Easy BACnet
  1. Home
  2. BACnet points lists
  3. Carrier
  4. RTU Open v5

Rooftop unit controller · BACnet points list

Carrier RTU Open v5 BACnet points list

Updated 28 October 2026

Short answer

RTU Open is Carrier's multi-protocol controller for packaged rooftop units and heat pumps. It speaks BACnet MS/TP or ARC156 natively and can be switched to Modbus, N2 or LonWorks. Its device instance is derived from Carrier's vendor ID (16) and the rotary address switches. Points cover setpoints, sensor values, stages, economizer/ventilation, alarms and the 'system' points a BAS can write in place of local sensors.

This page lists 200 BACnet objects for the Carrier RTU Open v5 — 104 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
RTU Open v5
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
200 (104 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Not stated
Default device instance
16101xx (xx = rotary switch address)
Also known as
RTU Open, OPN-RTU, RTU-Open, 11-808-697-01
Source document
RTU Open v5 Integration Guide (Appendix A: Network Points List) · 11-808-697-01 · rev. 2019-11-19
Download CSV 200 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier RTU Open v5

Integration in brief

Set the RTU Open for BACnet MS/TP with its DIP switches and rotary address, then set Occupancy Source to BAS On/Off so the BMS can command occupancy through keypad_ovrde. Write setpoints directly. Any sensor the BMS supplies (space temp, OAT, RH, CO2) goes into the system_* points at priority 16 and has to be refreshed within each point's refresh window.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1002occ_sourceSet to 3 (BAS On/Off) to allow network occupancyWrite
MV 1001keypad_ovrdeBAS occupancy command: occupied/unoccupiedWrite
BV 9001shutdownNetwork shutdown commandWrite
AV 3001occ_cl_stptOccupied cooling setpointWrite
AV 3002occ_ht_stptOccupied heating setpointWrite
MV 2002run_statusCurrent system modeRead
BV 2008occ_statusConfirms occupied/unoccupiedRead
AV 2007space_tempSpace temperature the unit controls toRead
AV 1008sa_tempSupply air temperatureRead
BV 7008sfan_fail_alarmSupply fan failure alarmRead

Enable & remote start

Occupancy Source (occ_source, MSV:1002) defaults to Always Occupied. Set it to 3 = BAS On/Off, then write keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The shutdown point (BV:9001) stops the unit from the network.

Heartbeat & communication loss

No general heartbeat. Each system point has a recommended refresh time (min/max), e.g. space temperature 1 min / 5 min, OAT 5 min / 60 min. The network value is only used while it keeps being refreshed within that window; for OAT, a lost network value raises the Outdoor Air Temp Sensor alarm and the OAT lockouts stop working.

Sensors & values from the BMS

Write system_spt (AV:1902), system_oat (AV:1901), system_rh (AV:1904), system_iaq (AV:1903), system_oaq (AV:1908) and oae (BV:1901, OA enthalpy) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. Don't read the system point back to confirm a write, because the controller clears it after processing. Read the matching control point instead (space_temp, oa_temp, space_rh, iaq, oaq), at least 30 s after the write.

Network setup

Watch out for

Carrier RTU Open v5 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

200 of 200 shown
Type
Multi-state
Access
Show
Carrier RTU Open v5 BACnet Points List
DescriptionStates
AV3032tempering_stptSA Vent / Temper Setpoint (default 65)°FWrite
AV1030vfd_spd_cfgVFD Speed Config (default %)%/VWrite
AV3033heat_vfd_spdHeating VFD Output (default 100)%Write
AV83010ht_spd_voltVoltage Used to Set IDF VFD Heat Speed (default 4.4)VWrite
AV83011max_spd_voltVoltage Used to Set IDF VFD Maximum Speed (default 10)VWrite
AV83012min_spd_voltVoltage Used to Set IDF VFD Minimum Speed (default 5.2)VWrite
AV83016sa_tempering_enTempering Enable (default Disable)Write
AV81003vfd_spdv_testVFD Speed Test (default 0)VWrite
AV2032vfd_volt_outputSupply Fan VFD VoltageVRead
AV91010vfd_in_typeVFD Analog Input Channel Type (default 2 to 10)VdcWrite
AV2003heat_runActive Heat StagesRead
AV3005eff_cl_stptEffective Cool Setpoint°FRead
BV7011spt_hi_alarmHigh Space TemperatureRead0=Normal; 1=Alarm
BV7012spt_lo_alarmLow Space TemperatureRead0=Normal; 1=Alarm
AI1006ai_6Input_6°FRead
BV2001sfanSupply Fan Relay StateRead0=Off; 1=On
BV1003sfan_statusSupply Fan StatusRead0=Off; 1=On
AV2022econ_outputEconomizer Output%OpenRead
BV7006oaq_failOutdoor Air Quality SensorRead0=Normal; 1=Alarm
AV9011iaq_dpr_maxDCV Max Vent Damper Pos (default 50)%OpenWrite
AVmin2007space_tempSpace Temperature - Prime Variable°FRead
AV9004hp_rev_cycle_lockoutHP Rev Cycle Lockout Temp (default -3)°FWrite
AV1901system_oatSystem Outdoor Air Temperature (default -999)°FWrite
AV9029econ_purge_minEconomizer Purge Min Pos (default 40)%OpenWrite
AV2020comp_runActive Compressor StagesRead
MVmin2002run_statusSystem ModeRead1=Off; 2=Fan Only; 3=Economizer Cooling; 4=Cooling; 5=Heating; 6=Dehumidification; 7=Test; 8=Shutdown; 9=Unocc Free Cooling; 10=Fire Shutdown; 11=IAQ Override; 12=Pre-occ Purge; 13=IGC Override
AVmin1008sa_tempSupply Air Temperature°FRead
AV3013iaq_stpt_maxDCV Max Ctrl Setpoint (default 650)ppmWrite
AV3011occ_dehum_stptOcc Relative Humidity Setpoint (default 60)%rhWrite
BVmin2008occ_statusOccupancy StatusRead0=Unoccupied; 1=Occupied
MV2009start_typeOptimal Start Type (default 2)Write1=None; 2=Temp Compensated; 3=Learning Adaptive
AV3004unocc_ht_stptUnoccupied heat setpoint°FWrite
AV81001econ_testEconomizer Test (default 0)%OpenWrite
BV7022sprh_sensor_failSpace Relative Humidity SensorRead0=Normal; 1=Alarm
AV1006stpt_adjSetpoint Adjustment°FRead
AV3006eff_ht_stptEffective Heat Setpoint°FRead
AV9030econ_min_2Low Fan Econ Min Pos (default 33)%OpenWrite
BV7007fire_alarmFire / Smoke ShutdownRead0=Normal; 1=Alarm
BV7517filter_rntm_clrReset Filter Alarm (default Inactive (0))Write0=Off; 1=On
AV3003unocc_cl_stptUnoccupied cool setpoint°FWrite
BV7055zs_config_failZS Sensor ConfigurationRead0=Normal; 1=Alarm
AV1011space_rhSpace Relative Humidity%rhRead
AV1003oa_tempOutdoor Air Temperature°FRead
AV9002oat_cl_lockoutCooling Lockout Temperature (default 45)°FWrite
AV3010pexh_stptPower Exhaust Setpoint (default 50)%OpenWrite
MVmin1001keypad_ovrdeBAS On / Off (default 1)Write1=Inactive; 2=Occupied; 3=Unoccupied
AV1903system_iaqSystem Space AQ (default -999)ppmWrite
AV1904system_rhSystem Space RH (default -999)%Write
BV7013comp_alarmCompressor StatusRead0=Normal; 1=Alarm
AV2019filter_service_hrsFilter Service Alarm Timer (default 600)hrWrite
BV7039iaq_sensor_failIndoor Air Quality SensorRead0=Normal; 1=Alarm
AV9003oat_ht_lockoutHeating Lockout Temperature (default 65)°FWrite
BV2006dehumDehumidificationRead0=Inactive; 1=Active
BV2007aux_1Reversing Valve Relay StateRead0=Off; 1=On
AV90000ppoPassword Protected Output Variable (default 0)Write
AV9005econ_minVent Dmpr Pos / DCV Min Pos (default 20)%OpenWrite
BV7017filter_alarmFilterRead0=Clean; 1=Dirty
BV7024safety_alarmSafety ChainRead0=Normal; 1=Alarm
AV3012unocc_dehum_stptUnocc Relative Humidity Setpoint (default 95)%rhWrite
AVmin3002occ_ht_stptOccupied heat setpoint°FWrite
BV7020loc_sat_sensor_failSupply Air Temp SensorRead0=Normal; 1=Alarm
AV2016ovrde_timeOverride Time RemainingminRead
BV1013stpt_adj_enableSetpoint Adjustment (default Active (1))Write0=Disable; 1=Enable
AV1902system_sptSystem Space Temperature (default -999)°FWrite
AV91006stpt_adj_offsetSpace Temperature Offset Pot°FRead
AV1908system_oaqSystem Outdoor AQ (default -999)ppmWrite
BV7029oat_failOutdoor Air Temp SensorRead0=Normal; 1=Alarm
BV7032spt_sensor_failSPT SensorRead0=Normal; 1=Alarm
MV2004fan_runFan / SpeedRead1=Off; 2=Low; 3=Med; 4=High; 5=On
AV9015stpt_adj_rangeSetpoint Adjustment Range (default 5)Δ°FWrite
BV1901oaeEnthalpy (BACnet) (default Active (1))Write0=High; 1=Low
AV9026optm_startOptimal Start (default 1)hrWrite
AV9006cool_demand_levelSystem Cooling Demand LevelRead
AV9036heat_demand_levelSystem Heating Demand LevelRead
AV80001mstr_oa_tempSystem OAT Master°FRead
AV9023ovr_durT5x Override Duration (default 1)hrWrite
AV81002vfd_spd_testVFD Speed Test (default 0)%Write
BI1003di_3input_3Read0=Off; 1=On
BI1004di_4input_4Read0=Off; 1=On
BI1005di_5input_5Read0=Off; 1=On
BI1008di_8input_8Read0=Off; 1=On
BI1009di_9input_9Read0=Off; 1=On
BV7030air_linkage_failAirside LinkageRead0=Normal; 1=Alarm
BV7026ai_cfg_alarmAnalog Input ConfigurationRead0=Normal; 1=Alarm
BV7014comp1_rntm_alarmCompressor 1 RuntimeRead0=Normal; 1=Alarm
BV2005comp_1Compressor 1 Relay StateRead0=Off; 1=On
BV81005comp1_testCompressor 1 Test (default Inactive (0))Write0=Disable; 1=Enable
BV2004comp_2Compressor 2 Relay StateRead0=Off; 1=On
BV7015comp2_rntm_alarmCompressor 2 RuntimeRead0=Normal; 1=Alarm
BV81004comp2_testCompressor 2 Test (default Inactive (0))Write0=Disable; 1=Enable
BV1008comp_statusCompressor Safety StatusRead0=Normal; 1=Trouble
BV9002occ_exhContinuous Occupied Exhaust (default Inactive (0))Write0=No; 1=Yes
BV1027dcv_enableDCV Control (default Inactive (0))Write
BV81006dehum_testDehumidification Test (default Inactive (0))Write0=Disable; 1=Enable
BV1010door_contact_statusDoor Contact StatusRead0=Off; 1=On
BV99001econ_existEconomizer Exists (default Inactive (0))Write0=No; 1=Yes
BV1002enthalpy_statusEnthalpy StatusRead0=High; 1=Low
BV91000fac_test_enableFactory Test (default Inactive (0))Write0=Off; 1=On
BV91001relay1_fac_testFactory Test Relay 1 Control (default Inactive (0))Write0=Off; 1=On
BV91002relay2_fac_testFactory Test Relay 2 Control (default Inactive (0))Write0=Off; 1=On
BV91003relay3_fac_testFactory Test Relay 3 Control (default Inactive (0))Write0=Off; 1=On
BV91004relay4_fac_testFactory Test Relay 4 Control (default Inactive (0))Write0=Off; 1=On
BV91005relay5_fac_testFactory Test Relay 5 Control (default Inactive (0))Write0=Off; 1=On
BV91006relay6_fac_testFactory Test Relay 6 Control (default Inactive)Write0=Off; 1=On
BV91007relay7_fac_testFactory Test Relay 7 Control (default Inactive (0))Write0=Off; 1=On
BV91008relay8_fac_testFactory Test Relay 8 Control (default Inactive (0))Write0=Off; 1=On
BV1004filter_statusFilter StatusRead0=Clean; 1=Dirty
BV1005firedown_statusFire Shutdown StatusRead0=Run Enabled; 1=Shutdown
BV81003heat1_testHeat 1Test (default Inactive (0))Write0=Disable; 1=Enable
BV81002heat2_testHeat 2Test (default Inactive (0))Write0=Disable; 1=Enable
BV2003heat_1Heat Stage 1 Relay StateRead0=Off; 1=On
BV2002heat_2Heat Stage 2 Relay StateRead0=Off; 1=On
BV99002heat_typeHeat Type (default Inactive (0))Write0=Electric; 1=Gas
BV81010hi_spd_testHigh Speed Fan Test (default Inactive (0))Write0=Disable; 1=Enable
BV1006humstat_statusHumidistat Input StatusRead0=High; 1=Low
BV1022igcovr_statusIGC OverrideRead0=Off; 1=Active
BV7003loc_oat_sensor_failLocal OAT SensorRead0=Normal; 1=Alarm
BV1007occ_contact_statusOccupancy ContactRead0=Off; 1=On
BV2010pexhPower Exhaust Relay StateRead0=Off; 1=On
BV81008pexh_testPower Exhaust Test (default Inactive (0))Write0=Disable; 1=Enable
BV7514comp1_rntm_clrReset Comp 1 Runtime Alarm (default Inactive (0))Write0=Run; 1=Clear
BV7515comp2_rntm_clrReset Comp 2 Runtime Alarm (default Inactive (0))Write0=Run; 1=Clear
BV7510sfan_rntm_clrReset Supply Fan Runtime Alarm (default Inactive (0))Write0=Run; 1=Clear
BV1026rev_vlv_typeReversing Valve Output (default Inactive (0))Write
BV1025rh_enableRH Control (default Inactive (0))Write
BV1009safety_statusSafety Chain FeedbackRead0=Off; 1=On
BV8000scheduleSchedule (default 0)Write0=Unoccupied; 1=Occupied
BV81000test_enableService Test (default Inactive (0))Write0=Disable; 1=Enable
BV7002slidepot_alarmSetpoint SliderRead0=Normal; 1=Alarm
BVmin9001shutdownShutdown (default Inactive (0))Write0=Inactive; 1=Active
BVmin7008sfan_fail_alarmSupply Fan FailureRead0=Normal; 1=Alarm
BV7009sfan_hand_alarmSupply Fan in HandRead0=Normal; 1=Alarm
BV7010sfan_rntm_alarmSupply Fan RuntimeRead0=Normal; 1=Alarm
BV7025di_cfg_alarmSwitch ConfigurationRead0=Normal; 1=Alarm
BV2011shutdown_statusSystem is shut downRead0=No; 1=Yes
BV80001ntfc_enaUnocc Free Cool (default Inactive (0))Write0=Disable; 1=Enable
MV2005link_ahu_modeAir Source ModeRead1=Off; 2=Warmup; 3=Heating; 4=Cooling; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent
MV91003comp_stagesCompressor Stages (default 2)Write1=One Stage; 2=Two Stages
MV2001mode_statusEquipment StatusRead1=Disabled; 2=Test; 3=Run
MV9031fan_typeFan Control (default 3)Write1=Single Speed; 2=Two Speed; 3=Variable Speed
MV9032fan_modeFan Mode (default 2)Write1=Auto; 2=Continuous; 3=Always On
MV81001ai1_functionInput 1 Function (default 1)Write1=No Sensor; 2=IAQ Sensor; 3=OAQ Sensor; 4=Space RH Sensor
MV81002ai2_functionInput 2 Function (default 1)Write1=No Sensor; 2=IAQ Sensor; 3=OAQ Sensor; 4=Space RH Sensor
MV81003di3_functionInput 3 Function (default 2)Write1=No Function; 2=Compressory Safety; 3=Fan Status; 4=Filter Status; 5=Remote Occupancy; 6=Door Contact
MV81013di3_typeInput 3 Switch Configuration (default 1)Write1=NO; 2=NC
MV81005di5_functionInput 5 Function (default 2)Write1=No Function; 2=Fire Shutdown; 3=Fan Status; 4=Filter Status; 5=Remote Occupancy; 6=Door Contact
MV81015di5_typeInput 5 Switch Configuration (default 1)Write1=NO; 2=NC
MV81008di8_functionInput 8 Function (default 2)Write1=No Function; 2=Enthalpy Switch; 3=Fan Status; 4=Filter Status; 5=Remote Occupancy; 6=Door Contact
MV81018di8_typeInput 8 Switch Configuration (default 1)Write1=NO; 2=NC
MV81009di9_functionInput 9 Function (default 2)Write1=No Function; 2=HumidiStat; 3=Fan Status; 4=Filter Status; 5=Remote Occupancy; 6=Door Contact
MV81019di9_typeInput 9 Switch Configuration (default 1)Write1=NO; 2=NC
MV91004heat_stagesNumber Of Heat Stages (default 2)Write1=1; 2=2; 3=0
MVmin1002occ_sourceOccupancy Source (default 1)Write1=Always Occupied; 2=BACnet Schedule; 3=BAS On/Off; 4=Remote Occ Input
MV9001spt_typeSpace sensor type (default 1)Write1=T55; 2=T56; 3=SPT Sensor; 4=None
MV2003spt_statusSpace Temp SourceRead1=Sensor Failure; 2=SPT Sensor; 3=T55 / T56; 4=Network; 5=Airside Linkage; 6=Locked Value
MV9018unit_typeUnit Type (default 2)Write1=Heat / Cool; 2=LC WeatherExpert; 3=HP O/B Ctrl; 4=HP Y1/W1 Ctrl
BV7051zst_sensor_failZS Temp SensorRead0=Normal; 1=Alarm
BV7054econ_oprEconomizer OperationRead0=Normal; 1=Fault Detected
BV7056spt_alrm_statusSpace Temperature Alarm StatusRead0=Normal; 1=Alarm
AI1zone_temp_zone_tempSPT Sensor°FRead
AV1zone_temp_override_time_remainingSPT SensorminRead
AI1010ai_10input_10°FRead
AV91001ao1_fac_testFactory Test Analog 1 Control (default 0)%Write
AV9008oat_ec_lockoutEconomizer High OAT Lockout Temp (default 75)°FWrite
AV83004sat_ht_maxMaximum Heating SAT (default 120)°FWrite
AV2018comp2_rntmCompressor 2 RuntimehrRead
AV2611link_max_dmprLinkage Max Damper Position%Read
AV2608link_satAir Source Supply Air Temp°FRead
AV3026max_vfd_spdMax VFD Output (default 100)%Write
AV3028dehum_min_vfdDehum Min VFD Output (default 100)%Write
AV2609link_ahu_oatAir Source Outdoor Air Temp°FRead
AV83010stg_3_satStage 3 SAT Stpt (default 56)°FWrite
AV83008stg_1_satStage 1 SAT Stpt (default 57)°FWrite
AV3025oat_auxht_lockoutHP Aux Heat Lockout Temp (default 40)°FWrite
AI1001ai_1input_1Read
AV91002ao2_fac_testFactory Test Analog 2 Control (default 0)VWrite
AV83007comp2_service_hrsCompressor 2 Service Alarm Timer (default 0)hrWrite
AV83006comp1_service_hrsCompressor 1 Service Alarm Timer (default 0)hrWrite
AV2017comp1_rntmCompressor 1 RuntimehrRead
AV3027min_vfd_spdMin VFD Output (default 40)%Write
AV83009stg_2_satStage 2 SAT Stpt (default 57)°FWrite
AI1012slidepot_voltsslidepot voltage readingRead
AV2015filter_rntmFilter RuntimehrRead
AV9024fan_delay_offFan Off Delay (default 90)secondsWrite
AI1007ai_7input_7°FRead
AI1011ai_11input_11Read
AI1002ai_2input_2Read
AV83003sat_cl_minMinimum Cooling SAT (default 50)°FWrite
AV9007start_delayPower Fail Restart Delay (default 5)secondsWrite
AV83005sfan_service_hrsSupply Fan Service Alarm Timer (default 0)hrWrite
AV2014sfan_rntmSupply Fan RuntimehrRead
AV1009iaqIndoor Air Quality CO2 (ppm)ppmRead
AV2027vfd_outputSupply Fan VFD%Read
BV7005iaq_alarmIndoor Air QualityRead0=Normal; 1=Alarm
BV7004sat_alarmSupply Air TemperatureRead0=Normal; 1=Alarm
BV7018sprh_hi_alarmSpace Relative HumidityRead0=Normal; 1=Alarm
BV7001spt_failSpace Temp SensorRead0=Normal; 1=Alarm
AV1012oaqOutdoor Air Quality CO2 (ppm)ppmRead
BV7050igc_alarmGas ValveRead0=Normal; 1=Alarm
AVmin3001occ_cl_stptOccupied cool setpoint°FWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RTU Open v5 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier RTU Open v5

How many BACnet points does the Carrier RTU Open v5 have?

This list has 200 BACnet objects: 8 analog inputs, 80 analog values, 5 binary inputs, 83 binary values, 24 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier RTU Open v5 BACnet points are writable?

104 of the 200 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier RTU Open v5 BACnet documentation?

The source is RTU Open v5 Integration Guide (Appendix A: Network Points List) (11-808-697-01), revision 2019-11-19, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/04/11-808-697-01.pdf.

What are the minimum BACnet points to integrate the Carrier RTU Open v5?

Start with MV 1002 occ_source (Set to 3 (BAS On/Off) to allow network occupancy); MV 1001 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); MV 2002 run_status (Current system mode); BV 2008 occ_status (Confirms occupied/unoccupied); AV 2007 space_temp (Space temperature the unit controls to); AV 1008 sa_temp (Supply air temperature); BV 7008 sfan_fail_alarm (Supply fan failure alarm).

How do I enable BMS control of the Carrier RTU Open v5?

Occupancy Source (occ_source, MSV:1002) defaults to Always Occupied. Set it to 3 = BAS On/Off, then write keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied. The shutdown point (BV:9001) stops the unit from the network.

Does the Carrier RTU Open v5 need a BACnet heartbeat or have a communication timeout?

No general heartbeat. Each system point has a recommended refresh time (min/max), e.g. space temperature 1 min / 5 min, OAT 5 min / 60 min. The network value is only used while it keeps being refreshed within that window; for OAT, a lost network value raises the Outdoor Air Temp Sensor alarm and the OAT lockouts stop working.

Can the BMS supply sensor values to the Carrier RTU Open v5?

Write system_spt (AV:1902), system_oat (AV:1901), system_rh (AV:1904), system_iaq (AV:1903), system_oaq (AV:1908) and oae (BV:1901, OA enthalpy) at BACnet priority 16, no more than once a minute. A network value overrides the local sensor while it is refreshed in time. Don't read the system point back to confirm a write, because the controller clears it after processing. Read the matching control point instead (space_temp, oa_temp, space_rh, iaq, oaq), at least 30 s after the write.

How do I check these points on the real RTU Open v5?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: RTU Open v5 Integration Guide (Appendix A: Network Points List) · 11-808-697-01 · rev. 2019-11-19. Object names, instances and units are reproduced as published; descriptions are our own.