbus 401488; not polled by default | Read | ||
| AI | 502 | Programmable Cycle Timer 3 Output 3 status | Modbus 401489; not polled by default | Read | ||
| AI | 503 | Programmable Cycle Timer 4 Output 3 status | Modbus 401490; not polled by default | Read | ||
| AI | 504 | Programmable Cycle Timer 5 Output 3 status | Modbus 401491; not polled by default | Read | ||
| AI | 505 | Programmable Cycle Timer 6 Output 3 status | Modbus 401492; not polled by default | Read | ||
| AI | 506 | Programmable Cycle Timer 7 Output 3 status | Modbus 401493; not polled by default | Read | ||
| AO | 507 | Programmable Cycle Timer 1 Output 1 status | Modbus 402060; not polled by default | Command | ||
| AI | 508 | Programmable Cycle Timer 2 Output 1 status | Modbus 402061; not polled by default | Read | ||
| AI | 509 | Programmable Cycle Timer 3 Output 1 status | Modbus 402062; not polled by default | Read | ||
| AI | 510 | Programmable Cycle Timer 4 Output 1 status | Modbus 402063; not polled by default | Read | ||
| AI | 511 | Programmable Cycle Timer 5 Output 1 status | Modbus 402064; not polled by default | Read | ||
| AI | 512 | Programmable Cycle Timer 6 Output 1 status | Modbus 402065; not polled by default | Read | ||
| AI | 513 | Programmable Cycle Timer 7 Output 1 status | Modbus 402066; not polled by default | Read | ||
| AI | 514 | Programmable Cycle Timer 1 Output 2 status | Modbus 402067; not polled by default | Read | ||
| AI | 515 | Programmable Cycle Timer 2 Output 2 status | Modbus 402068; not polled by default | Read | ||
| AI | 516 | Programmable Cycle Timer 3 Output 2 status | Modbus 402069; not polled by default | Read | ||
| AI | 517 | Programmable Cycle Timer 4 Output 2 status | Modbus 402070; not polled by default | Read | ||
| AI | 518 | Programmable Cycle Timer 5 Output 2 status | Modbus 402071; not polled by default | Read | ||
| AI | 519 | Programmable Cycle Timer 6 Output 2 status | Modbus 402072; not polled by default | Read | ||
| AI | 520 | Programmable Cycle Timer 7 Output 2 status | Modbus 402073; not polled by default | Read | ||
| AI | 521 | Turbocharger 1 Compressor Inlet Temp | Modbus 402074; not polled by default | °C | Read | |
| AI | 522 | Turbocharger 2 Compressor Inlet Temp | Modbus 402075; not polled by default | °C | Read | |
| AI | 523 | Turbocharger 3 Compressor Inlet Temp | Modbus 402076; not polled by default | °C | Read | |
| AI | 524 | Turbocharger 4 Compressor Inlet Temp | Modbus 402077; not polled by default | °C | Read | |
| AI | 525 | Turbocharger 1 Turbine Inlet Temp | Modbus 402078; not polled by default | °C | Read | |
| AI | 526 | Turbocharger 1 Turbine Outlet Temp | Modbus 402079; not polled by default | °C | Read | |
| AI | 527 | Turbocharger 2 Turbine Inlet Temp | Modbus 402080; not polled by default | °C | Read | |
| AI | 528 | Turbocharger 2 Turbine Outlet Temp | Modbus 402081; not polled by default | °C | Read | |
| AI | 529 | Turbocharger 3 Turbine Inlet Temp | Modbus 402082; not polled by default | °C | Read | |
| AI | 530 | Turbocharger 3 Turbine Outlet Temp | Modbus 402083; not polled by default | °C | Read | |
| AI | 531 | Turbocharger 4 Turbine Inlet Temp | Modbus 402084; not polled by default | °C | Read | |
| AI | 532 | Turbocharger 4 Turbine Outlet Temp | Modbus 402085; not polled by default | °C | Read | |
| AI | 533 | Exhaust Temperature from Data Link | Modbus 402086; not polled by default | °C | Read | |
| AI | 534 | Fuel Pump Primer Status | Modbus 402087; not polled by default | Read | ||
| AI | 535 | Manual Fuel Priming Duration Remaining | Modbus 402091; not polled by default | Read | ||
| AI | 536 | Software Build Version Word 01 | Modbus 402188; not polled by default | Read | ||
| AI | 537 | Software Build Version Word 02 | Modbus 402189; not polled by default | Read | ||
| AI | 538 | Software Build Version Word 03 | Modbus 402190; not polled by default | Read | ||
| AI | 539 | Software Build Version Word 04 | Modbus 402191; not polled by default | Read | ||
| AI | 540 | Software Build Version Word 05 | Modbus 402192; not polled by default | Read | ||
| AI | 541 | Software Build Version Word 06 | Modbus 402193; not polled by default | Read | ||
| AI | 542 | Software Build Version Word 07 | Modbus 402194; not polled by default | Read | ||
| AI | 543 | Software Build Version Word 08 | Modbus 402195; not polled by default | Read | ||
| AI | 544 | Software Build Version Word 09 | Modbus 402196; not polled by default | Read | ||
| AI | 545 | Software Build Version Word 10 | Modbus 402197; not polled by default | Read | ||
| AI | 546 | Digital Output #1 Command | Modbus 402232; not polled by default | Read | ||
| AI | 547 | Digital Output #2 Command | Modbus 402233; not polled by default | Read | ||
| AI | 548 | Digital Output #3 Command | Modbus 402234; not polled by default | Read | ||
| AI | 549 | Digital Output #4 Command | Modbus 402235; not polled by default | Read | ||
| AI | 550 | Digital Output #5 Command | Modbus 402236; not polled by default | Read | ||
| AI | 551 | Digital Output #6 Command | Modbus 402237; not polled by default | Read | ||
| AI | 552 | Digital Output #7 Command | Modbus 402238; not polled by default | Read | ||
| AI | 553 | Digital Output #8 Command | Modbus 402239; not polled by default | Read | ||
| AI | 554 | Digital Output #9 Command | Modbus 402240; not polled by default | Read | ||
| AI | 555 | Digital Output #10 Command | Modbus 402241; not polled by default | Read | ||
| AI | 556 | Digital Output #11 Command | Modbus 402242; not polled by default | Read | ||
| AI | 557 | Digital Output #12 Command | Modbus 402243; not polled by default | Read | ||
| AI | 558 | Digital Output #13 Command | Modbus 402244; not polled by default | Read | ||
| AI | 559 | Digital Output #14 Command | Modbus 402245; not polled by default | Read | ||
| AI | 560 | Digital Output #15 Command | Modbus 402246; not polled by default | Read | ||
| AI | 561 | Digital Output #16 Command | Modbus 402247; not polled by default | Read | ||
| AI | 562 | Digital Output #17 Command | Modbus 402248; not polled by default | Read | ||
| AI | 563 | Relay Output #1 Command | Modbus 402252; not polled by default | Read | ||
| AI | 564 | Relay Output #2 Command | Modbus 402253; not polled by default | Read | ||
| AI | 565 | Relay Output #3 Command | Modbus 402254; not polled by default | Read | ||
| AI | 566 | Relay Output #4 Command | Modbus 402255; not polled by default | Read | ||
| AI | 567 | Relay Output #5 Command | Modbus 402256; not polled by default | Read | ||
| AI | 568 | Relay Output #6 Command | Modbus 402257; not polled by default | Read | ||
| AI | 569 | Relay Output #7 Command | Modbus 402258; not polled by default | Read | ||
| AI | 570 | Relay Output #8 Command | Modbus 402259; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Cat EMCP 4 point IDs by name
AI1Generator Average Line-Line AC RMS VoltageAI2Generator Average AC RMS CurrentAI3Generator Average AC RMS FrequencyAI4Generator Overall Power FactorAI5Generator Overall Power Factor LaggingAI6Generator Total Percent kWAI7Generator Total Real PowerAI8Generator Phase A Line-Line AC RMS VoltageAI9Generator Phase B Line-Line AC RMS VoltageAI10Generator Phase C Line-Line AC RMS VoltageAI11Generator Phase A AC RMS CurrentAI12Generator Phase B AC RMS CurrentAI13Generator Phase C AC RMS CurrentAI14Generator Phase A Line-Neutral AC RMS VoltageAI15Generator Phase B Line-Neutral AC RMS VoltageAI16Generator Phase C Line-Neutral AC RMS VoltageAI17Generator Phase A Real PowerAI18Generator Phase B Real PowerAI19Generator Phase C Real PowerAI20Generator Phase A Apparent PowerAI21Generator Phase B Apparent PowerAI22Generator Phase C Apparent PowerAI23Generator Phase A Reactive PowerAI24Generator Phase B Reactive PowerAI25Generator Phase C Reactive PowerAI26Generator Phase A Power FactorAI27Generator Phase B Power FactorAI28Generator Phase C Power FactorAI29Generator Total Apparent PowerAI30Generator Total Percent Apparent PowerAI31Generator Total Reactive PowerAI32Generator Total Percent Reactive PowerAI33Generator Total Real Energy ExportedAI34Generator Total Reactive Energy ExportedAI35Generator Average Line-Neutral AC RMS VoltageAI36Generator Front Bearing Temperature from Data LinkAI37Generator Rear Bearing Temperature from Data LinkAI38Generator Phase A Winding Temperature from Data LinkAI39Generator Phase B Winding Temperature from Data LinkAI40Generator Phase C Winding Temperature from Data LinkAI41Generator Phase A Power Factor LaggingAI42Generator Phase B Power Factor LaggingAI43Generator Phase C Power Factor LaggingAI44Generator Rear Bearing Temperature from I/O PinAI45Generator Average Line-Line AC RMS Voltage PercentAI46Bus Average Line-Line AC RMS VoltageAI47Bus Average AC RMS FrequencyAI48Bus Phase A Line-Line AC RMS VoltageAI49Bus Phase B Line-Line AC RMS VoltageAI50Bus Phase C Line-Line AC RMS VoltageAI51Bus Phase A Line-Neutral AC RMS VoltageAI52Bus Phase B Line-Neutral AC RMS VoltageAI53Bus Phase C Line-Neutral AC RMS VoltageAI54Bus Average Line-Neutral AC RMS VoltageAI55Bus Average Line-Line AC RMS Voltage PercentAI56Generator Total Percent CurrentAI57Utility Total Real PowerAI58Utility Total Reactive PowerAI59Utility Overall Power FactorAI60Generator Desired Power FactorAI61Desired Base LoadAI62Load Share Line Total Percent kWAI63Load Share Line Total Percent kVArAI64Generator Average AC RMS Frequency PercentAI65Fuel LevelAI66Engine Oil TemperatureAI67Engine Oil PressureAI68Engine Coolant TemperatureAI69Battery VoltageAI70Engine rpmAI71Engine Operating HoursAI72Automatic Start/Stop StateAI73Spare Analog Input PercentAI74Spare Analog Input TemperatureAI75Spare Analog Input PressureAI76Service Maintenance Interval Hours RemainingAI77Service Maintenance Interval Days RemainingAI78Number of Crank AttemptsAI79Number of Successful StartsAI80Engine Oil Pressure from Data LinkAI81Engine Coolant Temperature from Data LinkAI82Cylinder #1 Exhaust Port Temperature from Data LinkAI83Cylinder #2 Exhaust Port Temperature from Data LinkAI84Cylinder #3 Exhaust Port Temperature from Data LinkAI85Cylinder #4 Exhaust Port Temperature from Data LinkAI86Cylinder #5 Exhaust Port Temperature from Data LinkAI87Cylinder #6 Exhaust Port Temperature from Data LinkAI88Cylinder #7 Exhaust Port Temperature from Data LinkAI89Cylinder #8 Exhaust Port Temperature from Data LinkAI90Cylinder #9 Exhaust Port Temperature from Data LinkAI91Cylinder #10 Exhaust Port Temperature from Data LinkAI92Cylinder #11 Exhaust Port Temperature from Data LinkAI93Cylinder #12 Exhaust Port Temperature from Data LinkAI94Cylinder #13 Exhaust Port Temperature from Data LinkAI95Cylinder #14 Exhaust Port Temperature from Data LinkAI96Cylinder #15 Exhaust Port Temperature from Data LinkAI97Cylinder #16 Exhaust Port Temperature from Data LinkAI98Cylinder #17 Exhaust Port Temperature from Data LinkAI99Cylinder #18 Exhaust Port Temperature from Data LinkAI100Cylinder #19 Exhaust Port Temperature from Data LinkAI101Cylinder #20 Exhaust Port Temperature from Data LinkAI102Exhaust Manifold #1 (Left) TemperatureAI103Exhaust Manifold #2 (Right) Temperature from Data LinkAI104Intake Manifold #1 Temperature from Data LinkAI105Intake Manifold #2 Temperature from Data LinkAI106Engine Oil Temperature from Data LinkAI107Engine Fuel Temperature from Data LinkAI108Fuel Pressure from Data LinkAI109Crankcase Pressure from Data LinkAI110Boost Pressure from Data LinkAI111Oil Filter Differential Pressure from Data LinkAI112Fuel Filter Differential Pressure from Data LinkAI113Air Filter 1 Differential Pressure from Data LinkAI114Instantaneous Fuel Consumption from Data LinkAI115Atmospheric Pressure from Data LinkAI116Fuel LevelAI117Service Maintenance Interval Weeks RemainingAI118Bypass CooldownAI119Engine Control Switch PositionAI120Engine Control Switch CommandAI121Lamp Test CommandAI122Acknowledge All Events CommandAI123Auto Start/Stop Fuel Control EnabledAI124Key PressAI125SCR System Check Required StatusAI126Fuel Unload Pump ActiveAI127Fuel Load Pump ActiveAI128System Event CountAI129System Event Lamp StatusAI130Forced Idle Command ActiveAI131Generator Excitation Field Voltage from Data LinkAI132Generator Excitation Field Current from Data LinkBI133Alarm Group 1 Column 1 row 16BI134Alarm Group 1 Column 1 row 15BI135Alarm Group 1 Column 1 row 14BI136Alarm Group 1 Column 1 row 13BI137Alarm Group 1 Column 1 row 12BI138Alarm Group 1 Column 1 row 11BI139Alarm Group 1 Column 1 row 10BI140Alarm Group 1 Column 1 row 09BI141Alarm Group 1 Column 1 row 08BI142Alarm Group 1 Column 1 row 07BI143Alarm Group 1 Column 1 row 06BI144Alarm Group 1 Column 1 row 05BI145Alarm Group 1 Column 1 row 04BI146Alarm Group 1 Column 1 row 03BI147Alarm Group 1 Column 1 row 02BI148Alarm Group 1 Column 1 row 01BI149Alarm Group 1 Column 2 row 16BI150Alarm Group 1 Column 2 row 15BI151Alarm Group 1 Column 2 row 14BI152Alarm Group 1 Column 2 row 13BI153Alarm Group 1 Column 2 row 12BI154Alarm Group 1 Column 2 row 11BI155Alarm Group 1 Column 2 row 10BI156Alarm Group 1 Column 2 row 09BI157Alarm Group 1 Column 2 row 08BI158Alarm Group 1 Column 2 row 07BI159Alarm Group 1 Column 2 row 06BI160Alarm Group 1 Column 2 row 05BI161Alarm Group 1 Column 2 row 04BI162Alarm Group 1 Column 2 row 03BI163Alarm Group 1 Column 2 row 02BI164Alarm Group 1 Column 2 row 01BI165Alarm Group 1 Horn row 16BI166Alarm Group 1 Horn row 15BI167Alarm Group 1 Horn row 14BI168Alarm Group 1 Horn row 13BI169Alarm Group 1 Horn row 12BI170Alarm Group 1 Horn row 11BI171Alarm Group 1 Horn row 10BI172Alarm Group 1 Horn row 09BI173Alarm Group 1 Horn row 08BI174Alarm Group 1 Horn row 07BI175Alarm Group 1 Horn row 06BI176Alarm Group 1 Horn row 05BI177Alarm Group 1 Horn row 04BI178Alarm Group 1 Horn row 03BI179Alarm Group 1 Horn row 02BI180Alarm Group 1 Horn row 01BI181Alarm Group 2 Column 1 row 16BI182Alarm Group 2 Column 1 row 15BI183Alarm Group 2 Column 1 row 14BI184Alarm Group 2 Column 1 row 13BI185Alarm Group 2 Column 1 row 12BI186Alarm Group 2 Column 1 row 11BI187Alarm Group 2 Column 1 row 10BI188Alarm Group 2 Column 1 row 09BI189Alarm Group 2 Column 1 row 08BI190Alarm Group 2 Column 1 row 07BI191Alarm Group 2 Column 1 row 06BI192Alarm Group 2 Column 1 row 05BI193Alarm Group 2 Column 1 row 04BI194Alarm Group 2 Column 1 row 03BI195Alarm Group 2 Column 1 row 02BI196Alarm Group 2 Column 1 row 01BI197Alarm Group 2 Column 2 row 16BI198Alarm Group 2 Column 2 row 15BI199Alarm Group 2 Column 2 row 14BI200Alarm Group 2 Column 2 row 13BI201Alarm Group 2 Column 2 row 12BI202Alarm Group 2 Column 2 row 11BI203Alarm Group 2 Column 2 row 10BI204Alarm Group 2 Column 2 row 09BI205Alarm Group 2 Column 2 row 08BI206Alarm Group 2 Column 2 row 07BI207Alarm Group 2 Column 2 row 06BI208Alarm Group 2 Column 2 row 05BI209Alarm Group 2 Column 2 row 04BI210Alarm Group 2 Column 2 row 03BI211Alarm Group 2 Column 2 row 02BI212Alarm Group 2 Column 2 row 01BI213Alarm Group 2 Horn row 16BI214Alarm Group 2 Horn row 15BI215Alarm Group 2 Horn row 14BI216Alarm Group 2 Horn row 13BI217Alarm Group 2 Horn row 12BI218Alarm Group 2 Horn row 11BI219Alarm Group 2 Horn row 10BI220Alarm Group 2 Horn row 09BI221Alarm Group 2 Horn row 08BI222Alarm Group 2 Horn row 07BI223Alarm Group 2 Horn row 06BI224Alarm Group 2 Horn row 05BI225Alarm Group 2 Horn row 04BI226Alarm Group 2 Horn row 03BI227Alarm Group 2 Horn row 02BI228Alarm Group 2 Horn row 01BI229Alarm Group 3 Col 1 Aftertreatment Shutdown EventBI230Alarm Group 3 Col 1 High Battery Voltage Shutdown Event ActiveBI231Alarm Group 3 Col 1 Low Fuel or Gas Pressure shutdownBI232Alarm Group 3 Col 1 Low Coolant Level ShutdownBI233Alarm Group 3 Col 1 Overspeed Shotdown EventBI234Alarm Group 3 Col 1 Low Oil Pressure Shutdown EventBI235Alarm Group 3 Col 1 High Coolant Temperature ShutdownBI236Alarm Group 3 Col 1 Engine Failure to Start OvercrankBI237Alarm Group 3 Col 1 Emergency Stop ShutdownBI238Alarm Group 3 Col 2 Aftertreatment Warning Event ActiveBI239Alarm Group 3 Col 2 Engine Running Condition ActiveBI240Alarm Group 3 Col 2 Emerg Power Syst Sup Load Cond ActiveBI241Alarm Group 3 Col 2 Battery Charger AC Failure Event ActiveBI242Alarm Group 3 Col 2 Low Cranking Voltage Warning Event ActiveBI243Alarm Group 3 Col 2 Low Battery Voltage Warning Event ActiveBI244Alarm Group 3 Col 2 High Battery Voltage Warning Event ActiveBI245Alarm Group 3 Col 2 Engine Control Sw Not in Auto Event ActiveBI246Alarm Group 3 Col 2 Low Fuel Level or Gas Pres Warn Event ActBI247Alarm Group 3 Col 2 Low Coolant Level Warning Event ActiveBI248Alarm Group 3 Col 2 Low Oil Pressure Warning Event ActiveBI249Alarm Group 3 Col 2 Low Coolant Temperature Warning Event ActiveBI250Alarm Group 3 Col 2 High Coolant Temp Warning Event ActiveBI251Alarm Group 3 Col 2 Emergency Stop Diagnostic Event ActiveBI252Alarm Group 3 Horn Aftertreatment Event Horn ActiveBI253Alarm Group 3 Horn Engine Running Condition ActiveBI254Alarm Group 3 Horn Emerg Pwr Syst Supply Load Cond Horn ActiveBI255Alarm Group 3 Horn Battery Charger AC Failure Event Horn ActiveBI256Alarm Group 3 Horn Low Cranking Voltage Event Horn ActiveBI257Alarm Group 3 Horn Low Battery Voltage Event Horn ActiveBI258Alarm Group 3 Horn High Battery Voltage Event Horn ActiveBI259Alarm Group 3 Horn Eng Cont Sw Not in Auto Event Horn ActiveBI260Alarm Group 3 Horn Low Fuel Level or Gasd Press Event Horn ActBI261Alarm Group 3 Horn Low Coolant Level Event Horn ActiveBI262Alarm Group 3 Horn Overspeed Shutdown Event Horn ActiveBI263Alarm Group 3 Horn Low Oil Pressure Event Horn ActiveBI264Alarm Group 3 Horn Low Coolant Temp Event Horn ActiveBI265Alarm Group 3 Horn High Coolant Temperature Event Horn ActBI266Alarm Group 3 Horn Eng Fail Start Overcrank Shutdn Evt Horn ActBI267Alarm Group 3 Horn Emerg Stop Shutdown Diagnostic Horn ActiveBI268Alarm Group 4 Col 1 Aftertreatment Shutdown Event ActiveBI269Alarm Group 4 Col 1 Air Shutdown Damper Closed Event ActiveBI270Alarm Group 4 Col 1 High Battery Voltage Shutdown Event ActiveBI271Alarm Group 4 Col 1 Low Fuel Level Shutdown Event ActiveBI272Alarm Group 4 Col 1 Eventa A Event ActiveBI273Alarm Group 4 Col 1 Overspeed Shutdown Event ActiveBI274Alarm Group 4 Col 1 Low Oil Pressure Shutdown Event ActiveBI275Alarm Group 4 Col 1 High Coolant Temp Shutdown Event ActiveBI276Alarm Group 4 Col 1 Eng Fail to Start Overcrank Shutdn Event ActBI277Alarm Group 4 Col 1 Emergency Stop Shutdown Event ActiveBI278Alarm Group 4 Col 2 Aftertreatment Warning Event ActiveBI279Alarm Group 4 Col 2 Emerg Powr Sys Supply Load Condition ActBI280Alarm Group 4 Col 2 Battery Charger AC Failure Event ActiveBI281Alarm Group 4 Col 2 Low Cranking Voltage Warning Event ActiveBI282Alarm Group 4 Col 2 Low Battery Voltage Warning Event ActiveBI283Alarm Group 4 Col 2 High Battery Voltage Warning Event ActiveBI284Alarm Group 4 Col 2 Engine Control Switch Not in Auto Event ActBI285Alarm Group 4 Col 2 Low Fuel Level Warning Event ActBI286Alarm Group 4 Col 2 Low Coolant Level Warning Event ActBI287Alarm Group 4 Col 2 Low Oil Pressure Warning Event ActBI288Alarm Group 4 Col 2 Low Coolant Temp Warning Event ActBI289Alarm Group 4 Col 2 High Coolant Temp Warning Event ActBI290Alarm Group 4 Col 2 Emergency Stop Diagnostic Event ActBI291Alarm Group 4 Horn Aftertreatment Event Horn ActiveBI292Alarm Group 4 Horn Air Shutdown Damper Closed Event Horn ActBI293Alarm Group 4 Horn Emerg Pwr Sys Supply Load Condition Horn ActBI294Alarm Group 4 Horn Battery Charger AC Failure Event Horn ActBI295Alarm Group 4 Horn Low Cranking Voltage Event Horn ActiveBI296Alarm Group 4 Horn Low Battery Voltage Event Horn ActBI297Alarm Group 4 Horn = High Battery Voltage Event Horn ActBI298Alarm Group 4 Horn Engine Control Sw Not in Auto Event Horn ActBI299Alarm Group 4 Horn Low Fuel Level Event Horn ActiveBI300Alarm Group 4 Horn Low Coolant Level Event Horn ActBI301Alarm Group 4 Horn Overspeed Shutdown Event Horn ActBI302Alarm Group 4 Horn Low Oil Pressure Event Horn ActBI303Alarm Group 4 Horn = Low Coolant Temperature Event Horn ActiveBI304Alarm Group 4 Horn High Coolant Temperature Event Horn ActBI305Alarm Grp 4 Horn Eng Fail to Str Overcrank Shutdn Event Horn ActBI306Alarm Grp 4 Horn Emergency Stop Shutdown Diagnostic Horn ActAI307Urea Tank LevelAI308Aftertreatment #1 SCR Catalyst Reagent Tank #1 TemperatureAI309Urea Injection Air PressureAI310Catalyst Intake TemperatureAI311Aftertreatment 1 SCR Catalyst Exhaust Gas Differential PressureAI312Digital Input #1 Active StatusAI313Digital Input #2 Active StatusAI314Digital Input #3 Active StatusAI315Digital Input #4 Active StatusAI316Digital Input #5 Active StatusAI317Digital Input #6 Active StatusAI318Digital Input #7 Active StatusAI319Digital Input #8 Active StatusAI320Isolated Digital Input #1 Active StatusAI321Isolated Digital Input #2 Active StatusAI322Isolated Digital Input #3 Active StatusAI323Isolated Digital Input #4 Active StatusAI324Dedicated Digital Input #1 (E-Stop) Active StatusAI325Dedicated Digital Input #2 (Initiate Command) Active StatusAI326Dedicated Digital Input #3 (Gen CB Aux A) Active StatusAI327Dedicated Digital Input #4 (Gen CB Aux B) Active StatusAI328Relay Output #1 Active StatusAI329Relay Output #2 Active StatusAI330Relay Output #3 Active StatusAI331Relay Output #4 Active StatusAI332Relay Output #5 Active StatusAI333Relay Output #6 Active StatusAI334Relay Output #7 Active StatusAI335Relay Output #8 Active StatusAI336Digital Output #1 Active StatusAI337Digital Output #2 Active StatusAI338Digital Output #3 Active StatusAI339Digital Output #4 Active StatusAI340Digital Output #5 Active StatusAI341Digital Output #6 Active StatusAI342Digital Output #7 Active StatusAI343Digital Output #8 Active StatusAI344Digital Output #9 Active StatusAI345Digital Output #10 Active StatusAI346Digital Output #11 Active StatusAI347Digital Output #12 Active StatusAI348Digital Output #13 Active StatusAI349Digital Output #14 Active StatusAI350Digital Output #15 Active StatusAI351Digital Output #16 Active StatusAI352Digital Output #17 Active StatusAI353Group Start Active Status (DIDI-01)AI354Bell Alarm Active Status (DIDI-02)AI355Gen CB Trip Command Active Status (DIDI-03)AI356Gen CB Close Command Active Status (DIDI-04)AI357Arbitration Relay Active Status (DDO-01)AI358Gen CB Close Active Status (DDO-02)AI359Gen CB Trip Active Status (DDO-03)AI360Analog Input #1 Sensor ValueAI361Analog Input #2 Sensor ValueAI362Analog Input #3 Sensor ValueAI363Analog Input #4 Sensor ValueAI364Analog Input #1 Data ValueAI365Analog Input #2 Data ValueAI366Analog Input #3 Data ValueAI367Analog Input #4 Data ValueAI368Analog Output #1 Data ValueAI369Analog Output #2 Data ValueAI370Analog Output #3 Data ValueAI371PWM Output #1 Data ValueAI372PWM Output #2 Data ValueAO373Analog Output #1 Data CommandAO374Analog Output #2 Data CommandAO375Analog Output #3 Data CommandAO376PWM Output #1 Data CommandAO377PWM Output #2 Data CommandAO378Write Access Password Word 1AO379Write Access Password Word 2AO380Write Access Password Word 3AO381Write Access Password Word 4AO382Write Access Password Word 5AO383Write Access Password Word 6AO384Write Access Password Word 7AO385Write Access Password Word 8AO386Level 1 Password Word 1AO387Level 1 Password Word 2AO388Level 1 Password Word 3AO389Level 1 Password Word 4AO390Level 1 Password Word 5AO391Level 1 Password Word 6AO392Level 1 Password Word 7AO393Level 1 Password Word 8AO394Level 2 Password Word 1AO395Level 2 Password Word 2AO396Level 2 Password Word 3AO397Level 2 Password Word 4AO398Level 2 Password Word 5AO399Level 2 Password Word 6AO400Level 2 Password Word 7AO401Level 2 Password Word 8AO402SCADA Password Word 1AO403SCADA Password Word 2AO404SCADA Password Word 3AO405SCADA Password Word 4AO406SCADA Password Word 5AO407SCADA Password Word 6AO408SCADA Password Word 7AO409SCADA Password Word 8AI410Current Security LevelAO411Set Security LevelAI412Level 3 Password Phone In Prompt Word 1AI413Level 3 Password Phone In Prompt Word 2AI414Level 3 Password Phone In Prompt Word 3AI415Level 3 Password Phone In Prompt Word 4AI416Level 3 Password Phone In Prompt Word 5AI417Level 3 Password Phone In Prompt Word 6AI418Level 3 Password Phone In Prompt Word 7AI419Level 3 Password Phone In Prompt Word 8AI420Engine Oil Temperature from I/O PinAI421Exhaust TemperatureAI422Left Manifold Exhaust TemperatureAI423Right Manifold Exhaust Temperature from I/O PinAI424Fuel Level from I/O PinAI425External Tank Fuel Level from I/O PinAI426Engine Oil Level from I/O PinAI427Engine Coolant Level from I/O PinAI428Oil Filter Differential Pressure from I/O PinAI429Air Filter 1 Differential Pressure from I/O PinAI430Fuel Filter Differential Pressure from I/O PinAI431Main Tank Urea Level from I/O PinAI432Real Time Clock Word 1AI433Real Time Clock Word 2AI434Real Time Clock Word 3AO435Update Real Time Clock Command Word 1AO436Update Real Time Clock Command Word 2AO437Update Real Time Clock Command Word 3AI438Log Entry IndexAI439Log Entry Word 01AI440Log Entry Word 02AI441Log Entry Word 03AI442Log Entry Word 04AI443Log Entry Word 05AI444Log Entry Word 06AI445Log Entry Word 07AI446Log Entry Word 08AI447Log Entry Word 09AI448Log Entry Word 10AI449Log Entry Word 11AI450Log Entry Word 12AI451Log Entry Word 13AI452Log Entry Word 14AO453Reset Event Word 1AO454Reset Event Word 2AI455Cooldown Duration RemainingAO456Remote Initiate CommandAO457Emergency Stop CommandAI458Desired Genset Output VoltageAI459Total Voltage Bias PercentAO460Voltage Bias Percent Increment CommandAI461Requested Engine SpeedAI462Total Speed Bias PercentAO463Speed Bias Percent Increment CommandAI464Generator/Bus Phase DifferenceAI465Generator Circuit Breaker StatusAI466Generator Frequency within LimitsAI467Generator Voltage within LimitsAI468Bus Voltage within LimitsAI469Bus Live StatusAI470Genset Control OnlineAI471Engine Control OnlineAI472Secondary Engine Control OnlineAI473External I/O #1 OnlineAI474External I/O #2 OnlineAI475External I/O #3 OnlineAI476External I/O #4 OnlineAI477Digital AVR OnlineAI478RTD Module OnlineAI479Thermocouple #1 OnlineAI480Thermocouple #2 OnlineAI481SCR Module OnlineAI482Sync Mode Switch StateAI483Dead Bus Arbitration StateAI484Load Sense Load Demand StateAI485Load Shed Command Active StatusAI486Load Shed Command ResetAI487Primary Data Link StatusAI488Accessory Data Link StatusAI489RS-485 SCADA Data Link StatusAI490TCP/IP SCADA Data Link StatusAI491RS-485 Annunciator Data Link StatusAI492Low Idle State from ADEMAI493Engine Protection has Shut Down EngineAI494Control Serial Number Word 1AI495Control Serial Number Word 2AI496Control Serial Number Word 3AI497Control Serial Number Word 4AI498Control Serial Number Word 5AI499Control Serial Number Word 6AI500Programmable Cycle Timer 1 Output 3 statusAI501Programmable Cycle Timer 2 Output 3 statusAI502Programmable Cycle Timer 3 Output 3 statusAI503Programmable Cycle Timer 4 Output 3 statusAI504Programmable Cycle Timer 5 Output 3 statusAI505Programmable Cycle Timer 6 Output 3 statusAI506Programmable Cycle Timer 7 Output 3 statusAO507Programmable Cycle Timer 1 Output 1 statusAI508Programmable Cycle Timer 2 Output 1 statusAI509Programmable Cycle Timer 3 Output 1 statusAI510Programmable Cycle Timer 4 Output 1 statusAI511Programmable Cycle Timer 5 Output 1 statusAI512Programmable Cycle Timer 6 Output 1 statusAI513Programmable Cycle Timer 7 Output 1 statusAI514Programmable Cycle Timer 1 Output 2 statusAI515Programmable Cycle Timer 2 Output 2 statusAI516Programmable Cycle Timer 3 Output 2 statusAI517Programmable Cycle Timer 4 Output 2 statusAI518Programmable Cycle Timer 5 Output 2 statusAI519Programmable Cycle Timer 6 Output 2 statusAI520Programmable Cycle Timer 7 Output 2 statusAI521Turbocharger 1 Compressor Inlet TempAI522Turbocharger 2 Compressor Inlet TempAI523Turbocharger 3 Compressor Inlet TempAI524Turbocharger 4 Compressor Inlet TempAI525Turbocharger 1 Turbine Inlet TempAI526Turbocharger 1 Turbine Outlet TempAI527Turbocharger 2 Turbine Inlet TempAI528Turbocharger 2 Turbine Outlet TempAI529Turbocharger 3 Turbine Inlet TempAI530Turbocharger 3 Turbine Outlet TempAI531Turbocharger 4 Turbine Inlet TempAI532Turbocharger 4 Turbine Outlet TempAI533Exhaust Temperature from Data LinkAI534Fuel Pump Primer StatusAI535Manual Fuel Priming Duration RemainingAI536Software Build Version Word 01AI537Software Build Version Word 02AI538Software Build Version Word 03AI539Software Build Version Word 04AI540Software Build Version Word 05AI541Software Build Version Word 06AI542Software Build Version Word 07AI543Software Build Version Word 08AI544Software Build Version Word 09AI545Software Build Version Word 10AI546Digital Output #1 CommandAI547Digital Output #2 CommandAI548Digital Output #3 CommandAI549Digital Output #4 CommandAI550Digital Output #5 CommandAI551Digital Output #6 CommandAI552Digital Output #7 CommandAI553Digital Output #8 CommandAI554Digital Output #9 CommandAI555Digital Output #10 CommandAI556Digital Output #11 CommandAI557Digital Output #12 CommandAI558Digital Output #13 CommandAI559Digital Output #14 CommandAI560Digital Output #15 CommandAI561Digital Output #16 CommandAI562Digital Output #17 CommandAI563Relay Output #1 CommandAI564Relay Output #2 CommandAI565Relay Output #3 CommandAI566Relay Output #4 CommandAI567Relay Output #5 CommandAI568Relay Output #6 CommandAI569Relay Output #7 CommandAI570Relay Output #8 Command
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Caterpillar_EMCP_4_Data_Links_c_LX.csv; the profile maps the registers in the EMCP 4 Modbus data links manual (https://www.ccontrols.com/support/dp/ManualEMCP4.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 64 of the 570 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Fuel Level); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Caterpillar EMCP 4 generator set control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
How many BACnet points does the Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX have?
This list has 570 BACnet objects: 348 analog inputs, 48 analog outputs, 174 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX BACnet points are writable?
48 of the 570 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Caterpillar_EMCP_4_Data_Links_b (Caterpillar_EMCP_4_Data_Links_c_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Caterpillar_EMCP_4_Data_Links_c_LX.csv.
What are the minimum BACnet points to integrate the Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX?
Start with AI 7 Generator Total Real Power (Generator total real power); AI 1 Generator Average Line-Line AC RMS Voltage (Average line-line voltage); AI 2 Generator Average AC RMS Current (Average current); AI 3 Generator Average AC RMS Frequency (Generator frequency); AI 70 Engine rpm (Engine speed); AI 68 Engine Coolant Temperature (Coolant temperature); AI 67 Engine Oil Pressure (Oil pressure); AI 69 Battery Voltage (Battery voltage); AI 65 Fuel Level (Fuel level, %); AI 119 Engine Control Switch Position (Engine control switch position).
How do I check these points on the real Caterpillar EMCP 4 generator set control via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Caterpillar_EMCP_4_Data_Links_b · Caterpillar_EMCP_4_Data_Links_c_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.