- Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Packaged rooftop unit controller (BACnet option) · BACnet points list
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) BACnet points list
Updated 4 November 2026
On 48/50P large rooftops the BACnet option is a UPC Open controller in its own enclosure below the main control box. It speaks BACnet MS/TP to the BMS and CCN to the unit's ComfortLink board. The list has 169 rows of AVs and BVs: setpoints, air temperatures, pressures and CFM, up to three compressors per circuit, heat relays, economizer, Humidi-MiZer and VFD outputs, thermostat inputs, demand limit switches, alarms and 40 user-defined spare values.
This page lists 168 BACnet objects for the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) — 88 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
- Equipment
- Packaged rooftop unit controller (BACnet option)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 168 (88 writable)
- Transport
- BACnet MS/TP
- Firmware
- ComfortLink 9.x
- Default device instance
- Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
- Also known as
- 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T
Instance calculator. This list prints one unit; the other units follow a formula. Carrier Open controllers (RTU Open, WSHP Open, UPC Open...) instance calculator →
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
The BMS talks BACnet MS/TP to the UPC Open, which reads and writes the 48/50P ComfortLink control over CCN. Set the CCN schedule number for the occupancy source you want, then write occupancy, setpoints and (for VAV) the supply air setpoint; read HVAC mode, temperatures and alarm state. Values the BMS feeds in (space, return or outdoor temperature, RH, CO2) are forces that clear if not refreshed.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2008 | occ_status_1 | Occupied? (0 = no, 1 = yes); writable | Write |
| AV 3001 | occ_cl_stpt_1 | Occupied cooling setpoint | Write |
| AV 3002 | occ_ht_stpt_1 | Occupied heating setpoint | Write |
| AV 3007 | sa_temp_stpt_1 | Supply air setpoint (VAV units) | Write |
| AV 1022 | hvac_mode_1 | HVAC mode as a number | Read |
| BV 2001 | sfan_1 | Supply fan relay on/off | Read |
| AV 43 | ctrltemp_1 | Control temperature (RAT, SPT or zone) | Read |
| AV 10 | sat_1 | Supply air temperature leaving the fan | Read |
| BV 9 | alm_1 | Unit alarm state | Read |
| BV 105 | comm_lost_alm_1 | UPC lost CCN communication with the unit | Read |
Enable & remote start
Occupancy follows the ComfortLink CCN schedule number (Configuration > CCN > SC.OV > SCH.N): 0 = always occupied, 1 = local schedule (default), 65-99 = a CCN/global schedule. The points list makes Occupied? (BV:2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site. A remote switch input (RM.CF) can also set occupancy or start/stop the unit.
Heartbeat & communication loss
The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.
Sensors & values from the BMS
Space Temperature (AV:137), Return Air Temperature (AV:135), Outside Air Temperature (AV:1003), Outside Air RH (AV:119), IAQ (AV:1009) and OAQ (AV:113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).
Network setup
- Set the MAC address on the UPC Open's Tens and Ones rotary switches; the controller reads switches, DIP switches and jumpers only at power-up.
- Device instance = network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120.
- BAS port: DS3 enable, DS4 E1-485, DS5-DS8 set to MSTP; baud on DS1-DS2 (9600, 19.2k, 38.4k or 76.8k, Carrier default 76.8k); 8N1 fixed. EIA-485 jumpers to EIA-485 and 2W.
- Fit a BT485 terminator on the first and last controller of the MS/TP segment.
- The UPC Open and the ComfortLink board must use the same CCN element and bus numbers (factory 1 and 0); the CCN side stays at 9600 baud.
Watch out for
- Points depend on unit options (heat type, economizer, Humidi-MiZer, VFDs, expansion boards); objects for options not fitted carry no useful data.
- Thermostat inputs (Y1, Y2, W1, W2, G) are writable BVs, but they only act with the thermostat control type (C.TYP 3).
- The user-defined analog and binary values are spare objects with no unit function.
- UPC programs ship in English units; metric needs the UPC files rebuilt.
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 10 | sat_1 | Air Temp Lvg Supply Fan | °F | Read | |
| BV | 7030 | air_linkage_fail_1 | Airside Linkage Alarm | Read | 0=NORMAL, 1=ALARM | |
| BV | 2601 | a_link_status_1 | Airside Linkage Status | Read | 0=Not Active, 1=Active | |
| BVmin | 9 | alm_1 | Alarm State | Read | 0=NORMAL, 1=ALARM | |
| AV | 1070 | bldg_static_press_1 | Building Pressure | H2O | Read | |
| AV | 3070 | bldg_press_stpt_1 | Building Pressure Setp. (range –0.25 to 0.25) | H2O | Write | |
| AV | 1601 | discharge_press_a_1 | Cir A Discharge Pressure | psig | Read | |
| AV | 1602 | sat_cond_temp_a_1 | Cir A Sat. Condensing Temperature | °F | Read | |
| AV | 1603 | sat_suction_temp_a_1 | Cir A Sat. Suction Temperature | °F | Read | |
| AV | 1600 | suction_press_a_1 | Cir A Suction Pressure | psig | Read | |
| AV | 1605 | discharge_press_b_1 | Cir B Discharge Pressure | psig | Read | |
| AV | 1606 | sat_cond_temp_b_1 | Cir B Sat. Condensing Temperature | °F | Read | |
| AV | 1607 | sat_suction_temp_b_1 | Cir B Sat. Suction Temperature | °F | Read | |
| AV | 1604 | suction_press_b_1 | Cir B Suction Pressure | psig | Read | |
| BV | 16 | cmpa1_1 | Compressor A1 Relay | Read | 0=OFF, 1=ON | |
| BV | 17 | cmpa2_1 | Compressor A2 Relay | Read | 0=OFF, 1=ON | |
| BV | 13 | cmpa3_1 | Compressor A3 Relay | Read | 0=OFF, 1=ON | |
| BV | 18 | cmpb1_1 | Compressor B1 Relay | Read | 0=OFF, 1=ON | |
| BV | 19 | cmpb2_1 | Compressor B2 Relay | Read | 0=OFF, 1=ON | |
| BV | 14 | cmpb3_1 | Compressor B3 Relay | Read | 0=OFF, 1=ON | |
| AV | 1030 | ra_temp_1 | Controlling Return Air Temp (range –40 to 240) | °F | Write | |
| AV | 2007 | space_temp_1 | Controlling Space Temp (range –40 to 240) | °F | Write | |
| AV | 3055 | ct_sa_static_stpt_1 | Controlling Static Pressure Setpoint | inH2O | Read | |
| AV | 1024 | cool_ctrl_point_1 | Cooling Control Point | °F | Read | |
| AVmin | 3001 | occ_cl_stpt_1 | Cooling Occupied Setpoint (range 40 to 99) | °F | Write | |
| AV | 3003 | unocc_cl_stpt_1 | Cooling Unoccupied Setpoint (range 40 to 110) | °F | Write | |
| AVmin | 43 | ctrltemp_1 | Ctl.Temp RAT,SPT or ZONE - Prime Variable | °F | Read | |
| AV | 1023 | cool_capacity_1 | Current Running Capacity | % | Read | |
| AV | 44 | htsg_cap_1 | Current Running Capacity (Heat) | % | Read | |
| AV | 49 | dhcoolsp_1 | Dehumidify Cool Setpoint (range 40 to 55) | °F | Write | |
| BV | 30 | dhdiscin_1 | Dehumidify Input | Write | 0=OFF, 1=ON | |
| AV | 50 | dhrelhsp_1 | Dehumidify RH Setpoint (range 10 to 90) | % | Write | |
| AV | 53 | dlswsp1_1 | Demand Limit Sw.1 Setpt. (range 0 to 100) | % | Write | |
| AV | 54 | dlswsp2_1 | Demand Limit Sw.2 Setpt. (range 0 to 100) | % | Write | |
| BV | 1006 | dmd_sw1_1 | Demand Limit Switch 1 | Write | 0=OFF, 1=ON | |
| BV | 1007 | dmd_sw2_1 | Demand Limit Switch 2 | Write | 0=OFF, 1=ON | |
| AV | 1028 | econ_pos_1 | Economizer Act. Curr. Pos | % | Read | |
| BV | 36 | ecactive_1 | Economizer Active? | Read | 0=NO, 1=YES | |
| BV | 44 | edt_stat_1 | EDT Sensor Bad? | Read | 0=NO, 1=YES | |
| BV | 2999 | element_stat_1 | Element Comm Status | Read | 0=No Comm, 1=Normal | |
| BVmin | 105 | comm_lost_alm_1 | Element Communications Alarm | Read | 0=Comm Normal, 1=Comm Lost | |
| BV | 5123 | et_reset_as_link_1 | Equipment Touch reset linkage Alarm | Write | 0=NO, 1=YES | |
| AV | 76 | edt_1 | Evaporator Discharge Tmp | °F | Read | |
| AV | 2075 | ef_vfd_output_1 | Exhaust Fan VFD Speed | % | Read | |
| BV | 1052 | filter_status_1 | Filter Status Input | Write | 0=CLEAN, 1=DIRTY | |
| BV | 52 | hs1_1 | Heat Relay 1 | Read | 0=OFF, 1=ON | |
| BV | 53 | hs2_1 | Heat Relay 2 | Read | 0=OFF, 1=ON | |
| AV | 83 | hcsp_gap_1 | Heat-Cool Setpoint Gap (range 2-10) | Δ°F | Write | |
| AV | 1025 | heat_ctrl_point_1 | Heating Control Point | °F | Read | |
| AVmin | 3002 | occ_ht_stpt_1 | Heating Occupied Setpoint (range 40 to 99) | °F | Write | |
| AV | 3008 | saspheat_1 | Heating Supply Air Setpt (range 80 to 120) | °F | Write | |
| AV | 3004 | unocc_ht_stpt_1 | Heating Unoccupied Setpoint (range 40 to 99) | °F | Write | |
| AV | 55 | htclcpos_1 | Ht.Coil Command Position | % | Read | |
| BV | 47 | hum3wval_1 | HumidiMizer 3-way Valve | Read | 0=OFF, 1=ON | |
| AV | 57 | hmzrcapc_1 | HumidiMizer Capacity | % | Read | |
| AVmin | 1022 | hvac_mode_1 | HVAC Mode Numerical Form | Read | ||
| BV | 1050 | iaq_status_1 | IAQ - Discrete Input | Write | 0=LOW, 1=HIGH | |
| AV | 1009 | iaq_1 | IAQ - PPM Return CO2 (range 0 to 5000) | Write | ||
| AV | 2607 | link_iaq_1 | Indoor Air Quality | ppm | Read | |
| AV | 1027 | lvg_air_temperature_1 | Leaving Air Temperature | °F | Read | |
| AV | 2611 | link_max_dmpr_1 | Linkage Max Damper Position | % | Read | |
| BV | 5 | schedule_1 | Local Schedule | Read | 0=OFF, 1=ON | |
| AV | 3052 | max_dmpr_pos_1 | Maximum Damper Position (range 0 to 100) | % | Write | |
| AV | 3054 | max_reset_1 | Maximum Reset | inH2O | Write | |
| AV | 3053 | min_dmpr_pos_1 | Minimum Damper Position (range 0 to 100) | % | Write | |
| AV | 1500 | ma_temp_1 | Mixed Air Temperature | °F | Read | |
| AV | 113 | oaq_1 | OAQ - PPM Outdoor CO2 (range 0 to 5000) | Write | ||
| AV | 114 | occl_end_1 | Occupied Cool Mode End | °F | Read | |
| AV | 115 | occlstrt_1 | Occupied Cool Mode Start | °F | Read | |
| AV | 116 | ocht_end_1 | Occupied Heat Mode End | °F | Read | |
| AV | 117 | ochtstrt_1 | Occupied Heat Mode Start | °F | Read | |
| BVmin | 2008 | occ_status_1 | Occupied? | Write | 0=NO, 1=YES | |
| AV | 66 | oacfm_1 | Outside Air CFM | cfm | Read | |
| AV | 119 | oarh_1 | Outside Air Relative Humidity (range 0 to 100) | % | Write | |
| AV | 1003 | oat_1 | Outside Air Temperature (range –40 to 240) | °F | Write | |
| BV | 49 | pe1_1 | Power Exhaust Relay 1 | Read | 0=OFF, 1=ON | |
| BV | 51 | pe2_1 | Power Exhaust Relay 2 | Read | 0=OFF, 1=ON | |
| BV | 76 | hs3_1 | Relay 3 W1 Gas Valve 2 | Read | 0=OFF, 1=ON | |
| BV | 77 | hs4_1 | Relay 4 W2 Gas Valve 2 | Read | 0=OFF, 1=ON | |
| BV | 78 | hs5_1 | Relay 5 W1 Gas Valve 3 | Read | 0=OFF, 1=ON | |
| BV | 79 | hs6_1 | Relay 6 W2 Gas Valve 3 | Read | 0=OFF, 1=ON | |
| AV | 2003 | heat_run_1 | Requested Heat Stage | Read | ||
| AV | 69 | racfm_1 | Return Air CFM | cfm | Read | |
| AV | 134 | rarh_1 | Return Air Relative Humidity (range 0 to 100) | % | Write | |
| AV | 135 | rat_1 | Return Air Temperature (range –40 to 240) | °F | Write | |
| BV | 6 | stpt_adj_enable_1 | Setpoint Adjustment Enable | Write | 0=DISABLE, 1=ENABLE | |
| AV | 73 | sph_1 | SP High Alert Limit (range 0 to 5) | H2O | Write | |
| AV | 74 | spl_1 | SP Low Alert Limit (range 0 to 5) | H2O | Write | |
| AV | 2606 | link_rh_1 | Space Relative Humidity | % | Read | |
| AV | 72 | sprh_1 | Space Relative Humidity (range 0 to 100) | % | Write | |
| AV | 139 | spto_rng_1 | Space Temp Offset Range (range 1 to 10) | Δ°F | Write | |
| AV | 137 | spt_1 | Space Temperature (range –40 to 240) | °F | Write | |
| AV | 150 | lat1sgas_1 | Staged Gas LAT 1 | °F | Read | |
| AV | 151 | lat2sgas_1 | Staged Gas LAT 2 | °F | Read | |
| AV | 152 | lat3sgas_1 | Staged Gas LAT 3 | °F | Read | |
| AV | 1016 | static_press_1 | Static Pressure | H2O | Read | |
| AV | 157 | spreset_1 | Static Pressure Reset (range 0 to 15) | Write | ||
| BV | 3051 | st_pr_rst_en_1 | Static Pressure Reset Enable | Write | 0=DISABLE, 1=ENABLE | |
| AV | 3050 | sa_static_stpt_1 | Static Pressure Setpoint (range 0 to 5) | H2O | Write | |
| AV | 78 | sacfm_1 | Supply Air CFM | cfm | Read | |
| BV | 93 | modesars_1 | Supply Air Reset | Read | 0=OFF, 1=ON | |
| AV | 158 | sasprset_1 | Supply Air Setpnt. Reset (range 0 to 20) | Δ°F | Write | |
| AVmin | 3007 | sa_temp_stpt_1 | Supply Air Setpoint (range 45 to 75) | °F | Write | |
| BVmin | 2001 | sfan_1 | Supply Fan Relay | Read | 0=OFF, 1=ON | |
| BV | 95 | sfs_1 | Supply Fan Status Switch | Write | 0=OFF, 1=ON | |
| AV | 2050 | sf_vfd_output_1 | Supply Fan VFD Speed | % | Read | |
| AV | 9006 | cool_demand_level_1 | System Cooling Demand Level | Read | ||
| BV | 7 | dem_lmt_act_1 | System Demand Limiting | Read | 0=Inactive, 1=Active | |
| AV | 9036 | heat_demand_level_1 | System Heating Demand Level | Read | ||
| AV | 80001 | mstr_oa_temp_1 | System OAT Master | °F | Read | |
| AV | 1903 | system_aq_1 | System Space AQ | ppm | Read | |
| AV | 1904 | system_rh_1 | System Space RH | %rh | Read | |
| AV | 1902 | system_spt_1 | System Space Temperature | °F | Read | |
| BV | 1021 | g_input_1 | Thermostat G Input | Write | 0=OFF, 1=ON | |
| BV | 1019 | w1_input_1 | Thermostat W1 Input | Write | 0=OFF, 1=ON | |
| BV | 1020 | w2_input_1 | Thermostat W2 Input | Write | 0=OFF, 1=ON | |
| BV | 1017 | y1_input_1 | Thermostat Y1 Input | Write | 0=OFF, 1=ON | |
| BV | 1018 | y2_input_1 | Thermostat Y2 Input | Write | 0=OFF, 1=ON | |
| AV | 168 | uccl_end_1 | Unoccupied Cool Mode End | °F | Read | |
| AV | 169 | ucclstrt_1 | Unoccupied Cool Mode Start | °F | Read | |
| AV | 170 | ucht_end_1 | Unoccupied Heat Mode End | °F | Read | |
| AV | 171 | uchtstrt_1 | Unoccupied Heat Mode Start | °F | Read | |
| BV | 2605 | use_linkage_1 | Use Linkage | Write | 0=NO, 1=YES | |
| AV | 2901 | user_analog_1_1 | User Defined Analog 1 | Write | ||
| AV | 2909 | user_analog_10_1 | User Defined Analog 10 | Write | ||
| AV | 2910 | user_analog_11_1 | User Defined Analog 11 | Write | ||
| AV | 2912 | user_analog_12_1 | User Defined Analog 12 | Write | ||
| AV | 2913 | user_analog_13_1 | User Defined Analog 13 | Write | ||
| AV | 2914 | user_analog_14_1 | User Defined Analog 14 | Write | ||
| AV | 2915 | user_analog_15_1 | User Defined Analog 15 | Write | ||
| AV | 2916 | user_analog_16_1 | User Defined Analog 16 | Write | ||
| AV | 2917 | user_analog_17_1 | User Defined Analog 17 | Write | ||
| AV | 2918 | user_analog_18_1 | User Defined Analog 18 | Write | ||
| AV | 2919 | user_analog_19_1 | User Defined Analog 19 | Write | ||
| AV | 2902 | user_analog_2_1 | User Defined Analog 2 | Write | ||
| AV | 2920 | user_analog_20_1 | User Defined Analog 20 | Write | ||
| AV | 2903 | user_analog_3_1 | User Defined Analog 3 | Write | ||
| AV | 2904 | user_analog_4_1 | User Defined Analog 4 | Write | ||
| AV | 2905 | user_analog_5_1 | User Defined Analog 5 | Write | ||
| AV | 2906 | user_analog_6_1 | User Defined Analog 6 | Write | ||
| AV | 2907 | user_analog_8_1 | User Defined Analog 8 | Write | ||
| AV | 2908 | user_analog_9_1 | User Defined Analog 9 | Write | ||
| BV | 2951 | user_binary_1_1 | User Defined Binary 1 | Write | 0=OFF, 1=ON | |
| BV | 2960 | user_binary_10_1 | User Defined Binary 10 | Write | 0=OFF, 1=ON | |
| BV | 2961 | user_binary_11_1 | User Defined Binary 11 | Write | 0=OFF, 1=ON | |
| BV | 2962 | user_binary_12_1 | User Defined Binary 12 | Write | 0=OFF, 1=ON | |
| BV | 2963 | user_binary_13_1 | User Defined Binary 13 | Write | 0=OFF, 1=ON | |
| BV | 2964 | user_binary_14_1 | User Defined Binary 14 | Write | 0=OFF, 1=ON | |
| BV | 2965 | user_binary_15_1 | User Defined Binary 15 | Write | 0=OFF, 1=ON | |
| BV | 2966 | user_binary_16_1 | User Defined Binary 16 | Write | 0=OFF, 1=ON | |
| BV | 2967 | user_binary_17_1 | User Defined Binary 17 | Write | 0=OFF, 1=ON | |
| BV | 2968 | user_binary_18_1 | User Defined Binary 18 | Write | 0=OFF, 1=ON | |
| BV | 2969 | user_binary_19_1 | User Defined Binary 19 | Write | 0=OFF, 1=ON | |
| BV | 2952 | user_binary_2_1 | User Defined Binary 2 | Write | 0=OFF, 1=ON | |
| BV | 2970 | user_binary_20_1 | User Defined Binary 20 | Write | 0=OFF, 1=ON | |
| BV | 2953 | user_binary_3_1 | User Defined Binary 3 | Write | 0=OFF, 1=ON | |
| BV | 2954 | user_binary_4_1 | User Defined Binary 4 | Write | 0=OFF, 1=ON | |
| BV | 2955 | user_binary_5_1 | User Defined Binary 5 | Write | 0=OFF, 1=ON | |
| BV | 2956 | user_binary_6_1 | User Defined Binary 6 | Write | 0=OFF, 1=ON | |
| BV | 2957 | user_binary_7_1 | User Defined Binary 7 | Write | 0=OFF, 1=ON | |
| BV | 2958 | user_binary_8_1 | User Defined Binary 8 | Write | 0=OFF, 1=ON | |
| BV | 2959 | user_binary_9_1 | User Defined Binary 9 | Write | 0=OFF, 1=ON | |
| AV | 183 | dhvraoff_1 | Vent Reheat RAT Offset (range 0 to 8) | Δ°F | Write | |
| AV | 184 | dhvht_sp_1 | Vent Reheat Setpoint (range 55 to 95) | °F | Write | |
| BV | 203 | zs_co2_valid_1 | ZS CO2 Sensor Valid Status | Read | 0=N/A, 1=Valid / Connected | |
| BV | 202 | zs_hum_valid_1 | ZS Humidity Sensor Valid Status | Read | 0=N/A, 1=Valid / Connected | |
| BV | 201 | zs_sen_valid_1 | ZS Temp Sensor Valid Status | Read | 0=N/A, 1=Valid / Connected | |
| BV | 200 | zs_sen_alm_1 | ZS Thermostat Config Alarm | Read | 0=NORMAL, 1=ALARM |
No points match these filters.
Object ID lookup: Carrier Weathermaster 48/50P Large Rooftop point IDs by name
AV10sat_1BV7030air_linkage_fail_1BV2601a_link_status_1BV9alm_1AV1070bldg_static_press_1AV3070bldg_press_stpt_1AV1601discharge_press_a_1AV1602sat_cond_temp_a_1AV1603sat_suction_temp_a_1AV1600suction_press_a_1AV1605discharge_press_b_1AV1606sat_cond_temp_b_1AV1607sat_suction_temp_b_1AV1604suction_press_b_1BV16cmpa1_1BV17cmpa2_1BV13cmpa3_1BV18cmpb1_1BV19cmpb2_1BV14cmpb3_1AV1030ra_temp_1AV2007space_temp_1AV3055ct_sa_static_stpt_1AV1024cool_ctrl_point_1AV3001occ_cl_stpt_1AV3003unocc_cl_stpt_1AV43ctrltemp_1AV1023cool_capacity_1AV44htsg_cap_1AV49dhcoolsp_1BV30dhdiscin_1AV50dhrelhsp_1AV53dlswsp1_1AV54dlswsp2_1BV1006dmd_sw1_1BV1007dmd_sw2_1AV1028econ_pos_1BV36ecactive_1BV44edt_stat_1BV2999element_stat_1BV105comm_lost_alm_1BV5123et_reset_as_link_1AV76edt_1AV2075ef_vfd_output_1BV1052filter_status_1BV52hs1_1BV53hs2_1AV83hcsp_gap_1AV1025heat_ctrl_point_1AV3002occ_ht_stpt_1AV3008saspheat_1AV3004unocc_ht_stpt_1AV55htclcpos_1BV47hum3wval_1AV57hmzrcapc_1AV1022hvac_mode_1BV1050iaq_status_1AV1009iaq_1AV2607link_iaq_1AV1027lvg_air_temperature_1AV2611link_max_dmpr_1BV5schedule_1AV3052max_dmpr_pos_1AV3054max_reset_1AV3053min_dmpr_pos_1AV1500ma_temp_1AV113oaq_1AV114occl_end_1AV115occlstrt_1AV116ocht_end_1AV117ochtstrt_1BV2008occ_status_1AV66oacfm_1AV119oarh_1AV1003oat_1BV49pe1_1BV51pe2_1BV76hs3_1BV77hs4_1BV78hs5_1BV79hs6_1AV2003heat_run_1AV69racfm_1AV134rarh_1AV135rat_1BV6stpt_adj_enable_1AV73sph_1AV74spl_1AV2606link_rh_1AV72sprh_1AV139spto_rng_1AV137spt_1AV150lat1sgas_1AV151lat2sgas_1AV152lat3sgas_1AV1016static_press_1AV157spreset_1BV3051st_pr_rst_en_1AV3050sa_static_stpt_1AV78sacfm_1BV93modesars_1AV158sasprset_1AV3007sa_temp_stpt_1BV2001sfan_1BV95sfs_1AV2050sf_vfd_output_1AV9006cool_demand_level_1BV7dem_lmt_act_1AV9036heat_demand_level_1AV80001mstr_oa_temp_1AV1903system_aq_1AV1904system_rh_1AV1902system_spt_1BV1021g_input_1BV1019w1_input_1BV1020w2_input_1BV1017y1_input_1BV1018y2_input_1AV168uccl_end_1AV169ucclstrt_1AV170ucht_end_1AV171uchtstrt_1BV2605use_linkage_1AV2901user_analog_1_1AV2909user_analog_10_1AV2910user_analog_11_1AV2912user_analog_12_1AV2913user_analog_13_1AV2914user_analog_14_1AV2915user_analog_15_1AV2916user_analog_16_1AV2917user_analog_17_1AV2918user_analog_18_1AV2919user_analog_19_1AV2902user_analog_2_1AV2920user_analog_20_1AV2903user_analog_3_1AV2904user_analog_4_1AV2905user_analog_5_1AV2906user_analog_6_1AV2907user_analog_8_1AV2908user_analog_9_1BV2951user_binary_1_1BV2960user_binary_10_1BV2961user_binary_11_1BV2962user_binary_12_1BV2963user_binary_13_1BV2964user_binary_14_1BV2965user_binary_15_1BV2966user_binary_16_1BV2967user_binary_17_1BV2968user_binary_18_1BV2969user_binary_19_1BV2952user_binary_2_1BV2970user_binary_20_1BV2953user_binary_3_1BV2954user_binary_4_1BV2955user_binary_5_1BV2956user_binary_6_1BV2957user_binary_7_1BV2958user_binary_8_1BV2959user_binary_9_1AV183dhvraoff_1AV184dhvht_sp_1BV203zs_co2_valid_1BV202zs_hum_valid_1BV201zs_sen_valid_1BV200zs_sen_alm_1
Integration notes
- Object names end in _1. The CCN point name and default value columns are printed empty.
- The table prints AV:2906 twice (User Defined Analog 6 and User Defined Analog 7, user_analog_7_1); the second row is left out here. Analog 8-11 are printed at AV:2907-2910, while the 48/50A list numbers Analog 7-11 as 2907-2911. Check spare user values on the controller.
- Ranges are added to descriptions as printed. Units printed as °^F are shown as Δ°F (temperature differences).
- The 48/50A list (48-50A-17T) shares most objects but not all (e.g. comm-loss alarm BV:15 there vs BV:105 here, user binaries BV:2911+ vs BV:2951+), so it is a separate entry.
- This is ComfortLink + UPC Open, not the SystemVu or SmartVu controls used on other Carrier rooftops.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
How many BACnet points does the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) have?
This list has 168 BACnet objects: 102 analog values, 66 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) BACnet points are writable?
88 of the 168 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) BACnet documentation?
The source is Weathermaster 48/50P030-100 Single Package Large Rooftop Units with ComfortLink Version 9.X Controls - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix G: UPC Open Controller Network Points List) (48-50P-15T), revision 3-26, published free by Carrier at https://brandportal.carrier.com/asset/4dc39d43-803f-422b-8752-1d4064a34adc/48-50P-15T.pdf.
What are the minimum BACnet points to integrate the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)?
Start with BV 2008 occ_status_1 (Occupied? (0 = no, 1 = yes); writable); AV 3001 occ_cl_stpt_1 (Occupied cooling setpoint); AV 3002 occ_ht_stpt_1 (Occupied heating setpoint); AV 3007 sa_temp_stpt_1 (Supply air setpoint (VAV units)); AV 1022 hvac_mode_1 (HVAC mode as a number); BV 2001 sfan_1 (Supply fan relay on/off); AV 43 ctrltemp_1 (Control temperature (RAT, SPT or zone)); AV 10 sat_1 (Supply air temperature leaving the fan); BV 9 alm_1 (Unit alarm state); BV 105 comm_lost_alm_1 (UPC lost CCN communication with the unit).
How do I enable BMS control of the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)?
Occupancy follows the ComfortLink CCN schedule number (Configuration > CCN > SC.OV > SCH.N): 0 = always occupied, 1 = local schedule (default), 65-99 = a CCN/global schedule. The points list makes Occupied? (BV:2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site. A remote switch input (RM.CF) can also set occupancy or start/stop the unit.
Does the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) need a BACnet heartbeat or have a communication timeout?
The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.
Can the BMS supply sensor values to the Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)?
Space Temperature (AV:137), Return Air Temperature (AV:135), Outside Air Temperature (AV:1003), Outside Air RH (AV:119), IAQ (AV:1009) and OAQ (AV:113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).
How do I check these points on the real Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: Weathermaster 48/50P030-100 Single Package Large Rooftop Units with ComfortLink Version 9.X Controls - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix G: UPC Open Controller Network Points List) · 48-50P-15T · rev. 3-26. Object names, instances and units are reproduced as published; descriptions are our own.