  4. AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points

Air-cooled screw chiller (via BACnet translator) · BACnet points list

Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points BACnet points list

Updated 12 November 2026

Short answer

With the BACnet/Modbus Translator option the older AquaForce 30XV exposes a short CCN point map on BACnet MS/TP: start/stop, occupancy, emergency stop, setpoint select and control point commands, capacity, water, refrigerant and outdoor temperatures, pressures, input switches, cooling and limit setpoints, and two occupancy time schedules.

This page lists 69 BACnet objects for the Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points
Equipment
Air-cooled screw chiller (via BACnet translator)
Equipment type
Chillers
BACnet objects
69 (16 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
30XV, AquaForce 30XV, 30XV-2T, 30XV BACnet translator, BACnet/Modbus Translator
Source document
AquaForce 30XV140-500 Controls, Start-Up, Operation, Service and Troubleshooting, Appendix D BACnet/Modbus Translator Points · 30XV-2T (Cat. 04-53300196-01) · rev. 9-17
Download CSV 69 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points

Integration in brief

Select Network control on the chiller, then command BV 0 start/stop and BV 1 occupancy through the translator. Read control type, capacity and the water temperatures; write setpoints AV 45 onward and the demand limit AV 6.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0CHIL_S_SNetwork start/stop commandWrite
BV 1CHIL_OCCNetwork occupied commandWrite
BV 3EMSTOPEmergency stopWrite
AV 45csp1Cooling setpoint 1Write
AV 6DEM_LIMActive demand limit (writable)Write
AV 0CTRL_TYPControl type: Local, Network or RemoteRead
AV 3CAP_TPercent total capacityRead
AV 9COOL_LWTCooler leaving fluid temperatureRead
AV 8COOL_EWTCooler entering fluid temperatureRead

Enable & remote start

The chiller must be in Network control (CTRL_TYP = 1) for the network commands to act.

Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

69 of 69 shown
Type
AnalogBinaryOther
Access
Show
Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points BACnet Points List
DescriptionStates
AVmin0CTRL_TYPControl typeRead0=Local, 1=Network, 2=Remote
BVmin0CHIL_S_SNet.: Cmd Start/StopWrite
BVmin1CHIL_OCCNet.: Cmd OccupiedWrite
AV1min_leftMinutes Left for StartRead
AV2SP_SELSetpoint SelectWrite
BV2SP_OCCSetpoint Occupied?Write
AVmin3CAP_TPercent Total CapacityRead
AV4SPCurrent SetpointRead
AV5CTRL_PNTControl PointWrite
BVmin3EMSTOPEmergency StopWrite
AVmin6DEM_LIMActive Demand Limit ValWrite
AV7min_limDemand Limit MinimumRead
AVmin8COOL_EWTCooler Entering FluidRead
AVmin9COOL_LWTCooler Leaving FluidRead
AV10OATOutdoor Air TemperatureRead
AV11SCT_ASaturated Cond Tmp cir ARead
AV12SST_ASaturated Suction Temp ARead
AV13SLT_ASaturated Liquid Temp ARead
AV14SUCT_ACompressor Suction Tmp ARead
AV15DGT_ADischarge Gas Temp cir ARead
AV16CP_TMP_AMotor Temperature cir ARead
AV17ECO_T_AEXV Eco. Tmp cir ARead
AV18LIQ_T_ALiquid Temperature ARead
AV19SCT_BSaturated Cond Tmp cir BRead
AV20SST_BSaturated Suction Temp BRead
AV21SLT_BSaturated Liquid Temp BRead
AV22SUCT_BCompressor Suction Tmp BRead
AV23DGT_BDischarge Gas Temp cir BRead
AV24CP_TMP_BMotor Temperature cir BRead
AV25ECO_T_BEXV Eco. Tmp cir BRead
AV26LIQ_T_BLiquid Temperature BRead
AV27SPACETMPOptional Space TempRead
AV28CHWSTEMPCHWS TemperatureRead
AV29DP_ADischarge Pressure ARead
AV30SP_AMain Suction Pressure ARead
AV31OP_AOil Pressure ARead
AV32DOP_AOil Pressure DifferenceARead
AV33ECO_P_AEconomizer Pressure ARead
AV34LIQ_P_ALiquid Pressure ARead
AV35DP_BDischarge Pressure BRead
AV36SP_BMain Suction Pressure BRead
AV37OP_BOil Pressure BRead
AV38DOP_BOil Pressure DifferenceBRead
AV39ECO_P_BEconomizer Pressure BRead
AV40LIQ_P_BLiquid Pressure BRead
BV4ONOFF_SWRemote On/Off SwitchRead
BV5SETP_SWRemote Setpoint SwitchRead
BV6LIM_SW1Limit Switch 1Read
BV7LIM_SW2Limit Switch 2Read
BV8OIL_L_AOil Level Input ARead
BV9OIL_L_BOil Level Input BRead
AV41SP_RESETSetpoint Reset ControlRead
AV42LIM_ANAL4-20mA Limit signalRead
AV43leak_vLeakage Detector 1 valRead
AV44leak_2_vLeakage Detector 2 valRead
BV10REM_LOCKCustomer InterlockRead
BV11ICE_SWIce Done Storage SwitchRead
BV12OCC_OVSWOccupied Override SwitchRead
BV13HEATR_SWCooler Heater DetectorRead
BV14bacdonglBACnet dongleRead
AVmin45csp1Cooling Setpoint 1Write
AV46csp2Cooling Setpoint 2Write
AV47ice_spCooling Ice SetpointWrite
AV48cramp_spCooling Ramp LoadingWrite
AV49lim_sp1Switch Limit Setpoint 1Write
AV50lim_sp2Switch Limit Setpoint 2Write
AV51lim_sp3Switch Limit Setpoint 3Write
SCH0OCC1P01STime schedule 1Write
SCH1OCC2P02STime schedule 2Write
Object ID lookup: Carrier AquaForce 30XV 140-500 BACnet/Modbus Translator points point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points

How many BACnet points does the Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points have?

This list has 69 BACnet objects: 52 analog values, 15 binary values, 2 schedules. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points BACnet points are writable?

16 of the 69 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points BACnet documentation?

The source is AquaForce 30XV140-500 Controls, Start-Up, Operation, Service and Troubleshooting, Appendix D BACnet/Modbus Translator Points (30XV-2T (Cat. 04-53300196-01)), revision 9-17, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0A/30XV-2T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points?

Start with BV 0 CHIL_S_S (Network start/stop command); BV 1 CHIL_OCC (Network occupied command); BV 3 EMSTOP (Emergency stop); AV 45 csp1 (Cooling setpoint 1); AV 6 DEM_LIM (Active demand limit (writable)); AV 0 CTRL_TYP (Control type: Local, Network or Remote); AV 3 CAP_T (Percent total capacity); AV 9 COOL_LWT (Cooler leaving fluid temperature); AV 8 COOL_EWT (Cooler entering fluid temperature).

How do I enable BMS control of the Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points?

The chiller must be in Network control (CTRL_TYP = 1) for the network commands to act.

How do I check these points on the real AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaForce 30XV140-500 Controls, Start-Up, Operation, Service and Troubleshooting, Appendix D BACnet/Modbus Translator Points · 30XV-2T (Cat. 04-53300196-01) · rev. 9-17. Object names, instances and units are reproduced as published; descriptions are our own.