Short answer

These units speak BACnet IP when option 149 is activated with a software key. The object list has 274 objects: command objects written by the BMS carry a _wr suffix (start/stop, control point, demand limit, heat/cool select, occupancy), with read-back copies marked _rd, plus water temperatures, capacity, circuit data and one BV per alarm.

This page lists 274 BACnet objects for the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Equipment
Water-cooled chiller and water-to-water heat pump controller
Equipment type
Chillers
BACnet objects
274 (16 writable)
Transport
BACnet IP
Firmware
SmartVu PIC 6.0 SR 11.x / SmartVu 2.0 PIC 6.1 SR 1.x
Default device instance
1600001
Also known as
30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe
Source document
30WG/61WG/30WGA SmartVu2 (Pic61) Sr 1.x SmartVu (PIC60) SR 11.x - protocols (BACnet object list, 30Wg30Wga61Wg_Pic61Sr1.xPic60Sr11.x_BACnet.xlsx)
Download CSV 274 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)

Integration in brief

Activate option 149 with the software key, enable BACnet in the Network menu (BACnet Standard Conf.), and set the operating type to Network. Then command the unit through the _wr objects: start/stop, control point, demand limit and heat/cool select, and read status, water temperatures, capacity and the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 139GENUNIT_CHIL_OCC_wrNetwork occupancy commandWrite
AV 136GENUNIT_HC_SEL_wrHeat/cool select commandWrite
AV 1GENUNIT_CTRL_PNT_wrControl point (water temperature) from the BMSWrite
AV 2GENUNIT_DEM_LIM_wrDemand limit command (%)Write
AV 12GENUNIT_CTRL_TYPControl type: 0=Local, 1=Network, 2=RemoteRead
AV 13GENUNIT_STATUSRunning statusRead
AV 22TEMP_LWTLeaving water temperatureRead
AV 16GENUNIT_CAP_TPercent total capacityRead
AV 14ALARMRST_ALMUnit alarm statusRead

Enable & remote start

The unit follows network commands only in Network operating type. In Network mode the start/stop and occupancy commands can be forced from the BMS; the network emergency stop works in any operating type.

Network setup

Watch out for

Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

274 of 274 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet Points List
DescriptionStates
BVmin1GENUNIT_CHIL_S_S_wrChiller Start/Stop orderWrite
AVmin1GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin2GENUNIT_DEM_LIM_wrDemand LimitWrite
AV3GENCONF_off_on_dUnit Off to On DelayRead
AV4PUMPCONF_clpmpseqCooler Pumps SequenceRead
AV5PUMPCONF_clpmpsbyCool Pump Stopped in SbyRead
AV6PUMPCONF_clpmplocFlow Checked if Pump OffRead
AV7PUMPCONF_cdpmpseqCondenser Pumps SequenceRead
AV8PUMPCONF_cdpmpsbyCond Pump Stopped in SbyRead
AV9PUMPCONF_cdpmplocFlow Checked if Pump OffRead
AV10HCCONFIG_cr_selCooling Reset SelectRead
AV11HCCONFIG_hr_selHeating Reset SelectRead
BV2HCCONFIG_boil_on_wrBoiler Manual CommandWrite
AVmin12GENUNIT_CTRL_TYPControl typeRead0=Local, 1=Network, 2=Remote
AVmin13GENUNIT_STATUSRunning StatusRead
AVmin14ALARMRST_ALMAlarm StatusRead
AV15GENUNIT_HEATCOOLHeat/Cool StatusRead
BV3GENUNIT_CHIL_S_S_rdNet.: Cmd Start/StopRead
AVmin16GENUNIT_CAP_TPercent Total CapacityRead
AV17GENUNIT_CAPA_TCircuit A Total CapacityRead
AV18GENUNIT_CAPB_TCircuit B Total CapacityRead
AV19GENUNIT_DEM_LIM_rdActive Demand Limit ValRead
AV20GENUNIT_CTRL_PNT_rdControl PointRead
AV21TEMP_EWTEntering Water TempRead
AVmin22TEMP_LWTLeaving Water TempRead
AV23TEMP_OATOutside Air TemperatureRead
AV24TEMP_CHWSTEMPChilled Water Syst TempRead
AV25TEMP_HTWSTEMPHeat Water Syst TempRead
AV26TEMP_DGT_ADischarge Gas Temp cir ARead
AV27TEMP_SCT_ASaturated Condens Tp ARead
AV28TEMP_SST_ASaturated Suction Tp ARead
AV29TEMP_DGT_BDischarge Gas Temp cir BRead
AV30TEMP_SCT_BSaturated Condens Tp BRead
AV31TEMP_SST_BSaturated Suction Tp BRead
AV32TEMP_COND_EWTCond Entering Water TempRead
AV33TEMP_COND_LWTCond Leaving Water TempRead
AV34PRESSURE_DP_ADischarge Pressure ARead
AV35PRESSURE_SP_ASuction Pressure ARead
AV36PRESSURE_DP_BDischarge Pressure BRead
AV37PRESSURE_SP_BSuction Pressure BRead
BV4INPUTS_ONOFF_SWOn/Off - Remote SwitchRead
BV5INPUTS_FLOW_SWExchanger Flow SwitchRead
BV6OUTPUTS_CP_A1Compressor A1 OutputRead
BV7OUTPUTS_CP_A2Compressor A2 OutputRead
BV8OUTPUTS_CP_A3Compressor A3 OutputRead
BV9OUTPUTS_CP_B1Compressor B1 OutputRead
BV10OUTPUTS_CP_B2Compressor B2 OutputRead
AV38OUTPUTS_EXVPosAEXV Position Circuit ARead
AV39OUTPUTS_EXVPosBEXV Position Circuit BRead
BV11PUMPSTAT_CL_PUMP1Cooler Pump 1 CommandRead
BV12PUMPSTAT_CL_PUMP2Cooler Pump 2 CommandRead
AV40PUMPSTAT_CL_WPINCool Inlet Water PressRead
AV41PUMPSTAT_CL_WPOUTCool Outlet Water PressRead
AV42PUMPSTAT_CL_FILTRCool delta press. filtRead
AV43PUMPSTAT_CL_WPMINCool mini water pressureRead
AV44PUMPSTAT_CL_WFLOWCool Water flowRead
AV45PUMPSTAT_CL_DvPosCool Pump drive positionRead
BV13PUMPSTAT_CD_PUMP1Cond Pump 1 CommandRead
BV14PUMPSTAT_CD_PUMP2Cond Pump 2 CommandRead
AV46PUMPSTAT_CD_WPINCond Inlet Water PressRead
AV47PUMPSTAT_CD_WPOUTCond Outlet Water PressRead
AV48PUMPSTAT_CD_FILTRCond delta press. filtRead
AV49PUMPSTAT_CD_WPMINCond mini water pressureRead
AV50PUMPSTAT_CD_WFLOWCond Water flowRead
AV51PUMPSTAT_CD_DvPosCond Pump drive positionRead
AV52RUNTIME_hr_machMachine Operating HoursRead
AV53RUNTIME_chr_machCooling Operating HoursRead
AV54RUNTIME_hhr_machHeating Operating HoursRead
AV55RUNTIME_st_machMachine StartsRead
AV56RUNTIME_hr_cp_a1Compressor A1 HoursRead
AV57RUNTIME_hr_cp_a2Compressor A2 HoursRead
AV58RUNTIME_hr_cp_a3Compressor A3 HoursRead
AV59RUNTIME_hr_cp_b1Compressor B1 HoursRead
AV60RUNTIME_hr_cp_b2Compressor B2 HoursRead
AV61RUNTIME_st_cp_a1Compressor A1 StartsRead
AV62RUNTIME_st_cp_a2Compressor A2 StartsRead
AV63RUNTIME_st_cp_a3Compressor A3 StartsRead
AV64RUNTIME_st_cp_b1Compressor B1 StartsRead
AV65RUNTIME_st_cp_b2Compressor B2 StartsRead
AV66LOADFACT_ctrl_avgAverage Ctrl Water TempRead
AV67LOADFACT_delta_tWater Delta TRead
AV68LOADFACT_zmCurrent Z Multiplier ValRead
AV69LOADFACT_smzLoad/Unload FactorRead
AV70LOADFACT_over_capActive Capacity OverrideRead
AV71LOADFACT_SUCT_T_ASuction Gas Temp ARead
AV72LOADFACT_SUCT_T_BSuction Gas Temp BRead
AV73LOADFACT_SH_ASuction Superheat ARead
AV74LOADFACT_SH_BSuction Superheat BRead
AV75LOADFACT_pinch_aCooler Exchange DT Cir ARead
AV76LOADFACT_pinch_bCooler Exchange DT Cir BRead
AV77LOADFACT_ov_exv_aEXV Override Circuit ARead
AV78LOADFACT_ov_exv_bEXV Override Circuit BRead
AV79SETPOINT_cond_spCondensing SetpointRead
AV80UNIT_ms_ctrlMaster Control Type ucharRead
AV81M_MSTSLV_ms_activMaster/Slave Ctrl ActiveRead
AV82M_MSTSLV_lead_selLead Unit is the:Read
AV83M_MSTSLV_slv_statSlave Chiller StateRead
AV84M_MSTSLV_slv_captSlave Chiller Total CapRead
AV85M_MSTSLV_ms_errorMaster/Slave ErrorRead
AV86LAST_POR_date_on1Power On 1: day-mon-yearRead
AV87LAST_POR_date_on2Power On 2: day-mon-yearRead
AV88LAST_POR_date_on3Power On 3: day-mon-yearRead
AV89LAST_POR_date_on4Power On 4: day-mon-yearRead
AV90LAST_POR_date_on5Power On 5: day-mon-yearRead
AV91LAST_POR_time_on1Power On 1: hour-minuteRead
AV92LAST_POR_time_on2Power On 2: hour-minuteRead
AV93LAST_POR_time_on3Power On 3: hour-minuteRead
AV94LAST_POR_time_on4Power On 4: hour-minuteRead
AV95LAST_POR_time_on5Power On 5: hour-minuteRead
AV96LAST_POR_date_of1PowerDown 1:day-mon-yearRead
AV97LAST_POR_date_of2PowerDown 2:day-mon-yearRead
AV98LAST_POR_date_of3PowerDown 3:day-mon-yearRead
AV99LAST_POR_date_of4PowerDown 4:day-mon-yearRead
AV100LAST_POR_date_of5PowerDown 5:day-mon-yearRead
AV101LAST_POR_time_of1PowerDown 1:hour-minuteRead
AV102LAST_POR_time_of2PowerDown 2:hour-minuteRead
AV103LAST_POR_time_of3PowerDown 3:hour-minuteRead
AV104LAST_POR_time_of4PowerDown 4:hour-minuteRead
AV105LAST_POR_time_of5PowerDown 5:hour-minuteRead
AV106ALARMRST_alarm_1cCurrent Alarm 1Read
AV107ALARMRST_alarm_2cCurrent Alarm 2Read
AV108ALARMRST_alarm_3cCurrent Alarm 3Read
AV109ALARMRST_alarm_4cCurrent Alarm 4Read
AV110ALARMRST_alarm_5cCurrent Alarm 5Read
BV15CP_UNABL_un_cp_a1Compressor A1 DisableRead
BV16CP_UNABL_un_cp_a2Compressor A2 DisableRead
BV17CP_UNABL_un_cp_a3Compressor A3 DisableRead
BV18CP_UNABL_un_cp_b1Compressor B1 DisableRead
BV19CP_UNABL_un_cp_b2Compressor B2 DisableRead
AV111MST_SLV_ms_selMaster/Slave SelectRead
AV112MST_SLV_ms_ctrlMaster Control TypeRead
AV113MST_SLV_slv_addrSlave AddressRead
BV20MST_SLV_lag_pumpLag Unit Pump ControlRead
AV114FACTORY_flui_typFluid TypeRead
BV21GENCONF_ewt_optEntering Fluid ControlRead
AV115SERVICE1_sh_sp_aEXV A Superheat SetpointRead
AV116SERVICE1_sh_sp_bEXV B Superheat SetpointRead
AV117SERVICE1_mop_spEXV MOP SetpointRead
AV118SERVICE1_hp_thHigh Pressure ThresholdRead
AV119SERVICE1_pump_cycPump Cycling Freeze ProtRead
AV120SERVICE1_freezespBrine Freeze SetpointRead
AV121SERVICE1_min_lwtBrine Minimum LWTRead
AV122SERVICE1_zm_sptAuto Z MultiplierRead
AV123SERVICE1_hc_zmMaximum Z MultiplierRead
AV124PUMPCONF_cl_w_ctCool Flow Ctrl MethodRead
AV125PUMPCONF_clwdtsptCool Flow DT setpointRead
AV126PUMPCONF_clwdpsptCool Flow DP SetpointRead
AV127SERVICE1_cl_med_tCooler Water Medium TypeRead
AV128SERVICE1_cl_med_pCooler Water Medium PctRead
AV129PUMPCONF_cd_w_ctCond Flow Ctrl MethodRead
AV130PUMPCONF_cdwdtsptCond Flow DT setpointRead
AV131PUMPCONF_cdwdpsptCond Flow DP SetpointRead
AV132SERVICE1_cd_med_tConden Water Medium TypeRead
AV133SERVICE1_cd_med_pConden Water Medium PctRead
BV24ALM_COOL_EWT_FWater Exchanger Entering Fluid Thermistor FailureRead
BV25ALM_COOL_LWT_FWater Exchanger Leaving Fluid Thermistor FailureRead
BV26ALM_COND_EWT_FCondenser Entering Fluid Thermistor FailureRead
BV27ALM_COND_LWT_FCondenser Leaving Fluid Thermistor FailureRead
BV28ALM_OAT_FOAT Thermistor FailureRead
BV29ALM_CHWSTEMP_FMaster/Slave Common Fluid Thermistor FailureRead
BV30ALM_SUCTION_T_A_FCircuit A Suction Gas Thermistor FailureRead
BV31ALM_SUCTION_T_B_FCircuit B Suction Gas Thermistor FailureRead
BV32ALM_HTWSTEMP_FMaster/Slave Common Heating Fluid Thermistor FailureRead
BV33ALM_DRY_LWT_FDry Cooler LWT Thermistor FailureRead
BV34ALM_DGT_A_FCircuit A Discharge Gas Thermistor FailureRead
BV35ALM_DGT_B_FCircuit B Discharge Gas Thermistor FailureRead
BV36ALM_DP_A_FCircuit A Discharge Pressure Transducer FailureRead
BV37ALM_DP_B_FCircuit B Discharge Pressure Transducer FailureRead
BV38ALM_SP_A_FCircuit A Suction Pressure Transducer FailureRead
BV39ALM_SP_B_FCircuit B Suction Pressure Transducer FailureRead
BV40ALM_CL_WP_IN_FWater Exchanger Entering Fluid Transducer FailureRead
BV41ALM_CL_WP_OUT_FWater Exchanger Leaving Fluid Transducer FailureRead
BV42ALM_CD_WP_IN_FWater Condenser Entering Fluid Transducer FailureRead
BV43ALM_CD_WP_OUT_FWater Condenser Leaving Fluid Transducer FailureRead
BV44ALM_SIOB_A_COM_FLoss of communication with SIOB Board Number 1Read
BV45ALM_SIOB_B_COM_FLoss of communication with SIOB Board Number 2Read
BV46ALM_AUX1_HEATER_COM_FLoss of communication with AUX1 Heating Device Control boardRead
BV47ALM_AUX1_DRYC_COM_FLoss of communication with AUX1 Condenser boardRead
BV48ALM_AUX1_FREECOOL_COM_FLoss of communication with AUX1 FreeCooling boardRead
BV49ALM_AUX1_OPTION_COM_FLoss of communication with AUX1 Options boardRead
BV50ALM_FC_AUX1_COM_FLoss of communication with Free Cooling Board 1Read
BV51ALM_COOLER_FREEZE_FCooler Water Exchanger Freeze ProtectionRead
BV52ALM_LOW_SUCTION_A_FCircuit A Low Saturated Suction TemperatureRead
BV53ALM_LOW_SUCTION_B_FCircuit B Low Saturated Suction TemperatureRead
BV54ALM_HIGH_SH_A_FCircuit A High Suction SuperheatRead
BV55ALM_HIGH_SH_B_FCircuit B High Suction SuperheatRead
BV56ALM_LOW_SH_A_FCircuit A Low Suction SuperheatRead
BV57ALM_LOW_SH_B_FCircuit B Low Suction SuperheatRead
BV58ALM_CONDENSER_LOCK_FCondenser Flow Switch FailureRead
BV59ALM_CPA1_REVERSE_ROT_FCompressor A1 Not Started Or Pressure Increase not EstablishedRead
BV60ALM_CPA2_REVERSE_ROT_FCompressor A2 Not Started Or Pressure Increase not EstablishedRead
BV61ALM_CPA3_REVERSE_ROT_FCompressor A3 Not Started Or Pressure Increase not EstablishedRead
BV62ALM_CPB1_REVERSE_ROT_FCompressor B1 Not Started Or Pressure Increase not EstablishedRead
BV63ALM_CPB2_REVERSE_ROT_FCompressor B2 Not Started Or Pressure Increase not EstablishedRead
BV64ALM_LOCK_SW_FCustomer Interlock FailureRead
BV65ALM_LOSS_COM_SM_FLoss of communication with System ManagerRead
BV66ALM_LOSS_COM_MS_FMaster/Slave communication FailureRead
BV67ALM_NETWORK_EMSTOP_FUnit is in Network emergency stopRead
BV68ALM_COOL_PUMP1_FCooler pump 1 defaultRead
BV69ALM_COOL_PUMP2_FCooler pump 2 defaultRead
BV70ALM_REPEAT_HIGH_DGT_A_FCircuit A Repeated High Discharge Gas OverridesRead
BV71ALM_REPEAT_HIGH_DGT_B_FCircuit B Repeated High Discharge Gas OverridesRead
BV72ALM_REPEAT_LOW_SST_A_FCircuit A Repeated low suction temperature overridesRead
BV73ALM_REPEAT_LOW_SST_B_FCircuit B Repeated low suction temperature overridesRead
BV74ALM_HEAT_LOW_EWT_FLow entering water temperature in heatingRead
BV75ALM_COOLER_FLOW_FCooler flow switch failureRead
BV76ALM_HP_A_FCircuit A High pressure switch FailureRead
BV77ALM_HP_B_FCircuit B High pressure switch FailureRead
BV78ALM_COND_PUMP1_FCondenser pump 1 defaultRead
BV79ALM_COND_PUMP2_FCondenser pump 2 defaultRead
BV80ALM_SENSORS_SWAP_FCooler Water Exchanger Temperature Sensors SwappedRead
BV81ALM_COND_SENSORS_SWAP_FCondenser Water Exchanger Temperature Sensors SwappedRead
BV82ALM_M_S_CONFIG_FMaster/Slave configuration errorRead
BV83ALM_INI_FACT_CONF_FInitial factory configuration requiredRead
BV84ALM_ILL_FACT_CONF_FIllegal configurationRead
BV85ALM_SERVICE_MAINTNANCEService maintenance alertRead
BV86ALM_CL_PUMP_DRIVE_FCooler Water pump Variable Speed FailureRead
BV87ALM_CD_PUMP_DRIVE_FCondenser Water pump Variable Speed FailureRead
BV88ALM_CL_WL_PROCESS_FCooler Water loop process FailureRead
BV89ALM_CL_WL_PRES_ZERO_ERRCooler water loop process failure - zero errorRead
BV90ALM_CL_WL_PRES_TOO_LOWCooler water loop failure - water press too lowRead
BV91ALM_CL_WL_PUMP_NO_STARTCooler water loop failure - pump not startedRead
BV92ALM_CL_WL_SPECI_PUMP_RTCooler Water Loop : RT specificRead
BV93ALM_CL_WL_PUMP_OVERLOADCooler water loop failure - pump overloadRead
BV94ALM_CL_WL_FLOW_SWITCH_FCooler water loop failure - switch failRead
BV95ALM_CL_WL_PRES_CROSSCooler water loop failure - press crossRead
BV96ALM_CD_WL_PROCESS_FCondenser Water loop FailureRead
BV97ALM_CD_WL_PRES_ZERO_ERRCondenser water loop failure - zero errorRead
BV98ALM_CD_WL_PRES_TOO_LOWCondenser water loop failure - water press too lowRead
BV99ALM_CD_WL_PUMP_NO_STARTCondenser water loop failure - pump not startedRead
BV100ALM_CD_WL_SPECI_PUMP_RTCondenserer Water Loop : RT specificRead
BV101ALM_CD_WL_PUMP_OVERLOADCondenser water loop failure - pump overloadRead
BV102ALM_CD_WL_FLOW_SWITCH_FCondenser water loop failure - switch failRead
BV103ALM_CD_WL_PRES_CROSSCondenser water loop failure - press crossRead
BV104ALM_SIOB_A_LOW_VOLT_FSIOB 1 Low Voltage FailureRead
BV105ALM_SIOB_B_LOW_VOLT_FSIOB 2 Low Voltage FailureRead
BV106ALM_EXV_A_FMain EXV stepper motor failure - cir ARead
BV107ALM_EXV_B_FMain EXV stepper motor failure - cir BRead
BV108ALM_FGAS_NEEDEDFgas check needed, call your maintenance companyRead
BV109ALM_FLUIDE_FAILPossible Refrigerant Leakage FailureRead
BV110ALM_FC_PROCESS_FFree Cooling Process FailureRead
BV111ALM_FC_WLOOP_FFree Cooling Water Loop Thermistor FailureRead
BV112ALM_FC_LWT_FFree Cooling Leaving Water Thermistor FailureRead
BV113ALM_FC_OAT_FFree Cooling OAT Sensor FailureRead
AVmin136GENUNIT_HC_SEL_wrHeatCool SelectWrite
AV137SETPOINT_csp1Cooling Setpoint 1Write
AV138SETPOINT_csp2Cooling Setpoint 2Write
AV139SETPOINT_ice_spCooling Ice SetpointWrite
AV140SETPOINT_hsp1Heating Setpoint 1Write
AV141SETPOINT_hsp2Heating Setpoint 2Write
AV142SETPOINT_hsp3Heating Setpoint 3Write
BV22BACnet_bacenaBACnet EnableRead
BV23BACnet_bacunitMetric Units?Read
AV134BACnet_networkNetworkRead
AV135BACnet_identDevice Id Actually UsedRead
MV1BACnet_COLORALC color valueRead
AV143BACnet_PRIME_VALC prime valueRead
AV144BACnet_BMS_OCCBMS occupancy requestWrite0=UNOCC, 1=OCC, 2=None
BV137BACnet_sch_occBACnet schedule occupancyRead
BV138GENUNIT_EMSTOP_wrEmergency StopWrite
AV145GENUNIT_SP_SEL_wrSetpoint selectionWrite
BVmin139GENUNIT_CHIL_OCC_wrChiller occupancy orderWrite
BV140GENUNIT_SP_OCC_wrOccupied SetpointWrite
AV146GENUNIT_HC_SEL_rdHeat/Cool SelectRead
BV141GENUNIT_EMSTOP_rdEmergency StopRead
BV142GENUNIT_SP_SEL_rdSetpoint SelectRead
BV143GENUNIT_CHIL_OCC_rdNet.: Cmd OccupiedRead
BV144GENUNIT_SP_OCC_rdSetpoint Occupied?Read
BV145GENCONF_al_reverReverse Alarms RelayRead
AV147PUMPSTAT_CL_DrvPwCool Pump drive PowerRead
AV148PUMPSTAT_CD_DrvPwCond Pump drive PowerRead
AV149OUTPUTS_Water3wvThree Way Water ValveRead
AV150RUNTIME_hr_cdpm1Condenser Pump 1 HoursRead
AV151RUNTIME_hr_cdpm2Condenser Pump 2 HoursRead
Object ID lookup: Carrier 30WG/61WG SmartVu point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)

How many BACnet points does the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) have?

This list has 274 BACnet objects: 151 analog values, 122 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet points are writable?

16 of the 274 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149) BACnet documentation?

The source is 30WG/61WG/30WGA SmartVu2 (Pic61) Sr 1.x SmartVu (PIC60) SR 11.x - protocols (BACnet object list, 30Wg30Wga61Wg_Pic61Sr1.xPic60Sr11.x_BACnet.xlsx), published free by Carrier at https://brandportal.carrier.com/asset/36231853-567d-472c-87ed-68b3e7a177be/30WG-61WG-30WGA-SmartVu2-Pic61-Sr-1-x-SmartVu-PIC60-SR-11-x-protocols.zip.

What are the minimum BACnet points to integrate the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?

Start with BV 1 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 139 GENUNIT_CHIL_OCC_wr (Network occupancy command); AV 136 GENUNIT_HC_SEL_wr (Heat/cool select command); AV 1 GENUNIT_CTRL_PNT_wr (Control point (water temperature) from the BMS); AV 2 GENUNIT_DEM_LIM_wr (Demand limit command (%)); AV 12 GENUNIT_CTRL_TYP (Control type: 0=Local, 1=Network, 2=Remote); AV 13 GENUNIT_STATUS (Running status); AV 22 TEMP_LWT (Leaving water temperature); AV 16 GENUNIT_CAP_T (Percent total capacity); AV 14 ALARMRST_ALM (Unit alarm status).

How do I enable BMS control of the Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?

The unit follows network commands only in Network operating type. In Network mode the start/stop and occupancy commands can be forced from the BMS; the network emergency stop works in any operating type.

How do I check these points on the real 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: 30WG/61WG/30WGA SmartVu2 (Pic61) Sr 1.x SmartVu (PIC60) SR 11.x - protocols (BACnet object list, 30Wg30Wga61Wg_Pic61Sr1.xPic60Sr11.x_BACnet.xlsx). Object names, instances and units are reproduced as published; descriptions are our own.