Packaged rooftop unit controller (BACnet option) · BACnet points list

Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) BACnet points list

Updated 12 November 2026

Short answer

This is the ComfortLink 8.x generation of the 48/50A large rooftop. BACnet MS/TP comes from a UPC Open controller in its own enclosure below the main control box, which reads the ComfortLink board over CCN. The table has 268 rows (267 unique AV and BV IDs): occupancy, setpoints, air temperatures and pressures, building pressure, compressor relays, strikes and timeguards, economizer, demand levels, Humidi-MiZer, VAV and reheat settings, thermostat inputs, alarms and user-defined spare values.

This page lists 267 BACnet objects for the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) — 138 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Equipment
Packaged rooftop unit controller (BACnet option)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
267 (138 writable)
Transport
BACnet MS/TP
Firmware
ComfortLink 8.x
Default device instance
Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
Also known as
48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T
Source document
Weathermaker 48/50A2,A3,A4,A5020-060 Single Package Large Rooftop Units with ComfortLink Version 8.x Controls - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E: UPC Open Controller Network Points List) · 48/50A-13T · rev. 2-18
Download CSV 267 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)

Integration in brief

The BMS talks BACnet MS/TP to the UPC Open, which reads and writes the ComfortLink control over CCN. Set the CCN schedule number for the occupancy source you want, then write occupancy, setpoints and (for VAV) the supply air setpoint; read HVAC mode, temperatures and alarm state. Values the BMS feeds in (space, return or outdoor temperature, RH, CO2) are forces that clear if not refreshed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2008occ_status_1Occupied? (0 = no, 1 = yes); writableWrite
AV 3001occ_cl_stpt_1Occupied cooling setpointWrite
AV 3002occ_ht_stpt_1Occupied heating setpointWrite
AV 3007sa_temp_stpt_1Supply air setpoint (VAV units)Write
AV 1022hvac_mode_1HVAC mode as a numberRead
BV 94sfan_rly_1Supply fan relay on/offRead
AV 43ctrltemp_1Control temperature (RAT, SPT or zone)Read
AV 10sat_1Supply air temperature leaving the fanRead
BV 9alm_1Unit alarm stateRead
BV 2999element_stat_1UPC's CCN communication status with the unitRead

Enable & remote start

The unit ships with Local Machine Disable (Service Test > STOP, BV 59 unitstop_1) set to Yes; set it to No before the unit runs. Occupancy follows the ComfortLink CCN schedule number (Configuration > CCN > SC.OV > SCH.N): 0 = always occupied, 1 = local schedule (default), 65-99 = a CCN schedule; 2-64 are not used and are forced back to 1. The points list makes Occupied? (BV 2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site. Emergency stop (BV 45) is forced over CCN.

Heartbeat & communication loss

The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.

Sensors & values from the BMS

Space Temperature (AV 137), Return Air Temperature (AV 135), Outside Air Temperature (AV 1003), Outside Air RH (AV 119), IAQ (AV 1009) and OAQ (AV 113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).

Network setup

Watch out for

Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

267 of 267 shown
Type
AnalogBinary
Access
Show
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) BACnet Points List
DescriptionStates
AV9dem_lim_1Active Demand Limit%Write
AVmin10sat_1Air Temp Lvg Supply Fan°FRead
AV11cem4201_1CEM AN1 4-20 ma J5,1-2mAWrite
AV12cem10k1_1CEM AN1 10K temp J5,1-2°FWrite
AV13cem4202_1CEM AN2 4-20 ma J5,3-4mAWrite
AV14cem10k2_1CEM AN2 10K temp J5,3-4°FWrite
AV15sasptemp_1Temper Supply Air Setpt°FWrite
AV16bpperiod_1BP PID Evaluation Time LevelminWrite
AV17bpso_1BP Setpoint Offsetin H2OWrite
AV18bpz_gain_1BP Threshold AdjustmentWrite
AV22smz_1Capacity Load Factor%Read
AV23z_gain_1Capacity Threshold AdjWrite
AV24hr_a1_1Compressor A1 Run HourshrRead
AV25cy_a1_1Compressor A1 StartsRead
AV26cmpa1str_1Compressor A1 StrikesRead
AV27cmpa1_tg_1Compressor A1 TimeguardRead
AV28hr_a2_1Compressor A2 Run HourshrRead
AV29cy_a2_1Compressor A2 StartsRead
AV30cmpa2str_1Compressor A2 StrikesRead
AV31cmpa2_tg_1Compressor A2 TimeguardRead
AV32hr_b1_1Compressor B1 Run HourshrRead
AV33cy_b1_1Compressor B1 StartsRead
AV34cmpb1str_1Compressor B1 StrikesRead
AV35cmpb1_tg_1Compressor B1 TimeguardRead
AV36hr_b2_1Compressor B2 Run HourshrRead
AV37cy_b2_1Compressor B2 StartsRead
AV38cmpb2str_1Compressor B2 StrikesRead
AV39cmpb2_tg_1Compressor B2 TimeguardRead
AV40oatlcomp_1Compressor Lockout Temp°FWrite
AV41ctrendlv_1Cool Trend Demand LevelΔ°FWrite
AV42ctrendtm_1Cool Trend Time (secs)secWrite
AVmin43ctrltemp_1Ctl.Temp RAT,SPT or ZONE°FRead
AV44htsg_cap_1Current Running Capacity (HTSG_CAP)%Read
AV45daqfnoff_1DAQ PPM Fan Off SetpointWrite
AV46daqfnon_1DAQ PPM Fan On SetpointWrite
AV49dhcoolsp_1Dehumidify Cool Setpoint°FWrite
AV50dhrelhsp_1Dehumidify RH Setpoint%Write
AV52dmd_ctrl_1Demand Limit SelectWrite
AV53dlswsp1_1Demand Limit Sw.1 Setpt.%Write
AV54dlswsp2_1Demand Limit Sw.2 Setpt.%Write
AV56daq_1Diff.Air Quality in PPMRead
AV57Hmzrcapc_1HumidiMiZer Capacity%Read
AV58iaqreact_1Diff. AQ ResponsivenessWrite
AV59dmdlcoff_1Dmd Level(-) Low Cool OFFΔ°FWrite
AV60dmdlhoff_1Dmd Level(-) Low Heat OFFΔ°FWrite
AV61dmdhcon_1Dmd Level(+) Hi Cool ONΔ°FWrite
AV62dmdhhon_1Dmd Level(+) Hi Heat ONΔ°FWrite
AV63dmdlcon_1Dmd Level Low Cool ONΔ°FWrite
AV64dmdlhon_1Dmd Level Low Heat ONΔ°FWrite
AV66min_pos_1Econo Current Min. Pos.%Read
AV67econocmd_1Economizer Act. Cmd. Pos.%Write
AV68econpnt_1Economizer Control Point°FRead
AV70economax_1Economizer Max.Position%Write
AV76edt_1Evaporator Discharge Tmp°FRead
AV77fan_mode_1Fan ModeWrite
AV78elec_fod_1Fan-Off Delay, Elec HeatWrite
AV79gas_fod_1Fan-Off Delay, Gas HeatWrite
AV80cool_fod_1Fan-Off Delay, Mech CoolsecWrite
AV83hcsp_gap_1Heat-Cool Setpoint GapΔ°FWrite
AV85saspheat_1Heating Supply Air Setpt°FWrite
AV86bphplvl_1High BP LevelWrite
AV87bplplvl_1Low BP LevelWrite
AV93iaqovpos_1IAQ Econo Override Pos.%Write
AV95iaqrefh_1IAQ High ReferenceWrite
AV96iaqrefl_1IAQ Low ReferenceWrite
AV97iaqminov_1IAQ Min.Pos.Override%Write
AV98iaqptime_1IAQ Purge DurationminWrite
AV99iaqphtmp_1IAQ Purge HiTemp Min Pos%Write
AV100iaqpltmp_1IAQ Purge LoTemp Min Pos%Write
AV101iaqpntlo_1IAQ Purge OAT Lockout°FWrite
AV102htlatlim_1LAT Limit ConfigΔ°FWrite
AV107htmaxstg_1Maximum Heat StagesRead
AV112oaqlock_1OAQ Lockout ValueWrite
AV113oaq_1OAQ - PPM Outdoor CO2Write
AV114occl_end_1Occupied Cool Mode End°FRead
AV115occlstrt_1Occupied Cool Mode Start°FRead
AV116ocht_end_1Occupied Heat Mode End°FRead
AV117ochtstrt_1Occupied Heat Mode Start°FRead
AV118oa_humr_1Outside Air Humidity RatioRead
AV119oarh_1Outside Air Relative Humidity%Write
AV120otl_1Override Time LimithrWrite
AV121pwrm_1Power Exhaust MotorsWrite
AV122pes1_1Power Exhaust On Setp.1%Write
AV123pes2_1Power Exhaust On Setp.2%Write
AV130rmtincfg_1Remote Switch ConfigWrite
AV131limt_1Reset LimitΔ°FWrite
AV132rtio_1Reset RatioWrite
AV133rae_1Return Air EnthalpyRead
AV134rarh_1Return Air Relative Humidity%Write
AV135rat_1Return Air Temperature°FWrite
AV136schednum_1Schedule NumberWrite
AV137spt_1Space Temperature°FWrite
AV138spto_1Space Temperature OffsetΔ°FWrite
AV139spto_rng_1Space Temp Offset RangeΔ°FWrite
AV143sprlimit_1SP Reset LimitWrite
AV144sprratio_1SP Reset RatioWrite
AV150lat1sgas_1Staged Gas LAT 1°FRead
AV151lat2sgas_1Staged Gas LAT 2°FRead
AV152lat3sgas_1Staged Gas LAT 3°FRead
AV153lat_sgas_1Staged Gas LAT Sum°FRead
AV154limswtmp_1Staged Gas Limit Sw Temp°FRead
AV155delay_1Startup Delay TimesecWrite
AV156sprstcfg_1Stat. Pres. Reset ConfigWrite
AV157spreset_1Static Pressure ResetWrite
AV158sasprset_1Supply Air Setpnt. ResetΔ°FWrite
AV159tcstcool_1Temp Comp Start Cool FactorminWrite
AV160tcstheat_1Temp Comp Start Heat FactorminWrite
AV161tempcool_1Tempering in Cool SASPWrite
AV162temppurg_1Tempering Purge SASPWrite
AV163tempvocc_1Tempering Vent Occ SASPWrite
AV164tempvunc_1Temper Vent UnoccWrite
AV165sf_vfd_output_1Supply Fan VFD Speed (SFVFDTST)%Write
AV166uefcntlo_1Un.Ec.Free Cool OAT Lock°FWrite
AV168uccl_end_1Unoccupied Cool Mode End°FRead
AV169ucclstrt_1Unoccupied Cool Mode Start°FRead
AV170ucht_end_1Unoccupied Heat Mode End°FRead
AV171uchtstrt_1Unoccupied Heat Mode Start°FRead
AV172uefc_cfg_1Unoc Econ Free Cool CfgWrite
AV173uefctime_1Unoc Econ Free Cool TimeminWrite
AV179oaq_user_1User Determined OAQWrite
AV180vavocoff_1VAV Occ. Cool Off DeltaΔ°FWrite
AV181vavocon_1VAV Occ. Cool On DeltaΔ°FWrite
AV182sampmins_1VAV Unocc Fan Retry TimeminWrite
AV183dhvraoff_1Vent Reheat RAT OffsetΔ°FWrite
AV184dhvht_sp_1Vent Reheat Setpoint°FWrite
AV185dhvhtcfg_1Vent Reheat Setpt SelectWrite
AV186bldgpfso_1VFD/Act. Fire Speed/Pos.%Write
AV187statpfso_1VFD Fire Speed Override%Write
AV188statpmax_1VFD Maximum Speed%Write
AV189statpmin_1VFD Minimum Speed%Write
AV1003oat_1Outside Air Temperature°FWrite
AV1009iaq_1IAQ - PPM Indoor CO2Write
AV1016static_press_1Static Pressurein H2ORead
AVmin1022hvac_mode_1HVAC Mode Numerical FormRead
AV1023cool_capacity_1Current Running Capacity (CAPTOTAL)%Read
AV1024cool_ctrl_point_1Cooling Control Point°FRead
AV1025heat_ctrl_point_1Heating Control Point°FRead
AV1027lvg_air_temperature_1Leaving Air Temperature°FRead
AV1028econ_pos_1Economizer Act. Curr. Pos%Read
AV1030ra_temp_1Controlling Return Temp°FWrite
AV1070bldg_static_press_1Building Pressurein H2ORead
AV1500ma_temp_1Mixed Air Temperature°FRead
AV1600suction_press_a_1Cir A Suction PressurepsigRead
AV1601discharge_press_a_1Cir A Discharge PressurepsigRead
AV1602sat_cond_temp_a_1Cir A Sat. Condensing Temperature°FRead
AV1603sat_suction_temp_a_1Cir A Sat. Suction Temperature°FRead
AV1604suction_press_b_1Cir B Suction PressurepsigRead
AV1605discharge_press_b_1Cir B Discharge PressurepsigRead
AV1606sat_cond_temp_b_1Cir B Sat. Condensing Temperature°FRead
AV1607sat_suction_temp_b_1Cir B Sat. Suction Temperature°FRead
AV2003heat_run_1Requested Heat StageRead
AV2007space_temp_1Controlling Space Temp°FWrite
AV2050sfvfdtst_1Supply Fan VFD Speed (SFAN_VFD)%Read
AV2075ef_vfd_output_1Exhaust Fan VFD Speed%Read
AV2901user_analog_1_1User Defined Analog 1Read
AV2902user_analog_2_1User Defined Analog 2Read
AV2903user_analog_3_1User Defined Analog 3Read
AV2904user_analog_4_1User Defined Analog 4Read
AV2905user_analog_5_1User Defined Analog 5Read
AVmin3001occ_cl_stpt_1Cooling Occupied Setpoint°FWrite
AVmin3002occ_ht_stpt_1Heating Occupied Setpoint°FWrite
AV3003unocc_cl_stpt_1Cooling Unoccupied Setpoint°FWrite
AV3004unocc_ht_stpt_1Heating Unoccupied Setpoint°FWrite
AVmin3007sa_temp_stpt_1Supply Air Setpoint°FWrite
AV3016iaq_min_pos_1IAQ Demand Vent Min.Pos.%Write
AV3050sa_static_stpt_1Static Pressure Setpointin H2OWrite
AV3070bldg_press_stpt_1Building Pressure Setp.in H2OWrite
AV4005econ_min_1Economizer Min.Position%Write
AV9008econ_oat_lockout_1High OAT Lockout Temp°FWrite
BVmin9alm_1Alarm StateRead
BV10capmode_1Capacity Clamp ModeRead
BV11igcfan_1Fan request from IGCRead
BV12cmpa1lok_1Comp A1 Locked Out ?Read
BV13cmpa2lok_1Comp A2 Locked Out ?Read
BV14cmpb1lok_1Comp B1 Locked Out ?Read
BV15cmpb2ok_1Comp B2 Locked Out ?Read
BV16cmpa1_1Compressor A1 RelayRead
BV17cmpa2_1Compressor A2 RelayRead
BV18cmpb1_1Compressor B1 RelayRead
BV19cmpb2_1Compressor B2 RelayRead
BV20cool_off_1Cool Mode Not In Effect?Read
BV21modes_1Override Modes in EffectRead
BV22sfonstat_1Supply Fan not on 30s ?Read
BV25dbc_stat_1DBC - OAT Lockout?Read
BV26modeadcv_1DCV Resetting Min PosRead
BV27ddbcstat_1DDBC- OAT > RAT Lockout?Read
BV28dec_stat_1DEC - Diff.Enth.Lockout?Read
BV29dhdisabl_1Dehumid. Disabled Econ.?Read
BV30dhdiscin_1Dehumidify InputWrite
BV31modedmlt_1Demand Limit In EffectRead
BV32dew_stat_1DEW - OA Dewpt.Lockout?Read
BV34econunav_1Econ Act. Unavailable?Read
BV35dhecdisa_1Econ disable in DH mode?Write
BV36ecactive_1Economizer Active?Read
BV37ecosw_1Economizer Control InputWrite
BV38econforc_1Economizer Forced ?Read
BV41ecooride_1Econo Position OverrideWrite
BV42econheld_1Econ Recovery Hold Off?Read
BV44edt_stat_1EDT Sensor Bad ?Read
BV45emstop_1Emergency StopWrite
BV46cmpa1ena_1Enable Compressor A1Write
BV47cmpa2ena_1Enable Compressor A2Write
BV48cmpb1ena_1Enable Compressor B1Write
BV49cmpb2ena_1Enable Compressor B2Write
BV50sfs_shut_1Fan Fail Shuts Down UnitWrite
BV52hs1_1Heat Relay 1Read
BV53hs2_1Heat Relay 2Read
BV54bphpovrd_1High BP OverrideRead
BV55limtmode_1Hi Limit Switch Tmp ModeRead
BV56modeiqpg_1IAQ Pre-Occ Purge ActiveRead
BV57iaqpurge_1IAQ PurgeWrite
BV58latcmode_1LAT Cutoff ModeRead
BV59unitstop_1Local Machine DisableWrite
BV60bplpovrd_1Low BP OverrideRead
BV61low_temp_1Low Temp Cap OverrideRead
BV63modelock_1Mech Cooling Locked OutRead
BV64mlv_1Min. Load Valve (HGBP)Read
BV67oaecstat_1OAEC- OA Enth Lockout?Read
BV68oaqlockd_1OAQ Lockout In Effect ?Read
BV69oat_stat_1OAT Sensor Bad ?Read
BV70htoccena_1Occupied Heating EnabledWrite
BV72pe_a_1Power Exhaust Relay ARead
BV73pe_b_1Power Exhaust Relay BRead
BV74pe_c_1Power Exhaust Relay CRead
BV75pulldown_1Pull Down Cap OverrideRead
BV76hs3_1Relay 3 W1 Gas Valve 2Read
BV77hs4_1Relay 4 W2 Gas Valve 2Read
BV78hs5_1Relay 5 W1 Gas Valve 3Read
BV79hs6_1Relay 6 W2 Gas Valve 3Read
BV80econdisa_1Remote Econ. Disabled ?Read
BV81rmtin_1Remote Input StateWrite
BV86slo_chng_1Slow Change Cap OverrideRead
BV87softstop_1Soft Stop RequestWrite
BV93modesars_1Supply Air ResetRead
BVmin94sfan_rly_1Supply Fan RelayRead
BV95sfs_1Supply Fan Status SwitchWrite
BV96modetcst_1Temp Compensated StartRead
BV97modetovr_1Timed Override In EffectRead
BV98overlast_1Timed-Override in EffectRead
BV99tstatall_1TSTAT Both Heat and CoolWrite
BV1005firedown_status_1Fire Shutdown InputWrite
BV1006dmd_sw1_1Demand Limit Switch 1Write
BV1007dmd_sw2_1Demand Limit Switch 2Write
BV1010remote_econ_enable_1Remote Economizer EnableWrite
BV1017y1_input_1Thermostat Y1 InputWrite
BV1018y2_input_1Thermostat Y2 InputWrite
BV1019w1_input_1Thermostat W1 InputWrite
BV1020w2_input_1Thermostat W2 InputWrite
BV1021g_input_1Thermostat G InputWrite
BV1026heat_interlock_relay_1Heat Interlock RelayWrite
BV1050iaq_status_1IAQ - Discrete InputWrite
BV1052filter_status_1Filter Status InputWrite
BV1060smk_evac_1Evacuation InputWrite
BV1061smk_press_1Pressurization InputWrite
BV1062smk_purg_1Smoke Purge InputWrite
BV2001sfan_1Supply Fan StateRead
BV2004sfan_forc_1Supply Fan RequestWrite
BVmin2008occ_status_1Occupied?Write
BV2012cond_fan_a_1Condenser Fan Circuit ARead
BV2013cond_fan_b_1Condenser Fan Circuit BRead
BV2014aux_relay_1Remote Alarm/Aux RelayWrite
BV2911user_binary_1_1User Defined Binary 1Read
BV2912user_binary_2_1User Defined Binary 2Read
BV2913user_binary_3_1User Defined Binary 3Read
BV2914user_binary_4_1User Defined Binary 4Read
BV2915user_binary_5_1User Defined Binary 5Read
BVmin2999element_stat_1Element Comm StatusRead
Object ID lookup: Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)

How many BACnet points does the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) have?

This list has 267 BACnet objects: 169 analog values, 98 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) BACnet points are writable?

138 of the 267 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) BACnet documentation?

The source is Weathermaker 48/50A2,A3,A4,A5020-060 Single Package Large Rooftop Units with ComfortLink Version 8.x Controls - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E: UPC Open Controller Network Points List) (48/50A-13T), revision 2-18, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/01/48_50A-13T.pdf.

What are the minimum BACnet points to integrate the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)?

Start with BV 2008 occ_status_1 (Occupied? (0 = no, 1 = yes); writable); AV 3001 occ_cl_stpt_1 (Occupied cooling setpoint); AV 3002 occ_ht_stpt_1 (Occupied heating setpoint); AV 3007 sa_temp_stpt_1 (Supply air setpoint (VAV units)); AV 1022 hvac_mode_1 (HVAC mode as a number); BV 94 sfan_rly_1 (Supply fan relay on/off); AV 43 ctrltemp_1 (Control temperature (RAT, SPT or zone)); AV 10 sat_1 (Supply air temperature leaving the fan); BV 9 alm_1 (Unit alarm state); BV 2999 element_stat_1 (UPC's CCN communication status with the unit).

How do I enable BMS control of the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)?

The unit ships with Local Machine Disable (Service Test > STOP, BV 59 unitstop_1) set to Yes; set it to No before the unit runs. Occupancy follows the ComfortLink CCN schedule number (Configuration > CCN > SC.OV > SCH.N): 0 = always occupied, 1 = local schedule (default), 65-99 = a CCN schedule; 2-64 are not used and are forced back to 1. The points list makes Occupied? (BV 2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site. Emergency stop (BV 45) is forced over CCN.

Does the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option) need a BACnet heartbeat or have a communication timeout?

The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.

Can the BMS supply sensor values to the Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)?

Space Temperature (AV 137), Return Air Temperature (AV 135), Outside Air Temperature (AV 1003), Outside Air RH (AV 119), IAQ (AV 1009) and OAQ (AV 113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).

How do I check these points on the real WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Weathermaker 48/50A2,A3,A4,A5020-060 Single Package Large Rooftop Units with ComfortLink Version 8.x Controls - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E: UPC Open Controller Network Points List) · 48/50A-13T · rev. 2-18. Object names, instances and units are reproduced as published; descriptions are our own.