Fan coil (chilled water cassette) controller · BACnet points list

Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet points list

Updated 7 November 2026

Short answer

The 42WKN cassette controller has a built-in RS-485 port that runs BACnet MS/TP or Modbus RTU, chosen with DIP switch SW3.8 (on = BACnet). The object list has 105 objects: sensor inputs, valve and fan outputs, setpoints, mode, fan speed, occupancy and PID/fan-speed tuning values, and binary values for on/off, keypad locks and input polarity.

This page lists 105 BACnet objects for the Carrier 42WKN Chilled Water Cassette (microprocessor controller) — 93 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
42WKN Chilled Water Cassette (microprocessor controller)
Equipment
Fan coil (chilled water cassette) controller
Equipment type
VAV boxes & fan coils
BACnet objects
105 (93 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
315000 + MAC address
Also known as
42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002
Source document
Microprocessor Controls Manual for Chilled Water Cassettes, Models 42WKN - Controls Operation and Troubleshooting (Table 21, BACnet Points List) · 42WKN-1T · rev. 2026-10
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier 42WKN Chilled Water Cassette (microprocessor controller)

Integration in brief

Set SW3.8 on (BACnet MS/TP), give each cassette a unique address 0-63 on SW1, and the device instance becomes 315000 plus that address. From the BMS, turn the unit on/off with BV 0, write the mode (AV 4), fan speed (AV 6) and cooling/heating setpoints, and read the effective mode, fan, setpoint and return air temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0OnOffUnit on/off command (1=On)Write
AV 4ModeMode: 0=Fan only, 1=Cool, 2=Heat, 3=AutoWrite
AV 6FanSpeedFan speed: 0=Auto, 1=Low, 2=Medium, 3=HighWrite
AV 0SetPoint_SetPointCoolCooling setpointWrite
AV 1SetPointHeatHeating setpointWrite
BV 16UnoccupiedByNetworkNetwork unoccupied command (1=Unoccupied)Write
AV 5ModeEffectiveEffective mode (4=Off)Read
AV 7FanEffectiveEffective fan speedRead
AV 3ReturnAirSensorEffectiveReturn air temperature in useRead
BI 0DI_1Alarm relay input: 1 = fault, outputs offRead

Enable & remote start

No separate enable; the BMS writes On/Off (BV 0), mode and setpoints directly. Keypad lock BVs (BV 3-6) stop local changes at the touchscreen thermostat.

Network setup

Watch out for

Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

105 of 105 shown
Type
Access
Show
Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet Points List
DescriptionStates
AI0T1_Sensorrange 32 to 104°F (0 to 40°C)°FWrite
AI1T2_Sensorrange -4 to 212°F (-20 to 100°C)°FWrite
AI2T3_Sensorrange -4 to 212°F (-20 to 100°C)°FWrite
AO0AO_Coolcool/heat valve; range 0 to 100%%Write
AO1AO_Heatrange 0 to 100%%Write
AO2AO_Fanrange 0 to 100%%Write
AVmin0SetPoint_SetPointCoolrange 41 to 95°F (5 to 35°C)°FWrite
AVmin1SetPointHeatrange 41 to 95°F (5 to 35°C)°FWrite
AV2SetPointEffectiverange 41 to 95°F (5 to 35°C)°FRead
AVmin3ReturnAirSensorEffectiverange 32 to 212°F (0 to 100°C)°FRead
AVmin4ModeWrite0-Fan only, 1-Cool,2-Heat, 3-Auto, 6-emergency mode from IRP.
AVmin5ModeEffectiveRead0-Fan only, 1-Cool, 2-Heat, 4-Off, 5-None mode** (2-Pipe)
AVmin6FanSpeedWrite0-Auto, 1-Low, 2-Medium, 3-High
AVmin7FanEffectiveRead0-Auto, 1-Low, 2-Medium, 3-High, 4-Off
AV8ReturnAirSensorCalibrationrange -9 to 9°F (-5 to 5°C)°FWrite
AV9SetPointLimitCoolrange 41 to 95°F (5 to 35°C)°FWrite
AV10SetPointLimitHeatrange 41 to 95°F (5 to 35°C)°FWrite
AV11EconomySetPointInCoolrange 41 to 95°F (5 to 35°C)°FWrite
AV12EconomySetPointInHeatrange 41 to 95°F (5 to 35°C)°FWrite
AV13OccupancyEffectiveHVACRead0 - Occupied, 2-Unoccupied (AV#14=1), 3-Unoccupied (AV#14=2), 4-Unoccupied (AV#14=3)
AV14OccupancySensorFunctionWrite0-Not used, 1-On/Off, 2-Start/Stop, 3-Economy
AV15OccupancySensorHVACDelayTimerange 0 to 900 minminWrite
AV17T2_Effectiverange -9.9 to 210°F (-9.9 to 99°C)°FRead
AV18T3_Effectiverange -9.9 to 210°F (-9.9 to 99°C)°FRead
AV19CoolFanOnDelayrange 0 to 120 secsecWrite
AV20CoolFanOffDelayrange 0 to 120 secsecWrite
AV21HeatFanOnDelayrange 0 to 120 secsecWrite
AV22HeatFanOffDelayrange 0 to 120 secsecWrite
AV23FreezeProtectionCutInSetpointrange 46 to 59°F (8…15°C)°FWrite
AV24FreezeProtectionCutOutSetpointrange 50 to 63°F (10…17°C)°FWrite
AV27CoolDifferentialBandrange 1 to 9°F (0.5 to 5°C)°FWrite
AV28CoolDifferentialBandOffsetrange -9 to 9°F (-5 to 5°C)°FWrite
AV31ShiftBetweenCoolAndHeatrange 0 to 18°F (0 to 10°C)°FWrite
AV33ShiftBetweenHeatStagesrange 0 to 88°F (0 to 49°C)°FWrite
AV36TimeDelayOnNextHeatStagerange 0 to 600 secsecWrite
AV46FanSoftStartInHeatCutInTemperaturerange 57 to 99°F (14 to 37°C)°FWrite
AV47FanSoftStartInHeatCutOutTemperaturerange 54 to 95°F (12 to 35°C)°FWrite
AV48DifferentialOnOffFanSpeedsrange 0.6 to 4°F (0.3 to 2°C)°FWrite
AV49OutputsThresholdTimeCoolrange 0 to 100 secsecWrite
AV50OutputsThresholdTimeHeatrange 0 to 100 secsecWrite
AV51Kp_PIDCoolrange 0 to 100Write
AV52Kp_PIDHeatrange 0 to 100Write
AV53Ki_PIDCoolrange 0 to 100Write
AV54Ki_PIDHeatrange 0 to 100Write
AV55Kd_PIDCoolrange 0 to 100Write
AV56Kd_PIDHeatrange 0 to 100Write
AV57CoolValveProportionalBandrange 2 to 18°F (1 to 10°C)°FWrite
AV58CoolProportionalLowLimitrange 0 to 100%%Write
AV59CoolProportionalHighLimitrange 0 to 100%%Write
AV60HeatValveProportionalBandrange 2 to 18°F (1 to 10°C)°FWrite
AV61HeatProportionalLowLimitrange 0 to 100%%Write
AV62HeatProportionalHighLimitrange 0 to 100%%Write
AV64ProportionalOnPercentrange 0 to 30%%Write
AV65ProportionalOffPercentrange 0 to 20%%Write
AV66CoolVFSProportionalBandrange 2 to 18°F (1 to 10°C)°FWrite
AV67HeatVFSProportionalBandrange 2 to 18°F (1 to 10°C)°FWrite
AV68CoolVFSLowSpeedPercentrange 0 to 100%%Write
AV69CoolVFSMediumSpeedPercentrange 0 to 100%%Write
AV70CoolVFSHighSpeedPercentrange 0 to 100%%Write
AV71HeatVFSLowSpeedPercentrange 0 to 100%%Write
AV72HeatVFSMediumSpeedPercentrange 0 to 100%%Write
AV73HeatVFSHighSpeedPercentrange 0 to 100%%Write
AV75VFSMediumSpeedDiffrange 1 to 100%%Write
AV76VFSHighSpeedDiffrange 1 to 100%%Write
AV77CoolVFSLowLimitrange 0 to 100%%Write
AV78CoolVFSHighLimitrange 0 to 100%%Write
AV79HeatVFSLowLimitrange 0 to 100%%Write
AV80HeatVFSHighLimitrange 0 to 100%%Write
AV113ModbusBaudRatenot in use; range 0 to 4Write
AV133DipSwitchesStateSW2, SW3 configuration; range 0 to 65535Read
BImin0DI_1Read1-Open: Fault all outputs off, 0-Close: normal work (if BV#39=1)
BI1DI2_OccupancySensorRead1-Open:Occupied, 0-Close: Unoccupied (if BV#40=1)
BI2DI_3Read0-Open, 1-Close (if BV#41=0)
BI3DI_4Read0-Open, 1-Close (if BV#42=0)
BO0Heat1Write1-On, 0-Off
BO1Heat2Write1-On, 0-Off
BO2Heat3Write1-On, 0-Off
BO3Cool1cool/heat valveWrite1-On, 0-Off
BO5FanOnOffLowWrite1-On, 0-Off
BO6FanOnOffMediumWrite1-On, 0-Off
BO7FanOnOffHighWrite1-On, 0-Off
BO12PumpOutWrite1-On, 0-Off
BO13SwingOutWrite1-On, 0-Off
BVmin0OnOffWrite1-On, 0-Off
BV1AutoFanInCoolWrite1-Enable, 0-Disable
BV2C_F_ScaleWrite1-Celsius, 0-Fahrenheit
BV3LockFanWrite1-Lock, 0-Unlock
BV4LockModeWrite1-Lock, 0-Unlock
BV5LockOnOffWrite1-Lock, 0-Unlock
BV6LockSetpointWrite1-Lock, 0-Unlock
BV7One_TwoSetpointsWrite0-one setpoint, 1-two setpoints
BV10AutoModeEnableWrite1-Enable, 0-Disable
BV11FreezeProtectionEnableWrite1-Enable, 0-Disable
BV13RestoreDefaultWrite1-Perform Restore, 0-NOP
BVmin16UnoccupiedByNetworkWrite1-Unoccupied, 0-Off
BV35TemperatureOverrideEnableWrite1-Enable, 0-Disable
BV38AutoFanInHeatWrite1-On, 0-Off
BV39DI1_PolarityWrite1-Normally close, 0-Normally open
BV40DI2_PolarityWrite1-Normally open, 0-Normally close
BV41DI3_PolarityWrite1-Normally close, 0-Normally open
BV42DI4_PolarityWrite1-Normally close, 0-Normally open
BV47DisableOccupancySensorWrite0-Enable Occ. sensor, 1-Disable Occ. sensor
BV48SelectModeInFCByDI3EnableWrite0-Disable DI3 in 2 pipe, 1-Enable DI3 in 2 pipe
BV54DisablePollingWrite0-Enable Polling after power break, 1-Disable Polling after power break
BV55SwingEnableWrite0-Swing out disable, 1-Swing out enable (according to controller logic)
Object ID lookup: Carrier 42WKN point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 42WKN Chilled Water Cassette (microprocessor controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 42WKN Chilled Water Cassette (microprocessor controller)

How many BACnet points does the Carrier 42WKN Chilled Water Cassette (microprocessor controller) have?

This list has 105 BACnet objects: 3 analog inputs, 3 analog outputs, 64 analog values, 4 binary inputs, 9 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet points are writable?

93 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 42WKN Chilled Water Cassette (microprocessor controller) BACnet documentation?

The source is Microprocessor Controls Manual for Chilled Water Cassettes, Models 42WKN - Controls Operation and Troubleshooting (Table 21, BACnet Points List) (42WKN-1T), revision 2026-10, published free by Carrier at https://brandportal.carrier.com/asset/113fdae2-3fa6-4fd8-8f2f-52d362b2df24/42WKN-1T.pdf.

What are the minimum BACnet points to integrate the Carrier 42WKN Chilled Water Cassette (microprocessor controller)?

Start with BV 0 OnOff (Unit on/off command (1=On)); AV 4 Mode (Mode: 0=Fan only, 1=Cool, 2=Heat, 3=Auto); AV 6 FanSpeed (Fan speed: 0=Auto, 1=Low, 2=Medium, 3=High); AV 0 SetPoint_SetPointCool (Cooling setpoint); AV 1 SetPointHeat (Heating setpoint); BV 16 UnoccupiedByNetwork (Network unoccupied command (1=Unoccupied)); AV 5 ModeEffective (Effective mode (4=Off)); AV 7 FanEffective (Effective fan speed); AV 3 ReturnAirSensorEffective (Return air temperature in use); BI 0 DI_1 (Alarm relay input: 1 = fault, outputs off).

How do I enable BMS control of the Carrier 42WKN Chilled Water Cassette (microprocessor controller)?

No separate enable; the BMS writes On/Off (BV 0), mode and setpoints directly. Keypad lock BVs (BV 3-6) stop local changes at the touchscreen thermostat.

How do I check these points on the real 42WKN Chilled Water Cassette (microprocessor controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Microprocessor Controls Manual for Chilled Water Cassettes, Models 42WKN - Controls Operation and Troubleshooting (Table 21, BACnet Points List) · 42WKN-1T · rev. 2026-10. Object names, instances and units are reproduced as published; descriptions are our own.