Unit ventilator controller (fan coil / terminal unit) · BACnet points list
Carrier Unit Ventilator Open BACnet points list
Updated 4 November 2026
The Unit Vent (OPN-UV) is Carrier's i-Vu Open controller for unit ventilators. DIP switches select BACnet MS/TP (the default), BACnet ARC156, Modbus or N2, and a LonWorks option card is available. The points list has about 70 objects: setpoints, space, supply and outdoor temperatures, valve and damper outputs, enables, alarms and the 'system' points a BAS writes in place of local sensors.
This page lists 71 BACnet objects for the Carrier Unit Ventilator Open — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- Unit Ventilator Open
- Equipment
- Unit ventilator controller (fan coil / terminal unit)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 71 (32 writable)
- Transport
- BACnet MS/TP, BACnet ARC156
- Firmware
- Not stated
- Default device instance
- 16101xx (xx = rotary switch address)
- Also known as
- UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01
Instance calculator. This list prints one unit; the other units follow a formula. Carrier Open controllers (RTU Open, WSHP Open, UPC Open...) instance calculator →
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier Unit Ventilator Open
Set the Unit Vent for BACnet MS/TP with its DIP switches and rotary address. Disable the local Occupancy Schedules so the BAS can command occupancy through keypad_ovrde, then write setpoints directly. Space temperature, CO2, OAT and changeover water temperature from the BMS go into the system_* points at priority 16 and have to be refreshed within each point's window.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1001 | keypad_ovrde | BAS occupancy command: occupied/unoccupied | Write |
| BV 9001 | shutdown | Network shutdown command | Write |
| AV 3001 | occ_cl_stpt | Occupied cooling setpoint | Write |
| AV 3002 | occ_ht_stpt | Occupied heating setpoint | Write |
| MV 2002 | run_status | Current system mode | Read |
| BV 2008 | occ_status | Confirms occupied/unoccupied | Read |
| AV 2007 | space_temp | Space temperature the unit controls to | Read |
| AV 1008 | sa_temp | Supply air temperature | Read |
| BV 7008 | sfan_fail_alarm | Supply fan failure alarm | Read |
| BV 7037 | llt_alarm | Freezestat (low limit) alarm | Read |
Enable & remote start
The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The system-point table says the occupancy control configuration must be set to 3 (BAS On/Off). Shutdown (BV:9001) stops the unit; Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.
Heartbeat & communication loss
No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.
Sensors & values from the BMS
Write system_spt (AV:1902), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so read the matching control point instead (space_temp, iaq, oa_temp, chgovr_mode) at least 30 s after the write.
Network setup
- MS/TP MAC address is set on the Tens and Ones rotary switches (1-99); read only at power-up.
- Device instance defaults to 16101xx (xx = rotary address); it can be changed with an Equipment Touch.
- Baud on DIP switches 1-2 (9600/19.2k/38.4k/76.8k, 76.8k default); DIP 3 and 4 both Off for BACnet MS/TP; 8N1.
- Max Masters defaults to 127 and Max Info Frames to 10 (Equipment Touch). The controller counts as a full load on the MS/TP bus.
Watch out for
- System points must be written at priority 16; writes at any other priority are ignored.
- Never write a system point more than once per minute.
- Only controllers set as MS/TP masters answer Who-Is.
- Demand level points (cool_demand_level, heat_demand_level) are read-only in this list, although the guide says the unit accepts three demand levels from the network.
Carrier Unit Ventilator Open BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1010 | ra_temp | Return Air Temperature | °F | Read | |
| AVmin | 3001 | occ_cl_stpt | Occupied cooling setpoint | °F | Write | |
| AVmin | 3002 | occ_ht_stpt | Occupied heating setpoint | °F | Write | |
| AV | 3003 | unocc_cl_stpt | Unoccupied cooling setpoint | °F | Write | |
| AV | 3004 | unocc_ht_stpt | Unoccupied heating setpoint | °F | Write | |
| BV | 1003 | sfan_status | Supply Fan Status | Read | Off / On | |
| AVmin | 1008 | sa_temp | Supply Air Temperature | °F | Read | |
| AV | 9002 | oat_cl_lockout | Cooling Lockout Temperature (default 45) | °F | Write | |
| AV | 2025 | clg_output | Cooling Output | % | Read | |
| AV | 4004 | oatlecon | Damper Lockout Temp (default 63) | °F | Write | |
| AV | 2022 | oa_dpr_pos | Damper Output | % | Read | |
| AV | 4006 | dmpr_ovrde_val | Damper Setpoint Override Value (default 0) | °F | Write | |
| AV | 9029 | econ_purge_min | Economizer Purge Min Pos (default 40) | %Open | Write | |
| AV | 3005 | eff_cl_stpt | Effective Cool Setpoint | °F | Read | |
| AV | 3006 | eff_ht_stpt | Effective Heat Setpoint | °F | Read | |
| AV | 2019 | filter_service_hrs | Filter Service Alarm Timer (default 600) | hr | Write | |
| AV | 9003 | oat_ht_lockout | Heating Lockout Temperature (default 65) | °F | Write | |
| AV | 2026 | htg_output | Heating Output | % | Read | |
| AV | 9028 | occ_ovr_delay | Occ Override Delay (default 15) | min | Write | |
| AV | 1003 | oa_temp | Outdoor Air Temperature | °F | Read | |
| AV | 2016 | ovrde_time | Override Time Remaining | min | Read | |
| AV | 9007 | start_delay | Power Fail Restart Delay (default 5) | seconds | Write | |
| AV | 1006 | stpt_adj | Setpoint Adjustment | °F | Read | |
| AV | 9015 | stpt_adj_range | Setpoint Adjustment Range (default 5) | °F | Write | |
| AVmin | 2007 | space_temp | Space Temperature - Prime Variable | °F | Read | |
| AV | 1901 | system_oat | System Outdoor Air Temperature (default -999) | °F | Write | |
| AV | 1913 | system_stpt_adj | System Setpoint Adjustment (default -999) | °F | Write | |
| AV | 1903 | system_iaq | System Space AQ (default -999) | Write | ||
| AV | 1902 | system_spt | System Space Temperature (default -999) | °F | Write | |
| AV | 1905 | system_water_temp | System Water Temperature (default -999) | °F | Write | |
| BV | 1014 | chgovr_mode | Changeover Mode | Read | Cool / Heat | |
| BV | 1011 | cl_enable | Cool Enable (default Active (1)) | Write | Disable / Enable | |
| BV | 7017 | filter_alarm | Filter | Read | Clean / Dirty | |
| BV | 7007 | fire_alarm | Fire / Smoke Shutdown alarm | Read | Normal / Alarm | |
| BVmin | 7037 | llt_alarm | Freezestat alarm | Read | Normal / Alarm | |
| BV | 1012 | ht_enable | Heat Enable (default Active (1)) | Write | Disable / Enable | |
| BV | 7011 | spt_hi_alarm | High Space Temperature alarm | Read | Normal / Alarm | |
| BV | 7005 | iaq_alarm | Indoor Air Quality alarm | Read | Normal / Alarm | |
| BV | 7039 | iaq_sensor_fail | Indoor Air Quality Sensor alarm | Read | Normal / Alarm | |
| BV | 7012 | spt_lo_alarm | Low Space Temperature alarm | Read | Normal / Alarm | |
| BVmin | 2008 | occ_status | Occupancy Status | Read | Unoccupied / Occupied | |
| BV | 7036 | oat_alarm | Outdoor Air Temperature alarm | Read | Normal / Alarm | |
| BV | 7517 | filter_rntm_clr | Reset Filter Alarm (default Inactive (0)) | Write | Off / On | |
| BV | 7035 | rat_alarm | Return Air Temperature alarm | Read | Normal / Alarm | |
| BV | 1013 | stpt_adj_enable | Setpoint Adjustment (default Active (1)) | Write | Disable / Enable | |
| BVmin | 9001 | shutdown | Shutdown (default Inactive (0)) | Write | Inactive / Active | |
| BV | 7001 | spt_fail | Space Temp Sensor alarm | Read | Normal / Alarm | |
| BV | 7032 | spt_sensor_fail | SPT Sensor alarm | Read | Normal / Alarm | |
| BV | 7004 | sat_alarm | Supply Air Temperature alarm | Read | Normal / Alarm | |
| BVmin | 7008 | sfan_fail_alarm | Supply Fan Failure | Read | Normal / Alarm | |
| BV | 1016 | fan_cycle | Unoccupied Fan Cycling (default Active (1)) | Write | Disable / Enable | |
| MVmin | 1001 | keypad_ovrde | BAS On / Off (default 1) | Write | 1=Inactive, 2=Occupied, 3=Unoccupied | |
| MV | 2004 | fan_run | Fan / Speed | Read | 1=Off, 2=Low, 3=Med, 4=High, 5=On | |
| MV | 2009 | start_type | Optimal Start Type (default 2) | Write | 1=None, 2=Temp Compensated, 3=Learning Adaptive | |
| MVmin | 2002 | run_status | System Mode | Read | 1=Off, 2=Fan Only, 3=Economize, 4=Cooling, 5=Heating, 6=Cont Fan, 7=Test, 8=Start Delay, 9=Temper SAT, 10=Fire Shutdown, 11=Shutdown, 12=IAQ Override, 12=Pre-occ Purge | |
| AV | 4005 | econ_min | Vent Dmpr Pos / DCV Min Pos (default 20) | % | Write | |
| AV | 1009 | iaq | Indoor Air Quality CO2 (ppm) | ppm | Read | |
| AV | 9026 | optm_start | Optimal Start (default 1) | hr | Write | |
| AV | 83004 | sat_ht_max | Maximum Heating SAT (default 105) | °F | Write | |
| AV | 83003 | sat_cl_min | Minimum Cooling SAT (default 50) | °F | Write | |
| MV | 2003 | spt_status | Space Temp Source | Read | 1=Sensor Failure, 2=SPT Sensor, 3=RAT / T55, 4=Network, 5=Airside Linkage, 6=Locked Value, 7=T-Stat Linkage, 8=ZS Sensor | |
| AV | 9006 | cool_demand_level | System Cooling Demand Level | Read | ||
| AV | 9036 | heat_demand_level | System Heating Demand Level | Read | ||
| AV | 9024 | fan_delay_off | Fan Off Delay (default 90) | seconds | Write | |
| BV | 7034 | chgovr_fail | Changeover Sensor alarm | Read | Normal / Alarm | |
| BV | 7051 | zst_sensor_fail | ZS Temp Sensor alarm | Read | Normal / Alarm | |
| BV | 7055 | zs_config_fail | ZS Sensor Configuration alarm | Read | Normal / Alarm | |
| AV | 9025 | fan_delay_on | Fan On Delay (default 10) | seconds | Write | |
| AV | 2015 | filter_rntm | Filter Runtime | hr | Read | |
| BV | 2801 | t_link_status | Thermostat Linkage | Read | Not Active / Active | |
| BV | 7033 | link_therm_fail | Thermostat Linkage alarm | Read | Normal / Alarm |
No points match these filters.
Object ID lookup: Carrier Unit Ventilator Open point IDs by name
AV1010ra_tempAV3001occ_cl_stptAV3002occ_ht_stptAV3003unocc_cl_stptAV3004unocc_ht_stptBV1003sfan_statusAV1008sa_tempAV9002oat_cl_lockoutAV2025clg_outputAV4004oatleconAV2022oa_dpr_posAV4006dmpr_ovrde_valAV9029econ_purge_minAV3005eff_cl_stptAV3006eff_ht_stptAV2019filter_service_hrsAV9003oat_ht_lockoutAV2026htg_outputAV9028occ_ovr_delayAV1003oa_tempAV2016ovrde_timeAV9007start_delayAV1006stpt_adjAV9015stpt_adj_rangeAV2007space_tempAV1901system_oatAV1913system_stpt_adjAV1903system_iaqAV1902system_sptAV1905system_water_tempBV1014chgovr_modeBV1011cl_enableBV7017filter_alarmBV7007fire_alarmBV7037llt_alarmBV1012ht_enableBV7011spt_hi_alarmBV7005iaq_alarmBV7039iaq_sensor_failBV7012spt_lo_alarmBV2008occ_statusBV7036oat_alarmBV7517filter_rntm_clrBV7035rat_alarmBV1013stpt_adj_enableBV9001shutdownBV7001spt_failBV7032spt_sensor_failBV7004sat_alarmBV7008sfan_fail_alarmBV1016fan_cycleMV1001keypad_ovrdeMV2004fan_runMV2009start_typeMV2002run_statusAV4005econ_minAV1009iaqAV9026optm_startAV83004sat_ht_maxAV83003sat_cl_minMV2003spt_statusAV9006cool_demand_levelAV9036heat_demand_levelAV9024fan_delay_offBV7034chgovr_failBV7051zst_sensor_failBV7055zs_config_failAV9025fan_delay_onAV2015filter_rntmBV2801t_link_statusBV7033link_therm_fail
Integration notes
- System points (system_spt, system_iaq, system_oat, system_stpt_adj, system_water_temp) must be written at BACnet priority 16 and no more than once a minute; -999 means no network value.
- The guide's general system-point table also lists system_rh (AV:1904), system_oaq (AV:1908), oae (BV:1901), press_override (BV:1906) and fire_shutdown (BV:1907). They are not in the Unit Vent points list, so they are left out here.
- Four rows are printed with the display name 'Setpoint'; the descriptions here say which setpoint each object name is.
- System Mode (run_status) prints state 12 twice (IAQ Override and Pre-occ Purge); kept as printed.
- Defaults in the points list differ from the sequence text for the fan delays (Fan Off Delay 90 s vs 120 s, Fan On Delay 10 s vs 30 s); check on the controller.
- Each point also has a Modbus register in the same table (some later rows have none); only the BACnet side is captured here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Unit Ventilator Open and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier Unit Ventilator Open
How many BACnet points does the Carrier Unit Ventilator Open have?
This list has 71 BACnet objects: 39 analog values, 27 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier Unit Ventilator Open BACnet points are writable?
32 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier Unit Ventilator Open BACnet documentation?
The source is Unit Ventilator Integration Guide (Appendix A: Unit Vent Network Points List) (11-808-513-01), revision 2022-08-02, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/0D/11-808-513-01.pdf.
What are the minimum BACnet points to integrate the Carrier Unit Ventilator Open?
Start with MV 1001 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (Current system mode); BV 2008 occ_status (Confirms occupied/unoccupied); AV 2007 space_temp (Space temperature the unit controls to); AV 1008 sa_temp (Supply air temperature); BV 7008 sfan_fail_alarm (Supply fan failure alarm); BV 7037 llt_alarm (Freezestat (low limit) alarm).
How do I enable BMS control of the Carrier Unit Ventilator Open?
The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The system-point table says the occupancy control configuration must be set to 3 (BAS On/Off). Shutdown (BV:9001) stops the unit; Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.
Does the Carrier Unit Ventilator Open need a BACnet heartbeat or have a communication timeout?
No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.
Can the BMS supply sensor values to the Carrier Unit Ventilator Open?
Write system_spt (AV:1902), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so read the matching control point instead (space_temp, iaq, oa_temp, chgovr_mode) at least 30 s after the write.
How do I check these points on the real Unit Ventilator Open?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Unit Ventilator Integration Guide (Appendix A: Unit Vent Network Points List) · 11-808-513-01 · rev. 2022-08-02. Object names, instances and units are reproduced as published; descriptions are our own.