 "manufacturer": "Contemporary Controls",
 "manufacturer_slug": "contemporary-controls",
 "model": "Thermokon Thanos room operating unit via BASgatewayLX",
 "short_model": "BASgatewayLX Thermokon Thanos",
 "model_slug": "basgatewaylx-thermokon-thanos",
 "aliases": [
  "Thanos",
  "Thanos SR",
  "Thanos EH",
  "Thermokon Thanos Modbus"
 ],
 "equipment_type": "Room operating unit (thermostat / sensor)",
 "applies_to": "Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.",
 "summary": "Gateway profile for the Thermokon Thanos: 590 objects (72 AI, 456 AO, 62 BO), 192 polled by default. Most of the map is configuration: display, illumination, set point ranges and labels, fan stages, occupancy and two controller blocks (parameters, limits, fan coil interaction). Live values - internal temperature and humidity, effective set points, fan stage, occupancy, key states and controller outputs - are inputs and are unpolled by default.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "Built from Contemporary Controls' BASgatewayLX Modbus device profile Thermokon_Thanos_a_LX.csv; the profile maps the registers in the Thanos Modbus register list (https://www.ccontrols.com/support/dp/Thermokon_Thanos_a_LX.pdf).",
  "Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.",
  "Only 192 of the 590 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say \"not polled by default\".",
  "The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads."
 ],
 "source": {
  "title": "BASgatewayLX Modbus device profile Thermokon_Thanos_a",
  "doc_number": "Thermokon_Thanos_a_LX.csv",
  "revision_date": null,
  "url": "https://www.ccontrols.com/support/dp/Thermokon_Thanos_a_LX.zip"
 },
 "integration": {
  "summary": "Tick the live values (temperature, humidity, effective set point, fan stage, occupancy, controller outputs) before mapping; the polled defaults are mostly controller 1 and 2 parameters.",
  "minimum_points": [
   {
    "ref": "AI 446",
    "name": "Temperature internal sensor",
    "why": "Room temperature (internal sensor)"
   },
   {
    "ref": "AI 447",
    "name": "Humidity internal sensor",
    "why": "Room humidity (internal sensor)"
   },
   {
    "ref": "AI 435",
    "name": "Set point effective 1 (Default set point + set point offset)",
    "why": "Effective set point 1"
   },
   {
    "ref": "AI 448",
    "name": "Current fan stage",
    "why": "Current fan stage"
   },
   {
    "ref": "AI 449",
    "name": "Current room occupancy",
    "why": "Current room occupancy"
   },
   {
    "ref": "AI 450",
    "name": "Control variable Heating Controller 1",
    "why": "Controller 1 heating output"
   },
   {
    "ref": "AI 451",
    "name": "Control variable Cooling Controller 1",
    "why": "Controller 1 cooling output"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.",
   "One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled."
  ],
  "gotchas": [
   "The polled defaults are configuration outputs; writing them changes the device setup.",
   "Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Device code",
   "description": "Modbus 400001; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Firmware version",
   "description": "Modbus 400002; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Device version",
   "description": "Modbus 400003; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Humidity sensor existing",
   "description": "Modbus 400004; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "Rotation Display",
   "description": "Modbus 400005; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "Device location identification",
   "description": "Modbus 400006; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "Temperature offset",
   "description": "Modbus 400007; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "Humidity offset",
   "description": "Modbus 400008; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "Setting of the maximal available fan stages",
   "description": "Modbus 400009; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "Status fan stage after reset",
   "description": "Modbus 400010; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "Status room occupancy after reset",
   "description": "Modbus 400011; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "Bypass time room occupancy",
   "description": "Modbus 400012; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "Time cleaning function",
   "description": "Modbus 400013; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 14,
   "name": "Device type",
   "description": "Modbus 400014; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15,
   "name": "Minimum response delay time [ms]",
   "description": "Modbus 400015; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "Background illumination LCD",
   "description": "Modbus 400016; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Contrast",
   "description": "Modbus 400017; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 18,
   "name": "Intensity background illumination LCD Standard-Mode",
   "description": "Modbus 400018; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 19,
   "name": "Intensity background illumination LCD Idle-Mode",
   "description": "Modbus 400019; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "Intensity background illumination LCD Standby-Mode",
   "description": "Modbus 400020; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 21,
   "name": "Intensity background illumination keypad Standard",
   "description": "Modbus 400021; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "Intensity background illumination keypad Idle",
   "description": "Modbus 400022; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 23,
   "name": "Intensity background illumination keypad Standby",
   "description": "Modbus 400023; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 24,
   "name": "Time to switch Standard- in Idle mode",
   "description": "Modbus 400024; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "Time to switch Idle- in Standby mode",
   "description": "Modbus 400025; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 26,
   "name": "Duration of displaying a menu point",
   "description": "Modbus 400026; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 27,
   "name": "Duration of displaying an operation",
   "description": "Modbus 400027; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 28,
   "name": "Date display",
   "description": "Modbus 400028; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 29,
   "name": "Time display",
   "description": "Modbus 400029; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 30,
   "name": "Time mode",
   "description": "Modbus 400030; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 31,
   "name": "Register to configure available submenus (only S version!!)",
   "description": "Modbus 400031; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 32,
   "name": "Refresh interval of LCD in seconds",
   "description": "Modbus 400032; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 33,
   "name": "Display time of single submenus (only S version!!)",
   "description": "Modbus 400033; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 34,
   "name": "Upper range of adjustment Set point offset Set point 1",
   "description": "Modbus 400034; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 35,
   "name": "Lower range of adjustment Set point offset Set point 1",
   "description": "Modbus 400035; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 36,
   "name": "Step size set point adjustment Set point 1",
   "description": "Modbus 400036; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 37,
   "name": "Default set point after reset Set point 1",
   "description": "Modbus 400037; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 38,
   "name": "1. ASCII symbol unit Set point 1",
   "description": "Modbus 400038; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 39,
   "name": "2. ASCII symbol unit Set point 1",
   "description": "Modbus 400039; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 40,
   "name": "3. ASCII symbol unit Set point 1",
   "description": "Modbus 400040; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 41,
   "name": "1. ASCII symbol set point description Set point 1",
   "description": "Modbus 400041; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 42,
   "name": "2. ASCII symbol set point description Set point 1",
   "description": "Modbus 400042; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 43,
   "name": "3. ASCII symbol set point description Set point 1",
   "description": "Modbus 400043; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 44,
   "name": "4. ASCII symbol set point description Set point 1",
   "description": "Modbus 400044; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 45,
   "name": "Upper range of adjustment Set point adjustment Set point 2",
   "description": "Modbus 400045; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 46,
   "name": "Lower range of adjustment Set point adjustment Set point 2",
   "description": "Modbus 400046; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 47,
   "name": "Step size set point adjustment Set point 2",
   "description": "Modbus 400047; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 48,
   "name": "Default set point after reset Set point 2",
   "description": "Modbus 400048; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 49,
   "name": "1. ASCII symbol unit Set point 2",
   "description": "Modbus 400049; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 50,
   "name": "2. ASCII symbol unit Set point 2",
   "description": "Modbus 400050; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 51,
   "name": "3. ASCII symbol unit Set point 2",
   "description": "Modbus 400051; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 52,
   "name": "1. ASCII symbol set point description) Set point 2",
   "description": "Modbus 400052; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 53,
   "name": "2. ASCII symbol set point description Set point 2",
   "description": "Modbus 400053; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 54,
   "name": "3. ASCII symbol set point description Set point 2",
   "description": "Modbus 400054; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 55,
   "name": "4. ASCII symbol set point description Set point 2",
   "description": "Modbus 400055; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 56,
   "name": "Upper range of adjustment Set point offset (Set point 3",
   "description": "Modbus 400056; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 57,
   "name": "Lower range of adjustment Set point offset Set point 3",
   "description": "Modbus 400057; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 58,
   "name": "Step size set point adjustment Set point 3",
   "description": "Modbus 400058; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 59,
   "name": "Default set point 3 after reset Set point 3",
   "description": "Modbus 400059; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 60,
   "name": "1. ASCII symbol unit Set point 3",
   "description": "Modbus 400060; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 61,
   "name": "2. ASCII symbol unit Set point 3",
   "description": "Modbus 400061; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 62,
   "name": "3. ASCII symbol unit Set point 3",
   "description": "Modbus 400062; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 63,
   "name": "1. ASCII symbol set point description Set point 3",
   "description": "Modbus 400063; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 64,
   "name": "2. ASCII symbol set point description Set point 3",
   "description": "Modbus 400064; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 65,
   "name": "3. ASCII symbol set point description Set point 3",
   "description": "Modbus 400065; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 66,
   "name": "4. ASCII symbol set point description Set point 3",
   "description": "Modbus 400066; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 67,
   "name": "Upper range of adjustment Set point offset Set point 4",
   "description": "Modbus 400067; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 68,
   "name": "Lower range of adjustment Set point offset Set point 4",
   "description": "Modbus 400068; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 69,
   "name": "Step size set point adjustment Set point 4",
   "description": "Modbus 400069; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 70,
   "name": "Default set point 4 after reset Set point 4",
   "description": "Modbus 400070; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 71,
   "name": "1. ASCII symbol unit Set point 4",
   "description": "Modbus 400071; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 72,
   "name": "2. ASCII symbol unit Set point 4",
   "description": "Modbus 400072; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 73,
   "name": "3. ASCII symbol unit Set point 4",
   "description": "Modbus 400073; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 74,
   "name": "1. ASCII symbol set point description Set point 4",
   "description": "Modbus 400074; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 75,
   "name": "2. ASCII symbol set point description Set point 4",
   "description": "Modbus 400075; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 76,
   "name": "3. ASCII symbol set point description Set point 4",
   "description": "Modbus 400076; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 77,
   "name": "4. ASCII symbol set point description Set point 4",
   "description": "Modbus 400077; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 78,
   "name": "Upper range of adjustment Set point offset Set point 5",
   "description": "Modbus 400078; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 79,
   "name": "Lower range of adjustment Set point offset Set point 5",
   "description": "Modbus 400079; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 80,
   "name": "Step size set point adjustment Set point 5",
   "description": "Modbus 400080; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 81,
   "name": "Default set point 5 after reset Set point 5",
   "description": "Modbus 400081; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 82,
   "name": "1. ASCII symbol unit Set point 5",
   "description": "Modbus 400082; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 83,
   "name": "2. ASCII symbol unit Set point 5",
   "description": "Modbus 400083; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 84,
   "name": "3. ASCII symbol unit Set point 5",
   "description": "Modbus 400084; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 85,
   "name": "1. ASCII symbol set point description Set point 5",
   "description": "Modbus 400085; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 86,
   "name": "2. ASCII symbol set point description Set point 5",
   "description": "Modbus 400086; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 87,
   "name": "3. ASCII symbol set point description Set point 5",
   "description": "Modbus 400087; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 88,
   "name": "4. ASCII symbol set point description Set point 5",
   "description": "Modbus 400088; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 89,
   "name": "Upper range of adjustment Set point offset Set point 6",
   "description": "Modbus 400089; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 90,
   "name": "Lower range of adjustment Set point offset Set point 6",
   "description": "Modbus 400090; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 91,
   "name": "Step size set point adjustment Set point 6",
   "description": "Modbus 400091; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 92,
   "name": "Default set point 5 after reset Set point 6",
   "description": "Modbus 400092; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 93,
   "name": "1. ASCII symbol unit Set point 6",
   "description": "Modbus 400093; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 94,
   "name": "2. ASCII symbol unit Set point 6",
   "description": "Modbus 400094; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 95,
   "name": "3. ASCII symbol unit Set point 6",
   "description": "Modbus 400095; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 96,
   "name": "1. ASCII symbol set point description Set point 6",
   "description": "Modbus 400096; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 97,
   "name": "2. ASCII symbol set point description Set point 6",
   "description": "Modbus 400097; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 98,
   "name": "3. ASCII symbol set point description Set point 6",
   "description": "Modbus 400098; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 99,
   "name": "4. ASCII symbol set point description Set point 6",
   "description": "Modbus 400099; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 100,
   "name": "1. ASCII symbol unit External value 1",
   "description": "Modbus 400100; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 101,
   "name": "2. ASCII symbol unit External value 1",
   "description": "Modbus 400101; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 102,
   "name": "3. ASCII symbol unit External value 1",
   "description": "Modbus 400102; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 103,
   "name": "1. ASCII symbol description External value 1",
   "description": "Modbus 400103; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 104,
   "name": "2. ASCII symbol description External value 1",
   "description": "Modbus 400104; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 105,
   "name": "3. ASCII symbol description External value 1",
   "description": "Modbus 400105; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 106,
   "name": "4. ASCII symbol description External value 1",
   "description": "Modbus 400106; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 107,
   "name": "1. ASCII symbol unit External value 2",
   "description": "Modbus 400107; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 108,
   "name": "2. ASCII symbol unit External value 2",
   "description": "Modbus 400108; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 109,
   "name": "3. ASCII symbol unit External value 2",
   "description": "Modbus 400109; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 110,
   "name": "1. ASCII symbol description External value 2",
   "description": "Modbus 400110; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 111,
   "name": "2. ASCII symbol description External value 2",
   "description": "Modbus 400111; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 112,
   "name": "3. ASCII symbol description External value 2",
   "description": "Modbus 400112; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 113,
   "name": "4. ASCII symbol description External value 2",
   "description": "Modbus 400113; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 114,
   "name": "1. ASCII symbol unit External value 3",
   "description": "Modbus 400114; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 115,
   "name": "2. ASCII symbol unit External value 3",
   "description": "Modbus 400115; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 116,
   "name": "3. ASCII symbol unit External value 3",
   "description": "Modbus 400116; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 117,
   "name": "1. ASCII symbol description External value 3",
   "description": "Modbus 400117; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 118,
   "name": "2. ASCII symbol description External value 3",
   "description": "Modbus 400118; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 119,
   "name": "3. ASCII symbol description External value 3",
   "description": "Modbus 400119; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 120,
   "name": "4. ASCII symbol description External value 3",
   "description": "Modbus 400120; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 121,
   "name": "1. ASCII symbol unit External value 4",
   "description": "Modbus 400121; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 122,
   "name": "2. ASCII symbol unit External value 4",
   "description": "Modbus 400122; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 123,
   "name": "3. ASCII symbol unit External value 4",
   "description": "Modbus 400123; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 124,
   "name": "1. ASCII symbol description External value 4",
   "description": "Modbus 400124; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 125,
   "name": "2. ASCII symbol description External value 4",
   "description": "Modbus 400125; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 126,
   "name": "3. ASCII symbol description External value 4",
   "description": "Modbus 400126; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 127,
   "name": "4. ASCII symbol description External value 4",
   "description": "Modbus 400127; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 128,
   "name": "1. ASCII symbol unit External value 5",
   "description": "Modbus 400128; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 129,
   "name": "2. ASCII symbol unit External value 5",
   "description": "Modbus 400129; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 130,
   "name": "3. ASCII symbol unit External value 5",
   "description": "Modbus 400130; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 131,
   "name": "1. ASCII symbol description External value",
   "description": "Modbus 400131; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 132,
   "name": "2. ASCII symbol description External value 5",
   "description": "Modbus 400132; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 133,
   "name": "3. ASCII symbol description External value 5",
   "description": "Modbus 400133; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 134,
   "name": "4. ASCII symbol description External value 5",
   "description": "Modbus 400134; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 135,
   "name": "1. ASCII symbol unit External value 6",
   "description": "Modbus 400135; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 136,
   "name": "2. ASCII symbol unit External value 6",
   "description": "Modbus 400136; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 137,
   "name": "3. ASCII symbol unit External value 6",
   "description": "Modbus 400137; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 138,
   "name": "1. ASCII symbol description External value 6",
   "description": "Modbus 400138; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 139,
   "name": "2. ASCII symbol description External value 6",
   "description": "Modbus 400139; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 140,
   "name": "3. ASCII symbol description External value 6",
   "description": "Modbus 400140; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 141,
   "name": "4. ASCII symbol description External value 6",
   "description": "Modbus 400141; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 142,
   "name": "Configuration functional clip",
   "description": "Modbus 400142; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 143,
   "name": "Configuration menu key 1",
   "description": "Modbus 400143; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 144,
   "name": "Configuration menu key 4",
   "description": "Modbus 400144; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 145,
   "name": "onfiguration menu key 5",
   "description": "Modbus 400145; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 146,
   "name": "Configuration menu key 6",
   "description": "Modbus 400146; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 147,
   "name": "Configuration menu key 7",
   "description": "Modbus 400147; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 148,
   "name": "Configuration Direct key 8",
   "description": "Modbus 400148; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 149,
   "name": "Configuration Direct key 9",
   "description": "Modbus 400149; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 150,
   "name": "Configuration Direct key 10",
   "description": "Modbus 400150; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 151,
   "name": "Configuration Direct key 11",
   "description": "Modbus 400151; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 152,
   "name": "Configuration Direct key 12",
   "description": "Modbus 400152; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 153,
   "name": "Configuration Direct key 13",
   "description": "Modbus 400153; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 154,
   "name": "Configuration Direct key 14",
   "description": "Modbus 400154; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 155,
   "name": "Configuration Direct key 15",
   "description": "Modbus 400155; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 156,
   "name": "Lock external defaults",
   "description": "Modbus 400156; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 157,
   "name": "Controller 1 Default set point after reset Comfort",
   "description": "Modbus 400157",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 158,
   "name": "Controller 1 Set point difference Standby",
   "description": "Modbus 400158",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 159,
   "name": "Controller 1 Set point difference Unoccupied",
   "description": "Modbus 400159",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 160,
   "name": "Controller 1 Controller parameter XP Heating",
   "description": "Modbus 400160",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 161,
   "name": "Controller 1 Controller parameter TN Heating",
   "description": "Modbus 400161",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 162,
   "name": "Controller 1 Controller parameter XP Cooling",
   "description": "Modbus 400162",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 163,
   "name": "Controller 1 Controller parameter TN Cooling",
   "description": "Modbus 400163",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 164,
   "name": "Controller 1 Dead zone",
   "description": "Modbus 400164",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 165,
   "name": "Controller 1 Minimum control variable Heating",
   "description": "Modbus 400165",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 166,
   "name": "Controller 1 Maximum control variable Heating",
   "description": "Modbus 400166",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 167,
   "name": "Controller 1 Minimum control variable Cooling",
   "description": "Modbus 400167",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 168,
   "name": "Controller 1 Maximum control variable Cooling",
   "description": "Modbus 400168",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 169,
   "name": "Controller 1 Controller mode after reset",
   "description": "Modbus 400169",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 170,
   "name": "Controller 1 Selection actual value",
   "description": "Modbus 400170",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 171,
   "name": "Controller 1 Selection set value",
   "description": "Modbus 400171",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 172,
   "name": "Controller 1 Selection energy hold-off",
   "description": "Modbus 400172",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 173,
   "name": "Controller 1 Selection Un-/Occupied",
   "description": "Modbus 400173",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 174,
   "name": "Controller 1 Frost protection-Set point",
   "description": "Modbus 400174",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 175,
   "name": "Controller 1 Minimum control variable",
   "description": "Modbus 400175",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 176,
   "name": "Controller 1 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400176",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 177,
   "name": "Controller 1 Number of fan stages",
   "description": "Modbus 400177",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 178,
   "name": "Controller 1 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400178",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 179,
   "name": "Controller 1 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400179",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 180,
   "name": "Controller 1 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400180",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 181,
   "name": "Controller 1 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400181",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 182,
   "name": "Controller 1 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400182",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 183,
   "name": "Controller 1 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400183",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 184,
   "name": "Controller 1 PWM cycle time",
   "description": "Modbus 400184",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 185,
   "name": "Controller 1 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400185",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 186,
   "name": "Controller 1 Display dew point signal of controller",
   "description": "Modbus 400186",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 187,
   "name": "Controller 1 Bypass time",
   "description": "Modbus 400187",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 188,
   "name": "Controller 1 Minimal ON time for fan coil",
   "description": "Modbus 400188",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 189,
   "name": "Controller 2 Default set point after reset Comfort",
   "description": "Modbus 400189",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 190,
   "name": "Controller 2 Set point difference Standby",
   "description": "Modbus 400190",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 191,
   "name": "Controller 2 Set point difference Unoccupied",
   "description": "Modbus 400191",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 192,
   "name": "Controller 2 Controller parameter XP Heating",
   "description": "Modbus 400192",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 193,
   "name": "Controller 2 Controller parameter TN Heating",
   "description": "Modbus 400193",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 194,
   "name": "Controller 2 Controller parameter XP Cooling",
   "description": "Modbus 400194",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 195,
   "name": "Controller 2 Controller parameter TN Cooling",
   "description": "Modbus 400195",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 196,
   "name": "Controller 2 Dead zone",
   "description": "Modbus 400196",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 197,
   "name": "Controller 2 Minimum control variable Heating",
   "description": "Modbus 400197",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 198,
   "name": "Controller 2 Maximum control variable Heating",
   "description": "Modbus 400198",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 199,
   "name": "Controller 2 Minimum control variable Cooling",
   "description": "Modbus 400199",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 200,
   "name": "Controller 2 Maximum control variable Cooling",
   "description": "Modbus 400200",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 201,
   "name": "Controller 2 Controller mode after reset",
   "description": "Modbus 400201",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 202,
   "name": "Controller 2 Selection actual value",
   "description": "Modbus 400202",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 203,
   "name": "Controller 2 Selection set value",
   "description": "Modbus 400203",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 204,
   "name": "Controller 2 Selection energy hold-off",
   "description": "Modbus 400204",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 205,
   "name": "Controller 2 Selection Un-/Occupied",
   "description": "Modbus 400205",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 206,
   "name": "Controller 2 Frost protection-Set point",
   "description": "Modbus 400206",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 207,
   "name": "Controller 2 Minimum control variable",
   "description": "Modbus 400207",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 208,
   "name": "Controller 2 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400208",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 209,
   "name": "Controller 2 Number of fan stages",
   "description": "Modbus 400209",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 210,
   "name": "Controller 2 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400210",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 211,
   "name": "Controller 2 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400211",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 212,
   "name": "Controller 2 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400212",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 213,
   "name": "Controller 2 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400213",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 214,
   "name": "Controller 2 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400214",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 215,
   "name": "Controller 2 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400215",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 216,
   "name": "Controller 2 PWM cycle time",
   "description": "Modbus 400216",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 217,
   "name": "Controller 2 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400217",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 218,
   "name": "Controller 2 Display dew point signal of controller",
   "description": "Modbus 400218",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 219,
   "name": "Controller 2 Bypass time",
   "description": "Modbus 400219",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 220,
   "name": "Controller 2 Minimal ON time for fan coil",
   "description": "Modbus 400220",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 221,
   "name": "Controller 3 Default set point after reset Comfort",
   "description": "Modbus 400221",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 222,
   "name": "Controller 3 Set point difference Standby",
   "description": "Modbus 400222",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 223,
   "name": "Controller 3 Set point difference Unoccupied",
   "description": "Modbus 400223",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 224,
   "name": "Controller 3 Controller parameter XP Heating",
   "description": "Modbus 400224",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 225,
   "name": "Controller 3 Controller parameter TN Heating",
   "description": "Modbus 400225",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 226,
   "name": "Controller 3 Controller parameter XP Cooling",
   "description": "Modbus 400226",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 227,
   "name": "Controller 3 Controller parameter TN Cooling",
   "description": "Modbus 400227",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 228,
   "name": "Controller 3 Dead zone",
   "description": "Modbus 400228",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 229,
   "name": "Controller 3 Minimum control variable Heating",
   "description": "Modbus 400229",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 230,
   "name": "Controller 3 Maximum control variable Heating",
   "description": "Modbus 400230",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 231,
   "name": "Controller 3 Minimum control variable Cooling",
   "description": "Modbus 400231",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 232,
   "name": "Controller 3 Maximum control variable Cooling",
   "description": "Modbus 400232",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 233,
   "name": "Controller 3 Controller mode after reset",
   "description": "Modbus 400233",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 234,
   "name": "Controller 3 Selection actual value",
   "description": "Modbus 400234",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 235,
   "name": "Controller 3 Selection set value",
   "description": "Modbus 400235",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 236,
   "name": "Controller 3 Selection energy hold-off",
   "description": "Modbus 400236",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 237,
   "name": "Controller 3 Selection Un-/Occupied",
   "description": "Modbus 400237",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 238,
   "name": "Controller 3 Frost protection-Set point",
   "description": "Modbus 400238",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 239,
   "name": "Controller 3 Minimum control variable",
   "description": "Modbus 400239",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 240,
   "name": "Controller 3 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400240",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 241,
   "name": "Controller 3 Number of fan stages",
   "description": "Modbus 400241",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 242,
   "name": "Controller 3 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400242",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 243,
   "name": "Controller 3 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400243",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 244,
   "name": "Controller 3 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400244",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 245,
   "name": "Controller 3 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400245",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 246,
   "name": "Controller 3 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400246",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 247,
   "name": "Controller 3 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400247",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 248,
   "name": "Controller 3 PWM cycle time",
   "description": "Modbus 400248",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 249,
   "name": "Controller 3 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400249",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 250,
   "name": "Controller 3 Display dew point signal of controller",
   "description": "Modbus 400250",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 251,
   "name": "Controller 3 Bypass time",
   "description": "Modbus 400251",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 252,
   "name": "Controller 3 Minimal ON time for fan coil",
   "description": "Modbus 400252",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 253,
   "name": "Controller 4 Default set point after reset Comfort",
   "description": "Modbus 400253",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 254,
   "name": "Controller 4 Set point difference Standby",
   "description": "Modbus 400254",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 255,
   "name": "Controller 4 Set point difference Unoccupied",
   "description": "Modbus 400255",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 256,
   "name": "Controller 4 Controller parameter XP Heating",
   "description": "Modbus 400256",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 257,
   "name": "Controller 4 Controller parameter TN Heating",
   "description": "Modbus 400257",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 258,
   "name": "Controller 4 Controller parameter XP Cooling",
   "description": "Modbus 400258",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 259,
   "name": "Controller 4 Controller parameter TN Cooling",
   "description": "Modbus 400259",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 260,
   "name": "Controller 4 Dead zone",
   "description": "Modbus 400260",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 261,
   "name": "Controller 4 Minimum control variable Heating",
   "description": "Modbus 400261",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 262,
   "name": "Controller 4 Maximum control variable Heating",
   "description": "Modbus 400262",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 263,
   "name": "Controller 4 Minimum control variable Cooling",
   "description": "Modbus 400263",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 264,
   "name": "Controller 4 Maximum control variable Cooling",
   "description": "Modbus 400264",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 265,
   "name": "Controller 4 Controller mode after reset",
   "description": "Modbus 400265",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 266,
   "name": "Controller 4 Selection actual value",
   "description": "Modbus 400266",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 267,
   "name": "Controller 4 Selection set value",
   "description": "Modbus 400267",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 268,
   "name": "Controller 4 Selection energy hold-off",
   "description": "Modbus 400268",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 269,
   "name": "Controller 4 Selection Un-/Occupied",
   "description": "Modbus 400269",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 270,
   "name": "Controller 4 Frost protection-Set point",
   "description": "Modbus 400270",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 271,
   "name": "Controller 4 Minimum control variable",
   "description": "Modbus 400271",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 272,
   "name": "Controller 4 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400272",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 273,
   "name": "Controller 4 Number of fan stages",
   "description": "Modbus 400273",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 274,
   "name": "Controller 4 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400274",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 275,
   "name": "Controller 4 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400275",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 276,
   "name": "Controller 4 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400276",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 277,
   "name": "Controller 4 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400277",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 278,
   "name": "Controller 4 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400278",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 279,
   "name": "Controller 4 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400279",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 280,
   "name": "Controller 4 PWM cycle time",
   "description": "Modbus 400280",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 281,
   "name": "Controller 4 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400281",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 282,
   "name": "Controller 4 Display dew point signal of controller",
   "description": "Modbus 400282",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 283,
   "name": "Controller 4 Bypass time",
   "description": "Modbus 400283",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 284,
   "name": "Controller 4 Minimal ON time for fan coil",
   "description": "Modbus 400284",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 285,
   "name": "Controller 5 Default set point after reset Comfort",
   "description": "Modbus 400285",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 286,
   "name": "Controller 5 Set point difference Standby",
   "description": "Modbus 400286",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 287,
   "name": "Controller 5 Set point difference Unoccupied",
   "description": "Modbus 400287",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 288,
   "name": "Controller 5 Controller parameter XP Heating",
   "description": "Modbus 400288",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 289,
   "name": "Controller 5 Controller parameter TN Heating",
   "description": "Modbus 400289",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 290,
   "name": "Controller 5 Controller parameter XP Cooling",
   "description": "Modbus 400290",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 291,
   "name": "Controller 5 Controller parameter TN Cooling",
   "description": "Modbus 400291",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 292,
   "name": "Controller 5 Dead zone",
   "description": "Modbus 400292",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 293,
   "name": "Controller 5 Minimum control variable Heating",
   "description": "Modbus 400293",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 294,
   "name": "Controller 5 Maximum control variable Heating",
   "description": "Modbus 400294",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 295,
   "name": "Controller 5 Minimum control variable Cooling",
   "description": "Modbus 400295",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 296,
   "name": "Controller 5 Maximum control variable Cooling",
   "description": "Modbus 400296",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 297,
   "name": "Controller 5 Controller mode after reset",
   "description": "Modbus 400297",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 298,
   "name": "Controller 5 Selection actual value",
   "description": "Modbus 400298",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 299,
   "name": "Controller 5 Selection set value",
   "description": "Modbus 400299",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 300,
   "name": "Controller 5 Selection energy hold-off",
   "description": "Modbus 400300",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 301,
   "name": "Controller 5 Selection Un-/Occupied",
   "description": "Modbus 400301",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 302,
   "name": "Controller 5 Frost protection-Set point",
   "description": "Modbus 400302",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 303,
   "name": "Controller 5 Minimum control variable",
   "description": "Modbus 400303",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 304,
   "name": "Controller 5 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400304",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 305,
   "name": "Controller 5 Number of fan stages",
   "description": "Modbus 400305",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 306,
   "name": "Controller 5 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400306",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 307,
   "name": "Controller 5 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400307",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 308,
   "name": "Controller 5 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400308",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 309,
   "name": "Controller 5 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400309",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 310,
   "name": "Controller 5 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400310",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 311,
   "name": "Controller 5 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400311",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 312,
   "name": "Controller 5 PWM cycle time",
   "description": "Modbus 400312",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 313,
   "name": "Controller 5 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400313",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 314,
   "name": "Controller 5 Display dew point signal of controller",
   "description": "Modbus 400314",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 315,
   "name": "Controller 5 Bypass time",
   "description": "Modbus 400315",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 316,
   "name": "Controller 5 Minimal ON time for fan coil",
   "description": "Modbus 400316",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 317,
   "name": "Controller 6 Default set point after reset Comfort",
   "description": "Modbus 400317",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 318,
   "name": "Controller 6 Set point difference Standby",
   "description": "Modbus 400318",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 319,
   "name": "Controller 6 Set point difference Unoccupied",
   "description": "Modbus 400319",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 320,
   "name": "Controller 6 Controller parameter XP Heating",
   "description": "Modbus 400320",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 321,
   "name": "Controller 6 Controller parameter TN Heating",
   "description": "Modbus 400321",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 322,
   "name": "Controller 6 Controller parameter XP Cooling",
   "description": "Modbus 400322",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 323,
   "name": "Controller 6 Controller parameter TN Cooling",
   "description": "Modbus 400323",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 324,
   "name": "Controller 6 Dead zone",
   "description": "Modbus 400324",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 325,
   "name": "Controller 6 Minimum control variable Heating",
   "description": "Modbus 400325",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 326,
   "name": "Controller 6 Maximum control variable Heating",
   "description": "Modbus 400326",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 327,
   "name": "Controller 6 Minimum control variable Cooling",
   "description": "Modbus 400327",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 328,
   "name": "Controller 6 Maximum control variable Cooling",
   "description": "Modbus 400328",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 329,
   "name": "Controller 6 Controller mode after reset",
   "description": "Modbus 400329",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 330,
   "name": "Controller 6 Selection actual value",
   "description": "Modbus 400330",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 331,
   "name": "Controller 6 Selection set value",
   "description": "Modbus 400331",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 332,
   "name": "Controller 6 Selection energy hold-off",
   "description": "Modbus 400332",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 333,
   "name": "Controller 6 Selection Un-/Occupied",
   "description": "Modbus 400333",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 334,
   "name": "Controller 6 Frost protection-Set point",
   "description": "Modbus 400334",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 335,
   "name": "Controller 6 Minimum control variable",
   "description": "Modbus 400335",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 336,
   "name": "Controller 6 Controller has access to symbols Heating Cooling",
   "description": "Modbus 400336",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 337,
   "name": "Controller 6 Number of fan stages",
   "description": "Modbus 400337",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 338,
   "name": "Controller 6 Control variable threshold for fan stage 1 Heating",
   "description": "Modbus 400338",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 339,
   "name": "Controller 6 Control variable threshold for fan stage 2 Heating",
   "description": "Modbus 400339",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 340,
   "name": "Controller 6 Control variable threshold for fan stage 3 Heating",
   "description": "Modbus 400340",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 341,
   "name": "Controller 6 Control variable threshold for fan stage 1 Cooling",
   "description": "Modbus 400341",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 342,
   "name": "Controller 6 Control variable threshold for fan stage 2 Cooling",
   "description": "Modbus 400342",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 343,
   "name": "Controller 6 Control variable threshold for fan stage 3 Cooling",
   "description": "Modbus 400343",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 344,
   "name": "Controller 6 PWM cycle time",
   "description": "Modbus 400344",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 345,
   "name": "Controller 6 Select fan coil X interacts with Main-Fan control",
   "description": "Modbus 400345",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 346,
   "name": "Controller 6 Display dew point signal of controller",
   "description": "Modbus 400346",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 347,
   "name": "Controller 6 Bypass time",
   "description": "Modbus 400347",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 348,
   "name": "Controller 6 Minimal ON time for fan coil",
   "description": "Modbus 400348",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 349,
   "name": "Function digital Input 1",
   "description": "Modbus 400349; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 350,
   "name": "Function digital Input 2",
   "description": "Modbus 400350; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 351,
   "name": "Function digital Input 3",
   "description": "Modbus 400351; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 352,
   "name": "Function digital Input 4",
   "description": "Modbus 400352; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 353,
   "name": "Volume button sound",
   "description": "Modbus 400353; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 354,
   "name": "Direct key 16",
   "description": "Modbus 400354; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 355,
   "name": "Direct key 17",
   "description": "Modbus 400355; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 356,
   "name": "Direct key 18",
   "description": "Modbus 400356; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 357,
   "name": "Direct key 19",
   "description": "Modbus 400357; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 358,
   "name": "Direct key 20",
   "description": "Modbus 400358; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 359,
   "name": "Direct key 21",
   "description": "Modbus 400359; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 360,
   "name": "Direct key 22",
   "description": "Modbus 400360; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 361,
   "name": "Direct key 23",
   "description": "Modbus 400361; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 362,
   "name": "Direct key 24",
   "description": "Modbus 400362; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 363,
   "name": "Direct key 25",
   "description": "Modbus 400363; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 364,
   "name": "Direct key 26",
   "description": "Modbus 400364; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 365,
   "name": "Direct key 27",
   "description": "Modbus 400365; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 366,
   "name": "Direct key 28",
   "description": "Modbus 400366; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 367,
   "name": "Direct key 29",
   "description": "Modbus 400367; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 368,
   "name": "Direct key 30",
   "description": "Modbus 400368; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 369,
   "name": "Direct key 31",
   "description": "Modbus 400369; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 370,
   "name": "Standardscreen",
   "description": "Modbus 400370; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 371,
   "name": "Parameterversion (read only)",
   "description": "Modbus 400371; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 372,
   "name": "FanCoil OFF / AUTO only",
   "description": "Modbus 400372; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 373,
   "name": "Display temperature",
   "description": "Modbus 000001; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 374,
   "name": "Display humidity",
   "description": "Modbus 000002; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 375,
   "name": "Resolution temperature",
   "description": "Modbus 000003; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 376,
   "name": "Resolution humidity",
   "description": "Modbus 000004; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 377,
   "name": "Activate device first",
   "description": "Modbus 000005; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 378,
   "name": "Unit temperature",
   "description": "Modbus 000006; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 379,
   "name": "Fan stage after reset",
   "description": "Modbus 000007; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 380,
   "name": "Display room occupancy after reset",
   "description": "Modbus 000008; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 381,
   "name": "Show menu line 1",
   "description": "Modbus 000009; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 382,
   "name": "Show menu line 2",
   "description": "Modbus 000010; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 383,
   "name": "Show menu line 3",
   "description": "Modbus 000011; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 384,
   "name": "Show menu line 4",
   "description": "Modbus 000012; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 385,
   "name": "Show menu line 5",
   "description": "Modbus 000013; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 386,
   "name": "Display stage in auto mode",
   "description": "Modbus 000014; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 387,
   "name": "External value 1: Resolution",
   "description": "Modbus 000015; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 388,
   "name": "External value 1: Show",
   "description": "Modbus 000016; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 389,
   "name": "External value 2: Resolution",
   "description": "Modbus 000017; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 390,
   "name": "External value 2: Show",
   "description": "Modbus 000018; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 391,
   "name": "External value 3: Resolution",
   "description": "Modbus 000019; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 392,
   "name": "External value 3: Show",
   "description": "Modbus 000020; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 393,
   "name": "External value 4: Resolution",
   "description": "Modbus 000021; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 394,
   "name": "External value 4: Show",
   "description": "Modbus 000022; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 395,
   "name": "External value 5: Resolution",
   "description": "Modbus 000023; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 396,
   "name": "External value 5: Show",
   "description": "Modbus 000024; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 397,
   "name": "External value 6: Resolution",
   "description": "Modbus 000025; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 398,
   "name": "External value 6 Show",
   "description": "Modbus 000026; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 399,
   "name": "Set point 1: Resolution",
   "description": "Modbus 000027; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 400,
   "name": "Set point 1: Display with adjustment",
   "description": "Modbus 000028; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 401,
   "name": "Set point 1: Display effective value",
   "description": "Modbus 000029; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 402,
   "name": "Set point 1: Display offset value",
   "description": "Modbus 000030; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 403,
   "name": "Set point 2: Resolution",
   "description": "Modbus 000031; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 404,
   "name": "Set point 2: Display with adjustment",
   "description": "Modbus 000032; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 405,
   "name": "Set point 2: Display effective value",
   "description": "Modbus 000033; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 406,
   "name": "Set point 2: Display offset value",
   "description": "Modbus 000034; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 407,
   "name": "Set point 3: Resolution",
   "description": "Modbus 000035; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 408,
   "name": "Set point 3: Display with adjustment",
   "description": "Modbus 000036; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 409,
   "name": "Set point 3: Display effective value",
   "description": "Modbus 000037; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 410,
   "name": "Set point 3: Display offset value",
   "description": "Modbus 000038; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 411,
   "name": "Set point 4: Resolution",
   "description": "Modbus 000039; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 412,
   "name": "Set point 4: Display with adjustment",
   "description": "Modbus 000040; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 413,
   "name": "Set point 4: Display effective value",
   "description": "Modbus 000041; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 414,
   "name": "Set point 4: Display offset value",
   "description": "Modbus 000042; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 415,
   "name": "Set point 5: Resolution",
   "description": "Modbus 000043; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 416,
   "name": "Set point 5: Display with adjustment",
   "description": "Modbus 000044; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 417,
   "name": "Set point 5: Display effective value",
   "description": "Modbus 000045; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 418,
   "name": "Set point 5: Display offset value",
   "description": "Modbus 000046; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 419,
   "name": "Set point 6: Resolution",
   "description": "Modbus 000047; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 420,
   "name": "Set point 6: Display with adjustment",
   "description": "Modbus 000048; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 421,
   "name": "Set point 6: Display effective value",
   "description": "Modbus 000049; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 422,
   "name": "Set point 6: Display offset value",
   "description": "Modbus 000050; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 423,
   "name": "Selection if indices will be shown in the LCD.",
   "description": "Modbus 000051; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 424,
   "name": "Selection if indices will be shown even if their value is 0.",
   "description": "Modbus 000052; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 425,
   "name": "Current state of key 1...16",
   "description": "Modbus 300769; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 426,
   "name": "State of key since last call-off 1...16",
   "description": "Modbus 300770; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 427,
   "name": "State light function",
   "description": "Modbus 300771; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 428,
   "name": "Current state of + dimming key",
   "description": "Modbus 300772; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 429,
   "name": "Current state of - dimming key",
   "description": "Modbus 300773; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 430,
   "name": "State shutter/blind function",
   "description": "Modbus 300774; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 431,
   "name": "Current state of + Shutter/blind key",
   "description": "Modbus 300775; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 432,
   "name": "Current state of - Shutter/blind key",
   "description": "Modbus 300776; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 433,
   "name": "State Universal function",
   "description": "Modbus 300777; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 434,
   "name": "Current Offset for set point 1",
   "description": "Modbus 300778; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 435,
   "name": "Set point effective 1 (Default set point + set point offset)",
   "description": "Modbus 300779; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 436,
   "name": "Current Offset for set point 2",
   "description": "Modbus 300780; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 437,
   "name": "Set point effective 2 (Default set point + set point offset)",
   "description": "Modbus 300781; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 438,
   "name": "Current Offset for set point 3",
   "description": "Modbus 300782; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 439,
   "name": "Set point effective 3 (Default set point + set point offset)",
   "description": "Modbus 300783; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 440,
   "name": "Current Offset for set point 4",
   "description": "Modbus 300784; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 441,
   "name": "Set point effective 4 (Default set point + set point offset)",
   "description": "Modbus 300785; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 442,
   "name": "Current Offset for set point 5",
   "description": "Modbus 300786; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 443,
   "name": "Set point effective 5 (Default set point + set point offset)",
   "description": "Modbus 300787; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 444,
   "name": "Current Offset for set point 6",
   "description": "Modbus 300788; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 445,
   "name": "Set point effective 6 (Default set point + set point offset)",
   "description": "Modbus 300789; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 446,
   "name": "Temperature internal sensor",
   "description": "Modbus 300790; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 447,
   "name": "Humidity internal sensor",
   "description": "Modbus 300791; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 448,
   "name": "Current fan stage",
   "description": "Modbus 300792; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 449,
   "name": "Current room occupancy",
   "description": "Modbus 300793; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 450,
   "name": "Control variable Heating Controller 1",
   "description": "Modbus 300794; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 451,
   "name": "Control variable Cooling Controller 1",
   "description": "Modbus 300795; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 452,
   "name": "Output register PWM-signal Heating Controller 1",
   "description": "Modbus 300796; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 453,
   "name": "Output register PWM-signal Cooling Controller 1",
   "description": "Modbus 300797; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 454,
   "name": "Output controller mode Controller 1",
   "description": "Modbus 300798; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 455,
   "name": "Output register fan stage Controller 1",
   "description": "Modbus 300799; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 456,
   "name": "Effective controller set point Controller1",
   "description": "Modbus 300800; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 457,
   "name": "Control variable Heating Controller 2",
   "description": "Modbus 300801; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 458,
   "name": "Control variable Cooling Controller 2",
   "description": "Modbus 300802; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 459,
   "name": "Output register PWM-Signal Heating Controller 2",
   "description": "Modbus 300803; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 460,
   "name": "Output register PWM-Signal Cooling Controller 2",
   "description": "Modbus 300804; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 461,
   "name": "Output Controller mode Controller 2",
   "description": "Modbus 300805; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 462,
   "name": "Output register Fan Stage Controller 2",
   "description": "Modbus 300806; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 463,
   "name": "Effective controller set point Controller2",
   "description": "Modbus 300807; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 464,
   "name": "Control variable Heating Controller 3",
   "description": "Modbus 300808; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 465,
   "name": "Control variable Cooling Controller 3",
   "description": "Modbus 300809; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 466,
   "name": "Output register PWM-Signal Heating Controller 3",
   "description": "Modbus 300810; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 467,
   "name": "Output register PWM-Signal Cooling Controller 3",
   "description": "Modbus 300811; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 468,
   "name": "Output Controller mode Controller 3",
   "description": "Modbus 300812; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 469,
   "name": "Output register Fan Stage Controller 3",
   "description": "Modbus 300813; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 470,
   "name": "Effective controller set point Controller3",
   "description": "Modbus 300814; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 471,
   "name": "Control variable Heating Controller 4",
   "description": "Modbus 300815; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 472,
   "name": "Control variable Cooling Controller 4",
   "description": "Modbus 300816; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 473,
   "name": "Output register PWM-Signal Heating Controller 4",
   "description": "Modbus 300817; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 474,
   "name": "Output register PWM-Signal Cooling Controller 4",
   "description": "Modbus 300818; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 475,
   "name": "Output Controller mode Controller 4",
   "description": "Modbus 300819; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 476,
   "name": "Output register Fan Stage Controller 4",
   "description": "Modbus 300820; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 477,
   "name": "Effective controller set point Controller4",
   "description": "Modbus 300821; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 478,
   "name": "Control variable Heating Controller 5",
   "description": "Modbus 300822; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 479,
   "name": "Control variable Cooling Controller 5",
   "description": "Modbus 300823; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 480,
   "name": "Output register PWM-Signal Heating Controller 5",
   "description": "Modbus 300824; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 481,
   "name": "Output register PWM-Signal Cooling Controller 5",
   "description": "Modbus 300825; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 482,
   "name": "Output Controller mode Controller 5",
   "description": "Modbus 300826; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 483,
   "name": "Output register Fan Stage Controller 5",
   "description": "Modbus 300827; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 484,
   "name": "Effective controller set point Controller5",
   "description": "Modbus 300828; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 485,
   "name": "Control variable Heating Controller 6",
   "description": "Modbus 300829; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 486,
   "name": "Control variable Cooling Controller 6",
   "description": "Modbus 300830; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 487,
   "name": "Output register PWM-Signal Heating Controller 6",
   "description": "Modbus 300831; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 488,
   "name": "Output register PWM-Signal Cooling Controller 6",
   "description": "Modbus 300832; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 489,
   "name": "Output Controller mode Controller 6",
   "description": "Modbus 300833; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 490,
   "name": "Output register Fan Stage Controller 6",
   "description": "Modbus 300834; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 491,
   "name": "Effective controller set point Controller6",
   "description": "Modbus 400835; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 492,
   "name": "Digital Input1",
   "description": "Modbus 400836; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 493,
   "name": "Digital Input2",
   "description": "Modbus 400837; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 494,
   "name": "Digital Input3",
   "description": "Modbus 400838; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 495,
   "name": "Digital Input4",
   "description": "Modbus 400839; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 496,
   "name": "Current state of key 16...31",
   "description": "Modbus 400840; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 497,
   "name": "State of key since last call-off 16...31",
   "description": "Modbus 400841; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 498,
   "name": "Input seconds",
   "description": "Modbus 401025; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 499,
   "name": "Input minutes",
   "description": "Modbus 401026; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 500,
   "name": "Input hours",
   "description": "Modbus 401027; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 501,
   "name": "Input day of month",
   "description": "Modbus 401028; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 502,
   "name": "Input month",
   "description": "Modbus 401029; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 503,
   "name": "Input year",
   "description": "Modbus 401030; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 504,
   "name": "Default fan stage",
   "description": "Modbus 401031; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 505,
   "name": "Default occupancy",
   "description": "Modbus 401032; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 506,
   "name": "Bypass time re-trigger",
   "description": "Modbus 401033; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 507,
   "name": "Show message",
   "description": "Modbus 401034; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 508,
   "name": "External temperature default",
   "description": "Modbus 401035; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 509,
   "name": "External humidity default",
   "description": "Modbus 401036; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 510,
   "name": "Feedback status light function",
   "description": "Modbus 401037; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 511,
   "name": "Feedback shutter/blind function",
   "description": "Modbus 401038; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 512,
   "name": "Feedback universal function",
   "description": "Modbus 401039; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 513,
   "name": "External value1",
   "description": "Modbus 401040; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 514,
   "name": "External value2",
   "description": "Modbus 401041; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 515,
   "name": "External value3",
   "description": "Modbus 401042; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 516,
   "name": "External value4",
   "description": "Modbus 401043; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 517,
   "name": "External value5",
   "description": "Modbus 401044; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 518,
   "name": "External value6",
   "description": "Modbus 401045; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 519,
   "name": "Offset set point1",
   "description": "Modbus 401046; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 520,
   "name": "Standard set point1",
   "description": "Modbus 401047; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 521,
   "name": "Offset set point2",
   "description": "Modbus 401048; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 522,
   "name": "Basis set point2",
   "description": "Modbus 401049; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 523,
   "name": "Offset set point3",
   "description": "Modbus 401050; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 524,
   "name": "Basis set point3",
   "description": "Modbus 401051; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 525,
   "name": "Offset set point4",
   "description": "Modbus 401052; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 526,
   "name": "Basis set point4",
   "description": "Modbus 401053; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 527,
   "name": "Offset set point5",
   "description": "Modbus 401054; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 528,
   "name": "Basis set point5",
   "description": "Modbus 401055; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 529,
   "name": "Offset set point6",
   "description": "Modbus 401056; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 530,
   "name": "Basis set point6",
   "description": "Modbus 401057; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 531,
   "name": "Actual value Controller 1",
   "description": "Modbus 401058; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 532,
   "name": "Occupancy Controller 1",
   "description": "Modbus 401059; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 533,
   "name": "Energy hold-off Controller 1",
   "description": "Modbus 401060; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 534,
   "name": "Controller mode Controller 1",
   "description": "Modbus 401061; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 535,
   "name": "Base set point Controller 1",
   "description": "Modbus 401062; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 536,
   "name": "Dew point Controller 1",
   "description": "Modbus 401063; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 537,
   "name": "Trigger bypass time Controller 1",
   "description": "Modbus 401064; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 538,
   "name": "Default set point offset Controller 1",
   "description": "Modbus 401065; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 539,
   "name": "Actual value Controller 2",
   "description": "Modbus 401066; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 540,
   "name": "Occupancy Controller 2",
   "description": "Modbus 401067; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 541,
   "name": "Energy hold-off Controller 2",
   "description": "Modbus 401068; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 542,
   "name": "Controller mode Controller 2",
   "description": "Modbus 401069; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 543,
   "name": "Base set point Controller 2",
   "description": "Modbus 401070; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 544,
   "name": "Dew point Controller 2",
   "description": "Modbus 401071; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 545,
   "name": "Trigger bypass time Controller 2",
   "description": "Modbus 401072; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 546,
   "name": "Default set point offset Controller 2",
   "description": "Modbus 401073; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 547,
   "name": "Actual value Controller 3",
   "description": "Modbus 401074; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 548,
   "name": "Occupancy Controller 3",
   "description": "Modbus 401075; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 549,
   "name": "Energy hold-off Controller 3",
   "description": "Modbus 401076; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 550,
   "name": "Controller mode Controller 3",
   "description": "Modbus 401077; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 551,
   "name": "Base set point Controller 3",
   "description": "Modbus 401078; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 552,
   "name": "Dew point Controller 3",
   "description": "Modbus 401079; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 553,
   "name": "Trigger bypass time Controller 3",
   "description": "Modbus 401080; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 554,
   "name": "Default set point offset Controller 3",
   "description": "Modbus 401081; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 555,
   "name": "Actual value Controller 4",
   "description": "Modbus 401082; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 556,
   "name": "Occupancy Controller 4",
   "description": "Modbus 401083; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 557,
   "name": "Energy hold-off Controller 4",
   "description": "Modbus 401084; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 558,
   "name": "Controller mode Controller 4",
   "description": "Modbus 401085; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 559,
   "name": "Standard set point Controller 4",
   "description": "Modbus 401086; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 560,
   "name": "Dew point Controller 4",
   "description": "Modbus 401087; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 561,
   "name": "Trigger bypass time Controller 4",
   "description": "Modbus 401088; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 562,
   "name": "Default set point offset Controller 4",
   "description": "Modbus 401089; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 563,
   "name": "Actual value Controller 5",
   "description": "Modbus 401090; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 564,
   "name": "Occupancy Controller 5",
   "description": "Modbus 401091; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 565,
   "name": "Energy hold-off Controller 5",
   "description": "Modbus 401092; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 566,
   "name": "Controller mode Controller 5",
   "description": "Modbus 401093; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 567,
   "name": "Base set point Controller 5",
   "description": "Modbus 401094; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 568,
   "name": "Dew point Controller 5",
   "description": "Modbus 401095; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 569,
   "name": "Trigger bypass time Controller 5",
   "description": "Modbus 401096; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 570,
   "name": "Default set point offset Controller 5",
   "description": "Modbus 401097; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 571,
   "name": "Actual value Controller 6",
   "description": "Modbus 401098; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 572,
   "name": "Occupancy Controller 6",
   "description": "Modbus 401099; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 573,
   "name": "Energy hold-off Controller 6",
   "description": "Modbus 401100; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 574,
   "name": "Controller mode Controller 6",
   "description": "Modbus 401101; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 575,
   "name": "Base set point Controller 6",
   "description": "Modbus 401102; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 576,
   "name": "Dew point Controller 6",
   "description": "Modbus 401103; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 577,
   "name": "Trigger bypass time Controller 6",
   "description": "Modbus 401104; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 578,
   "name": "Default set point offset Controller 6",
   "description": "Modbus 401105; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 579,
   "name": "Restart 1",
   "description": "Modbus 401106; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 580,
   "name": "Restart 2",
   "description": "Modbus 401107; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 581,
   "name": "Symbol failure",
   "description": "Modbus 000257; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 582,
   "name": "Symbol heating",
   "description": "Modbus 000258; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 583,
   "name": "Symbol cooling",
   "description": "Modbus 000259; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 584,
   "name": "Symbol window",
   "description": "Modbus 000260; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 585,
   "name": "Symbol dew point",
   "description": "Modbus 000261; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 586,
   "name": "Key lock",
   "description": "Modbus 000262; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 587,
   "name": "Lock room occupancy",
   "description": "Modbus 000263; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 588,
   "name": "Lock fan stages",
   "description": "Modbus 000264; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 589,
   "name": "Lock set points",
   "description": "Modbus 000265; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 590,
   "name": "Activation of TFT- and key- illumination",
   "description": "Modbus 000266; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/contemporary-controls/basgatewaylx-thermokon-thanos",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}