Unit ventilator controller (fan coil / terminal unit) · BACnet points list

Carrier Unit Ventilator Open BACnet points list

Updated 4 November 2026

Short answer

The Unit Vent (OPN-UV) is Carrier's i-Vu Open controller for unit ventilators. DIP switches select BACnet MS/TP (the default), BACnet ARC156, Modbus or N2, and a LonWorks option card is available. The points list has about 70 objects: setpoints, space, supply and outdoor temperatures, valve and damper outputs, enables, alarms and the 'system' points a BAS writes in place of local sensors.

This page lists 71 BACnet objects for the Carrier Unit Ventilator Open — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
Unit Ventilator Open
Equipment
Unit ventilator controller (fan coil / terminal unit)
Equipment type
VAV boxes & fan coils
BACnet objects
71 (32 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Not stated
Default device instance
16101xx (xx = rotary switch address)
Also known as
UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01
Source document
Unit Ventilator Integration Guide (Appendix A: Unit Vent Network Points List) · 11-808-513-01 · rev. 2022-08-02

Instance calculator. This list prints one unit; the other units follow a formula. Carrier Open controllers (RTU Open, WSHP Open, UPC Open...) instance calculator →

Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier Unit Ventilator Open

Integration in brief

Set the Unit Vent for BACnet MS/TP with its DIP switches and rotary address. Disable the local Occupancy Schedules so the BAS can command occupancy through keypad_ovrde, then write setpoints directly. Space temperature, CO2, OAT and changeover water temperature from the BMS go into the system_* points at priority 16 and have to be refreshed within each point's window.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1001keypad_ovrdeBAS occupancy command: occupied/unoccupiedWrite
BV 9001shutdownNetwork shutdown commandWrite
AV 3001occ_cl_stptOccupied cooling setpointWrite
AV 3002occ_ht_stptOccupied heating setpointWrite
MV 2002run_statusCurrent system modeRead
BV 2008occ_statusConfirms occupied/unoccupiedRead
AV 2007space_tempSpace temperature the unit controls toRead
AV 1008sa_tempSupply air temperatureRead
BV 7008sfan_fail_alarmSupply fan failure alarmRead
BV 7037llt_alarmFreezestat (low limit) alarmRead

Enable & remote start

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The system-point table says the occupancy control configuration must be set to 3 (BAS On/Off). Shutdown (BV:9001) stops the unit; Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Heartbeat & communication loss

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.

Sensors & values from the BMS

Write system_spt (AV:1902), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so read the matching control point instead (space_temp, iaq, oa_temp, chgovr_mode) at least 30 s after the write.

Network setup

Watch out for

Carrier Unit Ventilator Open BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

71 of 71 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier Unit Ventilator Open BACnet Points List
DescriptionStates
AV1010ra_tempReturn Air Temperature°FRead
AVmin3001occ_cl_stptOccupied cooling setpoint°FWrite
AVmin3002occ_ht_stptOccupied heating setpoint°FWrite
AV3003unocc_cl_stptUnoccupied cooling setpoint°FWrite
AV3004unocc_ht_stptUnoccupied heating setpoint°FWrite
BV1003sfan_statusSupply Fan StatusReadOff / On
AVmin1008sa_tempSupply Air Temperature°FRead
AV9002oat_cl_lockoutCooling Lockout Temperature (default 45)°FWrite
AV2025clg_outputCooling Output%Read
AV4004oatleconDamper Lockout Temp (default 63)°FWrite
AV2022oa_dpr_posDamper Output%Read
AV4006dmpr_ovrde_valDamper Setpoint Override Value (default 0)°FWrite
AV9029econ_purge_minEconomizer Purge Min Pos (default 40)%OpenWrite
AV3005eff_cl_stptEffective Cool Setpoint°FRead
AV3006eff_ht_stptEffective Heat Setpoint°FRead
AV2019filter_service_hrsFilter Service Alarm Timer (default 600)hrWrite
AV9003oat_ht_lockoutHeating Lockout Temperature (default 65)°FWrite
AV2026htg_outputHeating Output%Read
AV9028occ_ovr_delayOcc Override Delay (default 15)minWrite
AV1003oa_tempOutdoor Air Temperature°FRead
AV2016ovrde_timeOverride Time RemainingminRead
AV9007start_delayPower Fail Restart Delay (default 5)secondsWrite
AV1006stpt_adjSetpoint Adjustment°FRead
AV9015stpt_adj_rangeSetpoint Adjustment Range (default 5)°FWrite
AVmin2007space_tempSpace Temperature - Prime Variable°FRead
AV1901system_oatSystem Outdoor Air Temperature (default -999)°FWrite
AV1913system_stpt_adjSystem Setpoint Adjustment (default -999)°FWrite
AV1903system_iaqSystem Space AQ (default -999)Write
AV1902system_sptSystem Space Temperature (default -999)°FWrite
AV1905system_water_tempSystem Water Temperature (default -999)°FWrite
BV1014chgovr_modeChangeover ModeReadCool / Heat
BV1011cl_enableCool Enable (default Active (1))WriteDisable / Enable
BV7017filter_alarmFilterReadClean / Dirty
BV7007fire_alarmFire / Smoke Shutdown alarmReadNormal / Alarm
BVmin7037llt_alarmFreezestat alarmReadNormal / Alarm
BV1012ht_enableHeat Enable (default Active (1))WriteDisable / Enable
BV7011spt_hi_alarmHigh Space Temperature alarmReadNormal / Alarm
BV7005iaq_alarmIndoor Air Quality alarmReadNormal / Alarm
BV7039iaq_sensor_failIndoor Air Quality Sensor alarmReadNormal / Alarm
BV7012spt_lo_alarmLow Space Temperature alarmReadNormal / Alarm
BVmin2008occ_statusOccupancy StatusReadUnoccupied / Occupied
BV7036oat_alarmOutdoor Air Temperature alarmReadNormal / Alarm
BV7517filter_rntm_clrReset Filter Alarm (default Inactive (0))WriteOff / On
BV7035rat_alarmReturn Air Temperature alarmReadNormal / Alarm
BV1013stpt_adj_enableSetpoint Adjustment (default Active (1))WriteDisable / Enable
BVmin9001shutdownShutdown (default Inactive (0))WriteInactive / Active
BV7001spt_failSpace Temp Sensor alarmReadNormal / Alarm
BV7032spt_sensor_failSPT Sensor alarmReadNormal / Alarm
BV7004sat_alarmSupply Air Temperature alarmReadNormal / Alarm
BVmin7008sfan_fail_alarmSupply Fan FailureReadNormal / Alarm
BV1016fan_cycleUnoccupied Fan Cycling (default Active (1))WriteDisable / Enable
MVmin1001keypad_ovrdeBAS On / Off (default 1)Write1=Inactive, 2=Occupied, 3=Unoccupied
MV2004fan_runFan / SpeedRead1=Off, 2=Low, 3=Med, 4=High, 5=On
MV2009start_typeOptimal Start Type (default 2)Write1=None, 2=Temp Compensated, 3=Learning Adaptive
MVmin2002run_statusSystem ModeRead1=Off, 2=Fan Only, 3=Economize, 4=Cooling, 5=Heating, 6=Cont Fan, 7=Test, 8=Start Delay, 9=Temper SAT, 10=Fire Shutdown, 11=Shutdown, 12=IAQ Override, 12=Pre-occ Purge
AV4005econ_minVent Dmpr Pos / DCV Min Pos (default 20)%Write
AV1009iaqIndoor Air Quality CO2 (ppm)ppmRead
AV9026optm_startOptimal Start (default 1)hrWrite
AV83004sat_ht_maxMaximum Heating SAT (default 105)°FWrite
AV83003sat_cl_minMinimum Cooling SAT (default 50)°FWrite
MV2003spt_statusSpace Temp SourceRead1=Sensor Failure, 2=SPT Sensor, 3=RAT / T55, 4=Network, 5=Airside Linkage, 6=Locked Value, 7=T-Stat Linkage, 8=ZS Sensor
AV9006cool_demand_levelSystem Cooling Demand LevelRead
AV9036heat_demand_levelSystem Heating Demand LevelRead
AV9024fan_delay_offFan Off Delay (default 90)secondsWrite
BV7034chgovr_failChangeover Sensor alarmReadNormal / Alarm
BV7051zst_sensor_failZS Temp Sensor alarmReadNormal / Alarm
BV7055zs_config_failZS Sensor Configuration alarmReadNormal / Alarm
AV9025fan_delay_onFan On Delay (default 10)secondsWrite
AV2015filter_rntmFilter RuntimehrRead
BV2801t_link_statusThermostat LinkageReadNot Active / Active
BV7033link_therm_failThermostat Linkage alarmReadNormal / Alarm
Object ID lookup: Carrier Unit Ventilator Open point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Unit Ventilator Open and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier Unit Ventilator Open

How many BACnet points does the Carrier Unit Ventilator Open have?

This list has 71 BACnet objects: 39 analog values, 27 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier Unit Ventilator Open BACnet points are writable?

32 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier Unit Ventilator Open BACnet documentation?

The source is Unit Ventilator Integration Guide (Appendix A: Unit Vent Network Points List) (11-808-513-01), revision 2022-08-02, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/0D/11-808-513-01.pdf.

What are the minimum BACnet points to integrate the Carrier Unit Ventilator Open?

Start with MV 1001 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (Current system mode); BV 2008 occ_status (Confirms occupied/unoccupied); AV 2007 space_temp (Space temperature the unit controls to); AV 1008 sa_temp (Supply air temperature); BV 7008 sfan_fail_alarm (Supply fan failure alarm); BV 7037 llt_alarm (Freezestat (low limit) alarm).

How do I enable BMS control of the Carrier Unit Ventilator Open?

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The system-point table says the occupancy control configuration must be set to 3 (BAS On/Off). Shutdown (BV:9001) stops the unit; Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Does the Carrier Unit Ventilator Open need a BACnet heartbeat or have a communication timeout?

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.

Can the BMS supply sensor values to the Carrier Unit Ventilator Open?

Write system_spt (AV:1902), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so read the matching control point instead (space_temp, iaq, oa_temp, chgovr_mode) at least 30 s after the write.

How do I check these points on the real Unit Ventilator Open?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Unit Ventilator Integration Guide (Appendix A: Unit Vent Network Points List) · 11-808-513-01 · rev. 2022-08-02. Object names, instances and units are reproduced as published; descriptions are our own.