Air-cooled screw chiller controller (BACnet option) · BACnet points list
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) BACnet points list
Updated 28 October 2026
This 30XA list covers the UPC Open BACnet MS/TP option on 30XA080-501 chillers. It has about 270 AVs and BVs: start/stop, occupancy, emergency stop, control point, demand and current limit, heat/cool select, setpoints, water temperatures, refrigerant pressures, fan and compressor run hours, pumps and alarm state.
This page lists 268 BACnet objects for the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) — 45 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaForce 30XA 080-501 (UPC Open BACnet option)
- Equipment
- Air-cooled screw chiller controller (BACnet option)
- Equipment type
- Chillers
- BACnet objects
- 268 (45 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
- Also known as
- 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller
BMS integration notes: Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Address the UPC Open, set the MS/TP DIP switches, and run the chiller in network (CCN) mode. The BMS writes chiller start/stop and occupancy, control point and demand limit; read run status, leaving fluid temperature, capacity and alarm state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | chil_s_s_1 | Network start/stop (0 Disable, 1 Enable) | Write |
| BV 2 | chil_occ_1 | Network occupied command | Write |
| BV 56 | emstop_1 | Emergency stop command | Write |
| AV 83 | ctrl_pnt_1 | Control point (leaving fluid setpoint) | Write |
| AV 79 | dem_lim_1 | Demand limit, 0-100 % | Write |
| AV 93 | status_1 | Run status code | Read |
| AV 96 | cool_lwt_1 | Cooler leaving fluid temperature | Read |
| AV 87 | cap_t_1 | Percent total capacity | Read |
| AV 137 | alm_1 | Alarm state: 0 Normal, 1 Partial, 2 Shutdown | Read |
Enable & remote start
Press the Start/Stop button on the Carrier Controller display and select CCN Mode on the Equipment Start screen. CHIL_S_S (BV 1) then starts and stops the chiller: forced to Disable the unit stops, forced to Enable it runs per schedule 1.
Heartbeat & communication loss
The manual says that if communication with the network is lost, the machine starts and is controlled locally.
Network setup
- The BACnet option adds a UPC Open controller; it speaks BACnet MS/TP at 9600, 19.2k, 38.4k or 76.8k (Carrier default 76.8k), set on BAS port DIP switches DS1-DS2.
- For MS/TP set DS3 to enable, DS4 to E1-485 and the protocol switches DS5-DS8 to MSTP; the EIA-485 jumpers must be set to EIA-485 and 2W.
- MAC address from the two rotary switches (tens and ones); the controller reads switches and DIP settings only at power-up.
- Device instance is auto-generated as the network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120; change it with i-Vu Tools or a BACview.
- Fit a BT485 terminator on the first and last controller of the MS/TP segment.
Watch out for
- The 30XA also has a separate BACnet/Modbus translator option with a different point list.
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | hr_fana1_1 | Circuit A Fan #1 Hours | hr | Read | |
| AV | 2 | hr_fana2_1 | Circuit A Fan #2 Hours | hr | Read | |
| AV | 3 | hr_fana3_1 | Circuit A Fan #3 Hours | hr | Read | |
| AV | 4 | hr_fana4_1 | Circuit A Fan #4 Hours | hr | Read | |
| AV | 5 | hr_fana5_1 | Circuit A Fan #5 Hours | hr | Read | |
| AV | 6 | hr_fana6_1 | Circuit A Fan #6 Hours | hr | Read | |
| AV | 7 | hr_fana7_1 | Circuit A Fan #7 Hours | hr | Read | |
| AV | 8 | hr_fana8_1 | Circuit A Fan #8 Hours | hr | Read | |
| AV | 9 | hr_fana9_1 | Circuit A Fan #9 Hours | hr | Read | |
| AV | 10 | hrfana10_1 | Circuit A Fan #10 Hours | hr | Read | |
| AV | 11 | hr_fanb1_1 | Circuit B Fan #1 Hours | hr | Read | |
| AV | 12 | hr_fanb2_1 | Circuit B Fan #2 Hours | hr | Read | |
| AV | 13 | hr_fanb3_1 | Circuit B Fan #3 Hours | hr | Read | |
| AV | 14 | hr_fanb4_1 | Circuit B Fan #4 Hours | hr | Read | |
| AV | 15 | hr_fanb5_1 | Circuit B Fan #5 Hours | hr | Read | |
| AV | 16 | hr_fanb6_1 | Circuit B Fan #6 Hours | hr | Read | |
| AV | 17 | hr_fanb7_1 | Circuit B Fan #7 Hours | hr | Read | |
| AV | 18 | hr_fanb8_1 | Circuit B Fan #8 Hours | hr | Read | |
| AV | 19 | hr_fanb9_1 | Circuit B Fan #9 Hours | hr | Read | |
| AV | 20 | hrfanb10_1 | Circuit B Fan #10 Hours | hr | Read | |
| AV | 21 | hr_fanc1_1 | Circuit C Fan #1 Hours | hr | Read | |
| AV | 22 | hr_fanc2_1 | Circuit C Fan #2 Hours | hr | Read | |
| AV | 23 | hr_fanc3_1 | Circuit C Fan #3 Hours | hr | Read | |
| AV | 24 | hr_fanc4_1 | Circuit C Fan #4 Hours | hr | Read | |
| AV | 25 | hr_fanc5_1 | Circuit C Fan #5 Hours | hr | Read | |
| AV | 26 | hr_fanc6_1 | Circuit C Fan #6 Hours | hr | Read | |
| AV | 27 | hr_fanc7_1 | Circuit C Fan #7 Hours | hr | Read | |
| AV | 28 | hr_fanc8_1 | Circuit C Fan #8 Hours | hr | Read | |
| AV | 29 | suct_t_a_1 | Compressor Suction Temp (circuit A) | °F | Read | |
| AV | 30 | suct_t_b_1 | Compressor Suction Temp (circuit B) | °F | Read | |
| AV | 31 | suct_t_c_1 | Compressor Suction Temp (circuit C) | °F | Read | |
| AV | 32 | dgt_a_1 | Discharge Gas Temp (circuit A) | °F | Read | |
| AV | 33 | dgt_b_1 | Discharge Gas Temp (circuit B) | °F | Read | |
| AV | 34 | dgt_c_1 | Discharge Gas Temp (circuit C) | °F | Read | |
| AV | 35 | dp_a_1 | Discharge Pressure (circuit A) | psi | Read | |
| AV | 36 | dp_b_1 | Discharge Pressure (circuit B) | psi | Read | |
| AV | 37 | dp_c_1 | Discharge Pressure (circuit C) | psi | Read | |
| AV | 38 | eco_tp_a_1 | Economizer Gas Temp (circuit A) | °F | Read | |
| AV | 39 | eco_tp_b_1 | Economizer Gas Temp (circuit B) | °F | Read | |
| AV | 40 | eco_tp_c_1 | Economizer Gas Temp (circuit C) | °F | Read | |
| AV | 41 | econ_p_a_1 | Economizer Pressure (circuit A) | psi | Read | |
| AV | 42 | econ_p_b_1 | Economizer Pressure (circuit B) | psi | Read | |
| AV | 43 | econ_p_c_1 | Economizer Pressure (circuit C) | psi | Read | |
| AV | 44 | exv_a_1 | EXV Position (circuit A) | % | Read | |
| AV | 45 | exv_b_1 | EXV Position (circuit B) | % | Read | |
| AV | 46 | exv_c_1 | EXV Position (circuit C) | % | Read | |
| AV | 47 | fan_st_a_1 | Fan Staging Number (circuit A) | Read | ||
| AV | 48 | fan_st_b_1 | Fan Staging Number (circuit B) | Read | ||
| AV | 49 | fan_st_c_1 | Fan Staging Number (circuit C) | Read | ||
| AV | 50 | hd_pos_a_1 | Head Pressure Actuator Position (circuit A) | % | Read | |
| AV | 51 | hd_pos_b_1 | Head Pressure Actuator Position (circuit B) | % | Read | |
| AV | 52 | hd_pos_c_1 | Head Pressure Actuator Position (circuit C) | % | Read | |
| AV | 53 | hc_sel_1 | Heat/Cool Select | Write | ||
| AV | 54 | min_left_1 | Minutes Left for Start | min | Read | |
| AV | 55 | curren_a_1 | Motor Current (circuit A) | A | Read | |
| AV | 56 | curren_b_1 | Motor Current (circuit B) | A | Read | |
| AV | 57 | curren_c_1 | Motor Current (circuit C) | A | Read | |
| AV | 58 | cp_tmp_a_1 | Motor Temperature (circuit A) | °F | Read | |
| AV | 59 | cp_tmp_b_1 | Motor Temperature (circuit B) | °F | Read | |
| AV | 60 | cp_tmp_c_1 | Motor Temperature (circuit C) | °F | Read | |
| AV | 61 | op_a_1 | Oil Pressure (circuit A) | psi | Read | |
| AV | 62 | op_b_1 | Oil Pressure (circuit B) | psi | Read | |
| AV | 63 | op_c_1 | Oil Pressure (circuit C) | psi | Read | |
| AV | 64 | dop_a_1 | Oil Pressure Difference (circuit A) | psi | Read | |
| AV | 65 | dop_b_1 | Oil Pressure Difference (circuit B) | psi | Read | |
| AV | 67 | capa_t_1 | Percent Total Capacity (circuit A) | % | Read | |
| AV | 68 | capb_t_1 | Percent Total Capacity (circuit B) | % | Read | |
| AV | 69 | capc_t_1 | Percent Total Capacity (circuit C) | % | Read | |
| AV | 70 | sct_a_1 | Saturated Condensing Temp (circuit A) | °F | Read | |
| AV | 71 | sct_b_1 | Saturated Condensing Temp (circuit B) | °F | Read | |
| AV | 72 | sct_c_1 | Saturated Condensing Temp (circuit C) | °F | Read | |
| AV | 73 | sst_a_1 | Saturated Suction Temp (circuit A) | °F | Read | |
| AV | 74 | sst_b_1 | Saturated Suction Temp (circuit B) | °F | Read | |
| AV | 75 | sst_c_1 | Saturated Suction Temp (circuit C) | °F | Read | |
| AV | 76 | sp_a_1 | Suction Pressure (circuit A) | psi | Read | |
| AV | 77 | sp_b_1 | Suction Pressure (circuit B) | psi | Read | |
| AV | 78 | sp_c_1 | Suction Pressure (circuit C) | psi | Read | |
| AVmin | 79 | dem_lim_1 | Active Demand Limit Value | % | Write | |
| AV | 80 | tot_curr_1 | Actual Chiller Current | A | Read | |
| AV | 81 | curr_lim_1 | Chiller Current Limit | A | Write | |
| AV | 82 | ctrl_wt_1 | Controlled Water temp | °F | Read | |
| AVmin | 83 | ctrl_pnt_1 | Control point | °F | Write | |
| AV | 84 | sp_1 | Current Setpoint | °F | Read | |
| AV | 85 | oat_1 | External Temperature | °F | Read | |
| AV | 86 | lag_lim_1 | Lag Capacity Limit Value | % | Read | |
| AVmin | 87 | cap_t_1 | Percent Total Capacity | % | Read | |
| AV | 88 | sp_sel_1 | Setpoint Select | Read | ||
| AV | 89 | capt_010_1 | Chiller Capacity Signal | V | Read | |
| AV | 90 | chwstemp_1 | CHWS Temperature | °F | Read | |
| AV | 91 | t_heat_c_1 | Circuit C Heater Temp | °F | Read | |
| AV | 92 | heatcool_1 | Heat/Cool Status | Read | ||
| AVmin | 93 | status_1 | Run Status | Read | ||
| AV | 94 | cool_ewt_1 | Cooler Entering Fluid | °F | Read | |
| AV | 95 | t_heater_1 | Cooler Heater Temp | °F | Read | |
| AVmin | 96 | cool_lwt_1 | Cooler Leaving Fluid - Prime Variable | °F | Read | |
| AV | 97 | cool_pwr_1 | Cooling power* | kW | Read | |
| AV | 98 | lim_anal_1 | Limit 4-20mA Signal | mA | Read | |
| AV | 99 | spacetmp_1 | Optional Space Temp | °F | Read | |
| AV | 100 | sp_reset_1 | Reset/Setpoint 4-20mA Signal | mA | Read | |
| AV | 101 | watpres1_1 | Water pressure before cooler* | psi | Read | |
| AV | 102 | watpres2_1 | Water pressure after cooler* | psi | Read | |
| AV | 103 | watpres3_1 | Water pressure before filter* | psi | Read | |
| AV | 104 | watpres4_1 | Water pressure after filter* | psi | Read | |
| AV | 105 | wat_flow_1 | Water flow* | gal/sec | Read | |
| AV | 106 | lead_cir_1 | Circuit Loading Sequence | Write | ||
| AV | 107 | hr_cp_a_1 | Compressor A Hours | hr | Read | |
| AV | 108 | st_cp_a_1 | Compressor A Starts | Read | ||
| AV | 109 | hr_cp_b_1 | Compressor B Hours | hr | Read | |
| AV | 110 | st_cp_b_1 | Compressor B Starts | Read | ||
| AV | 111 | hr_cp_c_1 | Compressor C Hours | hr | Read | |
| AV | 112 | st_cp_c_1 | Compressor C Starts | Read | ||
| AV | 113 | hr_cpum1_1 | Cooler pump #1 Hours | hr | Read | |
| AV | 114 | hr_cpum2_1 | Cooler pump #2 Hours | hr | Read | |
| AV | 115 | hr_mach_1 | Machine Operating Hours | hr | Read | |
| AV | 116 | st_mach_1 | Machine Starts | Read | ||
| AV | 117 | cpumpseq_1 | Cooler Pumps Sequence | Write | ||
| AV | 118 | curr_ful_1 | Current Limit at 100% | A | Write | |
| AV | 119 | pump_del_1 | Pump Auto Rotation Delay | hr | Write | |
| AV | 120 | off_on_d_1 | Unit Off-to-On Delay | min | Read | |
| AV | 121 | ice_sp_1 | Cooling Ice Setpoint | °F | Write | |
| AV | 122 | cramp_sp_1 | Cooling Ramp Loading | °F (delta) | Write | |
| AV | 123 | cr_deg_1 | Cooling Reset Degrees | °F (delta) | Write | |
| AV | 124 | csp1_1 | Cooling Setpoint 1 | °F | Write | |
| AV | 125 | csp2_1 | Cooling Setpoint 2 | °F | Write | |
| AV | 126 | v_cr_fu_1 | Current Full Reset Value | mA | Write | |
| AV | 127 | v_cr_no_1 | Current No Reset Value | mA | Write | |
| AV | 128 | dt_cr_fu_1 | Delta T Full Reset Value | °F (delta) | Write | |
| AV | 129 | dt_cr_no_1 | Delta T No Reset Value | °F (delta) | Write | |
| AV | 130 | oatcr_fu_1 | OAT Full Reset Value | °F | Write | |
| AV | 131 | oatcr_no_1 | OAT No Reset Value | °F | Write | |
| AV | 132 | spacr_fu_1 | Space T Full Reset Value | °F | Write | |
| AV | 133 | spacr_no_1 | Space T No Reset Value | °F | Write | |
| AV | 134 | lim_sp1_1 | Switch Limit Setpoint 1 | % | Write | |
| AV | 135 | lim_sp2_1 | Switch Limit Setpoint 2 | % | Write | |
| AV | 136 | lim_sp3_1 | Switch Limit Setpoint 3 | % | Write | |
| AVmin | 137 | alm_1 | Alarm State | Read | ||
| AV | 2901 | user_analog_1_1 | User Defined Analog 1 | Write | ||
| AV | 2902 | user_analog_2_1 | User Defined Analog 2 | Write | ||
| AV | 2903 | user_analog_3_1 | User Defined Analog 3 | Write | ||
| AV | 2904 | user_analog_4_1 | User Defined Analog 4 | Write | ||
| AV | 2905 | user_analog_5_1 | User Defined Analog 5 | Write | ||
| AV | 9006 | cool_demand_level_1 | System Cooling Demand Level | Read | ||
| AV | 80001 | mstr_oa_temp_1 | System OAT Master | °F | Read | |
| BVmin | 1 | chil_s_s_1 | Chiller Start/Stop | Write | 0 = Disable, 1 = Enable | |
| BVmin | 2 | chil_occ_1 | Chiller Occupied? | Write | 0 = No, 1 = Yes | |
| BV | 3 | iso_refa_1 | Ball Valve Position (circuit A) | Read | ||
| BV | 4 | iso_refb_1 | Ball Valve Position (circuit B) | Read | ||
| BV | 5 | iso_refc_1 | Ball Valve Position (circuit C) | Read | ||
| BV | 6 | comp_a_1 | Compressor Output (circuit A) | Read | ||
| BV | 7 | comp_b_1 | Compressor Output (circuit B) | Read | ||
| BV | 8 | comp_c_1 | Compressor Output (circuit C) | Read | ||
| BV | 9 | gascoola_1 | DGT Cooling Solenoid (circuit A) | Read | ||
| BV | 10 | gascoolb_1 | DGT Cooling Solenoid (circuit B) | Read | ||
| BV | 11 | gascoolc_1 | DGT Cooling Solenoid (circuit C) | Read | ||
| BV | 12 | fan_a1_1 | Fan Output DO #1 (circuit A) | Read | ||
| BV | 13 | fan_a2_1 | Fan Output DO #2 (circuit A) | Read | ||
| BV | 14 | fan_a3_1 | Fan Output DO #3 (circuit A) | Read | ||
| BV | 15 | fan_a4_1 | Fan Output DO #4 (circuit A) | Read | ||
| BV | 16 | fan_a5_1 | Fan Output DO #5 (circuit A) | Read | ||
| BV | 17 | fan_a6_1 | Fan Output DO #6 (circuit A) | Read | ||
| BV | 18 | fan_a7_1 | Fan Output DO #7 (circuit A) | Read | ||
| BV | 19 | fan_a8_1 | Fan Output DO #8 (circuit A) | Read | ||
| BV | 20 | fan_b1_1 | Fan Output DO #1 (circuit B) | Read | ||
| BV | 21 | fan_b2_1 | Fan Output DO #2 (circuit B) | Read | ||
| BV | 22 | fan_b3_1 | Fan Output DO #3 (circuit B) | Read | ||
| BV | 23 | fan_b4_1 | Fan Output DO #4 (circuit B) | Read | ||
| BV | 24 | fan_b5_1 | Fan Output DO #5 (circuit B) | Read | ||
| BV | 25 | fan_b6_1 | Fan Output DO #6 (circuit B) | Read | ||
| BV | 26 | fan_b7_1 | Fan Output DO #7 (circuit B) | Read | ||
| BV | 27 | fan_b8_1 | Fan Output DO #8 (circuit B) | Read | ||
| BV | 28 | fan_c1_1 | Fan Output DO #1 (circuit C) | Read | ||
| BV | 29 | fan_c2_1 | Fan Output DO #2 (circuit C) | Read | ||
| BV | 30 | fan_c3_1 | Fan Output DO #3 (circuit C) | Read | ||
| BV | 31 | fan_c4_1 | Fan Output DO #4 (circuit C) | Read | ||
| BV | 32 | fan_c5_1 | Fan Output DO #5 (circuit C) | Read | ||
| BV | 33 | fan_c6_1 | Fan Output DO #6 (circuit C) | Read | ||
| BV | 34 | fan_c7_1 | Fan Output DO #7 (circuit C) | Read | ||
| BV | 35 | fan_c8_1 | Fan Output DO #8 (circuit C) | Read | ||
| BV | 36 | fc_dsble_1 | Free Cooling Disable* | Write | No/Yes | |
| BV | 37 | recl_sel_1 | Heat Reclaim Select* | Write | No/Yes | |
| BV | 38 | hgbp_a_1 | Hot Gas Bypass A Output | Read | ||
| BV | 39 | hgbp_b_1 | Hot Gas Bypass B Output | Read | ||
| BV | 40 | hgbp_c_1 | Hot Gas Bypass C Output | Read | ||
| BV | 41 | oil_ht_a_1 | Oil Heater Output (circuit A) | Read | ||
| BV | 42 | oil_ht_b_1 | Oil Heater Output (circuit B) | Read | ||
| BV | 43 | oil_ht_c_1 | Oil Heater Output (circuit C) | Read | ||
| BV | 44 | oil_l_a_1 | Oil Level Input (circuit A) | Read | ||
| BV | 45 | oil_l_b_1 | Oil Level Input (circuit B) | Read | ||
| BV | 46 | oil_l_c_1 | Oil Level Input (circuit C) | Read | ||
| BV | 47 | oil_sl_a_1 | Oil Solenoid Output (circuit A) | Read | ||
| BV | 48 | oil_sl_b_1 | Oil Solenoid Output (circuit B) | Read | ||
| BV | 49 | oil_sl_c_1 | Oil Solenoid Output (circuit C) | Read | ||
| BV | 50 | slid_1_a_1 | Slide Valve 1 Output (circuit A) | Read | ||
| BV | 51 | slid_2_a_1 | Slide Valve 2 Output (circuit A) | Read | ||
| BV | 52 | slid_1_b_1 | Slide Valve 1 Output (circuit B) | Read | ||
| BV | 53 | slid_2_b_1 | Slide Valve 2 Output (circuit B) | Read | ||
| BV | 54 | slid_1_c_1 | Slide Valve 1 Output (circuit C) | Read | ||
| BV | 55 | slid_2_c_1 | Slide Valve 2 Output (circuit C) | Read | ||
| BVmin | 56 | emstop_1 | Emergency Stop | Write | 0 = Disable, 1 = Enable | |
| BV | 57 | sp_occ_1 | Setpoint Occupied? | Read | 0 = No, 1 = Yes | |
| BV | 59 | mode_02_1 | Second Setpoint in Use | Read | ||
| BV | 60 | mode_03_1 | Reset in Effect | Read | ||
| BV | 61 | mode_04_1 | Demand Limit Active | Read | ||
| BV | 62 | mode_05_1 | Ramp Loading Active | Read | ||
| BV | 63 | mode_06_1 | Cooler Heater Active | Read | ||
| BV | 64 | mode_07_1 | Cooler Pumps Rotation | Read | ||
| BV | 65 | mode_08_1 | Pump Periodic Start | Read | ||
| BV | 66 | mode_09_1 | Night Low Noise Active | Read | ||
| BV | 67 | mode_10_1 | System Manager Active | Read | ||
| BV | 68 | mode_11_1 | Master Slave Active | Read | ||
| BV | 69 | mode_12_1 | Auto Changeover Active | Read | ||
| BV | 70 | mode_13_1 | Free Cooling Active | Read | ||
| BV | 71 | mode_14_1 | Reclaim Active | Read | ||
| BV | 72 | mode_15_1 | Boiler Active | Read | ||
| BV | 73 | mode_16_1 | Heating Low EWT Lockout | Read | ||
| BV | 74 | mode_17_1 | Condenser pumps Rotation | Read | ||
| BV | 75 | mode_18_1 | Ice Mode in Effect | Read | ||
| BV | 76 | mode_19_1 | Defrost Active on Circuit A | Read | ||
| BV | 77 | mode_20_1 | Defrost Active on Circuit B | Read | ||
| BV | 78 | mode_21_1 | Low Suction Circuit A | Read | ||
| BV | 79 | mode_22_1 | Low Suction Circuit B | Read | ||
| BV | 80 | mode_23_1 | Low Suction Circuit C | Read | ||
| BV | 81 | mode_24_1 | High DGT Circuit A | Read | ||
| BV | 82 | mode_25_1 | High DGT Circuit B | Read | ||
| BV | 83 | mode_26_1 | High DGT Circuit C | Read | ||
| BV | 84 | mode_27_1 | High Pressure Override Circuit A | Read | ||
| BV | 85 | mode_28_1 | High Pressure Override Circuit B | Read | ||
| BV | 86 | mode_29_1 | High Pressure Override Circuit C | Read | ||
| BV | 87 | mode_30_1 | Low Superheat Circuit A | Read | ||
| BV | 88 | mode_31_1 | Low Superheat Circuit B | Read | ||
| BV | 89 | mode_32_1 | Low Superheat Circuit C | Read | ||
| BV | 90 | alarmout_1 | Alarm Relay Status | Read | ||
| BV | 91 | alert_1 | Alert Relay Status | Read | ||
| BV | 92 | boiler_1 | Boiler Command | Read | ||
| BV | 93 | condflow_1 | Condenser Flow Status | Read | ||
| BV | 94 | set_flow_1 | Cooler Flow Setpoint Out | Read | Off/On | |
| BV | 95 | flow_sw_1 | Cooler Flow Switch | Read | ||
| BV | 96 | coolheat_1 | Cooler Heater Command | Read | ||
| BV | 97 | cpump_1_1 | Cooler Pump #1 Command | Write | Off/On | |
| BV | 98 | cpump_2_1 | Cooler Pump #2 Command | Write | Off/On | |
| BV | 99 | cpumpdef_1 | Cooler Pump Run Status | Read | ||
| BV | 100 | elec_box_1 | Electrical Box Interlock | Read | ||
| BV | 101 | ramp_sel_1 | Ramped Loading Select | Write | No/Yes | |
| BV | 102 | seq_typ_1 | Staged Loading Sequence | Write | No/Yes | |
| BV | 103 | dem_lmt_act_1 | System Demand Limiting | Read | ||
| BV | 104 | fc_sw_1 | Free Cooling Disable Switch* | Read | ||
| BV | 105 | ice_sw_1 | Ice Done Storage Switch | Read | ||
| BV | 106 | lim_sw1_1 | Limit Switch 1 Status | Read | ||
| BV | 107 | lim_sw2_1 | Limit Switch 2 Status | Read | ||
| BV | 108 | occ_ovsw_1 | Occupied Override Switch | Read | ||
| BV | 109 | onoff_sw_1 | On/Off - Remote Switch | Read | ||
| BV | 110 | ready_1 | Ready or Running Status | Read | ||
| BV | 111 | hc_sw_1 | Remote Heat/Cool Switch | Read | ||
| BV | 112 | rem_lock_1 | Remote Interlock Status | Read | ||
| BV | 113 | recl_sw_1 | Remote Reclaim Switch | Read | ||
| BV | 114 | setp_sw_1 | Remote Setpoint Switch | Read | ||
| BV | 115 | rotcpump_1 | Rotate Cooler Pumps? | Write | 0 = No, 1 = Yes | |
| BV | 116 | running_1 | Running Status | Read | ||
| BV | 117 | shutdown_1 | Shutdown Indicator State | Read | ||
| BV | 118 | curr_sel_1 | Current Limit Select | Write | Off/On | |
| BV | 119 | schedule_1 | Local Schedule | Read | ||
| BV | 120 | comm_lost_alm_1 | Element Communications Alarm | Read | ||
| BV | 2911 | user_binary_1_1 | User Defined Binary 1 | Write | ||
| BV | 2912 | user_binary_2_1 | User Defined Binary 2 | Write | ||
| BV | 2913 | user_binary_3_1 | User Defined Binary 3 | Write | ||
| BV | 2914 | user_binary_4_1 | User Defined Binary 4 | Write | ||
| BV | 2915 | user_binary_5_1 | User Defined Binary 5 | Write | ||
| BV | 2999 | element_stat_1 | Element Comm Status | Read |
No points match these filters.
Integration notes
- BACnet comes from the optional UPC Open controller, mounted in a separate enclosure below the main control box; object names end in _1.
- The Network Points List gives a point description, CCN name, read/write, units, default and range for each object; descriptions here are the printed point descriptions.
- This is the UPC Open BACnet MS/TP option for 30XA080-501 with the Carrier Controller display. The separate 30XA BACnet/Modbus translator list (30XA-100T, 30XA140-352 with Touch Pilot) is a different interface with its own, much shorter object list; check which one is fitted.
- The table has no CCN name column on these pages.
- AV 93 Run Status codes: 0 Off, 1 Running, 2 Stopping, 3 Delay, 4 Tripout, 5 Ready, 6 Override, 7 Defrost, 8 Run Test, 9 Test. AV 137 Alarm State: 0 Normal, 1 Partial, 2 Shutdown.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XA 080-501 (UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
How many BACnet points does the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) have?
This list has 268 BACnet objects: 143 analog values, 125 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) BACnet points are writable?
45 of the 268 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) BACnet documentation?
The source is AquaForce 30XA080-501 Air-Cooled Liquid Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix G, BACnet Communication, Network Points List) (30XA-7T), revision 2-24, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0E/30XA-7T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)?
Start with BV 1 chil_s_s_1 (Network start/stop (0 Disable, 1 Enable)); BV 2 chil_occ_1 (Network occupied command); BV 56 emstop_1 (Emergency stop command); AV 83 ctrl_pnt_1 (Control point (leaving fluid setpoint)); AV 79 dem_lim_1 (Demand limit, 0-100 %); AV 93 status_1 (Run status code); AV 96 cool_lwt_1 (Cooler leaving fluid temperature); AV 87 cap_t_1 (Percent total capacity); AV 137 alm_1 (Alarm state: 0 Normal, 1 Partial, 2 Shutdown).
How do I enable BMS control of the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)?
Press the Start/Stop button on the Carrier Controller display and select CCN Mode on the Equipment Start screen. CHIL_S_S (BV 1) then starts and stops the chiller: forced to Disable the unit stops, forced to Enable it runs per schedule 1.
Does the Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) need a BACnet heartbeat or have a communication timeout?
The manual says that if communication with the network is lost, the machine starts and is controlled locally.
How do I check these points on the real AquaForce 30XA 080-501 (UPC Open BACnet option)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01