Water-source heat pump controller · BACnet points list

Carrier WSHP Open v3 BACnet points list

Updated 28 October 2026

Short answer

WSHP Open is the multi-protocol controller on Carrier water-source heat pumps. DIP switches select BACnet MS/TP (the default), BACnet ARC156, Modbus or N2, and a LonWorks option card is available. The device instance is built from Carrier's vendor ID (16) and the rotary address. Points cover setpoints, space and water temperatures, fan and compressor status, waterside economizer, alarms and the 'system' points a BAS writes in place of local sensors.

This page lists 83 BACnet objects for the Carrier WSHP Open v3 — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
WSHP Open v3
Equipment
Water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
83 (30 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Not stated
Default device instance
16101xx (xx = rotary switch address)
Also known as
WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source document
WSHP Open v3 Integration Guide (Appendix A: Network Points List) · 11-808-539-01 · rev. 2021-06-15
Download CSV 83 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier WSHP Open v3

Integration in brief

Set the WSHP Open for BACnet MS/TP with its DIP switches and rotary address. Disable the local Occupancy Schedules so the BAS can command occupancy through keypad_ovrde, then write setpoints directly. Space temperature, humidity, CO2 and OAT from the BMS go into the system_* points at priority 16 and have to be refreshed within each point's window.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1001keypad_ovrdeBAS occupancy command: occupied/unoccupiedWrite
BV 9001shutdownNetwork shutdown commandWrite
AV 3001occ_cl_stptOccupied cooling setpointWrite
AV 3002occ_ht_stptOccupied heating setpointWrite
MV 2002run_statusCurrent system modeRead
BV 2008occ_statusConfirms occupied/unoccupiedRead
AV 2007space_tempSpace temperature the unit controls toRead
AV 1008sa_tempSupply air temperatureRead
BV 7013comp_alarmCompressor failure alarmRead
BV 7028overflow_alarmCondensate overflow alarm; stops compressor and fanRead

Enable & remote start

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. Shutdown (BV:9001) = Active stops the unit in a controlled way; when it returns to Inactive the unit restarts after the power fail restart delay. Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Heartbeat & communication loss

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, RH and CO2 5 min / 10 min, OAT 5 min / 60 min. A network OAT that stops updating raises the Outdoor Air Temp Sensor alarm (oat_fail, BV:7029) after about an hour.

Sensors & values from the BMS

Write system_spt (AV:1902), system_rh (AV:1904), system_iaq (AV:1903), system_oat (AV:1901) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. The controller clears a system point after processing it, so read the matching control point instead (space_temp, space_rh, iaq, oa_temp) at least 30 s after the write.

Network setup

Watch out for

Carrier WSHP Open v3 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

83 of 83 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier WSHP Open v3 BACnet Points List
DescriptionStates
AV3014aux_heat_stptAux Heat Control Setpoint°FRead
AV2021aux_heat_outputAuxiliary Heat Output%Read
AV9002oat_cl_lockoutCooling Lockout Temperature (default 45)°FWrite
AV2022oa_dpr_posDamper Output%Read
AV1017cwl_tempLeaving Source Water Temp°FRead
AV4005econ_minVent Dmpr Pos / DCV Min Pos (default 20)%Write
AV1003oa_tempOutdoor Air Temperature°FRead
AV2016ovrde_timeOverride Time RemainingminRead
AVmin3002occ_ht_stptOccupied heat setpoint°FWrite
AV1006stpt_adjSetpoint Adjustment°FRead
AVmin2007space_tempSpace Temperature - Prime Variable°FRead
AVmin1008sa_tempSupply Air Temperature°FRead
AV1903system_iaqSystem Space AQ (default -999)ppmWrite
AV1904system_rhSystem Space RH (default -999)%Write
AV1902system_sptSystem Space Temperature (default -999)°FWrite
AV3012unocc_dehum_stptUnocc Relative Humidity Setpoint (default 95)%rhWrite
AV3015h2o_econ_ctrl_stptWater Economizer Control Setpoint°FRead
AV2023h2o_econ_outputWater Economizer Output%Read
BVmin7013comp_alarmCompressor StatusRead0=Normal; 1=Alarm
BVmin7028overflow_alarmCondensate OverflowRead0=Normal; 1=Alarm
BV7027cwt_alarmSource Water TemperatureRead0=Normal; 1=Alarm
BV1011cl_enableCool Enable (default Enable)Write0=Disable; 1=Enable
BV2006dehumDehumidificationRead0=Disable; 1=Enable
BV1003sfan_statusSupply Fan StatusRead0=Off; 1=On
BV7017filter_alarmFilter alarm (fan run hours)Read0=Normal; 1=Alarm
BV7007fire_alarmFire / Smoke ShutdownRead0=Normal; 1=Alarm
BV1012ht_enableHeat Enable (default Enable)Write0=Disable; 1=Enable
BV7011spt_hi_alarmHigh Space TemperatureRead0=Normal; 1=Alarm
BV7005iaq_alarmIndoor Air QualityRead0=Normal; 1=Alarm
BV7012spt_lo_alarmLow Space TemperatureRead0=Normal; 1=Alarm
BVmin2008occ_statusOccupancy StatusRead0=Unoccupied; 1=Occupied
BV1013stpt_adj_enableSetpoint Adjustment (default Enable)Write0=Disable; 1=Enable
BVmin9001shutdownShutdown (default Inactive)Write0=Inactive; 1=Active
BV7018sprh_hi_alarmSpace Relative HumidityRead0=Normal; 1=Alarm
BV7001spt_failSpace Temp SensorRead0=Normal; 1=Alarm
BV7004sat_alarmSupply Air TemperatureRead0=Normal; 1=Alarm
BV7008sfan_fail_alarmSupply Fan FailureRead0=Normal; 1=Alarm
MV2004fan_runFan / SpeedRead1=Off; 2=Low; 3=Med; 4=High; 5=On
MV2009start_typeOptimal Start Type (default 2)Write1=None; 2=Temp Compensated; 3=Learning Adaptive
MVmin2002run_statusSystem ModeRead1=Off; 2=Fan Only; 3=Economize; 4=Cooling; 5=Heating; 6=Cont Fan; 7=Test; 8=Start Delay
AV3011occ_dehum_stptOcc Relative Humidity Setpoint (default 60)%rhWrite
AV9026optm_startOptimal Start (default 1)hrWrite
BV1004smk_detectSmoke Detector ContactRead0=Alarm / Open; 1=Normal / Closed
AV3005eff_cl_stptEffective Cool Setpoint°FRead
AV3003unocc_cl_stptUnoccupied cool setpoint°FWrite
AV9003oat_ht_lockoutHeating Lockout Temperature (default 65)°FWrite
AV9007start_delayPower Fail Restart Delay (default 180)secondsWrite
AVmin3001occ_cl_stptOccupied cool setpoint°FWrite
AV2019filter_service_hrsFilter Service Alarm Timer (default 600)hrWrite
AV1009iaqIndoor Air Quality CO2 (ppm)ppmRead
AV3004unocc_ht_stptUnoccupied heat setpoint°FWrite
AV1901system_oatSystem Outdoor Air Temperature (default -999)°FWrite
AV1913system_stpt_adjSystem Setpoint Adjustment (default -999)°FWrite
BV7517filter_rntm_clrReset Filter Alarm (default Off)Write0=Off; 1=On
AV3006eff_ht_stptEffective Heat Setpoint°FRead
AV83004sat_ht_maxMaximum Heating SAT (default 110)°FWrite
AV83003sat_cl_minMinimum Cooling SAT (default 50)°FWrite
AV9015stpt_adj_rangeSetpoint Adjustment Range (default 5)°FWrite
MVmin1001keypad_ovrdeBAS On / Off (default 1)Write1=Inactive; 2=Occupied; 3=Unoccupied
BV7055zs_config_failZS Sensor ConfigurationRead0=Normal; 1=Alarm
AV1011space_rhSpace Relative Humidity%rhRead
MV2003spt_statusSpace Temp SourceRead1=Sensor Failure; 2=SPT Sensor; 3=T55 / T56; 4=Network; 5=Airside Linkage; 6=Locked Value
AV9024fan_delay_offFan Off Delay (default 90)secondsWrite
AV2608link_satAir Source Supply Air Temp°FRead
AV2701link_cwtWater Loop Temp°FRead
AV2702link_hwtAux Heat Boiler Water Temp°FRead
BV7030air_linkage_failAirside LinkageRead0=Normal; 1=Alarm
BV7031cond_water_linkage_failSource Water LinkageRead0=Normal; 1=Alarm
AV9036heat_demand_levelSystem Heating Demand LevelRead
BV2601a_link_statusAirside LinkageRead0=Not Active; 1=Active
AV9028occ_ovr_delayOcc Override Delay (default 15)minWrite
AV2024loop_requestLoop Pump RequestRead
BV2701cw_link_statusSource Water LinkageRead0=Not Active; 1=Active
BV2703hw_pumpAux Heat HW Pump StatusRead0=Off; 1=On
AV9006cool_demand_levelSystem Cooling Demand LevelRead
AV2015filter_rntmFilter RuntimehrRead
AV5001comp_capCompressor Capacity%Read
MV2005link_ahu_modeAir Source ModeRead1=Off; 2=Warmup; 3=Heat; 4=Cooling; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent
BV7032spt_sensor_failSPT SensorRead0=Normal; 1=Alarm
BV7051zst_sensor_failZS Temp SensorRead0=Normal; 1=Alarm
BV2702loop_pumpLoop Pump StatusRead0=Off; 1=On
BV7029oat_failOutdoor Air Temp SensorRead0=Normal; 1=Alarm
AV9025fan_delay_onFan On Delay (default 10)secondsWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WSHP Open v3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier WSHP Open v3

How many BACnet points does the Carrier WSHP Open v3 have?

This list has 83 BACnet objects: 46 analog values, 31 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier WSHP Open v3 BACnet points are writable?

30 of the 83 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier WSHP Open v3 BACnet documentation?

The source is WSHP Open v3 Integration Guide (Appendix A: Network Points List) (11-808-539-01), revision 2021-06-15, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/04/11-808-539-01.pdf.

What are the minimum BACnet points to integrate the Carrier WSHP Open v3?

Start with MV 1001 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (Current system mode); BV 2008 occ_status (Confirms occupied/unoccupied); AV 2007 space_temp (Space temperature the unit controls to); AV 1008 sa_temp (Supply air temperature); BV 7013 comp_alarm (Compressor failure alarm); BV 7028 overflow_alarm (Condensate overflow alarm; stops compressor and fan).

How do I enable BMS control of the Carrier WSHP Open v3?

The unit runs occupied 24/7 until a schedule or the BAS takes over. Disable Occupancy Schedules (Configuration > Unit Configuration) so the BAS can control it, then write BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. Shutdown (BV:9001) = Active stops the unit in a controlled way; when it returns to Inactive the unit restarts after the power fail restart delay. Cool Enable (BV:1011) and Heat Enable (BV:1012) lock out cooling or heating.

Does the Carrier WSHP Open v3 need a BACnet heartbeat or have a communication timeout?

No general heartbeat. Each system point is only used while it is refreshed within its window: space temperature 1 min / 5 min, RH and CO2 5 min / 10 min, OAT 5 min / 60 min. A network OAT that stops updating raises the Outdoor Air Temp Sensor alarm (oat_fail, BV:7029) after about an hour.

Can the BMS supply sensor values to the Carrier WSHP Open v3?

Write system_spt (AV:1902), system_rh (AV:1904), system_iaq (AV:1903), system_oat (AV:1901) and system_stpt_adj (AV:1913) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. The controller clears a system point after processing it, so read the matching control point instead (space_temp, space_rh, iaq, oa_temp) at least 30 s after the write.

How do I check these points on the real WSHP Open v3?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: WSHP Open v3 Integration Guide (Appendix A: Network Points List) · 11-808-539-01 · rev. 2021-06-15. Object names, instances and units are reproduced as published; descriptions are our own.