 "manufacturer": "Contemporary Controls",
 "manufacturer_slug": "contemporary-controls",
 "model": "Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX",
 "short_model": "BASgatewayLX Acromag 961EN/962EN",
 "model_slug": "basgatewaylx-acromag-961en-962en",
 "aliases": [
  "961EN",
  "962EN",
  "961EN-4006",
  "962EN-4006",
  "Acromag EtherStax"
 ],
 "equipment_type": "I/O module (analog inputs)",
 "applies_to": "Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.",
 "summary": "Gateway profile for the Acromag 961EN/962EN: 139 objects (133 AI, 4 AO, 2 BI), 18 polled by default (status, value and count for channels 0-5). Module settings, calibration registers, ranges and min/max/average values are unpolled.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "Built from Contemporary Controls' BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/961_962EN_MODBUS_EXTRACT.pdf).",
  "Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.",
  "Only 18 of the 139 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say \"not polled by default\".",
  "The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.",
  "Names use the letter O for zero in channel 00/01 (CHOO, CHOI) as printed."
 ],
 "source": {
  "title": "BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a",
  "doc_number": "Acromag_961_962EN_Module_a_LX.csv",
  "revision_date": null,
  "url": "https://www.ccontrols.com/support/dp/Acromag_961_962EN_Module.zip"
 },
 "integration": {
  "summary": "Map channel 0 value, channel 1 value and channel 2 value first. The listed objects are read-only.",
  "minimum_points": [
   {
    "ref": "AI 11",
    "name": "CHOO Value",
    "why": "Channel 0 value"
   },
   {
    "ref": "AI 12",
    "name": "CHOI Value",
    "why": "Channel 1 value"
   },
   {
    "ref": "AI 13",
    "name": "CH02 Value",
    "why": "Channel 2 value"
   },
   {
    "ref": "AI 14",
    "name": "CH03 Value",
    "why": "Channel 3 value"
   },
   {
    "ref": "AI 15",
    "name": "CH04 Value",
    "why": "Channel 4 value"
   },
   {
    "ref": "AI 16",
    "name": "CH05 Value",
    "why": "Channel 5 value"
   },
   {
    "ref": "AI 5",
    "name": "CHOO Status",
    "why": "Channel 0 status"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.",
   "One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled."
  ],
  "gotchas": [
   "Calibration access and the span/zero calibration registers (AO 25, AO 138, AO 139) are unpolled; leave them that way.",
   "Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 1,
   "name": "Wink Mode Flag",
   "description": "Modbus 300001 bit 14; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Default Mode Flag",
   "description": "Modbus 300001 bit 13; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Input Range (CH 0 1 2 )",
   "description": "Modbus 300002; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Input Range (CH 3 4 5 )",
   "description": "Modbus 300003; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "CHOO Status",
   "description": "Modbus 300004",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "CHOI Status",
   "description": "Modbus 300005",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "CH02 Status",
   "description": "Modbus 300006",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "CH03 Status",
   "description": "Modbus 300007",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "CH04 Status",
   "description": "Modbus 300008",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "CH05 Status",
   "description": "Modbus 300009",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "CHOO Value",
   "description": "Modbus 300010",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "CHOI Value",
   "description": "Modbus 300011",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "CH02 Value",
   "description": "Modbus 300012",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "CH03 Value",
   "description": "Modbus 300013",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "CH04 Value",
   "description": "Modbus 300014",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "CH05 Value",
   "description": "Modbus 300015",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "CHOO Count",
   "description": "Modbus 300016",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "CHOI Count",
   "description": "Modbus 300017",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "CH02 Count",
   "description": "Modbus 300018",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "CH03 Count",
   "description": "Modbus 300019",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "CH04 Count",
   "description": "Modbus 300020",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "CH05 Count",
   "description": "Modbus 300021",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 23,
   "name": "Input Range (CH 0 1 2 ) R _W",
   "description": "Modbus 400001; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Input Range (CH 3 4 5 ) R_W",
   "description": "Modbus 400002; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "Calibration Access",
   "description": "Modbus 400014; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "CHO Cal Hi Range 0",
   "description": "Modbus 400022; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "CHO Cal Lo Range 0",
   "description": "Modbus 400023; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "CHO Cal Hi Range 1",
   "description": "Modbus 400024; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "CHO Cal Lo Range 1",
   "description": "Modbus 400025; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "CHO Cal Hi Range 2",
   "description": "Modbus 400026; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "CHO Cal Lo Range 2",
   "description": "Modbus 400027; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "CHO Cal Hi Range 3",
   "description": "Modbus 400028; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "CHO Cal Lo Range 3",
   "description": "Modbus 400029; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "CHO Cal Hi Range 4",
   "description": "Modbus 400030; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "CHO Cal Lo Range 4",
   "description": "Modbus 400031; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "CHO Cal Hi Range 5",
   "description": "Modbus 400032; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "CHO Cal Lo Range 5",
   "description": "Modbus 400033; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "CHO Cal Hi Range 6",
   "description": "Modbus 400034; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "CHO Cal Lo Range 6",
   "description": "Modbus 400035; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "CHO Cal Hi Range 7",
   "description": "Modbus 400036; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "CHO Cal Lo Range 7",
   "description": "Modbus 400037; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "CH1 Cal Hi Range 0",
   "description": "Modbus 400038; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "CH1 Cal Lo Range 0",
   "description": "Modbus 400039; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "CH1 Cal Hi Range 1",
   "description": "Modbus 400040; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "CH1 Cal Lo Range 1",
   "description": "Modbus 400041; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "CH1 Cal Hi Range 2",
   "description": "Modbus 400042; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "CH1 Cal Lo Range 2",
   "description": "Modbus 400043; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "CH1 Cal Hi Range 3",
   "description": "Modbus 400044; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "CH1 Cal Lo Range 3",
   "description": "Modbus 400045; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "CH1 Cal Hi Range 4",
   "description": "Modbus 400046; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "CH1 Cal Lo Range 4",
   "description": "Modbus 400047; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "CH1 Cal Hi Range 5",
   "description": "Modbus 400048; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "CH1 Cal Lo Range 5",
   "description": "Modbus 400049; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "CH1 Cal Hi Range 6",
   "description": "Modbus 400050; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "CH1 Cal Lo Range 6",
   "description": "Modbus 400051; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "CH1 Cal Hi Range 7",
   "description": "Modbus 400052; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "CH1 Cal Lo Range 7",
   "description": "Modbus 400053; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "CH2 Cal Hi Range 0",
   "description": "Modbus 400054; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "CH2 Cal Lo Range 0",
   "description": "Modbus 400055; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "CH2 Cal Hi Range 1",
   "description": "Modbus 400056; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "CH2 Cal Lo Range 1",
   "description": "Modbus 400057; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "CH2 Cal Hi Range 2",
   "description": "Modbus 400058; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "CH2 Cal Lo Range 2",
   "description": "Modbus 400059; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "CH2 Cal Hi Range 3",
   "description": "Modbus 400060; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "CH2 Cal Lo Range 3",
   "description": "Modbus 400061; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "CH2 Cal Hi Range 4",
   "description": "Modbus 400062; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "CH2 Cal Lo Range 4",
   "description": "Modbus 400063; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "CH2 Cal Hi Range 5",
   "description": "Modbus 400064; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "CH2 Cal Lo Range 5",
   "description": "Modbus 400065; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "CH2 Cal Hi Range 6",
   "description": "Modbus 400066; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "CH2 Cal Lo Range 6",
   "description": "Modbus 400067; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "CH2 Cal Hi Range 7",
   "description": "Modbus 400068; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "CH2 Cal Lo Range 7",
   "description": "Modbus 400069; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "CH3 Cal Hi Range 0",
   "description": "Modbus 400070; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "CH3 Cal Lo Range 0",
   "description": "Modbus 400071; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "CH3 Cal Hi Range 1",
   "description": "Modbus 400072; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "CH3 Cal Lo Range 1",
   "description": "Modbus 400073; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "CH3 Cal Hi Range 2",
   "description": "Modbus 400074; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "CH3 Cal Lo Range 2",
   "description": "Modbus 400075; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "CH3 Cal Hi Range 3",
   "description": "Modbus 400076; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "CH3 Cal Lo Range 3",
   "description": "Modbus 400077; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "CH3 Cal Hi Range 4",
   "description": "Modbus 400078; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "CH3 Cal Lo Range 4",
   "description": "Modbus 400079; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "CH3 Cal Hi Range 5",
   "description": "Modbus 400080; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "CH3 Cal Lo Range 5",
   "description": "Modbus 400081; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "CH3 Cal Hi Range 6",
   "description": "Modbus 400082; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "CH3 Cal Lo Range 6",
   "description": "Modbus 400083; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "CH3 Cal Hi Range 7",
   "description": "Modbus 400084; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "CH3 Cal Lo Range 7",
   "description": "Modbus 400085; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "CH4 Cal Hi Range 0",
   "description": "Modbus 400086; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "CH4 Cal Lo Range 0",
   "description": "Modbus 400087; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "CH4 Cal Hi Range 1",
   "description": "Modbus 400088; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "CH4 Cal Lo Range 1",
   "description": "Modbus 400089; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "CH4 Cal Hi Range 2",
   "description": "Modbus 400090; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "CH4 Cal Lo Range 2",
   "description": "Modbus 400091; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "CH4 Cal Hi Range 3",
   "description": "Modbus 400092; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "CH4 Cal Lo Range 3",
   "description": "Modbus 400093; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "CH4 Cal Hi Range 4",
   "description": "Modbus 400094; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "CH4 Cal Lo Range 4",
   "description": "Modbus 400095; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "CH4 Cal Hi Range 5",
   "description": "Modbus 400096; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "CH4 Cal Lo Range 5",
   "description": "Modbus 400097; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "CH4 Cal Hi Range 6",
   "description": "Modbus 400098; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "CH4 Cal Lo Range 6",
   "description": "Modbus 400099; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "CH4 Cal Hi Range 7",
   "description": "Modbus 400100; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "CH4 Cal Lo Range 7",
   "description": "Modbus 400101; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "CH5 Cal Hi Range 0",
   "description": "Modbus 400102; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "CH5 Cal Lo Range 0",
   "description": "Modbus 400103; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "CH5 Cal Hi Range 1",
   "description": "Modbus 400104; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "CH5 Cal Lo Range 1",
   "description": "Modbus 400105; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "CH5 Cal Hi Range 2",
   "description": "Modbus 400106; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "CH5 Cal Lo Range 2",
   "description": "Modbus 400107; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "CH5 Cal Hi Range 3",
   "description": "Modbus 400108; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "CH5 Cal Lo Range 3",
   "description": "Modbus 400109; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "CH5 Cal Hi Range 4",
   "description": "Modbus 400110; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 115,
   "name": "CH5 Cal Lo Range 4",
   "description": "Modbus 400111; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "CH5 Cal Hi Range 5",
   "description": "Modbus 400112; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 117,
   "name": "CH5 Cal Lo Range 5",
   "description": "Modbus 400113; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "CH5 Cal Hi Range 6",
   "description": "Modbus 400114; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "CH5 Cal Lo Range 6",
   "description": "Modbus 400115; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "CH5 Cal Hi Range 7",
   "description": "Modbus 400116; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "CH5 Cal Lo Range 7",
   "description": "Modbus 400117; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "Ideal Range 0 Hi",
   "description": "Modbus 400118; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "Ideal Range 0 Lo",
   "description": "Modbus 400119; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "Ideal Range 1 Hi",
   "description": "Modbus 400120; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "Ideal Range 1 Lo",
   "description": "Modbus 400121; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "Ideal Range 2 Hi",
   "description": "Modbus 400122; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "Ideal Range 2 Lo",
   "description": "Modbus 400123; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "Ideal Range 3 Hi",
   "description": "Modbus 400124; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "Ideal Range 3 Lo",
   "description": "Modbus 400125; not polled by default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "Ideal Range 4 Hi",
   "description": "Modbus 400126; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "Ideal Range 4 Lo",
   "description": "Modbus 400127; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "Ideal Range 5 Hi",
   "description": "Modbus 400128; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "Ideal Range 5 Lo",
   "description": "Modbus 400129; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "Ideal Range 6 Hi",
   "description": "Modbus 400130; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "Ideal Range 6 Lo",
   "description": "Modbus 400131; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "Ideal Range 7 Hi",
   "description": "Modbus 400132; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "Ideal Range 7 Lo",
   "description": "Modbus 400133; not polled by default",
   "units": "mV",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 138,
   "name": "Span Cal Register",
   "description": "Modbus 400136; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 139,
   "name": "Zero Cal Register",
   "description": "Modbus 400137; not polled by default",
   "units": "",
   "access": "C",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/contemporary-controls/basgatewaylx-acromag-961en-962en",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}