Commercial Wi-Fi thermostat · BACnet points list
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 BACnet points list
Updated 7 November 2026
The Connect 33TCSPF-4 / 33TWSPF-4 thermostat exposes 149 BACnet objects (plus two network port objects) over BACnet MS/TP or BACnet IP over Wi-Fi (it has an MS/TP network port object and an IPv4 network port object). Compared with the earlier 33CONNECTSTAT43 list it adds outdoor air quality values, standby setpoints, hydronic fan coil and analog output (hot water valve) points, door switch points and network general purpose outputs. Configuration objects are gated: they only accept writes after BACnet Config Write Enable is turned on.
This page lists 149 BACnet objects for the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 — 97 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
- Equipment
- Commercial Wi-Fi thermostat
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 149 (97 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Connect the thermostat on MS/TP or IP, then drive it with the user mode (MV 400), heat/cool setpoints and the BMS occupancy point (BV 405, enabled by BV 507). Read current mode, space temperature for control and the stage output BVs. Turn on BV 511 only when you need to change gated configuration objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 400 | USER_MODE | System mode: Off, Heat, Cool, Auto, E-Heat | Write |
| BV 405 | BMS_OCC | BMS occupancy command (needs BV 507 enabled) | Write |
| AV 400 | OCC_HT_SP | Occupied heating setpoint | Write |
| AV 401 | OCC_CL_SP | Occupied cooling setpoint | Write |
| AV 103 | NET_SP_TEMP | Network space temperature (with BV 407 enabled) | Write |
| MV 300 | CURRENT_MODE | Current mode status: Off, Heat, Cool | Read |
| AV 104 | SP_TEMP_CTRL | Space temperature used for control | Read |
| BV 205 | G_OUT | Fan output status | Read |
| BV 200 | Y1_OUT | First stage cooling output status | Read |
| BV 203 | W1_OUT | First stage heating output status | Read |
Enable & remote start
BMS occupancy is used only when BMS Occupancy Enable (BV 507) is enabled; the BMS then writes BACnet BMS Occupancy (BV 405). Gated configuration objects need BACnet Config Write Enable (BV 511).
Heartbeat & communication loss
Network Space Temperature (AV 103) and Network Space Humidity (AV 105) must be rewritten at least every 5 minutes; if not, the control value falls back to the thermostat's own sensor (AI 100 / AI 101).
Sensors & values from the BMS
Network Space Temperature (AV 103) and Network Space Humidity (AV 105) are written by the BMS and take effect only when BV 407 / BV 408 are enabled and the value was written within the last 5 minutes. AV 104 and AV 106 show the values the control logic actually uses.
Network setup
- Network port objects: MSTP_PORT (500) for MS/TP and IP_PORT (501) for BACnet IP, including BBMD foreign device settings.
- Up to 7 concurrent COV subscriptions, for BV and MV objects only, lifetime 1 s to 8 h.
Watch out for
- The BACnet Reliability property is used to flag objects that the current configuration does not use (e.g. no-sensor, no-output).
- Leave CFG_WR_EN (BV 511) disabled in normal operation so gated settings cannot be changed by accident.
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 100 | ID_SPACE_TEMP | Indoor Space Temperature | Read | ||
| AI | 101 | ID_SPACE_HUM | Indoor Space Humidity | Read | ||
| AI | 102 | ID_SPACE_CO2 | Indoor Space CO2 | Read | ||
| AV | 100 | REM_SPACE_TEMP | Remote Space Temperature | Read | ||
| AV | 101 | OD_TEMP | Outdoor Temperature | Read | ||
| AV | 102 | SAT | Supply Air Temperature | Read | ||
| AVmin | 103 | NET_SP_TEMP | Network Space Temperature | Write | ||
| AVmin | 104 | SP_TEMP_CTRL | Space Temperature for Control | Read | ||
| AV | 105 | NET_SP_HUM | Network Space Humidity | Write | ||
| AV | 106 | SP_HUM_CTRL | Space Humidity for Control | Read | ||
| AV | 107 | OD_HUM | Outdoor Humidity | Read | ||
| AV | 108 | OD_AQI | Outdoor Air Quality Index | Read | ||
| AV | 109 | OD_CO | Outdoor Carbon Monoxide | Read | ||
| AV | 110 | OD_NO2 | Outdoor Nitrogen Dioxide | Read | ||
| AV | 111 | OD_O3 | Outdoor Ozone | Read | ||
| AV | 112 | OD_PM2_5 | Outdoor PM2.5 | Read | ||
| AV | 113 | OD_PM10 | Outdoor PM10 | Read | ||
| AV | 114 | OD_SO2 | Outdoor Sulphur Dioxide | Read | ||
| AV | 200 | AN_OUT | Analog Output | Read | ||
| AV | 201 | NET_GP_AO_OUT | Network General Purpose Output AO | Write | ||
| AV | 300 | AIR_FLTR_HRS_LFT | Air Filter Hours Left | Read | ||
| AV | 301 | OVRD_TIME | Override Time Remaining | Read | ||
| AVmin | 400 | OCC_HT_SP | Occupied Heat Setpoint | Write | ||
| AVmin | 401 | OCC_CL_SP | Occupied Cool Setpoint | Write | ||
| AV | 402 | UNOCC_HT_SP | Unoccupied Heat Setpoint | Write | ||
| AV | 403 | UNOCC_CL_SP | Unoccupied Cool Setpoint | Write | ||
| AV | 406 | DEHUM_SP | Dehumidification Setpoint | Write | ||
| AV | 407 | HUM_SP | Humidification Setpoint | Write | ||
| AV | 408 | SCRN_TMT | Screen Timeout | Write | ||
| AV | 409 | HEAT_SP | Heat Setpoint | Write | ||
| AV | 410 | COOL_SP | Cool Setpoint | Write | ||
| AV | 411 | ACTV_BCKLT | Active Backlight | Write | ||
| AV | 412 | DRMNT_BCKLT | Dormant Backlight | Write | ||
| AV | 413 | STBY_HT_SP | Standby Heat Setpoint | Write | ||
| AV | 414 | STBY_CL_SP | Standby Cool Setpoint | Write | ||
| AV | 500 | ID_STAGES | Indoor Equip Stages | Write | ||
| AV | 501 | OD_STAGES | Outdoor Equip Stages | Write | ||
| AV | 502 | MAX_HOLD_TIME | Max Temperature Hold Time | Write | ||
| AV | 503 | AUTO_XOVR | Auto Changeover Delay | Write | ||
| AV | 504 | COOL_LOCKOUT | Cool Lockout Temperature | Write | ||
| AV | 505 | LO_CL_LCKOUT | Low Cool Lockout (HP only) | Write | ||
| AV | 506 | LO_HT_LCKOUT | Low Heat Lockout (HP only) | Write | ||
| AV | 507 | DLY_BW_FUEL | Delay Between Fuel (HP only) | Write | ||
| AV | 508 | CYCLES_HR | Cycles Per Hour | Write | ||
| AV | 509 | MAX_HT_SP | Max Heat Setpoint | Write | ||
| AV | 510 | MIN_CL_SP | Min Cool Setpoint | Write | ||
| AV | 511 | AUX_HT_LCKOUT | Aux Heat Lockout (HP only) | Write | ||
| AV | 512 | HP_LCKOUT | Heat Pump Lockout | Write | ||
| AV | 513 | STG_DELAY | Stage Delay | Write | ||
| AV | 514 | FRCD_STG_UP | Forced Stage Up Delay | Write | ||
| AV | 515 | DIFFERENTIAL | Stage Change Temp Differential | Write | ||
| AV | 516 | LINE_FREQ | Line Frequency (not implemented) | Read | ||
| AV | 517 | ID_TEMP_OFF | Indoor Temperature Offset | Write | ||
| AV | 518 | ID_HUM_OFF | Indoor Humidity Offset | Write | ||
| AV | 519 | SAT_OFFSET | SAT Temp Offset | Write | ||
| AV | 520 | AIR_FLT_HRS | Air Filter Hours | Write | ||
| AV | 521 | MAX_SP_ERR | Max Setpoint Error | Write | ||
| AV | 522 | ID_TMP_FLT_INHBT | Indoor Temp Fault Inhibit | Write | ||
| AV | 523 | C02_FLT_THRESHLD | C02 Fault Threshold (currently not used) | Write | ||
| AV | 524 | AO_HT_EN_TEMP | Hot Water Valve Enable Temp | Write | ||
| AV | 525 | WATER_TEMP_OFF | Water Temperature Offset | Write | ||
| AV | 526 | DOOR_OPEN_HT_STPT | Door Open Heat Setpoint | Write | ||
| AV | 527 | DOOR_OPEN_CL_STPT | Door Open Cool Setpoint | Write | ||
| BVmin | 200 | Y1_OUT | 1st Stage Cooling Out Status | Read | 0=OFF, 1=ON | |
| BV | 201 | Y2_OUT | 2nd Stage Cooling Out Status | Read | 0=OFF, 1=ON | |
| BV | 202 | Y3_OUT | 3rd Stage Cooling Out Status | Read | 0=OFF, 1=ON | |
| BVmin | 203 | W1_OUT | 1st Stage Heating Out Status | Read | 0=OFF, 1=ON | |
| BV | 204 | W2_OUT | 2nd Stage Heating Out Status | Read | 0=OFF, 1=ON | |
| BVmin | 205 | G_OUT | Fan Out Status | Read | 0=OFF, 1=ON | |
| BV | 206 | OB_OUT | Reversing Valve Out Status | Read | 0=OFF, 1=ON | |
| BV | 208 | OCC_OUT | Occupancy Out Status | Read | 0=OFF, 1=ON | |
| BV | 209 | HUM_OUT | Humidifier Out Status | Read | 0=OFF, 1=ON | |
| BV | 210 | DEHUM_OUT | Dehumidifier Out Status | Read | 0=OFF, 1=ON | |
| BV | 211 | NET_GP_Y3_OUT | Network General Purpose Out Y3 | Write | 0=OFF, 1=ON | |
| BV | 212 | NET_GP_W2_OUT | Network General Purpose Out W2 | Write | 0=OFF, 1=ON | |
| BV | 213 | NET_GP_OB_OUT | Network General Purpose Out OB | Write | 0=OFF, 1=ON | |
| BV | 214 | FAN_LOW | Hydronic Fan Coil Fan Low | Read | 0=OFF, 1=ON | |
| BV | 215 | FAN_MED | Hydronic Fan Coil Fan Medium | Read | 0=OFF, 1=ON | |
| BV | 216 | FAN_HIGH | Hydronic Fan Coil Fan High | Read | 0=OFF, 1=ON | |
| BV | 300 | DOOR_IS_OPEN | Door Is Open | Read | 0=NO, 1=YES | |
| BV | 400 | WIFI_TIME_SYNC | Wi-Fi Time Synchronization | Write | 0=DISABLED, 1=ENABLED | |
| BV | 401 | PROXIMITY_EN | Proximity Sensor Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 402 | AUTO_DST | Auto DST Time Shift | Write | 0=DISABLED, 1=ENABLED | |
| BV | 403 | WIFI_ENABLE | Wi-Fi Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 404 | SETPT_OVERRIDE | Setpoint Override | Write | 0=DISABLED, 1=ENABLED | |
| BVmin | 405 | BMS_OCC | BACnet BMS Occupancy | Write | ||
| BV | 406 | FLTR_TMR_RST | Filter Timer Reset | Write | 0=INACTIVE, 1=ACTIVE | |
| BV | 407 | NET_SP_TEMP_EN | Network Space Temperature Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 408 | NET_SP_HUM_EN | Network Space Humidity Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 500 | OCC_IN_POL | Occupancy Input Polarity | Write | ||
| BV | 501 | ALLOW_AUTO | Auto Mode Allowed | Write | ||
| BV | 502 | ALLOW_PROG | Prog Mode Allowed | Write | ||
| BV | 503 | CELSIUS_DISP | Celsius Display | Write | ||
| BV | 504 | FAN_WITH_W | Fan On with W | Write | ||
| BV | 505 | RVS_VLV_DIR | Rvs Vlv Energized Ht | Write | ||
| BV | 506 | HUM_INST | Humidifier Installed | Write | ||
| BV | 507 | BMS_OCC_EN | BMS Occupancy Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 511 | CFG_WR_EN | BACnet Config Write Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 512 | CL_LO_EN | Cooling Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 513 | AUX_HT_LO_EN | Aux Heat Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 514 | HP_LO_EN | Heat Pump Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 515 | LO_CL_LO_EN | Low Cool Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 516 | LO_HT_LO_EN | Low Heat Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 517 | AO_HT_VLV_LO_EN | Hot Water Valve Lockout Enable | Write | 0=DISABLED, 1=ENABLED | |
| BV | 518 | DOOR_OPEN_SW_STATE | Door open switch state | Write | 0=OPEN, 1=CLOSED | |
| BV | 900 | ID_TEMP_SENS_HI | ID TEMP SENSOR HIGH | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 901 | ID_TEMP_SENS_LO | ID TEMP SENSOR LOW | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 902 | REM_TEMP_HI | REMOTE SENSOR HIGH | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 903 | REM_TEMP_LO | REMOTE SENSOR LOW | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 904 | HUM_TEMP_HI | HUM TEMP SENSOR HIGH | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 905 | HUM_TEMP_LO | HUM TEMP SENSOR LOW | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 906 | ID_TEMP_RNG_HI | ID TEMP RANGE HIGH | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 907 | ID_TEMP_RNG_LO | ID TEMP RANGE LOW | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 908 | HUM_SENS_FAIL | HUM SENSOR FAILURE | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 909 | HUM_TOO_HI | HUMIDITY RANGE HIGH | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 910 | HUM_TOO_LO | HUMIDITY RANGE LOW | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 911 | OD_TEMP_FAIL | OUTDOOR SENSOR FAILURE | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 912 | SRVR_CONN_FAIL | NOT CONNECTED TO SERVER | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 913 | RTR_CONN_FAIL | NOT CONNECTED TO ROUTER | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 914 | WIFI_CONF_FAIL | WIFI HARDWARE FAULT | Read | 0=INACTIVE, 1=ACTIVE | |
| BV | 915 | ECON_FAULT | ECONOMIZER FAULT | Read | 0=INACTIVE, 1=ACTIVE | |
| MVmin | 300 | CURRENT_MODE | Current Mode Status | Read | 1=OFF, 2=HEAT, 3=COOL | |
| MVmin | 400 | USER_MODE | User Mode | Write | 1=OFF, 2=HEAT, 3=COOL, 4=AUTO, 5=E-HEAT | |
| MV | 401 | PROX_SENS | IR Proximity Sensitivity | Write | 1=HIGH, 2=MEDIUM, 3=LOW | |
| MV | 402 | SOUND | Sound Effect | Write | 1=OFF, 2=CLICK, 3=BEEP | |
| MV | 403 | SCHED_DAY_PARTS | Number of Parts in Schedule Day | Write | 1=2 PARTS, 2=4 PARTS | |
| MV | 404 | OCC_FAN | Occupied Fan Mode | Write | 1=AUTO, 2=ON | |
| MV | 405 | UNOCC_FAN | Unoccupied Fan Mode | Write | 1=AUTO, 2=ON | |
| MV | 406 | FAN MODE | Current Fan Mode | Write | 1=AUTO, 2=ON, 3=OVERRIDE AUTO, 4=OVERRIDE ON | |
| MV | 407 | STANDBY_FAN | Standby Fan Mode | Write | 1=AUTO, 2=ON | |
| MV | 500 | ID_EQUIP_TYPE | Indoor Equipment Type | Read | 1=NO INDOOR, 2=FURNACE, 3=AIR HANDLER | |
| MV | 501 | OD_EQUIP_TYPE | Outdoor Equipment Type | Write | 1=NO OUTDOOR, 2=A/C, 3=HEAT PUMP | |
| MV | 502 | REMOTE_SENSOR | Remote Sensor Type | Write | 1=NONE, 2=OUTDOOR, 3=SPACE, 4=AVERAGE, 5=OCCUPANCY, 6=FAULT_INPUT, 7=SAT, 8=FILTER | |
| MV | 503 | DEHUM_TYPE | Dehumidification Type | Write | 1=NO, 2=YES, 3=OVRCL (2F), 4=HUMIDIMIZER | |
| MV | 504 | OCC_OUTPUT | Occupancy Output Terminal | Write | 1=OFF, 2=Y3, 3=O/B, 4=W2 | |
| MV | 505 | HUM_OUTPUT | Humidification Output Terminal | Write | 1=OFF, 2=Y3, 3=O/B, 4=W2 | |
| MV | 506 | DEHUM_OUTPUT | Dehumidification Output Terminal | Write | 1=OFF, 2=Y3, 3=O/B, 4=W2 | |
| MV | 507 | SMART_RECVRY | Smart Recovery | Write | 1=NO, 2=30 min, 3=60 min, 4=90 min | |
| MV | 508 | GP_OUT_TIMEOUT | General Purpose Output Timeout | Write | 1=2 min, 2=20 min, 3=1 hr, 4=UNLIMITED | |
| MV | 509 | NET_GP_Y3_MODE | Network GP Y3 Mode | Write | 1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE | |
| MV | 510 | NET_GP_W2_MODE | Network GP W2 Mode | Write | 1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE | |
| MV | 511 | NET_GP_OB_MODE | Network GP OB Mode | Write | 1=DISABLED, 2=ENERGIZED_ACTIVE, 3=ENERGIZED_INACTIVE | |
| MV | 512 | ANALOG_INPUT | Analog Input (not used) | Write | 1=None, 2=Humidity, 3=CO2 | |
| MV | 513 | ANALOG_IN_SCALE | Analog Input Scaling (not used) | Write | 1=2-10V (4-20mAw/ext 500 Ohm), 2=0-10V | |
| MV | 514 | ANALOG_OUTPUT | Analog Output Configuration | Write | 1=None, 2=Water Valve, 3=Three Speed Fan | |
| MV | 515 | ANALOG_OUT_SCALE | Analog Output Scaling | Write | 1=2-10v, 2=0-10v | |
| MV | 516 | ANALOG_OUT_TYPE | Analog Output Type | Write | 1=NORMALLY CLOSED, 2=NORMALLY OPEN | |
| MV | 517 | NET_GP_AO_MODE | Network GP AO Mode | Write | 1=DISABLED, 2=DIRECT LV DEFAULT, 3=DIRECT HV DEFAULT, 4=REVERSE LV DEFAULT, 5=REVERSE HV DEFAULT | |
| MV | 518 | BMS_OCC_WSTBY | BMS OCC with Standby | Write | 1=UNOCCUPIED, 2=OCCUPIED, 3=STANDBY |
No points match these filters.
Object ID lookup: Carrier Connect 33TCSPF-4 point IDs by name
AI100ID_SPACE_TEMPAI101ID_SPACE_HUMAI102ID_SPACE_CO2AV100REM_SPACE_TEMPAV101OD_TEMPAV102SATAV103NET_SP_TEMPAV104SP_TEMP_CTRLAV105NET_SP_HUMAV106SP_HUM_CTRLAV107OD_HUMAV108OD_AQIAV109OD_COAV110OD_NO2AV111OD_O3AV112OD_PM2_5AV113OD_PM10AV114OD_SO2AV200AN_OUTAV201NET_GP_AO_OUTAV300AIR_FLTR_HRS_LFTAV301OVRD_TIMEAV400OCC_HT_SPAV401OCC_CL_SPAV402UNOCC_HT_SPAV403UNOCC_CL_SPAV406DEHUM_SPAV407HUM_SPAV408SCRN_TMTAV409HEAT_SPAV410COOL_SPAV411ACTV_BCKLTAV412DRMNT_BCKLTAV413STBY_HT_SPAV414STBY_CL_SPAV500ID_STAGESAV501OD_STAGESAV502MAX_HOLD_TIMEAV503AUTO_XOVRAV504COOL_LOCKOUTAV505LO_CL_LCKOUTAV506LO_HT_LCKOUTAV507DLY_BW_FUELAV508CYCLES_HRAV509MAX_HT_SPAV510MIN_CL_SPAV511AUX_HT_LCKOUTAV512HP_LCKOUTAV513STG_DELAYAV514FRCD_STG_UPAV515DIFFERENTIALAV516LINE_FREQAV517ID_TEMP_OFFAV518ID_HUM_OFFAV519SAT_OFFSETAV520AIR_FLT_HRSAV521MAX_SP_ERRAV522ID_TMP_FLT_INHBTAV523C02_FLT_THRESHLDAV524AO_HT_EN_TEMPAV525WATER_TEMP_OFFAV526DOOR_OPEN_HT_STPTAV527DOOR_OPEN_CL_STPTBV200Y1_OUTBV201Y2_OUTBV202Y3_OUTBV203W1_OUTBV204W2_OUTBV205G_OUTBV206OB_OUTBV208OCC_OUTBV209HUM_OUTBV210DEHUM_OUTBV211NET_GP_Y3_OUTBV212NET_GP_W2_OUTBV213NET_GP_OB_OUTBV214FAN_LOWBV215FAN_MEDBV216FAN_HIGHBV300DOOR_IS_OPENBV400WIFI_TIME_SYNCBV401PROXIMITY_ENBV402AUTO_DSTBV403WIFI_ENABLEBV404SETPT_OVERRIDEBV405BMS_OCCBV406FLTR_TMR_RSTBV407NET_SP_TEMP_ENBV408NET_SP_HUM_ENBV500OCC_IN_POLBV501ALLOW_AUTOBV502ALLOW_PROGBV503CELSIUS_DISPBV504FAN_WITH_WBV505RVS_VLV_DIRBV506HUM_INSTBV507BMS_OCC_ENBV511CFG_WR_ENBV512CL_LO_ENBV513AUX_HT_LO_ENBV514HP_LO_ENBV515LO_CL_LO_ENBV516LO_HT_LO_ENBV517AO_HT_VLV_LO_ENBV518DOOR_OPEN_SW_STATEBV900ID_TEMP_SENS_HIBV901ID_TEMP_SENS_LOBV902REM_TEMP_HIBV903REM_TEMP_LOBV904HUM_TEMP_HIBV905HUM_TEMP_LOBV906ID_TEMP_RNG_HIBV907ID_TEMP_RNG_LOBV908HUM_SENS_FAILBV909HUM_TOO_HIBV910HUM_TOO_LOBV911OD_TEMP_FAILBV912SRVR_CONN_FAILBV913RTR_CONN_FAILBV914WIFI_CONF_FAILBV915ECON_FAULTMV300CURRENT_MODEMV400USER_MODEMV401PROX_SENSMV402SOUNDMV403SCHED_DAY_PARTSMV404OCC_FANMV405UNOCC_FANMV406FAN MODEMV407STANDBY_FANMV500ID_EQUIP_TYPEMV501OD_EQUIP_TYPEMV502REMOTE_SENSORMV503DEHUM_TYPEMV504OCC_OUTPUTMV505HUM_OUTPUTMV506DEHUM_OUTPUTMV507SMART_RECVRYMV508GP_OUT_TIMEOUTMV509NET_GP_Y3_MODEMV510NET_GP_W2_MODEMV511NET_GP_OB_MODEMV512ANALOG_INPUTMV513ANALOG_IN_SCALEMV514ANALOG_OUTPUTMV515ANALOG_OUT_SCALEMV516ANALOG_OUT_TYPEMV517NET_GP_AO_MODEMV518BMS_OCC_WSTBY
Integration notes
- Carrier's tables call value objects 'Analog Variable' / 'Binary Variable'; they are AV and BV objects.
- Access mapping: READ_ONLY = R; READ_WRITE and GATED_WRITE = W (GATED_WRITE needs BV 511 CFG_WR_EN enabled); WRITE_WHEN_OOS (the three AIs) = R, writable only when the object is out of service.
- BV 916 LOCKOUT_FAIL is printed as removed (changed from a fault to a system event) and is left out.
- The 33TWSPF-4 has its own guide (11-808-1227-01) with the same object appendix.
- Multistate state numbers (1, 2, 3...) follow the printed order of the state list; MV 509 states continue across a page break.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
How many BACnet points does the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 have?
This list has 149 BACnet objects: 3 analog inputs, 60 analog values, 58 binary values, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 BACnet points are writable?
97 of the 149 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 BACnet documentation?
The source is Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 Installation Guide (Appendix A, BACnet Objects) (11-808-1226-01), revision 2026-06, published free by Carrier at https://brandportal.carrier.com/asset/18e1e0a0-9538-47b1-b623-d4ea88f27b22/11-808-1226-01.pdf.
What are the minimum BACnet points to integrate the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4?
Start with MV 400 USER_MODE (System mode: Off, Heat, Cool, Auto, E-Heat); BV 405 BMS_OCC (BMS occupancy command (needs BV 507 enabled)); AV 400 OCC_HT_SP (Occupied heating setpoint); AV 401 OCC_CL_SP (Occupied cooling setpoint); AV 103 NET_SP_TEMP (Network space temperature (with BV 407 enabled)); MV 300 CURRENT_MODE (Current mode status: Off, Heat, Cool); AV 104 SP_TEMP_CTRL (Space temperature used for control); BV 205 G_OUT (Fan output status); BV 200 Y1_OUT (First stage cooling output status); BV 203 W1_OUT (First stage heating output status).
How do I enable BMS control of the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4?
BMS occupancy is used only when BMS Occupancy Enable (BV 507) is enabled; the BMS then writes BACnet BMS Occupancy (BV 405). Gated configuration objects need BACnet Config Write Enable (BV 511).
Does the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 need a BACnet heartbeat or have a communication timeout?
Network Space Temperature (AV 103) and Network Space Humidity (AV 105) must be rewritten at least every 5 minutes; if not, the control value falls back to the thermostat's own sensor (AI 100 / AI 101).
Can the BMS supply sensor values to the Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4?
Network Space Temperature (AV 103) and Network Space Humidity (AV 105) are written by the BMS and take effect only when BV 407 / BV 408 are enabled and the value was written within the last 5 minutes. AV 104 and AV 106 show the values the control logic actually uses.
How do I check these points on the real Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4 Installation Guide (Appendix A, BACnet Objects) · 11-808-1226-01 · rev. 2026-06. Object names, instances and units are reproduced as published; descriptions are our own.