Air-cooled screw chiller controller · BACnet points list

Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points BACnet points list

Updated 12 November 2026

Short answer

The older AquaForce 30XV with the Touch Pilot controller has a native BACnet IP object list: Analog Values for temperatures, pressures, capacity, drive frequencies, setpoints and configuration, Binary Values for status, inputs, outputs and one flag per alarm, and 50 Trend Log objects. Network commands use separate _wr objects (start/stop, occupancy, emergency stop, control point, demand limit, setpoint select).

This page lists 800 BACnet objects for the Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points — 70 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
800 (70 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
30XV, AquaForce 30XV, 30XV-2T, 30XV Touch Pilot, 30XV Series A, Greenspeed 30XV
Source document
AquaForce 30XV140-500 Variable Speed Air-Cooled Liquid Chillers - Controls, Start-Up, Operation, Service and Troubleshooting, Appendix E BACnet IP Points · 30XV-2T (Cat. 04-53300196-01) · rev. 9-17
Download CSV 800 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points

Integration in brief

Put the chiller in Network control, then command through the _wr objects: start/stop, occupancy, control point and demand limit. Read control type, run status, capacity, entering and leaving water temperatures and the alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 120GENUNIT_CHIL_S_S_wrNetwork start/stop commandCommand
BV 126GENUNIT_CHIL_OCC_wrNetwork occupied commandCommand
AV 525GENUNIT_CTRL_PNT_wrLeaving water control point from the BMSCommand
AV 526GENUNIT_DEM_LIM_wrDemand limit commandCommand
AV 20GENUNIT_CTRL_TYPControl type: Local, Network or RemoteRead
AV 21GENUNIT_STATUSRunning statusRead
AV 30TEMP_COOL_LWTLeaving chilled water temperatureRead
AV 29TEMP_COOL_EWTEntering chilled water temperatureRead
AV 24GENUNIT_CAP_TPercent total capacityRead
AV 109ALARMRST_ALMUnit alarm stateRead

Enable & remote start

Network control has to be selected on the chiller (machine control method) before the _wr commands take effect.

Watch out for

Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

800 of 800 shown
Type
AnalogBinaryOther
Access
Show
Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points BACnet Points List
DescriptionStates
AV1GENCONF_prio_cirCir Priority Sequence 0=Auto 1=A Prio 2=B PrioRead
AV2GENCONF_off_on_dUnit Off to On DelayRead
AV3GENCONF_lim_selDemand Limit Type Select 0 = None 1 = Switch Control 2Read
AV4GENCONF_nh_startNight Mode Start HourRead
AV5GENCONF_nh_endNight Mode End HourRead
AV6GENCONF_nh_limitNight Capacity LimitRead
AV7PUMPCONF_cpumpseq0 = No Pump 1 = One Pump Only 2 = TwoRead
AV8PUMPCONF_pump_del4 = Pump#2 Manual Pump Auto Rotation DelayRead
AV9USERCONF_use_passUser PasswordWrite
AV10RESETCFG_cr_sel0=None 1=OAT 2=Delta T 3=4-20mA control 4=Space Temp Do not modify !Read
AV11RESETCFG_oat_crnoOAT No Reset ValueRead
AV12RESETCFG_oat_crfuOAT Full Reset ValueRead
AV13RESETCFG_dt_cr_noDelta T No Reset ValueRead
AV14RESETCFG_dt_cr_fuDelta T Full Reset ValueRead
AV15RESETCFG_v_cr_noCurrent No Reset ValueRead
AV16RESETCFG_v_cr_fuCurrent Full Reset ValueRead
AV17RESETCFG_spacr_noSpace T No Reset ValueRead
AV18RESETCFG_spacr_fuSpace T Full Reset ValueRead
AV19RESETCFG_cr_degCooling Reset Deg. Value Cooling Reset SelectRead
AVmin20GENUNIT_CTRL_TYPLocal=0 Net.=1 Remote=2Read
AVmin21GENUNIT_STATUSRun StatusRead
AV22GENUNIT_min_leftMinutes Left for StartRead
AV23GENUNIT_SP_SEL_rdSetpoint Select 0=Auto 1=Spt1 2=Spt2Read
AVmin24GENUNIT_CAP_TPercent Total CapacityRead
AV25GENUNIT_SPCurrent SetpointRead
AV26GENUNIT_CTRL_PNT_rdControl PointRead
AV27GENUNIT_DEM_LIM_rdActive Demand Limit ValRead
AV28GENUNIT_min_limDemand Limit MinimumRead
AVmin29TEMP_COOL_EWTEvap Entering FluidRead
AVmin30TEMP_COOL_LWTEvap Leaving FluidRead
AV31TEMP_OATOutdoor Air TemperatureRead
AV32TEMP_SCT_ASaturated Cond Tmp Cir ARead
AV33TEMP_SST_ASaturated Suction Temp ARead
AV34TEMP_SLT_ASaturated Liquid Temp ARead
AV35TEMP_SUCT_ACompressor Suction Tmp ARead
AV36TEMP_DGT_ADischarge Gas Temp Cir ARead
AV37TEMP_CP_TMP_AMotor Temperature Cir ARead
AV38TEMP_ECO_T_AEXV Eco. Tmp Cir ARead
AV39TEMP_LIQ_T_ALiquid Temperature ARead
AV40TEMP_SCT_BSaturated Cond Tmp Cir BRead
AV41TEMP_SST_BSaturated Suction Temp BRead
AV42TEMP_SLT_BSaturated Liquid Temp BRead
AV43TEMP_SUCT_BCompressor Suction Tmp BRead
AV44TEMP_DGT_BDischarge Gas Temp Cir BRead
AV45TEMP_CP_TMP_BMotor Temperature Cir BRead
AV46TEMP_ECO_T_BEXV Eco. Tmp Cir BRead
AV47TEMP_LIQ_T_BLiquid Temperature BRead
AV48TEMP_SPACETMPSpace Temp (Opt.)Read
AV49TEMP_CHWSTEMPChill Water Temp (Opt.)Read
AV50PRESSURE_DP_ADischarge Pressure ARead
AV51PRESSURE_SP_AMain Suction Pressure ARead
AV52PRESSURE_OP_AOil Pressure ARead
AV53PRESSURE_DOP_ADelta Oil Pressure ARead
AV54PRESSURE_ECO_P_AEconomizer Pressure ARead
AV55PRESSURE_LIQ_P_ALiquid Pressure ARead
AV56PRESSURE_DP_BDischarge Pressure BRead
AV57PRESSURE_SP_BMain Suction Pressure B Evap Pumps SequenceRead
AV58PRESSURE_OP_BOil Pressure BRead
AV59PRESSURE_DOP_BDelta Oil Pressure BRead
AV60PRESSURE_ECO_P_BEconomizer Pressure BRead
AV61PRESSURE_LIQ_P_BLiquid Pressure BRead
AV62INPUTS_SP_RESETRemote Reset SetpointRead
AV63INPUTS_LIM_ANALRemote Dem. LimitRead
AV64INPUTS_leak_vLeakage Detector 1Read
AV65INPUTS_leak_2_vLeakage Detector 2Read
AV66OUTPUTS_CAPT010ACapacity Signal Cir ARead
AV67OUTPUTS_VFAN_AVariFan Speed ARead
AV68OUTPUTS_CAPT010BCapacity Signal Cir BRead
AV69OUTPUTS_VFAN_BVariFan Speed BRead
AV70OUTPUTS_CAPT_010Chiller Capacity SignalRead
AV71RUNTIME_HR_MACHMachine Operating HoursRead
AV72RUNTIME_st_machMachine StartsRead
AV73RUNTIME_HR_CP_ACompressor A HoursRead
AV74RUNTIME_st_cp_aCompressor A StartsRead
AV75RUNTIME_HR_CP_BCompressor B HoursRead
AV76RUNTIME_st_cp_bCompressor B StartsRead
AV77RUNTIME_hr_cpum1Evap Pump #1 HoursRead
AV78RUNTIME_hr_cpum2Evap Pump #2 HoursRead
AV79RUNTIME_VIctAVI Cycle Count ARead
AV80RUNTIME_VIctBVI Cycle Count BRead
AV81RUNTIME_hrfana01Circuit A Fan #1 HoursRead
AV82RUNTIME_hrfana02Circuit A Fan #2 HoursRead
AV83RUNTIME_hrfana03Circuit A Fan #3 HoursRead
AV84RUNTIME_hrfana04Circuit A Fan #4 HoursRead
AV85RUNTIME_hrfana05Circuit A Fan #5 HoursRead
AV86RUNTIME_hrfana06Circuit A Fan #6 HoursRead
AV87RUNTIME_hrfana07Circuit A Fan #7 HoursRead
AV88RUNTIME_hrfana08Circuit A Fan #8 HoursRead
AV89RUNTIME_hrfana09Circuit A Fan #9 HoursRead
AV90RUNTIME_hrfana10Circuit A Fan #10 HoursRead
AV91RUNTIME_hrfana11Circuit A Fan #11 HoursRead
AV92RUNTIME_hrfana12Circuit A Fan #12 HoursRead
AV93RUNTIME_hrfana13Circuit A Fan #13 HoursRead
AV94RUNTIME_hrfana14Circuit A Fan #14 HoursRead
AV95RUNTIME_hrfanb01Circuit B Fan #1 HoursRead
AV96RUNTIME_hrfanb02Circuit B Fan #2 HoursRead
AV97RUNTIME_hrfanb03Circuit B Fan #3 HoursRead
AV98RUNTIME_hrfanb04Circuit B Fan #4 HoursRead
AV99RUNTIME_hrfanb05Circuit B Fan #5 HoursRead
AV100RUNTIME_hrfanb06Circuit B Fan #6 HoursRead
AV101RUNTIME_hrfanb07Circuit B Fan #7 HoursRead
AV102RUNTIME_hrfanb08Circuit B Fan #8 HoursRead
AV103RUNTIME_hrfanb09Circuit B Fan #9 HoursRead
AV104RUNTIME_hrfanb10Circuit B Fan #10 HoursRead
AV105RUNTIME_hrfanb11Circuit B Fan #11 HoursRead
AV106RUNTIME_hrfanb12Circuit B Fan #12 HoursRead
AV107RUNTIME_hrfanb13Circuit B Fan #13 HoursRead
AV108RUNTIME_hrfanb14Circuit B Fan #14 HoursRead
AVmin109ALARMRST_ALMAlarm StateRead
AV110ALARMRST_alarm_1Jbus Current Alarm 1Read
AV111ALARMRST_alarm_2Jbus Current Alarm 2Read
AV112ALARMRST_alarm_3Jbus Current Alarm 3Read
AV113ALARMRST_alarm_4Jbus Current Alarm 4Read
AV114ALARMRST_alarm_5Jbus Current Alarm 5Read
AV115VLT_DRV_drv_pwraCir A Drive PowerRead
AV116VLT_DRV_drv_IaCir A Drive AmpsRead
AV117VLT_DRV_drv_VaCir A Drive VoltageRead
AV118VLT_DRV_drv_SaCir A Drive SpeedRead
AV119VLT_DRV_drv_FaCir A Drive FrequencyRead
AV120VLT_DRV_drv_TaCir A Drive TorqueRead
AV121VLT_DRV_drv_DCVaCir A Drive DC Link VoltRead
AV122VLT_DRV_drv_HSTaCir A Drive Heat Sink TRead
AV123VLT_DRV_drv_CCTaCir A Drive Ctrl Card TRead
AV124VLT_DRV_drv_HTRaCir A Drive HeaterRead
AV125VLT_DRV_drv_pwrbCir B Drive PowerRead
AV126VLT_DRV_drv_IbCir B Drive AmpsRead
AV127VLT_DRV_drv_VbCir B Drive VoltageRead
AV128VLT_DRV_drv_SbCir B Drive SpeedRead
AV129VLT_DRV_drv_FbCir B Drive FrequencyRead
AV130VLT_DRV_drv_TbCir B Drive TorqueRead
AV131VLT_DRV_drv_DCVbCir B Drive DC Link VoltRead
AV132VLT_DRV_drv_HSTbCir B Drive Heat Sink TRead
AV133VLT_DRV_drv_CCTbCir B Drive Ctrl Card TRead
AV134VLT_DRV_drv_HTRbCir B Drive HeaterRead
AV135LAST_POR_date_on1Power On 1 :day-mon-yearRead
AV136LAST_POR_time_on1Power On 1 :hour-minuteRead
AV137LAST_POR_date_of1PowerDown 1:day-mon-yearRead
AV138LAST_POR_time_of1PowerDown 1:hour-minuteRead
AV139LAST_POR_date_on2Power On 2 :day-mon-yearRead
AV140LAST_POR_time_on2Power On 2 :hour-minuteRead
AV141LAST_POR_date_of2PowerDown 2:day-mon-yearRead
AV142LAST_POR_time_of2PowerDown 2:hour-minuteRead
AV143LAST_POR_date_on3Power On 3 :day-mon-yearRead
AV144LAST_POR_time_on3Power On 3 :hour-minuteRead
AV145LAST_POR_date_of3PowerDown 3:day-mon-yearRead
AV146LAST_POR_time_of3PowerDown 3:hour-minuteRead
AV147LAST_POR_date_on4Power On 4 :day-mon-yearRead
AV148LAST_POR_time_on4Power On 4 :hour-minuteRead
AV149LAST_POR_date_of4PowerDown 4:day-mon-yearRead
AV150LAST_POR_time_of4PowerDown 4:hour-minuteRead
AV151LAST_POR_date_on5Power On 5 :day-mon-yearRead
AV152LAST_POR_time_on5Power On 5 :hour-minuteRead
AV153LAST_POR_date_of5PowerDown 5:day-mon-yearRead
AV154LAST_POR_time_of5PowerDown 5:hour-minuteRead
AV155EXV_CTRL_ov_exv_aEXV Override Circuit ARead
AV156EXV_CTRL_EXV_AEXV Position Circuit ARead
AV157EXV_CTRL_DSH_ADischarge Superheat ARead
AV158EXV_CTRL_SH_ASuction Superheat ARead
AV159EXV_CTRL_sh_sp_aSuct. Superheat Setpnt ARead
AV160EXV_CTRL_pinch_aEvap ExchangeDT Cir ARead
AV161EXV_CTRL_subcoolaSubcooling Circuit ARead
AV162EXV_CTRL_subc_spaSubcooling Setpoint ARead
AV163EXV_CTRL_exv_staEXV State ARead
AV164EXV_CTRL_exv_lstaEXV Previous State ARead
AV165EXV_CTRL_exvwposaEXV Wished Position ARead
AV166EXV_CTRL_ov_exv_bEXV Override Circuit BRead
AV167EXV_CTRL_EXV_BEXV Position Circuit BRead
AV168EXV_CTRL_DSH_BDischarge Superheat BRead
AV169EXV_CTRL_SH_BSuction Superheat BRead
AV170EXV_CTRL_sh_sp_bSuct. Superheat Setpnt BRead
AV171EXV_CTRL_pinch_bEvap ExchangeDT Cir BRead
AV172EXV_CTRL_subcoolbSubcooling Circuit BRead
AV173EXV_CTRL_subc_spbSubcooling Setpoint BRead
AV174EXV_CTRL_exv_stbEXV State BRead
AV175EXV_CTRL_exv_lstbEXV Previous State BRead
AV176EXV_CTRL_exvwposbEXV Wished Position BRead
AV177M_MSTSLV_slv_statSlave Chiller StateRead
AV178M_MSTSLV_slv_captSlave Chiller Total CapRead
AV179M_MSTSLV_l_strt_dLag Start DelayRead
AV180M_MSTSLV_ll_hr_dLead/lag Hours DeltaRead
AV181M_MSTSLV_ms_errorMaster/Slave ErrorRead
AV182M_MSTSLV_lagstatSlave lagstatRead
AV183M_MSTSLV_slav_hrSlave Operating HoursRead
AV184M_MSTSLV_slav_ewtSlave Evap Ent. FluidRead
AV185M_MSTSLV_slav_lwtSlave Evap Leav. FluidRead
AV186CAPACTRL_ctrl_wtControled Water TempRead
AV187CAPACTRL_cwt_rateCtrl Water Temp, Deg/MinRead
AV188CAPACTRL_cap_limCurrent Capacity LimitRead
AV189CAPACTRL_drvcmdaWished Comp. Frequency ARead
AV190CAPACTRL_capmodaCapa Ctrl Stat Nb ARead
AV191CAPACTRL_lcapmodaLast Capa Ctrl Stat Nb ARead
AV192CAPACTRL_overridaOverride Capacity Nb ARead
AV193CAPACTRL_cap_pc_aEstimated Capacity ARead
AV194CAPACTRL_drvcmdbWished Comp. Frequency BRead
AV195CAPACTRL_capmodbCapacity Ctrl Stat Nb BRead
AV196CAPACTRL_lcapmodbLast Capa Ctrl Stat Nb BRead
AV197CAPACTRL_overridbOverride Capacity Nb BRead
AV198CAPACTRL_cap_pc_bEstimated Capacity BRead
AV199CAPACTRL_cMaxFrqAMax Comp. Frequency ARead
AV200CAPACTRL_cMaxFrqBMax Comp. Frequency BRead
AV201CAPACTRL_viCmdAComp. VI Cmd ARead
AV202CAPACTRL_viCmdBComp. VI Cmd BRead
AV203CAPACTRL_resetReset AmountRead
AV204CAPACTRL_CirRunNbCircuit Running NumberRead
AV205CAPACTRL_StatCirAState of Circuit ARead
AV206CAPACTRL_StatCirBState of Circuit BRead
AV207CAPACTRL_DualMastDual Circuit MasterRead
AV208CAPACTRL_xSpdHighTransfer Spd, add cirRead
AV209CAPACTRL_xSpdLow_rdTransfer Spd, remove cirRead
AV210LIMITS_dshactaEXV_dsh_act ARead
AV211LIMITS_dshstpaEXV_dsh_stp ARead
AV212LIMITS_elspactaEXV_lsp_act ARead
AV213LIMITS_elspstpaEXV_lsp_stp ARead
AV214LIMITS_chdpactaENV comp high dp act ARead
AV215LIMITS_chdpstpaENV comp high dp stp ARead
AV216LIMITS_fhdpactaENV fan high dp act ARead
AV217LIMITS_fhdpstpaENV fan high dp stp ARead
AV218LIMITS_ldpactaENV low dp act ARead
AV219LIMITS_ldpstpaENV low dp stp ARead
AV220LIMITS_hspactaENV high sp act ARead
AV221LIMITS_hspstpaENV high sp stp ARead
AV222LIMITS_lspactaENV low sp act ARead
AV223LIMITS_lspstpaENV low sp stp ARead
AV224LIMITS_dgtactadgt act ARead
AV225LIMITS_dgtstpadgt stp ARead
AV226LIMITS_dshactbEXV_dsh_act BRead
AV227LIMITS_dshstpbEXV_dsh_stp BRead
AV228LIMITS_elspactbEXV_lsp_act BRead
AV229LIMITS_elspstpbEXV_lsp_stp BRead
AV230LIMITS_chdpactbENV comp high dp act BRead
AV231LIMITS_chdpstpbENV comp high dp stp BRead
AV232LIMITS_fhdpactbENV fan high dp act BRead
AV233LIMITS_fhdpstpbENV fan high dp stp BRead
AV234LIMITS_ldpactbENV low dp act BRead
AV235LIMITS_ldpstpbENV low dp stp BRead
AV236LIMITS_hspactbENV high sp act BRead
AV237LIMITS_hspstpbENV high sp stp BRead
AV238LIMITS_lspactbENV low sp act BRead
AV239LIMITS_lspstpbENV low sp stp BRead
AV240LIMITS_dgtactbdgt_act BRead
AV241LIMITS_dgtstpbdgt_stp BRead
AV242FAN_CTRL_fan_f_aFan Freq Cir ARead
AV243FAN_CTRL_fan_staFan State ARead
AV244FAN_CTRL_fan_lstaFan Previous State ARead
AV245FAN_CTRL_wfan_f_aFan Wished Freq ARead
AV246FAN_CTRL_fan_modaFan Mode ARead
AV247FAN_CTRL_fan_txtaFan Mode Text ARead
AV248FAN_CTRL_ftotpowaFan Tot Pwr Filtered ARead
AV249FAN_CTRL_fcont_aFan Contactors On ARead
AV250FAN_CTRL_fan_f_bFan Freq Cir BRead
AV251FAN_CTRL_fan_stbFan State BRead
AV252FAN_CTRL_fan_lstbFan Previous State BRead
AV253FAN_CTRL_wfan_f_bFan Wished Freq BRead
AV254FAN_CTRL_fan_modbFan Mode BRead
AV255FAN_CTRL_fan_txtbFan Mode Text BRead
AV256FAN_CTRL_ftotpowbFan Tot Pwr Filtered BRead
AV257FAN_CTRL_fcont_bFan Contactors On BRead
AV258FAN_DRV_fd_pwra1Fan Drive Power A1Read
AV259FAN_DRV_fd_Ia1Fan Drive Amps A1Read
AV260FAN_DRV_fd_Va1Fan Drive Voltage A1Read
AV261FAN_DRV_fd_Sa1Fan Drive Speed A1Read
AV262FAN_DRV_fd_Fa1Fan Drive Frequency A1Read
AV263FAN_DRV_fd_Ta1Fan Drive Torque A1Read
AV264FAN_DRV_fd_DCVa1Fan Drv DC Link Volt A1Read
AV265FAN_DRV_fd_HSTa1Fan Drive Heat Sink T A1Read
AV266FAN_DRV_fd_CCTa1Fan Drive Ctrl Card T A1Read
AV267FAN_DRV_fd_pwra2Fan Drive Power A2Read
AV268FAN_DRV_fd_Ia2Fan Drive Amps A2Read
AV269FAN_DRV_fd_Va2Fan Drive Voltage A2Read
AV270FAN_DRV_fd_Sa2Fan Drive Speed A2Read
AV271FAN_DRV_fd_Fa2Fan Drive Frequency A2Read
AV272FAN_DRV_fd_Ta2Fan Drive Torque A2Read
AV273FAN_DRV_fd_DCVa2Fan Drv DC Link Volt A2Read
AV274FAN_DRV_fd_HSTa2Fan Drive Heat Sink T A2Read
AV275FAN_DRV_fd_CCTa2Fan Drive Ctrl Card T A2Read
AV276FAN_DRV_fd_pwra3Fan Drive Power A3Read
AV277FAN_DRV_fd_Ia3Fan Drive Amps A3Read
AV278FAN_DRV_fd_Va3Fan Drive Voltage A3Read
AV279FAN_DRV_fd_Sa3Fan Drive Speed A3Read
AV280FAN_DRV_fd_Fa3Fan Drive Frequency A3Read
AV281FAN_DRV_fd_Ta3Fan Drive Torque A3Read
AV282FAN_DRV_fd_DCVa3Fan Drv DC Link Volt A3Read
AV283FAN_DRV_fd_HSTa3Fan Drive Heat Sink T A3Read
AV284FAN_DRV_fd_CCTa3Fan Drive Ctrl Card T A3Read
AV285FAN_DRV_fd_pwrb1Fan Drive Power B1Read
AV286FAN_DRV_fd_Ib1Fan Drive Amps B1Read
AV287FAN_DRV_fd_Vb1Fan Drive Voltage B1Read
AV288FAN_DRV_fd_Sb1Fan Drive Speed B1Read
AV289FAN_DRV_fd_Fb1Fan Drive Frequency B1Read
AV290FAN_DRV_fd_Tb1Fan Drive Torque B1Read
AV291FAN_DRV_fd_DCVb1Fan Drv DC Link Volt B1Read
AV292FAN_DRV_fd_HSTb1Fan Drive Heat Sink T B1Read
AV293FAN_DRV_fd_CCTb1Fan Drive Ctrl Card T B1Read
AV294FAN_DRV_fd_pwrb2Fan Drive Power B2Read
AV295FAN_DRV_fd_Ib2Fan Drive Amps B2Read
AV296FAN_DRV_fd_Vb2Fan Drive Voltage B2Read
AV297FAN_DRV_fd_Sb2Fan Drive Speed B2Read
AV298FAN_DRV_fd_Fb2Fan Drive Frequency B2Read
AV299FAN_DRV_fd_Tb2Fan Drive Torque B2Read
AV300FAN_DRV_fd_DCVb2Fan Drv DC Link Volt B2Read
AV301FAN_DRV_fd_HSTb2Fan Drive Heat Sink T B2Read
AV302FAN_DRV_fd_CCTb2Fan Drive Ctrl Card T B2Read
AV303FAN_DRV_fd_pwrb3Fan Drive Power B3Read
AV304FAN_DRV_fd_Ib3Fan Drive Amps B3Read
AV305FAN_DRV_fd_Vb3Fan Drive Voltage B3Read
AV306FAN_DRV_fd_Sb3Fan Drive Speed B3Read
AV307FAN_DRV_fd_Fb3Fan Drive Frequency B3Read
AV308FAN_DRV_fd_Tb3Fan Drive Torque B3Read
AV309FAN_DRV_fd_DCVb3Fan Drv DC Link Volt B3Read
AV310FAN_DRV_fd_HSTb3Fan Drive Heat Sink T B3Read
AV311FAN_DRV_fd_CCTb3Fan Drive Ctrl Card T B3Read
AV312FACTORY_unitsizeUnit CapacityRead
AV313FACTORY_voltagePower Supply VoltageRead
AV314FACTORY_mfg_tierTier 0=STD 1=MID 2=HIRead
AV315FACTORY_cpass_nbEvap Pass NumberRead
AV316FACTORY_fac_passFactory PasswordRead
AV317FACTORY_fMaxOvrAMax Frequency Override ARead
AV318FACTORY_fMaxOvrBMax Frequency Override BRead
AV319FACTORY_fan_factFan Freq Factor(0.7-1.1)Read
AV320FACTORY2_exvmax_aEXV A Maximum Steps NumbRead
AV321FACTORY2_exvmax_bEXV B Maximum Steps NumbRead
AV322FACTORY2_eco_cnfaEconomizer A Steps NumbRead
AV323FACTORY2_eco_cnfbEconomizer B Steps NumbRead
AV324FACTORY2_vfd_cmpNb VFD CompressorRead
AV325FACTORY2_vfd_fanaNb Fan Drive Cir ARead
AV326FACTORY2_vfd_fanbNb Fan Drive Cir BRead
AV327SERVICE1_flui_typEvaporator Fluid Type 1 = Water 2 = Med Brine 3 =Read
AV328SERVICE1_freezespBrine Freeze SetpointRead
AV329SERVICE1_mini_lwtBrine Minimum Fluid TempRead
AV330SERVICE1_fastcaprFast Capacity RecoveryRead
AV331SERVICE1_ewt_cirAEWT Probe on Cir A SideRead
AV332SERVICE1_leak_thrLeakage Charge ThresholdRead
AV333SERVICE1_leak_tmrLeakage Charge TimerRead
AV334SERVICE1_heaterspEvap Heater Delta SptRead
AV335SERVICE1_freez_ovFreeze Override OffsetRead
AV336SERVICE1_ViPwrChkVI Self-Test ThresholdWrite
AV337UPDTHOUR_hr_machMachine Operating HoursRead
AV338UPDTHOUR_st_machMachine Starts NumberRead
AV339UPDTHOUR_hr_cp_aCompressor A HoursRead
AV340UPDTHOUR_st_cp_aCompressor A StartsRead
AV341UPDTHOUR_hr_cp_bCompressor B HoursRead
AV342UPDTHOUR_st_cp_bCompressor B StartsRead
AV343UPDTHOUR_hr_cpum1Evap Pump #1 HoursRead
AV344UPDTHOUR_hr_cpum2Evap Pump #2 HoursRead
AV345UPDTHOUR_VIctAVI Cycle Count ARead
AV346UPDTHOUR_VIctBVI Cycle Count BRead
AV347UPDTHOUR_hrfana01Circuit A Fan #1 HoursRead
AV348UPDTHOUR_hrfana02Circuit A Fan #2 HoursRead
AV349UPDTHOUR_hrfana03Circuit A Fan #3 HoursRead
AV350UPDTHOUR_hrfana04Circuit A Fan #4 HoursRead
AV351UPDTHOUR_hrfana05Circuit A Fan #5 HoursRead
AV352UPDTHOUR_hrfana06Circuit A Fan #6 HoursRead
AV353UPDTHOUR_hrfana07Circuit A Fan #7 HoursRead
AV354UPDTHOUR_hrfana08Circuit A Fan #8 HoursRead
AV355UPDTHOUR_hrfana09Circuit A Fan #9 HoursRead
AV356UPDTHOUR_hrfana10Circuit A Fan #10 HoursRead
AV357UPDTHOUR_hrfana11Circuit A Fan #11 HoursRead
AV358UPDTHOUR_hrfana12Circuit A Fan #12 HoursRead
AV359UPDTHOUR_hrfana13Circuit A Fan #13 HoursRead
AV360UPDTHOUR_hrfana14Circuit A Fan #14 HoursRead
AV361UPDTHOUR_hrfanb01Circuit B Fan #1 HoursRead
AV362UPDTHOUR_hrfanb02Circuit B Fan #2 HoursRead
AV363UPDTHOUR_hrfanb03Circuit B Fan #3 HoursRead
AV364UPDTHOUR_hrfanb04Circuit B Fan #4 HoursRead
AV365UPDTHOUR_hrfanb05Circuit B Fan #5 HoursRead
AV366UPDTHOUR_hrfanb06Circuit B Fan #6 HoursRead
AV367UPDTHOUR_hrfanb07Circuit B Fan #7 HoursRead
AV368UPDTHOUR_hrfanb08Circuit B Fan #8 HoursRead
AV369UPDTHOUR_hrfanb09Circuit B Fan #9 HoursRead
AV370UPDTHOUR_hrfanb10Circuit B Fan #10 HoursRead
AV371UPDTHOUR_hrfanb11Circuit B Fan #11 HoursRead
AV372UPDTHOUR_hrfanb12Circuit B Fan #12 HoursRead
AV373UPDTHOUR_hrfanb13Circuit B Fan #13 HoursRead
AV374UPDTHOUR_hrfanb14Circuit B Fan #14 HoursRead
AV375MST_SLV_ms_selMaster/Slave Select 0=Disable 1=Master 2=SlaveRead
AV376MST_SLV_ms_ctrlMaster Control Type 1=Local Control 2=Remote Control 3=CCN ControlRead
AV377MST_SLV_slv_addrSlave AddressRead
AV378MST_SLV_lead_selLead Lag Select 0=Always Lead 1=Lag Once Failed Only 2=Lead/Lag Runtime SelRead
AV379MST_SLV_ll_bal_dLead/Lag Balance DeltaRead
AV380MST_SLV_lstr_timLead/Lag Start TimerRead
AV381MST_SLV_lead_pulLead Pulldown TimeRead
AV382MST_SLV_start_dtStart If Error HigherRead
AV383MST_SLV_lag_miniLag Minimum Running TimeRead
AV384MST_SLV_lag_pumpLag Unit Pump Control 0=Stop if Unit Stops 1=Run if Unit StopsRead
AV385CMP_PI_wt_kp_aWater Temp PI, Kp, Cir ARead
AV386CMP_PI_wt_ti_aWater Temp PI, Ti Cir ARead
AV387CMP_PI_wt_ni_aWater Temp PI, NI Cir ARead
AV388CMP_PI_dgt_kp_aDGT PI Kp, Cir ARead
AV389CMP_PI_dgt_ti_aDGT PI, Ti Cir ARead
AV390CMP_PI_dgt_ni_aDGT PI, NI Cir ARead
AV391CMP_PI_cpt_kp_aComp Temp PI, Kp Cir ARead
AV392CMP_PI_cpt_ti_aComp Temp PI, Ti Cir ARead
AV393CMP_PI_cpt_ni_aComp Temp PI, NI Cir ARead
AV394CMP_PI_dp_kp_aDisch Press PI, Kp Cir ARead
AV395CMP_PI_dp_ti_aDisch Press PI, Ti Cir ARead
AV396CMP_PI_dp_ni_aDisch Press PI, NI Cir ARead
AV397CMP_PI_lsp_kp_aLow SP PI, Kp Cir ARead
AV398CMP_PI_lsp_ti_aLow SP PI, Ti Cir ARead
AV399CMP_PI_lsp_ni_aLow SP PI, NI Cir ARead
AV400CMP_PI_wt_kp_bWater Temp PI, Kp, Cir BRead
AV401CMP_PI_wt_ti_bWater Temp PI, Ti Cir BRead
AV402CMP_PI_wt_ni_bWater Temp PI, NI Cir BRead
AV403CMP_PI_dgt_kp_bDGT PI Kp, Cir BRead
AV404CMP_PI_dgt_ti_bDGT PI, Ti Cir BRead
AV405CMP_PI_dgt_ni_bDGT PI, NI Cir BRead
AV406CMP_PI_cpt_kp_bComp Temp PI, Kp Cir BRead
AV407CMP_PI_cpt_ti_bComp Temp PI, Ti Cir BRead
AV408CMP_PI_cpt_ni_bComp Temp PI, NI Cir BRead
AV409CMP_PI_dp_kp_bDisch Press PI, Kp Cir BRead
AV410CMP_PI_dp_ti_bDisch Press PI, Ti Cir BRead
AV411CMP_PI_dp_ni_bDisch Press PI, NI Cir BRead
AV412CMP_PI_lsp_kp_bLow SP PI, Kp Cir BRead
AV413CMP_PI_lsp_ti_bLow SP PI, Ti Cir BRead
AV414CMP_PI_lsp_ni_bLow SP PI, NI Cir BRead
AV415EXV_CFG_fixeddshFixed DSH SetpointRead
AV416EXV_CFG_scsp_maxSubcooling Setpoint MaxRead
AV417EXV_CFG_scsp_minSubcooling Setpoint MinRead
AV418EXV_CFG_sh_sp_aSuperheat Setpoint ARead
AV419EXV_CFG_sh_sp_bSuperheat Setpoint BRead
AV420EXV_CFG_sbc_kp_aSubcool PI, Kp Cir ARead
AV421EXV_CFG_sbc_ti_aSubcool PI, Ti Cir ARead
AV422EXV_CFG_sbc_ni_aSubcool PI, NI Cir ARead
AV423EXV_CFG_dsh_kp_aDSH PI, Kp Cir ARead
AV424EXV_CFG_dsh_ti_aDSH PI, Ti Cir ARead
AV425EXV_CFG_dsh_ni_aDSH PI, NI Cir ARead
AV426EXV_CFG_hsp_kp_aHigh SP PI, Kp Cir ARead
AV427EXV_CFG_hsp_ti_aHigh SP PI, Ti Cir ARead
AV428EXV_CFG_hsp_ni_aHigh SP PI, NI Cir ARead
AV429EXV_CFG_lsp_kp_aLow SP PI, Kp Cir ARead
AV430EXV_CFG_lsp_ti_aLow SP PI, Ti Cir ARead
AV431EXV_CFG_lsp_ni_aLow SP PI, NI Cir ARead
AV432EXV_CFG_dop_kp_aDop PI, Kp Cir ARead
AV433EXV_CFG_dop_ti_aDop PI, Ti Cir ARead
AV434EXV_CFG_dop_ni_aDop PI, NI Cir ARead
AV435EXV_CFG_ssh_kp_aSuction SH PI, Kp Cir ARead
AV436EXV_CFG_ssh_ti_aSuction SH PI, Ti Cir ARead
AV437EXV_CFG_ssh_ni_aSuction SH PI, NI Cir ARead
AV438EXV_CFG_sbc_kp_bSubcool PI, Kp Cir BRead
AV439EXV_CFG_sbc_ti_bSubcool PI, Ti Cir BRead
AV440EXV_CFG_sbc_ni_bSubcool PI, NI Cir BRead
AV441EXV_CFG_dsh_kp_bDSH PI, Kp Cir BRead
AV442EXV_CFG_dsh_ti_bDSH PI, Ti Cir BRead
AV443EXV_CFG_dsh_ni_bDSH PI, NI Cir BRead
AV444EXV_CFG_hsp_kp_bHigh SP PI, Kp Cir BRead
AV445EXV_CFG_hsp_ti_bHigh SP PI, Ti Cir BRead
AV446EXV_CFG_hsp_ni_bHigh SP PI, NI Cir BRead
AV447EXV_CFG_lsp_kp_bLow SP PI, Kp Cir BRead
AV448EXV_CFG_lsp_ti_bLow SP PI, Ti Cir BRead
AV449EXV_CFG_lsp_ni_bLow SP PI, NI Cir BRead
AV450EXV_CFG_dop_kp_bDop PI, Kp Cir BRead
AV451EXV_CFG_dop_ti_bDop PI, Ti Cir BRead
AV452EXV_CFG_dop_ni_bDop PI, NI Cir BRead
AV453EXV_CFG_ssh_kp_bSuction SH PI, Kp Cir BRead
AV454EXV_CFG_ssh_ti_bSuction SH PI, Ti Cir BRead
AV455EXV_CFG_ssh_ni_bSuction SH PI, NI Cir BRead
AV456DELTA_wateesyswater_t_hysteresysRead
AV457DELTA_chdp_hyscmp high dp hysteresysRead
AV458DELTA_chdtdactcmp high dt act offsetRead
AV459DELTA_chdtdsptcmp high dt stp offsetRead
AV460DELTA_fhdp_hysfan high dp hysteresysRead
AV461DELTA_fhdtdactfan high dt act offsetRead
AV462DELTA_fhdtdstpfan high dt stp offsetRead
AV463DELTA_ldp_hyslow dp hysteresysRead
AV464DELTA_ldtdactlow dt act offsetRead
AV465DELTA_ldtdsptlow dt stp offsetRead
AV466DELTA_hsp_hysthigh sp hysteresysRead
AV467DELTA_hstdacthigh st act offsetRead
AV468DELTA_hstdspthigh st stp offsetRead
AV469DELTA_lsp_hystlow sp hysteresysRead
AV470DELTA_lstdactlow st act offsetRead
AV471DELTA_lstdsptlow st stp offsetRead
AV472DELTA_lstdcpadeltat lstEXV vs lstCAPA MOTOR TEMPERATURERead
AV473DELTA_mt_hystmotor temp hysteresisRead
AV474DELTA_dgt_hystdgt hysteresysRead
AV475DELTA_dgt_actdgt limit act offsetRead
AV476DELTA_dgt_sptdgt limit spt offset DIS. SUPERHEATRead
AV477DELTA_dsh_hystdsh hysteresysRead
AV478DELTA_dsh_actdsh act offsetRead
AV479DELTA_dshdelayexv_no_dsh_delayRead
AV480DELTA_mopdelayexv_no_mop_delay EXV SUBCOOLING (DX)Read
AV481DELTA_sbc_hyssubcool hysteresysRead
AV482DELTA_sbc_actsubcool act offsetRead
AV483DELTA_sbc_sptSubcooling Setpoint ARead
AV484BACNET_networkNetworkRead
AV485BACNET_identIdentifierRead
AV486BACNET_bbmdBACnet Management DeviceRead
AV487FAN_CFG_fldp_kpaFan Low DP PI, Kp, Cir ARead
AV488FAN_CFG_fldp_tiaFan Low DP PI, Ti Cir ARead
AV489FAN_CFG_fldp_niaFan Low DP PI, NI Cir ARead
AV490FAN_CFG_fldp_kpbFan Low DP PI, Kp, Cir BRead
AV491FAN_CFG_fldp_tibFan Low DP PI, Ti Cir BRead
AV492FAN_CFG_fldp_nibFan Low DP PI, NI Cir BRead
AV493FAN_CFG_fan_hlimFan Max FrequencyRead
AV494FAN_CFG_fan_llimFan Min FrequencyRead
AV495FAN_CFG_sync_KpSychronizing Output KpRead
AV496FAN_CFG_n_coilsACir Cond Coil Number ARead
AV497FAN_CFG_n_coilsBCir Cond Coil Number BRead
AV498FAN_CFG_cp_factACompressor Factor ARead
AV499FAN_CFG_cp_factBCompressor Factor BRead
AV500FAN_CFG_fldtfactFan Low Dis. FactorRead
AV501FAN_CFG_xt_s_smpStablility Sample NbRead
AV502FAN_CFG_xt_in_tlOpt. Deviation ToleranceRead
AV503FAN_CFG_os_d_ampOpt. Disturbance Ampl.Read
AV504FAN_CFG_os_d_perOpt. Disturbance PeriodRead
AV505FAN_CFG_os_f_powOpt. Freeze Power Tol.Read
AV506FAN_CFG_xtos_fltOpt. Filter TimeRead
AV507ECO_PI_ecsh_kpaEXV Eco. SH Kp, Cir ARead
AV508ECO_PI_ecsh_tiaEXV Eco. SH Ti Cir ARead
AV509ECO_PI_ecsh_niaEXV Eco. SH NI Cir ARead
AV510ECO_PI_ecsh_kpbEXV Eco. SH Kp, Cir BRead
AV511ECO_PI_ecsh_tibEXV Eco. SH Ti Cir BRead
AV512ECO_PI_ecsh_nibEXV Eco. SH NI Cir BRead
AV513ECO_PI_eco_minEXV Eco. Min PositionRead
AV514ECO_PI_eco_maxEXV Eco. Max PositionRead
AV515ECO_PI_capa_limCapacity Lim Disable EcoRead
AV516ECO_PI_ecoshspaEco Superheat Setpoint ARead
AV517ECO_PI_ecoshspbEco Superheat Setpoint BRead
AV518SETPOINT_csp1Cooling Setpoint 1Write
AV519SETPOINT_csp2Cooling Setpoint 2Write
AV520SETPOINT_ice_spCooling Ice SetpointWrite
AV521SETPOINT_cramp_spCooling Ramp LoadingWrite
AV522SETPOINT_lim_sp1Switch Limit Setpoint 1Write
AV523SETPOINT_lim_sp2Switch Limit Setpoint 2Write
AV524SETPOINT_lim_sp3Switch Limit Setpoint 3Write
AVmin525GENUNIT_CTRL_PNT_wrControl PointCommand
AVmin526GENUNIT_DEM_LIM_wrActive Demand Limit ValCommand
AV527GENUNIT_SP_SEL_wrSetpoint SelectCommand
BV1GENCONF_ramp_selRamp Loading EnableRead
BV2GENCONF_ice_cnfgIce Mode EnableRead
BV3GENCONF_shortcycShort Cycle ManagementRead
BV4PUMPCONF_pump_perPump Sticking ProtectionRead
BV5PUMPCONF_pump_locFlow Checked If Pump OffRead
BV6GENUNIT_CHIL_S_S_rdNet.: Cmd Start/StopRead
BV7GENUNIT_CHIL_OCC_rdNet.: Cmd OccupiedRead
BV8GENUNIT_SP_OCC_rdSetpoint Occupied?Read
BV9GENUNIT_EMSTOP_rdEmergency StopRead
BV10INPUTS_ONOFF_SWRemote On/Off SwitchRead
BV11INPUTS_SETP_SWRemote Setpoint SwitchRead
BV12INPUTS_LIM_SW1Limit Switch 1Read
BV13INPUTS_LIM_SW2Limit Switch 2Read
BV14INPUTS_OIL_L_AOil Level Input ARead
BV15INPUTS_OIL_L_BOil Level Input BRead
BV16INPUTS_REM_LOCKCustomer InterlockRead
BV17INPUTS_ICE_SWIce Done Storage SwitchRead
BV18INPUTS_OCC_OVSWOccupied Override SwitchRead
BV19INPUTS_HEATR_SWEvap Heater DetectorRead
BV20OUTPUTS_LABEL_ACIRCUIT ARead
BV21OUTPUTS_CP_ACompressor ARead
BV22OUTPUTS_OIL_SL_AOil Solenoid Output ARead
BV23OUTPUTS_VI_AVI Solenoid Output ARead
BV24OUTPUTS_ISO_OP_ARef Iso Relay Energize ARead
BV25OUTPUTS_ISO_POSARef Iso Valve State ARead
BV26OUTPUTS_OIL_HT_AOil Heater Output ARead
BV27OUTPUTS_LABEL_BCIRCUIT BRead
BV28OUTPUTS_CP_BCompressor BRead
BV29OUTPUTS_OIL_SL_BOil Solenoid Output BRead
BV30OUTPUTS_VI_BVI Solenoid Output BRead
BV31OUTPUTS_ISO_OP_BRef Iso Relay Energize BRead
BV32OUTPUTS_ISO_POSBRef Iso Valve State BRead
BV33OUTPUTS_OIL_HT_BOil Heater Output BRead
BV34OUTPUTS_ALARMAlarm Relay StatusRead
BV35OUTPUTS_RUNNINGRunning Relay StatusRead
BV36OUTPUTS_ALERTAlert Relay StateRead
BV37OUTPUTS_SHUTDOWNShutdown Indicator StateRead
BV38OUTPUTS_C_HEATEREvap Heater OutputRead
BV39OUTPUTS_FCA1Fan Contactor 1ARead
BV40OUTPUTS_FCA2Fan Contactor 2ARead
BV41OUTPUTS_FCA3Fan Contactor 3ARead
BV42OUTPUTS_FCA4Fan Contactor 4ARead
BV43OUTPUTS_FCA5Fan Contactor 5ARead
BV44OUTPUTS_FCA6Fan Contactor 6ARead
BV45OUTPUTS_FCA7Fan Contactor 7ARead
BV46OUTPUTS_FCA8Fan Contactor 8ARead
BV47OUTPUTS_FCB1Fan Contactor 1BRead
BV48OUTPUTS_FCB2Fan Contactor 2BRead
BV49OUTPUTS_FCB3Fan Contactor 3BRead
BV50OUTPUTS_FCB4Fan Contactor 4BRead
BV51OUTPUTS_FCB5Fan Contactor 5BRead
BV52OUTPUTS_FCB6Fan Contactor 6BRead
BV53OUTPUTS_FCB7Fan Contactor 7BRead
BV54OUTPUTS_FCB8Fan Contactor 8BRead
BV55OUTPUTS_VFD_EN_AComp. HW Enable ARead
BV56OUTPUTS_VFD_EN_BComp. HW Enable BRead
BV57OUTPUTS_BOX_HTRControl Box HeaterRead
BV58PUMPSTAT_CPUMP_1_rdEvap Pump #1 CommandRead
BV59PUMPSTAT_CPUMP_2_rdEvap Pump #2 CommandRead
BV60PUMPSTAT_ROTCPUMP_rdRotate Evap Pumps ?Read
BV61PUMPSTAT_FLOW_SWEvap Flow Switch #1Read
BV62PUMPSTAT_FLOW_SWBEvap Flow Switch #2Read
BV63MODES_m_delayStart Up Delay In EffectRead
BV64MODES_m_2stptSecond Setpoint In UseRead
BV65MODES_m_resetReset In EffectRead
BV66MODES_m_demlimDemand Limit ActiveRead
BV67MODES_m_pmprotEvaporator Pump RotationRead
BV68MODES_m_pmpperPump Periodic StartRead
BV69MODES_m_nightNight Low Noise ActiveRead
BV70MODES_m_slaveMaster Slave ActiveRead
BV71MODES_m_iceIce Mode In EffectRead
BV72ALARMRST_RST_ALMAlarm ResetRead
BV73VLT_DRV_SET_DRVADrive A AttachRead
BV74VLT_DRV_SET_DRVBDrive B AttachRead
BV75VLT_DRV_VLT_COMAComm with Drive A OkRead
BV76VLT_DRV_VLT_COMBComm with Drive B OkRead
BV77M_MSTSLV_ms_activMaster/Slave Ctrl ActiveRead
BV78M_MSTSLV_lead_selLead Unit is the:Read
BV79M_MSTSLV_ll_changLead/lag Changeover?Read
BV80M_MSTSLV_ll_pullLead Pulldown ?Read
BV81M_MSTSLV_cap_maxMax Available Capacity ?Read
BV82FAN_DRV2_SET_FDA1Fan Drive A1 AttachRead
BV83FAN_DRV2_SET_FDA2Fan Drive A2 AttachRead
BV84FAN_DRV2_SET_FDA3Fan Drive A3 AttachRead
BV85FAN_DRV2_SET_FDB1Fan Drive B1 AttachRead
BV86FAN_DRV2_SET_FDB2Fan Drive B2 AttachRead
BV87FAN_DRV2_SET_FDB3Fan Drive B3 AttachRead
BV88FAN_DRV2_FD_COMA1Comm Fan Drive A1 OkRead
BV89FAN_DRV2_FD_COMA2Comm Fan Drive A2 OkRead
BV90FAN_DRV2_FD_COMA3Comm Fan Drive A3 OkRead
BV91FAN_DRV2_FD_COMB1Comm Fan Drive B1 OkRead
BV92FAN_DRV2_FD_COMB2Comm Fan Drive B2 OkRead
BV93FAN_DRV2_FD_COMB3Comm Fan Drive B3 OkRead
BV94FAN_DRV2_stopfanaStop Cir A Fan DriveRead
BV95FAN_DRV2_stopfanbStop Cir B Fan DriveRead
BV96FACTORY_dxcoolerDX Evaporator InstalledRead
BV97FACTORY_heat_selEvap Heater InstalledRead
BV98FACTORY_mst_slvMaster Slave SetupRead
BV99FACTORY_emm_nrcpEnergy Management ModuleRead
BV100FACTORY_loamboptLow Ambient Option (STD)Read
BV101FACTORY_leak_chkLeakage Charge DetectionRead
BV102FACTORY_fMaxEnAEnable Max Frequency ARead
BV103FACTORY_fMaxEnBEnable Max Frequency BRead
BV104SERVICE1_ewt_optEntering Fluid ControlRead
BV105SERVICE1_ser_passService PasswordRead
BV106SERVICE1_RFI_confCompressor RFI Filter EnRead
BV107SERVICE1_metricMetric Units? (Blackbox)Read
BV108SERVICE1_fdrv_cfgSend fan drive config?Read
BV109SERVICE1_cdrv_cfgSend comp. drive config?Read
BV110SERVICE1_auto_smAuto Start When SM LostRead
BV111SERVICE1_ViChkEnVI Self-Test EnableWrite
BV112SERVICE1_AntiFrzPump Rot. AntiFrz ProtecRead
BV113MST_SLV_ll_serieChiller In SeriesRead
BV114BACNET_bacenaBACnet EnableRead
BV115BACNET_bacunitMetric Units? (Blackbox)Read
BV116FAN_CFG_fan_ctrlFan Ctrl Type (Vari,Fix) Optimization ParametersRead
BV117FAN_CFG_xt_enablOptimization EnableRead
BV118CP_ENABL_en_cp_aCompressor A DisableRead
BV119CP_ENABL_en_cp_bCompressor B DisableRead
BVmin120GENUNIT_CHIL_S_S_wrNet.: Cmd Start/StopCommand
BV121PUMPSTAT_CPUMP_1_wrEvap Pump #1 CommandCommand
BV122PUMPSTAT_CPUMP_2_wrEvap Pump #2 CommandCommand
BV123GENUNIT_EMSTOP_wrEmergency StopCommand
BV124PUMPSTAT_ROTCPUMP_wrRotate Evap Pumps ?Command
BV125GENUNIT_SP_OCC_wrSetpoint Occupied?Command
BVmin126GENUNIT_CHIL_OCC_wrNet.: Cmd OccupiedCommand
BV127ALM_COOL_EWT_FCOOL_EWT_FRead
BV128ALM_COOL_LWT_FCOOL_LWT_FRead
BV129ALM_OAT_FOAT_FRead
BV130ALM_CHWSTEMP_FCHWSTEMP_FRead
BV131ALM_SUCTION_T_A_FSUCTION_T_A_FRead
BV132ALM_SUCTION_T_B_FSUCTION_T_B_FRead
BV133ALM_DGT_A_T_FDGT_A_T_FRead
BV134ALM_DGT_B_T_FDGT_B_T_FRead
BV135ALM_LIQUID_T_A_FLIQUID_T_A_FRead
BV136ALM_LIQUID_T_B_FLIQUID_T_B_FRead
BV137ALM_CP_TMP_A_FCP_TMP_A_FRead
BV138ALM_CP_TMP_B_FCP_TMP_B_FRead
BV139ALM_ECO_T_A_FECO_T_A_FRead
BV140ALM_ECO_T_B_FECO_T_B_FRead
BV141ALM_SPACE_TEMP_FSPACE_TEMP_FRead
BV142ALM_DP_A_FDP_A_FRead
BV143ALM_DP_B_FDP_B_FRead
BV144ALM_SP_A_FSP_A_FRead
BV145ALM_SP_B_FSP_B_FRead
BV146ALM_OIL_P_A_FOIL_P_A_FRead
BV147ALM_OIL_P_B_FOIL_P_B_FRead
BV148ALM_ECO_P_A_FECO_P_A_FRead
BV149ALM_ECO_P_B_FECO_P_B_FRead
BV150ALM_LIQUID_P_A_FLIQUID_P_A_FRead
BV151ALM_LIQUID_P_B_FLIQUID_P_B_FRead
BV152ALM_SIOB1_COM_FSIOB1_COM_FRead
BV153ALM_SIOB2_COM_FSIOB2_COM_FRead
BV154ALM_AUX1_1_COM_FAUX1_1_COM_FRead
BV155ALM_AUX1_2_COM_FAUX1_2_COM_FRead
BV156ALM_AUX1_3_COM_FAUX1_3_COM_FRead
BV157ALM_AUX1_4_COM_FAUX1_4_COM_FRead
BV158ALM_EMM_BRD_COM_FEMM_BOARD_COM_FRead
BV159ALM_VLT_DRIVE1_COM_FVLT_DRIVE1_COM_FRead
BV160ALM_VLT_DRIVE2_COM_FVLT_DRIVE2_COM_FRead
BV161ALM_FAN_DRIVEA1_COM_FFAN_DRIVEA1_COM_FRead
BV162ALM_FAN_DRIVEA2_COM_FFAN_DRIVEA2_COM_FRead
BV163ALM_FAN_DRIVEA3_COM_FFAN_DRIVEA3_COM_FRead
BV164ALM_FAN_DRIVEB1_COM_FFAN_DRIVEB1_COM_FRead
BV165ALM_FAN_DRIVEB2_COM_FFAN_DRIVEB2_COM_FRead
BV166ALM_FAN_DRIVEB3_COM_FFAN_DRIVEB3_COM_FRead
BV167ALM_COOLER_FREEZE_FCOOLER_FREEZE_FRead
BV168ALM_LOW_SUCTION_A_FLOW_SUCTION_A_FRead
BV169ALM_LOW_SUCTION_B_FLOW_SUCTION_B_FRead
BV170ALM_LOCK_FLOCK_FRead
BV171ALM_LOSS_COM_MS_FLOSS_COM_MS_FRead
BV172ALM_LOW_OIL_A_P_FLOW_OIL_A_P_FRead
BV173ALM_LOW_OIL_B_P_FLOW_OIL_B_P_FRead
BV174ALM_OIL_FILT_A_P_FOIL_FILT_A_P_FRead
BV175ALM_OIL_FILT_B_P_FOIL_FILT_B_P_FRead
BV176ALM_OIL_DROP_A_P_FOIL_DROP_A_P_FRead
BV177ALM_OIL_DROP_B_P_FOIL_DROP_B_P_FRead
BV178ALM_LOW_OIL_LEVEL_A_FLOW_OIL_LEVEL_A_FRead
BV179ALM_LOW_OIL_LEVEL_B_FLOW_OIL_LEVEL_B_FRead
BV180ALM_M_S_CONFIG_FM_S_CONFIG_FRead
BV181ALM_INI_FACT_CONF_FINI_FACT_CONF_FRead
BV182ALM_ILL_FACT_CONF_FILL_FACT_CONF_FRead
BV183ALM_CCN_EMSTOP_FCCN_EMSTOP_FRead
BV184ALM_COOL_PUMP1_FCOOL_PUMP1_FRead
BV185ALM_COOL_PUMP2_FCOOL_PUMP2_FRead
BV186ALM_SCT_OUT_OF_CP_M_A_FSCT_OUT_OF_CP_MAP_A_FRead
BV187ALM_SCT_OUT_OF_CP_M_B_FSCT_OUT_OF_CP_MAP_B_FRead
BV188ALM_REFRIG_ESCAPE_FREFRIGERANT_ESCAPE_FRead
BV189ALM_HIGH_DGT_A_FHIGH_DGT_A_FRead
BV190ALM_HIGH_DGT_B_FHIGH_DGT_B_FRead
BV191ALM_SUCT_VALV_CLOSD_A_FSUCT_VALV_CLOSED_A_FRead
BV192ALM_SUCT_VALV_CLOSD_B_FSUCT_VALV_CLOSED_B_FRead
BV193ALM_COOLER_FLOW_FCOOLER_FLOW_FRead
BV194ALM_SENSORS_SWAP_FSENSORS_SWAP_FRead
BV195ALM_SST_OUT_OF_CP_M_A_FSST_OUT_OF_CP_MAP_A_FRead
BV196ALM_SST_OUT_OF_CP_M_B_FSST_OUT_OF_CP_MAP_B_FRead
BV197ALM_VLT_DRIVE_A_FVLT_DRIVE_A_FRead
BV198ALM_VLT_DRIVE_B_FVLT_DRIVE_B_FRead
BV199ALM_FAN_DRIVE_A1_FFAN_DRIVE_A1_FRead
BV201ALM_FAN_DRIVE_A3_FFAN_DRIVE_A3_FRead
BV202ALM_FAN_DRIVE_B1_FFAN_DRIVE_B1_FRead
BV203ALM_FAN_DRIVE_B2_FFAN_DRIVE_B2_FRead
BV204ALM_FAN_DRIVE_B3_FFAN_DRIVE_B3_FRead
BV205ALM_VLT_DRIVE_A_ALERTVLT_DRIVE_A_ALERTRead
BV206ALM_VLT_DRIVE_B_ALERTVLT_DRIVE_B_ALERTRead
BV207ALM_FAN_DRIVE_A1_ALERTFAN_DRIVE_A1_ALERTRead
BV208ALM_FAN_DRIVE_A2_ALERTFAN_DRIVE_A2_ALERTRead
BV209ALM_FAN_DRIVE_A3_ALERTFAN_DRIVE_A3_ALERTRead
BV210ALM_FAN_DRIVE_B1_ALERTFAN_DRIVE_B1_ALERTRead
BV211ALM_FAN_DRIVE_B2_ALERTFAN_DRIVE_B2_ALERTRead
BV212ALM_FAN_DRIVE_B3_ALERTFAN_DRIVE_B3_ALERTRead
BV213ALM_HIGH_CP_TMP_A_FHIGH_CP_TMP_A_FRead
BV214ALM_HIGH_CP_TMP_B_FHIGH_CP_TMP_B_FRead
BV215ALM_HP_SWITCH_A_FHP_SWITCH_A_FRead
BV216ALM_HP_SWITCH_B_FHP_SWITCH_B_FRead
BV217ALM_DATABASE_FDATABASE_FRead
BV218ALM_LENSCAN_FLENSCAN_FRead
BV219ALM_STEPPER_EXV_A_FSTEPPER_EXV_A_FRead
BV220ALM_STEPPER_EXV_B_FSTEPPER_EXV_B_FRead
BV221ALM_STEPPER_ECO_A_FSTEPPER_ECO_A_FRead
BV222ALM_STEPPER_ECO_B_FSTEPPER_ECO_B_FRead
BV223ALM_VI_DIAG_A_ALERTVI_DIAG_A_ALERTRead
BV224ALM_VI_DIAG_B_ALERTVI_DIAG_B_ALERTRead
TL1TL_STATUSRun StatusWrite
TL2TL_SP_SELSetpoint SelectWrite
TL3TL_DEM_LIMActive Demand Limit ValWrite
TL4TL_COOL_EWTEvap Entering FluidWrite
TL5TL_COOL_LWTEvap Leaving FluidWrite
TL6TL_OATOutdoor Air TemperatureWrite
TL7TL_SCT_ASaturated Cond Tmp Cir AWrite
TL8TL_SST_ASaturated Suction Temp AWrite
TL9TL_DGT_ADischarge Gas Temp Cir AWrite
TL10TL_CP_TMP_AMotor Temperature Cir AWrite
TL11TL_ECO_T_AEXV Eco. Tmp Cir AWrite
TL12TL_SCT_BSaturated Cond Tmp Cir BWrite
TL13TL_SST_BSaturated Suction Temp BWrite
TL14TL_DGT_BDischarge Gas Temp Cir BWrite
TL15TL_CP_TMP_BMotor Temperature Cir BWrite
TL16TL_ECO_T_BEXV Eco. Tmp Cir BWrite
TL17TL_ECO_P_AEconomizer Pressure AWrite
TL18TL_ECO_P_BEconomizer Pressure BWrite
TL19TL_OIL_L_AOil Level Input AWrite
TL20TL_OIL_L_BOil Level Input BWrite
TL21TL_HR_MACHMachine Operating HoursWrite
TL22TL_st_machMachine StartsWrite
TL23TL_HR_CP_ACompressor A HoursWrite
TL24TL_st_cp_aCompressor A StartsWrite
TL25TL_HR_CP_BCompressor B HoursWrite
TL26TL_st_cp_bCompressor B StartsWrite
TL27TL_drv_pwraCir A Drive PowerWrite
TL28TL_drv_IaCir A Drive AmpsWrite
TL29TL_drv_FaCir A Drive FrequencyWrite
TL30TL_drv_pwrbCir B Drive PowerWrite
TL31TL_drv_IbCir B Drive AmpsWrite
TL32TL_drv_FbCir B Drive FrequencyWrite
TL33TL_ov_exv_aEXV Override Circuit AWrite
TL34TL_EXV_AEXV Position Circuit AWrite
TL35TL_ov_exv_bEXV Override Circuit BWrite
TL36TL_EXV_BEXV Position Circuit BWrite
TL37TL_ctrl_wtControled Water TempWrite
TL38TL_overridaOverride Capacity Nb AWrite
TL39TL_cap_pc_aEstimated Capacity AWrite
TL40TL_overridbOverride Capacity Nb BWrite
TL41TL_cap_pc_bEstimated Capacity BWrite
TL42TL_eco_aEXV Eco Position Cir AWrite
TL43TL_eco_bEXV Eco Position Cir BWrite
TL44TL_fan_f_aFan Freq Cir AWrite
TL45TL_fan_f_bFan Freq Cir BWrite
TL46TL_fd_pwra1Fan Drive Power A1Write
TL47TL_fd_pwra2Fan Drive Power A2Write
TL48TL_fd_pwrb1Fan Drive Power B1Write
TL49TL_fd_pwrb2Fan Drive Power B2Write
TL50Trend Log 50Write
Object ID lookup: Carrier AquaForce 30XV 140-500 native BACnet IP points point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points

How many BACnet points does the Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points have?

This list has 800 BACnet objects: 527 analog values, 223 binary values, 50 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points BACnet points are writable?

70 of the 800 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points BACnet documentation?

The source is AquaForce 30XV140-500 Variable Speed Air-Cooled Liquid Chillers - Controls, Start-Up, Operation, Service and Troubleshooting, Appendix E BACnet IP Points (30XV-2T (Cat. 04-53300196-01)), revision 9-17, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0A/30XV-2T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points?

Start with BV 120 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 126 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 525 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 526 GENUNIT_DEM_LIM_wr (Demand limit command); AV 20 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 21 GENUNIT_STATUS (Running status); AV 30 TEMP_COOL_LWT (Leaving chilled water temperature); AV 29 TEMP_COOL_EWT (Entering chilled water temperature); AV 24 GENUNIT_CAP_T (Percent total capacity); AV 109 ALARMRST_ALM (Unit alarm state).

How do I enable BMS control of the Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points?

Network control has to be selected on the chiller (machine control method) before the _wr commands take effect.

How do I check these points on the real AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaForce 30XV140-500 Variable Speed Air-Cooled Liquid Chillers - Controls, Start-Up, Operation, Service and Troubleshooting, Appendix E BACnet IP Points · 30XV-2T (Cat. 04-53300196-01) · rev. 9-17. Object names, instances and units are reproduced as published; descriptions are our own.