Fan coil unit controller · BACnet points list

Carrier Fan Coil Open BACnet points list

Updated 28 October 2026

Short answer

The Fan Coil (OPN-FC) controller ships as an integrated part of Carrier packaged fan coil units. DIP switches and the communications selector choose BACnet MS/TP (the default), BACnet ARC156, Modbus or N2, and a LonWorks option card is available. The default device instance is 16101 followed by the two-digit rotary address. Points cover setpoints, space and supply temperatures, fan speed and valve outputs, 2-pipe changeover, alarms and the 'system' points a BAS writes in place of local sensors.

This page lists 80 BACnet objects for the Carrier Fan Coil Open — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
Fan Coil Open
Equipment
Fan coil unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
80 (33 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Not stated
Default device instance
16101xx (xx = rotary switch address)
Also known as
OPN-FC, Carrier Fan Coil controller, 11-808-540-01
Source document
Fan Coil Integration Guide (Appendix A: Fan Coil Network Points List) · 11-808-540-01 · rev. 2022-07-21
Download CSV 80 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier Fan Coil Open

Integration in brief

Set the Fan Coil Open for BACnet MS/TP with its DIP switches and rotary address. Disable the local Occupancy Schedules so the BAS can command occupancy through keypad_ovrde, then write setpoints directly. Space temperature, humidity, CO2, OAT and 2-pipe water temperature from the BMS go into the system_* points at priority 16 and have to be refreshed within each point's window.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1keypad_ovrdeBAS occupancy command: occupied/unoccupiedWrite
BV 9001shutdownNetwork shutdown commandWrite
AV 3001occ_cl_stptOccupied cooling setpointWrite
AV 3002occ_ht_stptOccupied heating setpointWrite
MV 2002run_statusCurrent system modeRead
BV 2008occ_statusConfirms occupied/unoccupiedRead
AV 2007space_tempSpace temperature the unit controls toRead
AV 1008sa_tempSupply air temperatureRead
BV 7008sfan_fail_alarmSupply fan failure alarmRead
BV 7028overflow_alarmCondensate overflow alarm; stops the fanRead

Enable & remote start

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1 in the points list): 1=Inactive, 2=Occupied, 3=Unoccupied. Shutdown (BV:9001) stops the unit from the network. Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Heartbeat & communication loss

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, RH and CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.

Sensors & values from the BMS

Write system_spt (AV:1902), system_rh (AV:1904), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. system_water_temp sets the 2-pipe changeover mode and takes priority over the local changeover sensor. The controller clears a system point after processing it, so read the matching control point instead (space_temp, space_rh, iaq, oa_temp, chgovr_mode) at least 30 s after the write.

Network setup

Watch out for

Carrier Fan Coil Open BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

80 of 80 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier Fan Coil Open BACnet Points List
DescriptionStates
AV9002oat_cl_lockoutCooling Lockout Temperature (default 45)°FWrite
AV2025clg_outputCooling Output%Read
AV2022oa_dpr_posDamper Output%Read
AV3005eff_cl_stptEffective Cool Setpoint°FRead
AV3006eff_ht_stptEffective Heat Setpoint°FRead
AV2019filter_service_hrsFilter Service Alarm Timer (default 600)hrWrite
AV9003oat_ht_lockoutHeating Lockout Temperature (default 65)°FWrite
AV2026htg_outputHeating Output%Read
AV3011occ_dehum_stptOcc Relative Humidity Setpoint (default 60)%rhWrite
AV9026optm_startOptimal Start (default 1)hrWrite
AV2016ovrde_timeOverride Time RemainingminRead
AV9007start_delayPower Fail Restart Delay (default 5)secondsWrite
AV1010ra_tempReturn Air Temperature°FRead
AV1003oa_tempOutdoor Air Temperature°FRead
AVmin3001occ_cl_stptOccupied cool setpoint°FWrite
AV1006stpt_adjSetpoint Adjustment°FRead
AV9015stpt_adj_rangeSetpoint Adjustment Range (default 5)°FWrite
AV1011space_rhSpace Relative Humidity%rhRead
AVmin2007space_tempSpace Temperature - Prime Variable°FRead
AV1901system_oatSystem Outdoor Air Temperature (default -999)°FWrite
AV1913system_stpt_adjSystem Setpoint Adjustment (default -999)°FWrite
AV1903system_iaqSystem Space AQ (default -999)Write
AV1904system_rhSystem Space RH (default -999)%Write
AV1902system_sptSystem Space Temperature (default -999)°FWrite
AV1905system_water_tempSystem Water Temperature (default -999)°FWrite
AV3012unocc_dehum_stptUnocc Relative Humidity Setpoint (default 95)%rhWrite
BV1014chgovr_modeChangeover ModeRead0=Off; 1=On
BVmin7028overflow_alarmCondensate OverflowRead0=Normal; 1=Alarm
BV1011cl_enableCool Enable (default Enable)Write0=Disable; 1=Enable
BV2006dehum_statusDehumidificationRead0=Inactive; 1=Active
BV7017filter_alarmFilterRead0=Normal; 1=Alarm
BV7007fire_alarmFire / Smoke ShutdownRead0=Normal; 1=Alarm
BV1012ht_enableHeat Enable (default Enable)Write0=Disable; 1=Enable
BV7011spt_hi_alarmHigh Space TemperatureRead0=Normal; 1=Alarm
BV7005iaq_alarmIndoor Air QualityRead0=Normal; 1=Alarm
BV7012spt_lo_alarmLow Space TemperatureRead0=Normal; 1=Alarm
BVmin2008occ_statusOccupancy StatusRead0=Unoccupied; 1=Occupied
BV1015reht_enableReheat Enable (default Disable)Write0=Disable; 1=Enable
BV7517filter_rntm_clrReset Filter Alarm (default Inactive)Write0=Off; 1=On
BV7035rat_alarmReturn Air TemperatureRead0=Normal; 1=Alarm
BV1013stpt_adj_enableSetpoint Adjustment (default Enable)Write0=Disable; 1=Enable
BVmin9001shutdownShutdown (default Inactive)Write0=Inactive; 1=Active
BV7018sprh_hi_alarmSpace Relative HumidityRead0=Normal; 1=Alarm
BV7004sat_alarmSupply Air TemperatureRead0=Normal; 1=Alarm
BVmin7008sfan_fail_alarmSupply Fan FailureRead0=Normal; 1=Alarm
MV2004fan_runFan / SpeedRead1=Off; 2=Low; 3=Med; 4=High; 5=On
MV2009start_typeOptimal Start Type (default 2)Write1=None; 2=Temp Compensated; 3=Learning Adaptive
MVmin2002run_statusSystem ModeRead1=Off; 2=Fan Only; 3=Economize; 4=Cooling; 5=Heating; 6=Cont Fan; 7=Test; 8=Start Delay; 9=Temper SAT; 10=Fire Shutdown; 11=Shutdown; 12=IAQ Override; 13=Dehumidify
AVmin3002occ_ht_stptOccupied heat setpoint°FWrite
AV3003unocc_cl_stptUnoccupied cool setpoint°FWrite
AV3004unocc_ht_stptUnoccupied heat setpoint°FWrite
AV4005econ_minVent Dmpr Pos / DCV Min Pos (default 20)%Write
AV1009iaqIndoor Air Quality CO2 (ppm)ppmRead
BV7037llt_alarmFreezestatRead0=Normal; 1=Alarm
BV7001spt_failSpace Temp SensorRead0=Normal; 1=Alarm
BV7029oat_failOutdoor Air Temp SensorRead0=Normal; 1=Alarm
AV9028occ_ovr_delayOcc Override Delay (default 15)minWrite
BV1016fan_cycleUnoccupied Fan Cycling (default Enable)Write0=Disable; 1=Enable
AVmin1008sa_tempSupply Air Temperature°FRead
BV7033link_therm_failThermostat LinkageRead0=Normal; 1=Alarm
AV83004sat_ht_maxMaximum Heating SAT (default 110)°FWrite
AV83003sat_cl_minMinimum Cooling SAT (default 50)°FWrite
MV2005link_ahu_modeAir Source ModeRead1=Off; 2=Warmup; 3=Heat; 4=Cooling; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent
MV2003spt_statusSpace Temp SourceRead1=Sensor Failure; 2=SPT Sensor; 3=RAT / T55; 4=Network; 5=Airside Linkage; 6=Locked Value; 7=T-Stat Linkage; 8=ZS Sensor
BV7051zst_sensor_failZS Temp SensorRead0=Normal; 1=Alarm
AV9006cool_demand_levelSystem Cooling Demand LevelRead
AV9036heat_demand_levelSystem Heating Demand LevelRead
AV2608link_satAir Source Supply Air Temp°FRead
BV7030air_linkage_failAirside LinkageRead0=Normal; 1=Alarm
AV9024fan_delay_offFan Off Delay (default 90)secondsWrite
BV7034chgovr_failChangeover SensorRead0=Normal; 1=Alarm
BV2009frz_statusFreezestatRead0=Normal; 1=Alarm
AV2015filter_rntmFilter RuntimehrRead
BV2601a_link_statusAirside LinkageRead0=Not Active; 1=Active
AV9025fan_delay_onFan On Delay (default 10)secondsWrite
BV7032spt_sensor_failSPT SensorRead0=Normal; 1=Alarm
MVmin1keypad_ovrdeBAS On / Off (default 1)Write1=Inactive; 2=Occupied; 3=Unoccupied
BV2801t_link_statusThermostat LinkageRead0=Not Active; 1=Active
BV1003sfan_statusSupply Fan StatusRead0=Off; 1=On
BV7055zs_config_failZS Sensor ConfigurationRead0=Normal; 1=Alarm

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Fan Coil Open and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier Fan Coil Open

How many BACnet points does the Carrier Fan Coil Open have?

This list has 80 BACnet objects: 41 analog values, 33 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier Fan Coil Open BACnet points are writable?

33 of the 80 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier Fan Coil Open BACnet documentation?

The source is Fan Coil Integration Guide (Appendix A: Fan Coil Network Points List) (11-808-540-01), revision 2022-07-21, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/0E/11-808-540-01.pdf.

What are the minimum BACnet points to integrate the Carrier Fan Coil Open?

Start with MV 1 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (Current system mode); BV 2008 occ_status (Confirms occupied/unoccupied); AV 2007 space_temp (Space temperature the unit controls to); AV 1008 sa_temp (Supply air temperature); BV 7008 sfan_fail_alarm (Supply fan failure alarm); BV 7028 overflow_alarm (Condensate overflow alarm; stops the fan).

How do I enable BMS control of the Carrier Fan Coil Open?

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1 in the points list): 1=Inactive, 2=Occupied, 3=Unoccupied. Shutdown (BV:9001) stops the unit from the network. Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Does the Carrier Fan Coil Open need a BACnet heartbeat or have a communication timeout?

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, RH and CO2 5 min / 10 min, OAT and water temperature 5 min / 60 min.

Can the BMS supply sensor values to the Carrier Fan Coil Open?

Write system_spt (AV:1902), system_rh (AV:1904), system_iaq (AV:1903), system_oat (AV:1901), system_water_temp (AV:1905) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. system_water_temp sets the 2-pipe changeover mode and takes priority over the local changeover sensor. The controller clears a system point after processing it, so read the matching control point instead (space_temp, space_rh, iaq, oa_temp, chgovr_mode) at least 30 s after the write.

How do I check these points on the real Fan Coil Open?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: Fan Coil Integration Guide (Appendix A: Fan Coil Network Points List) · 11-808-540-01 · rev. 2022-07-21. Object names, instances and units are reproduced as published; descriptions are our own.