Fan coil (chilled water cassette) controller · BACnet points list
Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet points list
Updated 7 November 2026
The 42WKN cassette controller has a built-in RS-485 port that runs BACnet MS/TP or Modbus RTU, chosen with DIP switch SW3.8 (on = BACnet). The object list has 105 objects: sensor inputs, valve and fan outputs, setpoints, mode, fan speed, occupancy and PID/fan-speed tuning values, and binary values for on/off, keypad locks and input polarity.
This page lists 105 BACnet objects for the Carrier 42WKN Chilled Water Cassette (microprocessor controller) — 93 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 42WKN Chilled Water Cassette (microprocessor controller)
- Equipment
- Fan coil (chilled water cassette) controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 105 (93 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 315000 + MAC address
- Also known as
- 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Set SW3.8 on (BACnet MS/TP), give each cassette a unique address 0-63 on SW1, and the device instance becomes 315000 plus that address. From the BMS, turn the unit on/off with BV 0, write the mode (AV 4), fan speed (AV 6) and cooling/heating setpoints, and read the effective mode, fan, setpoint and return air temperature.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | OnOff | Unit on/off command (1=On) | Write |
| AV 4 | Mode | Mode: 0=Fan only, 1=Cool, 2=Heat, 3=Auto | Write |
| AV 6 | FanSpeed | Fan speed: 0=Auto, 1=Low, 2=Medium, 3=High | Write |
| AV 0 | SetPoint_SetPointCool | Cooling setpoint | Write |
| AV 1 | SetPointHeat | Heating setpoint | Write |
| BV 16 | UnoccupiedByNetwork | Network unoccupied command (1=Unoccupied) | Write |
| AV 5 | ModeEffective | Effective mode (4=Off) | Read |
| AV 7 | FanEffective | Effective fan speed | Read |
| AV 3 | ReturnAirSensorEffective | Return air temperature in use | Read |
| BI 0 | DI_1 | Alarm relay input: 1 = fault, outputs off | Read |
Enable & remote start
No separate enable; the BMS writes On/Off (BV 0), mode and setpoints directly. Keypad lock BVs (BV 3-6) stop local changes at the touchscreen thermostat.
Network setup
- SW3.8 on = BACnet MS/TP (default), off = Modbus.
- MAC address 0-63 is set on DIP switches SW1.1-SW1.6.
- MS/TP baud rate 9600, 19200, 38400 or 76800; no parity, 8 data bits, 1 stop bit.
- Device instance = 315000 + MAC address.
Watch out for
- BV 13 RestoreDefault resets the controller to factory settings; do not write it.
- Mode, fan speed and occupancy are analog values with numeric codes, not multistate objects.
Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | T1_Sensor | range 32 to 104°F (0 to 40°C) | °F | Write | |
| AI | 1 | T2_Sensor | range -4 to 212°F (-20 to 100°C) | °F | Write | |
| AI | 2 | T3_Sensor | range -4 to 212°F (-20 to 100°C) | °F | Write | |
| AO | 0 | AO_Cool | cool/heat valve; range 0 to 100% | % | Write | |
| AO | 1 | AO_Heat | range 0 to 100% | % | Write | |
| AO | 2 | AO_Fan | range 0 to 100% | % | Write | |
| AVmin | 0 | SetPoint_SetPointCool | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AVmin | 1 | SetPointHeat | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AV | 2 | SetPointEffective | range 41 to 95°F (5 to 35°C) | °F | Read | |
| AVmin | 3 | ReturnAirSensorEffective | range 32 to 212°F (0 to 100°C) | °F | Read | |
| AVmin | 4 | Mode | Write | 0-Fan only, 1-Cool,2-Heat, 3-Auto, 6-emergency mode from IRP. | ||
| AVmin | 5 | ModeEffective | Read | 0-Fan only, 1-Cool, 2-Heat, 4-Off, 5-None mode** (2-Pipe) | ||
| AVmin | 6 | FanSpeed | Write | 0-Auto, 1-Low, 2-Medium, 3-High | ||
| AVmin | 7 | FanEffective | Read | 0-Auto, 1-Low, 2-Medium, 3-High, 4-Off | ||
| AV | 8 | ReturnAirSensorCalibration | range -9 to 9°F (-5 to 5°C) | °F | Write | |
| AV | 9 | SetPointLimitCool | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AV | 10 | SetPointLimitHeat | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AV | 11 | EconomySetPointInCool | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AV | 12 | EconomySetPointInHeat | range 41 to 95°F (5 to 35°C) | °F | Write | |
| AV | 13 | OccupancyEffectiveHVAC | Read | 0 - Occupied, 2-Unoccupied (AV#14=1), 3-Unoccupied (AV#14=2), 4-Unoccupied (AV#14=3) | ||
| AV | 14 | OccupancySensorFunction | Write | 0-Not used, 1-On/Off, 2-Start/Stop, 3-Economy | ||
| AV | 15 | OccupancySensorHVACDelayTime | range 0 to 900 min | min | Write | |
| AV | 17 | T2_Effective | range -9.9 to 210°F (-9.9 to 99°C) | °F | Read | |
| AV | 18 | T3_Effective | range -9.9 to 210°F (-9.9 to 99°C) | °F | Read | |
| AV | 19 | CoolFanOnDelay | range 0 to 120 sec | sec | Write | |
| AV | 20 | CoolFanOffDelay | range 0 to 120 sec | sec | Write | |
| AV | 21 | HeatFanOnDelay | range 0 to 120 sec | sec | Write | |
| AV | 22 | HeatFanOffDelay | range 0 to 120 sec | sec | Write | |
| AV | 23 | FreezeProtectionCutInSetpoint | range 46 to 59°F (8…15°C) | °F | Write | |
| AV | 24 | FreezeProtectionCutOutSetpoint | range 50 to 63°F (10…17°C) | °F | Write | |
| AV | 27 | CoolDifferentialBand | range 1 to 9°F (0.5 to 5°C) | °F | Write | |
| AV | 28 | CoolDifferentialBandOffset | range -9 to 9°F (-5 to 5°C) | °F | Write | |
| AV | 31 | ShiftBetweenCoolAndHeat | range 0 to 18°F (0 to 10°C) | °F | Write | |
| AV | 33 | ShiftBetweenHeatStages | range 0 to 88°F (0 to 49°C) | °F | Write | |
| AV | 36 | TimeDelayOnNextHeatStage | range 0 to 600 sec | sec | Write | |
| AV | 46 | FanSoftStartInHeatCutInTemperature | range 57 to 99°F (14 to 37°C) | °F | Write | |
| AV | 47 | FanSoftStartInHeatCutOutTemperature | range 54 to 95°F (12 to 35°C) | °F | Write | |
| AV | 48 | DifferentialOnOffFanSpeeds | range 0.6 to 4°F (0.3 to 2°C) | °F | Write | |
| AV | 49 | OutputsThresholdTimeCool | range 0 to 100 sec | sec | Write | |
| AV | 50 | OutputsThresholdTimeHeat | range 0 to 100 sec | sec | Write | |
| AV | 51 | Kp_PIDCool | range 0 to 100 | Write | ||
| AV | 52 | Kp_PIDHeat | range 0 to 100 | Write | ||
| AV | 53 | Ki_PIDCool | range 0 to 100 | Write | ||
| AV | 54 | Ki_PIDHeat | range 0 to 100 | Write | ||
| AV | 55 | Kd_PIDCool | range 0 to 100 | Write | ||
| AV | 56 | Kd_PIDHeat | range 0 to 100 | Write | ||
| AV | 57 | CoolValveProportionalBand | range 2 to 18°F (1 to 10°C) | °F | Write | |
| AV | 58 | CoolProportionalLowLimit | range 0 to 100% | % | Write | |
| AV | 59 | CoolProportionalHighLimit | range 0 to 100% | % | Write | |
| AV | 60 | HeatValveProportionalBand | range 2 to 18°F (1 to 10°C) | °F | Write | |
| AV | 61 | HeatProportionalLowLimit | range 0 to 100% | % | Write | |
| AV | 62 | HeatProportionalHighLimit | range 0 to 100% | % | Write | |
| AV | 64 | ProportionalOnPercent | range 0 to 30% | % | Write | |
| AV | 65 | ProportionalOffPercent | range 0 to 20% | % | Write | |
| AV | 66 | CoolVFSProportionalBand | range 2 to 18°F (1 to 10°C) | °F | Write | |
| AV | 67 | HeatVFSProportionalBand | range 2 to 18°F (1 to 10°C) | °F | Write | |
| AV | 68 | CoolVFSLowSpeedPercent | range 0 to 100% | % | Write | |
| AV | 69 | CoolVFSMediumSpeedPercent | range 0 to 100% | % | Write | |
| AV | 70 | CoolVFSHighSpeedPercent | range 0 to 100% | % | Write | |
| AV | 71 | HeatVFSLowSpeedPercent | range 0 to 100% | % | Write | |
| AV | 72 | HeatVFSMediumSpeedPercent | range 0 to 100% | % | Write | |
| AV | 73 | HeatVFSHighSpeedPercent | range 0 to 100% | % | Write | |
| AV | 75 | VFSMediumSpeedDiff | range 1 to 100% | % | Write | |
| AV | 76 | VFSHighSpeedDiff | range 1 to 100% | % | Write | |
| AV | 77 | CoolVFSLowLimit | range 0 to 100% | % | Write | |
| AV | 78 | CoolVFSHighLimit | range 0 to 100% | % | Write | |
| AV | 79 | HeatVFSLowLimit | range 0 to 100% | % | Write | |
| AV | 80 | HeatVFSHighLimit | range 0 to 100% | % | Write | |
| AV | 113 | ModbusBaudRate | not in use; range 0 to 4 | Write | ||
| AV | 133 | DipSwitchesState | SW2, SW3 configuration; range 0 to 65535 | Read | ||
| BImin | 0 | DI_1 | Read | 1-Open: Fault all outputs off, 0-Close: normal work (if BV#39=1) | ||
| BI | 1 | DI2_OccupancySensor | Read | 1-Open:Occupied, 0-Close: Unoccupied (if BV#40=1) | ||
| BI | 2 | DI_3 | Read | 0-Open, 1-Close (if BV#41=0) | ||
| BI | 3 | DI_4 | Read | 0-Open, 1-Close (if BV#42=0) | ||
| BO | 0 | Heat1 | Write | 1-On, 0-Off | ||
| BO | 1 | Heat2 | Write | 1-On, 0-Off | ||
| BO | 2 | Heat3 | Write | 1-On, 0-Off | ||
| BO | 3 | Cool1 | cool/heat valve | Write | 1-On, 0-Off | |
| BO | 5 | FanOnOffLow | Write | 1-On, 0-Off | ||
| BO | 6 | FanOnOffMedium | Write | 1-On, 0-Off | ||
| BO | 7 | FanOnOffHigh | Write | 1-On, 0-Off | ||
| BO | 12 | PumpOut | Write | 1-On, 0-Off | ||
| BO | 13 | SwingOut | Write | 1-On, 0-Off | ||
| BVmin | 0 | OnOff | Write | 1-On, 0-Off | ||
| BV | 1 | AutoFanInCool | Write | 1-Enable, 0-Disable | ||
| BV | 2 | C_F_Scale | Write | 1-Celsius, 0-Fahrenheit | ||
| BV | 3 | LockFan | Write | 1-Lock, 0-Unlock | ||
| BV | 4 | LockMode | Write | 1-Lock, 0-Unlock | ||
| BV | 5 | LockOnOff | Write | 1-Lock, 0-Unlock | ||
| BV | 6 | LockSetpoint | Write | 1-Lock, 0-Unlock | ||
| BV | 7 | One_TwoSetpoints | Write | 0-one setpoint, 1-two setpoints | ||
| BV | 10 | AutoModeEnable | Write | 1-Enable, 0-Disable | ||
| BV | 11 | FreezeProtectionEnable | Write | 1-Enable, 0-Disable | ||
| BV | 13 | RestoreDefault | Write | 1-Perform Restore, 0-NOP | ||
| BVmin | 16 | UnoccupiedByNetwork | Write | 1-Unoccupied, 0-Off | ||
| BV | 35 | TemperatureOverrideEnable | Write | 1-Enable, 0-Disable | ||
| BV | 38 | AutoFanInHeat | Write | 1-On, 0-Off | ||
| BV | 39 | DI1_Polarity | Write | 1-Normally close, 0-Normally open | ||
| BV | 40 | DI2_Polarity | Write | 1-Normally open, 0-Normally close | ||
| BV | 41 | DI3_Polarity | Write | 1-Normally close, 0-Normally open | ||
| BV | 42 | DI4_Polarity | Write | 1-Normally close, 0-Normally open | ||
| BV | 47 | DisableOccupancySensor | Write | 0-Enable Occ. sensor, 1-Disable Occ. sensor | ||
| BV | 48 | SelectModeInFCByDI3Enable | Write | 0-Disable DI3 in 2 pipe, 1-Enable DI3 in 2 pipe | ||
| BV | 54 | DisablePolling | Write | 0-Enable Polling after power break, 1-Disable Polling after power break | ||
| BV | 55 | SwingEnable | Write | 0-Swing out disable, 1-Swing out enable (according to controller logic) |
No points match these filters.
Object ID lookup: Carrier 42WKN point IDs by name
AI0T1_SensorAI1T2_SensorAI2T3_SensorAO0AO_CoolAO1AO_HeatAO2AO_FanAV0SetPoint_SetPointCoolAV1SetPointHeatAV2SetPointEffectiveAV3ReturnAirSensorEffectiveAV4ModeAV5ModeEffectiveAV6FanSpeedAV7FanEffectiveAV8ReturnAirSensorCalibrationAV9SetPointLimitCoolAV10SetPointLimitHeatAV11EconomySetPointInCoolAV12EconomySetPointInHeatAV13OccupancyEffectiveHVACAV14OccupancySensorFunctionAV15OccupancySensorHVACDelayTimeAV17T2_EffectiveAV18T3_EffectiveAV19CoolFanOnDelayAV20CoolFanOffDelayAV21HeatFanOnDelayAV22HeatFanOffDelayAV23FreezeProtectionCutInSetpointAV24FreezeProtectionCutOutSetpointAV27CoolDifferentialBandAV28CoolDifferentialBandOffsetAV31ShiftBetweenCoolAndHeatAV33ShiftBetweenHeatStagesAV36TimeDelayOnNextHeatStageAV46FanSoftStartInHeatCutInTemperatureAV47FanSoftStartInHeatCutOutTemperatureAV48DifferentialOnOffFanSpeedsAV49OutputsThresholdTimeCoolAV50OutputsThresholdTimeHeatAV51Kp_PIDCoolAV52Kp_PIDHeatAV53Ki_PIDCoolAV54Ki_PIDHeatAV55Kd_PIDCoolAV56Kd_PIDHeatAV57CoolValveProportionalBandAV58CoolProportionalLowLimitAV59CoolProportionalHighLimitAV60HeatValveProportionalBandAV61HeatProportionalLowLimitAV62HeatProportionalHighLimitAV64ProportionalOnPercentAV65ProportionalOffPercentAV66CoolVFSProportionalBandAV67HeatVFSProportionalBandAV68CoolVFSLowSpeedPercentAV69CoolVFSMediumSpeedPercentAV70CoolVFSHighSpeedPercentAV71HeatVFSLowSpeedPercentAV72HeatVFSMediumSpeedPercentAV73HeatVFSHighSpeedPercentAV75VFSMediumSpeedDiffAV76VFSHighSpeedDiffAV77CoolVFSLowLimitAV78CoolVFSHighLimitAV79HeatVFSLowLimitAV80HeatVFSHighLimitAV113ModbusBaudRateAV133DipSwitchesStateBI0DI_1BI1DI2_OccupancySensorBI2DI_3BI3DI_4BO0Heat1BO1Heat2BO2Heat3BO3Cool1BO5FanOnOffLowBO6FanOnOffMediumBO7FanOnOffHighBO12PumpOutBO13SwingOutBV0OnOffBV1AutoFanInCoolBV2C_F_ScaleBV3LockFanBV4LockModeBV5LockOnOffBV6LockSetpointBV7One_TwoSetpointsBV10AutoModeEnableBV11FreezeProtectionEnableBV13RestoreDefaultBV16UnoccupiedByNetworkBV35TemperatureOverrideEnableBV38AutoFanInHeatBV39DI1_PolarityBV40DI2_PolarityBV41DI3_PolarityBV42DI4_PolarityBV47DisableOccupancySensorBV48SelectModeInFCByDI3EnableBV54DisablePollingBV55SwingEnable
Integration notes
- Objects are printed as 'Analog Value #0' style references; the number after # is the object instance.
- Mode, fan speed and occupancy points are analog values whose numeric codes are given in the Value column (e.g. 0-Fan only, 1-Cool, 2-Heat, 3-Auto); those codes are kept in the states field.
- For analog objects the printed range is kept in the description; temperatures are shown in °F with °C in brackets.
- AV 113 ModbusBaudRate is marked not in use.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 42WKN Chilled Water Cassette (microprocessor controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 42WKN Chilled Water Cassette (microprocessor controller)
How many BACnet points does the Carrier 42WKN Chilled Water Cassette (microprocessor controller) have?
This list has 105 BACnet objects: 3 analog inputs, 3 analog outputs, 64 analog values, 4 binary inputs, 9 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet points are writable?
93 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet documentation?
The source is Microprocessor Controls Manual for Chilled Water Cassettes, Models 42WKN - Controls Operation and Troubleshooting (Table 21, BACnet Points List) (42WKN-1T), revision 2026-10, published free by Carrier at https://brandportal.carrier.com/asset/113fdae2-3fa6-4fd8-8f2f-52d362b2df24/42WKN-1T.pdf.
What are the minimum BACnet points to integrate the Carrier 42WKN Chilled Water Cassette (microprocessor controller)?
Start with BV 0 OnOff (Unit on/off command (1=On)); AV 4 Mode (Mode: 0=Fan only, 1=Cool, 2=Heat, 3=Auto); AV 6 FanSpeed (Fan speed: 0=Auto, 1=Low, 2=Medium, 3=High); AV 0 SetPoint_SetPointCool (Cooling setpoint); AV 1 SetPointHeat (Heating setpoint); BV 16 UnoccupiedByNetwork (Network unoccupied command (1=Unoccupied)); AV 5 ModeEffective (Effective mode (4=Off)); AV 7 FanEffective (Effective fan speed); AV 3 ReturnAirSensorEffective (Return air temperature in use); BI 0 DI_1 (Alarm relay input: 1 = fault, outputs off).
How do I enable BMS control of the Carrier 42WKN Chilled Water Cassette (microprocessor controller)?
No separate enable; the BMS writes On/Off (BV 0), mode and setpoints directly. Keypad lock BVs (BV 3-6) stop local changes at the touchscreen thermostat.
How do I check these points on the real 42WKN Chilled Water Cassette (microprocessor controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Microprocessor Controls Manual for Chilled Water Cassettes, Models 42WKN - Controls Operation and Troubleshooting (Table 21, BACnet Points List) · 42WKN-1T · rev. 2026-10. Object names, instances and units are reproduced as published; descriptions are our own.