- Home
- BACnet points lists
- Carrier
- 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Water-cooled chiller and water-to-water heat pump controller · BACnet points list
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet points list
Updated 7 November 2026
These units speak BACnet IP when option 149 is activated with a software key. The object list has 274 objects: command objects written by the BMS carry a _wr suffix (start/stop, control point, demand limit, heat/cool select, occupancy), with read-back copies marked _rd, plus water temperatures, capacity, circuit data and one BV per alarm.
This page lists 274 BACnet objects for the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
- Equipment
- Water-cooled chiller and water-to-water heat pump controller
- Equipment type
- Chillers
- BACnet objects
- 274 (16 writable)
- Transport
- BACnet IP
- Firmware
- SmartVu PIC 6.0 SR 11.x / SmartVu 2.0 PIC 6.1 SR 1.x
- Default device instance
- 1600001
- Also known as
- 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Activate option 149 with the software key, enable BACnet in the Network menu (BACnet Standard Conf.), and set the operating type to Network. Then command the unit through the _wr objects: start/stop, control point, demand limit and heat/cool select, and read status, water temperatures, capacity and the alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 139 | GENUNIT_CHIL_OCC_wr | Network occupancy command | Write |
| AV 136 | GENUNIT_HC_SEL_wr | Heat/cool select command | Write |
| AV 1 | GENUNIT_CTRL_PNT_wr | Control point (water temperature) from the BMS | Write |
| AV 2 | GENUNIT_DEM_LIM_wr | Demand limit command (%) | Write |
| AV 12 | GENUNIT_CTRL_TYP | Control type: 0=Local, 1=Network, 2=Remote | Read |
| AV 13 | GENUNIT_STATUS | Running status | Read |
| AV 22 | TEMP_LWT | Leaving water temperature | Read |
| AV 16 | GENUNIT_CAP_T | Percent total capacity | Read |
| AV 14 | ALARMRST_ALM | Unit alarm status | Read |
Enable & remote start
The unit follows network commands only in Network operating type. In Network mode the start/stop and occupancy commands can be forced from the BMS; the network emergency stop works in any operating type.
Network setup
- BACnet (option 149) needs a Software Activation Key before it can be enabled.
- BACnet Standard Conf. defaults: BACnet Enable = disable, network 1600, UDP port 47808, manual device ID 1600001, auto device ID off.
- IP port interface name (conifnam) selects J5/J15 (0) or J16 (1).
Watch out for
- Write the _wr objects; the _rd copies only report the active value.
- BACnet_BMS_OCC (AV 144: 0=unocc, 1=occ, 2=none) works with the BACnet Manage Occupancy setting (mng_occ, default no); check how it interacts with CHIL_OCC before relying on it.
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | GENUNIT_CHIL_S_S_wr | Chiller Start/Stop order | Write | ||
| AVmin | 1 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 2 | GENUNIT_DEM_LIM_wr | Demand Limit | Write | ||
| AV | 3 | GENCONF_off_on_d | Unit Off to On Delay | Read | ||
| AV | 4 | PUMPCONF_clpmpseq | Cooler Pumps Sequence | Read | ||
| AV | 5 | PUMPCONF_clpmpsby | Cool Pump Stopped in Sby | Read | ||
| AV | 6 | PUMPCONF_clpmploc | Flow Checked if Pump Off | Read | ||
| AV | 7 | PUMPCONF_cdpmpseq | Condenser Pumps Sequence | Read | ||
| AV | 8 | PUMPCONF_cdpmpsby | Cond Pump Stopped in Sby | Read | ||
| AV | 9 | PUMPCONF_cdpmploc | Flow Checked if Pump Off | Read | ||
| AV | 10 | HCCONFIG_cr_sel | Cooling Reset Select | Read | ||
| AV | 11 | HCCONFIG_hr_sel | Heating Reset Select | Read | ||
| BV | 2 | HCCONFIG_boil_on_wr | Boiler Manual Command | Write | ||
| AVmin | 12 | GENUNIT_CTRL_TYP | Control type | Read | 0=Local, 1=Network, 2=Remote | |
| AVmin | 13 | GENUNIT_STATUS | Running Status | Read | ||
| AVmin | 14 | ALARMRST_ALM | Alarm Status | Read | ||
| AV | 15 | GENUNIT_HEATCOOL | Heat/Cool Status | Read | ||
| BV | 3 | GENUNIT_CHIL_S_S_rd | Net.: Cmd Start/Stop | Read | ||
| AVmin | 16 | GENUNIT_CAP_T | Percent Total Capacity | Read | ||
| AV | 17 | GENUNIT_CAPA_T | Circuit A Total Capacity | Read | ||
| AV | 18 | GENUNIT_CAPB_T | Circuit B Total Capacity | Read | ||
| AV | 19 | GENUNIT_DEM_LIM_rd | Active Demand Limit Val | Read | ||
| AV | 20 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AV | 21 | TEMP_EWT | Entering Water Temp | Read | ||
| AVmin | 22 | TEMP_LWT | Leaving Water Temp | Read | ||
| AV | 23 | TEMP_OAT | Outside Air Temperature | Read | ||
| AV | 24 | TEMP_CHWSTEMP | Chilled Water Syst Temp | Read | ||
| AV | 25 | TEMP_HTWSTEMP | Heat Water Syst Temp | Read | ||
| AV | 26 | TEMP_DGT_A | Discharge Gas Temp cir A | Read | ||
| AV | 27 | TEMP_SCT_A | Saturated Condens Tp A | Read | ||
| AV | 28 | TEMP_SST_A | Saturated Suction Tp A | Read | ||
| AV | 29 | TEMP_DGT_B | Discharge Gas Temp cir B | Read | ||
| AV | 30 | TEMP_SCT_B | Saturated Condens Tp B | Read | ||
| AV | 31 | TEMP_SST_B | Saturated Suction Tp B | Read | ||
| AV | 32 | TEMP_COND_EWT | Cond Entering Water Temp | Read | ||
| AV | 33 | TEMP_COND_LWT | Cond Leaving Water Temp | Read | ||
| AV | 34 | PRESSURE_DP_A | Discharge Pressure A | Read | ||
| AV | 35 | PRESSURE_SP_A | Suction Pressure A | Read | ||
| AV | 36 | PRESSURE_DP_B | Discharge Pressure B | Read | ||
| AV | 37 | PRESSURE_SP_B | Suction Pressure B | Read | ||
| BV | 4 | INPUTS_ONOFF_SW | On/Off - Remote Switch | Read | ||
| BV | 5 | INPUTS_FLOW_SW | Exchanger Flow Switch | Read | ||
| BV | 6 | OUTPUTS_CP_A1 | Compressor A1 Output | Read | ||
| BV | 7 | OUTPUTS_CP_A2 | Compressor A2 Output | Read | ||
| BV | 8 | OUTPUTS_CP_A3 | Compressor A3 Output | Read | ||
| BV | 9 | OUTPUTS_CP_B1 | Compressor B1 Output | Read | ||
| BV | 10 | OUTPUTS_CP_B2 | Compressor B2 Output | Read | ||
| AV | 38 | OUTPUTS_EXVPosA | EXV Position Circuit A | Read | ||
| AV | 39 | OUTPUTS_EXVPosB | EXV Position Circuit B | Read | ||
| BV | 11 | PUMPSTAT_CL_PUMP1 | Cooler Pump 1 Command | Read | ||
| BV | 12 | PUMPSTAT_CL_PUMP2 | Cooler Pump 2 Command | Read | ||
| AV | 40 | PUMPSTAT_CL_WPIN | Cool Inlet Water Press | Read | ||
| AV | 41 | PUMPSTAT_CL_WPOUT | Cool Outlet Water Press | Read | ||
| AV | 42 | PUMPSTAT_CL_FILTR | Cool delta press. filt | Read | ||
| AV | 43 | PUMPSTAT_CL_WPMIN | Cool mini water pressure | Read | ||
| AV | 44 | PUMPSTAT_CL_WFLOW | Cool Water flow | Read | ||
| AV | 45 | PUMPSTAT_CL_DvPos | Cool Pump drive position | Read | ||
| BV | 13 | PUMPSTAT_CD_PUMP1 | Cond Pump 1 Command | Read | ||
| BV | 14 | PUMPSTAT_CD_PUMP2 | Cond Pump 2 Command | Read | ||
| AV | 46 | PUMPSTAT_CD_WPIN | Cond Inlet Water Press | Read | ||
| AV | 47 | PUMPSTAT_CD_WPOUT | Cond Outlet Water Press | Read | ||
| AV | 48 | PUMPSTAT_CD_FILTR | Cond delta press. filt | Read | ||
| AV | 49 | PUMPSTAT_CD_WPMIN | Cond mini water pressure | Read | ||
| AV | 50 | PUMPSTAT_CD_WFLOW | Cond Water flow | Read | ||
| AV | 51 | PUMPSTAT_CD_DvPos | Cond Pump drive position | Read | ||
| AV | 52 | RUNTIME_hr_mach | Machine Operating Hours | Read | ||
| AV | 53 | RUNTIME_chr_mach | Cooling Operating Hours | Read | ||
| AV | 54 | RUNTIME_hhr_mach | Heating Operating Hours | Read | ||
| AV | 55 | RUNTIME_st_mach | Machine Starts | Read | ||
| AV | 56 | RUNTIME_hr_cp_a1 | Compressor A1 Hours | Read | ||
| AV | 57 | RUNTIME_hr_cp_a2 | Compressor A2 Hours | Read | ||
| AV | 58 | RUNTIME_hr_cp_a3 | Compressor A3 Hours | Read | ||
| AV | 59 | RUNTIME_hr_cp_b1 | Compressor B1 Hours | Read | ||
| AV | 60 | RUNTIME_hr_cp_b2 | Compressor B2 Hours | Read | ||
| AV | 61 | RUNTIME_st_cp_a1 | Compressor A1 Starts | Read | ||
| AV | 62 | RUNTIME_st_cp_a2 | Compressor A2 Starts | Read | ||
| AV | 63 | RUNTIME_st_cp_a3 | Compressor A3 Starts | Read | ||
| AV | 64 | RUNTIME_st_cp_b1 | Compressor B1 Starts | Read | ||
| AV | 65 | RUNTIME_st_cp_b2 | Compressor B2 Starts | Read | ||
| AV | 66 | LOADFACT_ctrl_avg | Average Ctrl Water Temp | Read | ||
| AV | 67 | LOADFACT_delta_t | Water Delta T | Read | ||
| AV | 68 | LOADFACT_zm | Current Z Multiplier Val | Read | ||
| AV | 69 | LOADFACT_smz | Load/Unload Factor | Read | ||
| AV | 70 | LOADFACT_over_cap | Active Capacity Override | Read | ||
| AV | 71 | LOADFACT_SUCT_T_A | Suction Gas Temp A | Read | ||
| AV | 72 | LOADFACT_SUCT_T_B | Suction Gas Temp B | Read | ||
| AV | 73 | LOADFACT_SH_A | Suction Superheat A | Read | ||
| AV | 74 | LOADFACT_SH_B | Suction Superheat B | Read | ||
| AV | 75 | LOADFACT_pinch_a | Cooler Exchange DT Cir A | Read | ||
| AV | 76 | LOADFACT_pinch_b | Cooler Exchange DT Cir B | Read | ||
| AV | 77 | LOADFACT_ov_exv_a | EXV Override Circuit A | Read | ||
| AV | 78 | LOADFACT_ov_exv_b | EXV Override Circuit B | Read | ||
| AV | 79 | SETPOINT_cond_sp | Condensing Setpoint | Read | ||
| AV | 80 | UNIT_ms_ctrl | Master Control Type uchar | Read | ||
| AV | 81 | M_MSTSLV_ms_activ | Master/Slave Ctrl Active | Read | ||
| AV | 82 | M_MSTSLV_lead_sel | Lead Unit is the: | Read | ||
| AV | 83 | M_MSTSLV_slv_stat | Slave Chiller State | Read | ||
| AV | 84 | M_MSTSLV_slv_capt | Slave Chiller Total Cap | Read | ||
| AV | 85 | M_MSTSLV_ms_error | Master/Slave Error | Read | ||
| AV | 86 | LAST_POR_date_on1 | Power On 1: day-mon-year | Read | ||
| AV | 87 | LAST_POR_date_on2 | Power On 2: day-mon-year | Read | ||
| AV | 88 | LAST_POR_date_on3 | Power On 3: day-mon-year | Read | ||
| AV | 89 | LAST_POR_date_on4 | Power On 4: day-mon-year | Read | ||
| AV | 90 | LAST_POR_date_on5 | Power On 5: day-mon-year | Read | ||
| AV | 91 | LAST_POR_time_on1 | Power On 1: hour-minute | Read | ||
| AV | 92 | LAST_POR_time_on2 | Power On 2: hour-minute | Read | ||
| AV | 93 | LAST_POR_time_on3 | Power On 3: hour-minute | Read | ||
| AV | 94 | LAST_POR_time_on4 | Power On 4: hour-minute | Read | ||
| AV | 95 | LAST_POR_time_on5 | Power On 5: hour-minute | Read | ||
| AV | 96 | LAST_POR_date_of1 | PowerDown 1:day-mon-year | Read | ||
| AV | 97 | LAST_POR_date_of2 | PowerDown 2:day-mon-year | Read | ||
| AV | 98 | LAST_POR_date_of3 | PowerDown 3:day-mon-year | Read | ||
| AV | 99 | LAST_POR_date_of4 | PowerDown 4:day-mon-year | Read | ||
| AV | 100 | LAST_POR_date_of5 | PowerDown 5:day-mon-year | Read | ||
| AV | 101 | LAST_POR_time_of1 | PowerDown 1:hour-minute | Read | ||
| AV | 102 | LAST_POR_time_of2 | PowerDown 2:hour-minute | Read | ||
| AV | 103 | LAST_POR_time_of3 | PowerDown 3:hour-minute | Read | ||
| AV | 104 | LAST_POR_time_of4 | PowerDown 4:hour-minute | Read | ||
| AV | 105 | LAST_POR_time_of5 | PowerDown 5:hour-minute | Read | ||
| AV | 106 | ALARMRST_alarm_1c | Current Alarm 1 | Read | ||
| AV | 107 | ALARMRST_alarm_2c | Current Alarm 2 | Read | ||
| AV | 108 | ALARMRST_alarm_3c | Current Alarm 3 | Read | ||
| AV | 109 | ALARMRST_alarm_4c | Current Alarm 4 | Read | ||
| AV | 110 | ALARMRST_alarm_5c | Current Alarm 5 | Read | ||
| BV | 15 | CP_UNABL_un_cp_a1 | Compressor A1 Disable | Read | ||
| BV | 16 | CP_UNABL_un_cp_a2 | Compressor A2 Disable | Read | ||
| BV | 17 | CP_UNABL_un_cp_a3 | Compressor A3 Disable | Read | ||
| BV | 18 | CP_UNABL_un_cp_b1 | Compressor B1 Disable | Read | ||
| BV | 19 | CP_UNABL_un_cp_b2 | Compressor B2 Disable | Read | ||
| AV | 111 | MST_SLV_ms_sel | Master/Slave Select | Read | ||
| AV | 112 | MST_SLV_ms_ctrl | Master Control Type | Read | ||
| AV | 113 | MST_SLV_slv_addr | Slave Address | Read | ||
| BV | 20 | MST_SLV_lag_pump | Lag Unit Pump Control | Read | ||
| AV | 114 | FACTORY_flui_typ | Fluid Type | Read | ||
| BV | 21 | GENCONF_ewt_opt | Entering Fluid Control | Read | ||
| AV | 115 | SERVICE1_sh_sp_a | EXV A Superheat Setpoint | Read | ||
| AV | 116 | SERVICE1_sh_sp_b | EXV B Superheat Setpoint | Read | ||
| AV | 117 | SERVICE1_mop_sp | EXV MOP Setpoint | Read | ||
| AV | 118 | SERVICE1_hp_th | High Pressure Threshold | Read | ||
| AV | 119 | SERVICE1_pump_cyc | Pump Cycling Freeze Prot | Read | ||
| AV | 120 | SERVICE1_freezesp | Brine Freeze Setpoint | Read | ||
| AV | 121 | SERVICE1_min_lwt | Brine Minimum LWT | Read | ||
| AV | 122 | SERVICE1_zm_spt | Auto Z Multiplier | Read | ||
| AV | 123 | SERVICE1_hc_zm | Maximum Z Multiplier | Read | ||
| AV | 124 | PUMPCONF_cl_w_ct | Cool Flow Ctrl Method | Read | ||
| AV | 125 | PUMPCONF_clwdtspt | Cool Flow DT setpoint | Read | ||
| AV | 126 | PUMPCONF_clwdpspt | Cool Flow DP Setpoint | Read | ||
| AV | 127 | SERVICE1_cl_med_t | Cooler Water Medium Type | Read | ||
| AV | 128 | SERVICE1_cl_med_p | Cooler Water Medium Pct | Read | ||
| AV | 129 | PUMPCONF_cd_w_ct | Cond Flow Ctrl Method | Read | ||
| AV | 130 | PUMPCONF_cdwdtspt | Cond Flow DT setpoint | Read | ||
| AV | 131 | PUMPCONF_cdwdpspt | Cond Flow DP Setpoint | Read | ||
| AV | 132 | SERVICE1_cd_med_t | Conden Water Medium Type | Read | ||
| AV | 133 | SERVICE1_cd_med_p | Conden Water Medium Pct | Read | ||
| BV | 24 | ALM_COOL_EWT_F | Water Exchanger Entering Fluid Thermistor Failure | Read | ||
| BV | 25 | ALM_COOL_LWT_F | Water Exchanger Leaving Fluid Thermistor Failure | Read | ||
| BV | 26 | ALM_COND_EWT_F | Condenser Entering Fluid Thermistor Failure | Read | ||
| BV | 27 | ALM_COND_LWT_F | Condenser Leaving Fluid Thermistor Failure | Read | ||
| BV | 28 | ALM_OAT_F | OAT Thermistor Failure | Read | ||
| BV | 29 | ALM_CHWSTEMP_F | Master/Slave Common Fluid Thermistor Failure | Read | ||
| BV | 30 | ALM_SUCTION_T_A_F | Circuit A Suction Gas Thermistor Failure | Read | ||
| BV | 31 | ALM_SUCTION_T_B_F | Circuit B Suction Gas Thermistor Failure | Read | ||
| BV | 32 | ALM_HTWSTEMP_F | Master/Slave Common Heating Fluid Thermistor Failure | Read | ||
| BV | 33 | ALM_DRY_LWT_F | Dry Cooler LWT Thermistor Failure | Read | ||
| BV | 34 | ALM_DGT_A_F | Circuit A Discharge Gas Thermistor Failure | Read | ||
| BV | 35 | ALM_DGT_B_F | Circuit B Discharge Gas Thermistor Failure | Read | ||
| BV | 36 | ALM_DP_A_F | Circuit A Discharge Pressure Transducer Failure | Read | ||
| BV | 37 | ALM_DP_B_F | Circuit B Discharge Pressure Transducer Failure | Read | ||
| BV | 38 | ALM_SP_A_F | Circuit A Suction Pressure Transducer Failure | Read | ||
| BV | 39 | ALM_SP_B_F | Circuit B Suction Pressure Transducer Failure | Read | ||
| BV | 40 | ALM_CL_WP_IN_F | Water Exchanger Entering Fluid Transducer Failure | Read | ||
| BV | 41 | ALM_CL_WP_OUT_F | Water Exchanger Leaving Fluid Transducer Failure | Read | ||
| BV | 42 | ALM_CD_WP_IN_F | Water Condenser Entering Fluid Transducer Failure | Read | ||
| BV | 43 | ALM_CD_WP_OUT_F | Water Condenser Leaving Fluid Transducer Failure | Read | ||
| BV | 44 | ALM_SIOB_A_COM_F | Loss of communication with SIOB Board Number 1 | Read | ||
| BV | 45 | ALM_SIOB_B_COM_F | Loss of communication with SIOB Board Number 2 | Read | ||
| BV | 46 | ALM_AUX1_HEATER_COM_F | Loss of communication with AUX1 Heating Device Control board | Read | ||
| BV | 47 | ALM_AUX1_DRYC_COM_F | Loss of communication with AUX1 Condenser board | Read | ||
| BV | 48 | ALM_AUX1_FREECOOL_COM_F | Loss of communication with AUX1 FreeCooling board | Read | ||
| BV | 49 | ALM_AUX1_OPTION_COM_F | Loss of communication with AUX1 Options board | Read | ||
| BV | 50 | ALM_FC_AUX1_COM_F | Loss of communication with Free Cooling Board 1 | Read | ||
| BV | 51 | ALM_COOLER_FREEZE_F | Cooler Water Exchanger Freeze Protection | Read | ||
| BV | 52 | ALM_LOW_SUCTION_A_F | Circuit A Low Saturated Suction Temperature | Read | ||
| BV | 53 | ALM_LOW_SUCTION_B_F | Circuit B Low Saturated Suction Temperature | Read | ||
| BV | 54 | ALM_HIGH_SH_A_F | Circuit A High Suction Superheat | Read | ||
| BV | 55 | ALM_HIGH_SH_B_F | Circuit B High Suction Superheat | Read | ||
| BV | 56 | ALM_LOW_SH_A_F | Circuit A Low Suction Superheat | Read | ||
| BV | 57 | ALM_LOW_SH_B_F | Circuit B Low Suction Superheat | Read | ||
| BV | 58 | ALM_CONDENSER_LOCK_F | Condenser Flow Switch Failure | Read | ||
| BV | 59 | ALM_CPA1_REVERSE_ROT_F | Compressor A1 Not Started Or Pressure Increase not Established | Read | ||
| BV | 60 | ALM_CPA2_REVERSE_ROT_F | Compressor A2 Not Started Or Pressure Increase not Established | Read | ||
| BV | 61 | ALM_CPA3_REVERSE_ROT_F | Compressor A3 Not Started Or Pressure Increase not Established | Read | ||
| BV | 62 | ALM_CPB1_REVERSE_ROT_F | Compressor B1 Not Started Or Pressure Increase not Established | Read | ||
| BV | 63 | ALM_CPB2_REVERSE_ROT_F | Compressor B2 Not Started Or Pressure Increase not Established | Read | ||
| BV | 64 | ALM_LOCK_SW_F | Customer Interlock Failure | Read | ||
| BV | 65 | ALM_LOSS_COM_SM_F | Loss of communication with System Manager | Read | ||
| BV | 66 | ALM_LOSS_COM_MS_F | Master/Slave communication Failure | Read | ||
| BV | 67 | ALM_NETWORK_EMSTOP_F | Unit is in Network emergency stop | Read | ||
| BV | 68 | ALM_COOL_PUMP1_F | Cooler pump 1 default | Read | ||
| BV | 69 | ALM_COOL_PUMP2_F | Cooler pump 2 default | Read | ||
| BV | 70 | ALM_REPEAT_HIGH_DGT_A_F | Circuit A Repeated High Discharge Gas Overrides | Read | ||
| BV | 71 | ALM_REPEAT_HIGH_DGT_B_F | Circuit B Repeated High Discharge Gas Overrides | Read | ||
| BV | 72 | ALM_REPEAT_LOW_SST_A_F | Circuit A Repeated low suction temperature overrides | Read | ||
| BV | 73 | ALM_REPEAT_LOW_SST_B_F | Circuit B Repeated low suction temperature overrides | Read | ||
| BV | 74 | ALM_HEAT_LOW_EWT_F | Low entering water temperature in heating | Read | ||
| BV | 75 | ALM_COOLER_FLOW_F | Cooler flow switch failure | Read | ||
| BV | 76 | ALM_HP_A_F | Circuit A High pressure switch Failure | Read | ||
| BV | 77 | ALM_HP_B_F | Circuit B High pressure switch Failure | Read | ||
| BV | 78 | ALM_COND_PUMP1_F | Condenser pump 1 default | Read | ||
| BV | 79 | ALM_COND_PUMP2_F | Condenser pump 2 default | Read | ||
| BV | 80 | ALM_SENSORS_SWAP_F | Cooler Water Exchanger Temperature Sensors Swapped | Read | ||
| BV | 81 | ALM_COND_SENSORS_SWAP_F | Condenser Water Exchanger Temperature Sensors Swapped | Read | ||
| BV | 82 | ALM_M_S_CONFIG_F | Master/Slave configuration error | Read | ||
| BV | 83 | ALM_INI_FACT_CONF_F | Initial factory configuration required | Read | ||
| BV | 84 | ALM_ILL_FACT_CONF_F | Illegal configuration | Read | ||
| BV | 85 | ALM_SERVICE_MAINTNANCE | Service maintenance alert | Read | ||
| BV | 86 | ALM_CL_PUMP_DRIVE_F | Cooler Water pump Variable Speed Failure | Read | ||
| BV | 87 | ALM_CD_PUMP_DRIVE_F | Condenser Water pump Variable Speed Failure | Read | ||
| BV | 88 | ALM_CL_WL_PROCESS_F | Cooler Water loop process Failure | Read | ||
| BV | 89 | ALM_CL_WL_PRES_ZERO_ERR | Cooler water loop process failure - zero error | Read | ||
| BV | 90 | ALM_CL_WL_PRES_TOO_LOW | Cooler water loop failure - water press too low | Read | ||
| BV | 91 | ALM_CL_WL_PUMP_NO_START | Cooler water loop failure - pump not started | Read | ||
| BV | 92 | ALM_CL_WL_SPECI_PUMP_RT | Cooler Water Loop : RT specific | Read | ||
| BV | 93 | ALM_CL_WL_PUMP_OVERLOAD | Cooler water loop failure - pump overload | Read | ||
| BV | 94 | ALM_CL_WL_FLOW_SWITCH_F | Cooler water loop failure - switch fail | Read | ||
| BV | 95 | ALM_CL_WL_PRES_CROSS | Cooler water loop failure - press cross | Read | ||
| BV | 96 | ALM_CD_WL_PROCESS_F | Condenser Water loop Failure | Read | ||
| BV | 97 | ALM_CD_WL_PRES_ZERO_ERR | Condenser water loop failure - zero error | Read | ||
| BV | 98 | ALM_CD_WL_PRES_TOO_LOW | Condenser water loop failure - water press too low | Read | ||
| BV | 99 | ALM_CD_WL_PUMP_NO_START | Condenser water loop failure - pump not started | Read | ||
| BV | 100 | ALM_CD_WL_SPECI_PUMP_RT | Condenserer Water Loop : RT specific | Read | ||
| BV | 101 | ALM_CD_WL_PUMP_OVERLOAD | Condenser water loop failure - pump overload | Read | ||
| BV | 102 | ALM_CD_WL_FLOW_SWITCH_F | Condenser water loop failure - switch fail | Read | ||
| BV | 103 | ALM_CD_WL_PRES_CROSS | Condenser water loop failure - press cross | Read | ||
| BV | 104 | ALM_SIOB_A_LOW_VOLT_F | SIOB 1 Low Voltage Failure | Read | ||
| BV | 105 | ALM_SIOB_B_LOW_VOLT_F | SIOB 2 Low Voltage Failure | Read | ||
| BV | 106 | ALM_EXV_A_F | Main EXV stepper motor failure - cir A | Read | ||
| BV | 107 | ALM_EXV_B_F | Main EXV stepper motor failure - cir B | Read | ||
| BV | 108 | ALM_FGAS_NEEDED | Fgas check needed, call your maintenance company | Read | ||
| BV | 109 | ALM_FLUIDE_FAIL | Possible Refrigerant Leakage Failure | Read | ||
| BV | 110 | ALM_FC_PROCESS_F | Free Cooling Process Failure | Read | ||
| BV | 111 | ALM_FC_WLOOP_F | Free Cooling Water Loop Thermistor Failure | Read | ||
| BV | 112 | ALM_FC_LWT_F | Free Cooling Leaving Water Thermistor Failure | Read | ||
| BV | 113 | ALM_FC_OAT_F | Free Cooling OAT Sensor Failure | Read | ||
| AVmin | 136 | GENUNIT_HC_SEL_wr | HeatCool Select | Write | ||
| AV | 137 | SETPOINT_csp1 | Cooling Setpoint 1 | Write | ||
| AV | 138 | SETPOINT_csp2 | Cooling Setpoint 2 | Write | ||
| AV | 139 | SETPOINT_ice_sp | Cooling Ice Setpoint | Write | ||
| AV | 140 | SETPOINT_hsp1 | Heating Setpoint 1 | Write | ||
| AV | 141 | SETPOINT_hsp2 | Heating Setpoint 2 | Write | ||
| AV | 142 | SETPOINT_hsp3 | Heating Setpoint 3 | Write | ||
| BV | 22 | BACnet_bacena | BACnet Enable | Read | ||
| BV | 23 | BACnet_bacunit | Metric Units? | Read | ||
| AV | 134 | BACnet_network | Network | Read | ||
| AV | 135 | BACnet_ident | Device Id Actually Used | Read | ||
| MV | 1 | BACnet_COLOR | ALC color value | Read | ||
| AV | 143 | BACnet_PRIME_V | ALC prime value | Read | ||
| AV | 144 | BACnet_BMS_OCC | BMS occupancy request | Write | 0=UNOCC, 1=OCC, 2=None | |
| BV | 137 | BACnet_sch_occ | BACnet schedule occupancy | Read | ||
| BV | 138 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| AV | 145 | GENUNIT_SP_SEL_wr | Setpoint selection | Write | ||
| BVmin | 139 | GENUNIT_CHIL_OCC_wr | Chiller occupancy order | Write | ||
| BV | 140 | GENUNIT_SP_OCC_wr | Occupied Setpoint | Write | ||
| AV | 146 | GENUNIT_HC_SEL_rd | Heat/Cool Select | Read | ||
| BV | 141 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 142 | GENUNIT_SP_SEL_rd | Setpoint Select | Read | ||
| BV | 143 | GENUNIT_CHIL_OCC_rd | Net.: Cmd Occupied | Read | ||
| BV | 144 | GENUNIT_SP_OCC_rd | Setpoint Occupied? | Read | ||
| BV | 145 | GENCONF_al_rever | Reverse Alarms Relay | Read | ||
| AV | 147 | PUMPSTAT_CL_DrvPw | Cool Pump drive Power | Read | ||
| AV | 148 | PUMPSTAT_CD_DrvPw | Cond Pump drive Power | Read | ||
| AV | 149 | OUTPUTS_Water3wv | Three Way Water Valve | Read | ||
| AV | 150 | RUNTIME_hr_cdpm1 | Condenser Pump 1 Hours | Read | ||
| AV | 151 | RUNTIME_hr_cdpm2 | Condenser Pump 2 Hours | Read |
No points match these filters.
Object ID lookup: Carrier 30WG/61WG SmartVu point IDs by name
BV1GENUNIT_CHIL_S_S_wrAV1GENUNIT_CTRL_PNT_wrAV2GENUNIT_DEM_LIM_wrAV3GENCONF_off_on_dAV4PUMPCONF_clpmpseqAV5PUMPCONF_clpmpsbyAV6PUMPCONF_clpmplocAV7PUMPCONF_cdpmpseqAV8PUMPCONF_cdpmpsbyAV9PUMPCONF_cdpmplocAV10HCCONFIG_cr_selAV11HCCONFIG_hr_selBV2HCCONFIG_boil_on_wrAV12GENUNIT_CTRL_TYPAV13GENUNIT_STATUSAV14ALARMRST_ALMAV15GENUNIT_HEATCOOLBV3GENUNIT_CHIL_S_S_rdAV16GENUNIT_CAP_TAV17GENUNIT_CAPA_TAV18GENUNIT_CAPB_TAV19GENUNIT_DEM_LIM_rdAV20GENUNIT_CTRL_PNT_rdAV21TEMP_EWTAV22TEMP_LWTAV23TEMP_OATAV24TEMP_CHWSTEMPAV25TEMP_HTWSTEMPAV26TEMP_DGT_AAV27TEMP_SCT_AAV28TEMP_SST_AAV29TEMP_DGT_BAV30TEMP_SCT_BAV31TEMP_SST_BAV32TEMP_COND_EWTAV33TEMP_COND_LWTAV34PRESSURE_DP_AAV35PRESSURE_SP_AAV36PRESSURE_DP_BAV37PRESSURE_SP_BBV4INPUTS_ONOFF_SWBV5INPUTS_FLOW_SWBV6OUTPUTS_CP_A1BV7OUTPUTS_CP_A2BV8OUTPUTS_CP_A3BV9OUTPUTS_CP_B1BV10OUTPUTS_CP_B2AV38OUTPUTS_EXVPosAAV39OUTPUTS_EXVPosBBV11PUMPSTAT_CL_PUMP1BV12PUMPSTAT_CL_PUMP2AV40PUMPSTAT_CL_WPINAV41PUMPSTAT_CL_WPOUTAV42PUMPSTAT_CL_FILTRAV43PUMPSTAT_CL_WPMINAV44PUMPSTAT_CL_WFLOWAV45PUMPSTAT_CL_DvPosBV13PUMPSTAT_CD_PUMP1BV14PUMPSTAT_CD_PUMP2AV46PUMPSTAT_CD_WPINAV47PUMPSTAT_CD_WPOUTAV48PUMPSTAT_CD_FILTRAV49PUMPSTAT_CD_WPMINAV50PUMPSTAT_CD_WFLOWAV51PUMPSTAT_CD_DvPosAV52RUNTIME_hr_machAV53RUNTIME_chr_machAV54RUNTIME_hhr_machAV55RUNTIME_st_machAV56RUNTIME_hr_cp_a1AV57RUNTIME_hr_cp_a2AV58RUNTIME_hr_cp_a3AV59RUNTIME_hr_cp_b1AV60RUNTIME_hr_cp_b2AV61RUNTIME_st_cp_a1AV62RUNTIME_st_cp_a2AV63RUNTIME_st_cp_a3AV64RUNTIME_st_cp_b1AV65RUNTIME_st_cp_b2AV66LOADFACT_ctrl_avgAV67LOADFACT_delta_tAV68LOADFACT_zmAV69LOADFACT_smzAV70LOADFACT_over_capAV71LOADFACT_SUCT_T_AAV72LOADFACT_SUCT_T_BAV73LOADFACT_SH_AAV74LOADFACT_SH_BAV75LOADFACT_pinch_aAV76LOADFACT_pinch_bAV77LOADFACT_ov_exv_aAV78LOADFACT_ov_exv_bAV79SETPOINT_cond_spAV80UNIT_ms_ctrlAV81M_MSTSLV_ms_activAV82M_MSTSLV_lead_selAV83M_MSTSLV_slv_statAV84M_MSTSLV_slv_captAV85M_MSTSLV_ms_errorAV86LAST_POR_date_on1AV87LAST_POR_date_on2AV88LAST_POR_date_on3AV89LAST_POR_date_on4AV90LAST_POR_date_on5AV91LAST_POR_time_on1AV92LAST_POR_time_on2AV93LAST_POR_time_on3AV94LAST_POR_time_on4AV95LAST_POR_time_on5AV96LAST_POR_date_of1AV97LAST_POR_date_of2AV98LAST_POR_date_of3AV99LAST_POR_date_of4AV100LAST_POR_date_of5AV101LAST_POR_time_of1AV102LAST_POR_time_of2AV103LAST_POR_time_of3AV104LAST_POR_time_of4AV105LAST_POR_time_of5AV106ALARMRST_alarm_1cAV107ALARMRST_alarm_2cAV108ALARMRST_alarm_3cAV109ALARMRST_alarm_4cAV110ALARMRST_alarm_5cBV15CP_UNABL_un_cp_a1BV16CP_UNABL_un_cp_a2BV17CP_UNABL_un_cp_a3BV18CP_UNABL_un_cp_b1BV19CP_UNABL_un_cp_b2AV111MST_SLV_ms_selAV112MST_SLV_ms_ctrlAV113MST_SLV_slv_addrBV20MST_SLV_lag_pumpAV114FACTORY_flui_typBV21GENCONF_ewt_optAV115SERVICE1_sh_sp_aAV116SERVICE1_sh_sp_bAV117SERVICE1_mop_spAV118SERVICE1_hp_thAV119SERVICE1_pump_cycAV120SERVICE1_freezespAV121SERVICE1_min_lwtAV122SERVICE1_zm_sptAV123SERVICE1_hc_zmAV124PUMPCONF_cl_w_ctAV125PUMPCONF_clwdtsptAV126PUMPCONF_clwdpsptAV127SERVICE1_cl_med_tAV128SERVICE1_cl_med_pAV129PUMPCONF_cd_w_ctAV130PUMPCONF_cdwdtsptAV131PUMPCONF_cdwdpsptAV132SERVICE1_cd_med_tAV133SERVICE1_cd_med_pBV24ALM_COOL_EWT_FBV25ALM_COOL_LWT_FBV26ALM_COND_EWT_FBV27ALM_COND_LWT_FBV28ALM_OAT_FBV29ALM_CHWSTEMP_FBV30ALM_SUCTION_T_A_FBV31ALM_SUCTION_T_B_FBV32ALM_HTWSTEMP_FBV33ALM_DRY_LWT_FBV34ALM_DGT_A_FBV35ALM_DGT_B_FBV36ALM_DP_A_FBV37ALM_DP_B_FBV38ALM_SP_A_FBV39ALM_SP_B_FBV40ALM_CL_WP_IN_FBV41ALM_CL_WP_OUT_FBV42ALM_CD_WP_IN_FBV43ALM_CD_WP_OUT_FBV44ALM_SIOB_A_COM_FBV45ALM_SIOB_B_COM_FBV46ALM_AUX1_HEATER_COM_FBV47ALM_AUX1_DRYC_COM_FBV48ALM_AUX1_FREECOOL_COM_FBV49ALM_AUX1_OPTION_COM_FBV50ALM_FC_AUX1_COM_FBV51ALM_COOLER_FREEZE_FBV52ALM_LOW_SUCTION_A_FBV53ALM_LOW_SUCTION_B_FBV54ALM_HIGH_SH_A_FBV55ALM_HIGH_SH_B_FBV56ALM_LOW_SH_A_FBV57ALM_LOW_SH_B_FBV58ALM_CONDENSER_LOCK_FBV59ALM_CPA1_REVERSE_ROT_FBV60ALM_CPA2_REVERSE_ROT_FBV61ALM_CPA3_REVERSE_ROT_FBV62ALM_CPB1_REVERSE_ROT_FBV63ALM_CPB2_REVERSE_ROT_FBV64ALM_LOCK_SW_FBV65ALM_LOSS_COM_SM_FBV66ALM_LOSS_COM_MS_FBV67ALM_NETWORK_EMSTOP_FBV68ALM_COOL_PUMP1_FBV69ALM_COOL_PUMP2_FBV70ALM_REPEAT_HIGH_DGT_A_FBV71ALM_REPEAT_HIGH_DGT_B_FBV72ALM_REPEAT_LOW_SST_A_FBV73ALM_REPEAT_LOW_SST_B_FBV74ALM_HEAT_LOW_EWT_FBV75ALM_COOLER_FLOW_FBV76ALM_HP_A_FBV77ALM_HP_B_FBV78ALM_COND_PUMP1_FBV79ALM_COND_PUMP2_FBV80ALM_SENSORS_SWAP_FBV81ALM_COND_SENSORS_SWAP_FBV82ALM_M_S_CONFIG_FBV83ALM_INI_FACT_CONF_FBV84ALM_ILL_FACT_CONF_FBV85ALM_SERVICE_MAINTNANCEBV86ALM_CL_PUMP_DRIVE_FBV87ALM_CD_PUMP_DRIVE_FBV88ALM_CL_WL_PROCESS_FBV89ALM_CL_WL_PRES_ZERO_ERRBV90ALM_CL_WL_PRES_TOO_LOWBV91ALM_CL_WL_PUMP_NO_STARTBV92ALM_CL_WL_SPECI_PUMP_RTBV93ALM_CL_WL_PUMP_OVERLOADBV94ALM_CL_WL_FLOW_SWITCH_FBV95ALM_CL_WL_PRES_CROSSBV96ALM_CD_WL_PROCESS_FBV97ALM_CD_WL_PRES_ZERO_ERRBV98ALM_CD_WL_PRES_TOO_LOWBV99ALM_CD_WL_PUMP_NO_STARTBV100ALM_CD_WL_SPECI_PUMP_RTBV101ALM_CD_WL_PUMP_OVERLOADBV102ALM_CD_WL_FLOW_SWITCH_FBV103ALM_CD_WL_PRES_CROSSBV104ALM_SIOB_A_LOW_VOLT_FBV105ALM_SIOB_B_LOW_VOLT_FBV106ALM_EXV_A_FBV107ALM_EXV_B_FBV108ALM_FGAS_NEEDEDBV109ALM_FLUIDE_FAILBV110ALM_FC_PROCESS_FBV111ALM_FC_WLOOP_FBV112ALM_FC_LWT_FBV113ALM_FC_OAT_FAV136GENUNIT_HC_SEL_wrAV137SETPOINT_csp1AV138SETPOINT_csp2AV139SETPOINT_ice_spAV140SETPOINT_hsp1AV141SETPOINT_hsp2AV142SETPOINT_hsp3BV22BACnet_bacenaBV23BACnet_bacunitAV134BACnet_networkAV135BACnet_identMV1BACnet_COLORAV143BACnet_PRIME_VAV144BACnet_BMS_OCCBV137BACnet_sch_occBV138GENUNIT_EMSTOP_wrAV145GENUNIT_SP_SEL_wrBV139GENUNIT_CHIL_OCC_wrBV140GENUNIT_SP_OCC_wrAV146GENUNIT_HC_SEL_rdBV141GENUNIT_EMSTOP_rdBV142GENUNIT_SP_SEL_rdBV143GENUNIT_CHIL_OCC_rdBV144GENUNIT_SP_OCC_rdBV145GENCONF_al_reverAV147PUMPSTAT_CL_DrvPwAV148PUMPSTAT_CD_DrvPwAV149OUTPUTS_Water3wvAV150RUNTIME_hr_cdpm1AV151RUNTIME_hr_cdpm2
Integration notes
- Source is the BACnet object spreadsheet inside Carrier's "protocols" zip for these units; the zip also holds Modbus and CCN/LON files that are not used here.
- The spreadsheet also has a 38-entry trend log sheet; those are trend log objects pointing at points already listed, so they are not repeated.
- No units column; temperatures follow the BACnet Metric Units setting (bacunit, default yes).
- Condenser, free cooling, boiler and master/slave points only apply to units with those options.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
How many BACnet points does the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) have?
This list has 274 BACnet objects: 151 analog values, 122 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet points are writable?
16 of the 274 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet documentation?
The source is 30WG/61WG/30WGA SmartVu2 (Pic61) Sr 1.x SmartVu (PIC60) SR 11.x - protocols (BACnet object list, 30Wg30Wga61Wg_Pic61Sr1.xPic60Sr11.x_BACnet.xlsx), published free by Carrier at https://brandportal.carrier.com/asset/36231853-567d-472c-87ed-68b3e7a177be/30WG-61WG-30WGA-SmartVu2-Pic61-Sr-1-x-SmartVu-PIC60-SR-11-x-protocols.zip.
What are the minimum BACnet points to integrate the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?
Start with BV 1 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 139 GENUNIT_CHIL_OCC_wr (Network occupancy command); AV 136 GENUNIT_HC_SEL_wr (Heat/cool select command); AV 1 GENUNIT_CTRL_PNT_wr (Control point (water temperature) from the BMS); AV 2 GENUNIT_DEM_LIM_wr (Demand limit command (%)); AV 12 GENUNIT_CTRL_TYP (Control type: 0=Local, 1=Network, 2=Remote); AV 13 GENUNIT_STATUS (Running status); AV 22 TEMP_LWT (Leaving water temperature); AV 16 GENUNIT_CAP_T (Percent total capacity); AV 14 ALARMRST_ALM (Unit alarm status).
How do I enable BMS control of the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?
The unit follows network commands only in Network operating type. In Network mode the start/stop and occupancy commands can be forced from the BMS; the network emergency stop works in any operating type.
How do I check these points on the real 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: 30WG/61WG/30WGA SmartVu2 (Pic61) Sr 1.x SmartVu (PIC60) SR 11.x - protocols (BACnet object list, 30Wg30Wga61Wg_Pic61Sr1.xPic60Sr11.x_BACnet.xlsx). Object names, instances and units are reproduced as published; descriptions are our own.