Carrier ComfortVu BACnet Thermostat BACnet points list

Updated 28 October 2026

Short answer

The ComfortVu is a touchscreen room thermostat that can talk BACnet MS/TP on an RS-485 bus (a DIP switch selects BACnet or Modbus). Its object list mixes live values (temperatures, outputs, occupancy) with the technician settings, so many installer parameters are writable over the network. Several object instances are reused with different names depending on whether the thermostat is set up for a fan coil (FC) or an AC/heat pump (AC) system, so expect only one of each pair to exist on a given unit.

This page lists 165 BACnet objects for the Carrier ComfortVu BACnet Thermostat — 115 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
ComfortVu BACnet Thermostat
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
165 (115 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
ComfortVu, Carrier ComfortVu, 11-808-726-01
Source document
ComfortVu BACnet Thermostat Points List and Technician Settings · 11-808-726-01
Download CSV 165 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier ComfortVu BACnet Thermostat

Integration in brief

Put the thermostat on BACnet MS/TP, then command it like a wall stat: turn it on/off with OnOff, pick the mode and fan speed, and write the cooling and heating setpoints. Read back the effective setpoint, mode, fan and occupancy to confirm what the thermostat is actually doing. The points list gives no network timeout and no network space-temperature input.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0OnOffTurns the thermostat on or offWrite
AV 4ModeSelects fan only, cool, heat or autoWrite
BV 28UnoccupiedByNetworkOccupancy command; 1 = unoccupied, 0 = occupiedWrite
AV 0SetPoint_SetPointCoolCooling setpoint, 5-35 °C (41-95 °F)Write
AV 1SetPointHeatHeating setpoint, 5-35 °C (41-95 °F)Write
AV 6FanSpeedFan auto/low/medium/highWrite
AV 5ModeEffectiveMode actually runningRead
AV 13OccupancyEffectiveHVACResulting occupancy stateRead
AV 3ReturnAirSensorEffectiveTemperature the thermostat controls toRead

Enable & remote start

BV0 OnOff turns the thermostat on/off over the network. BI10 S1_8_UseBacnet shows whether the DIP switch has it set to BACnet (1) or Modbus (0).

Network setup

Watch out for

Carrier ComfortVu BACnet Thermostat BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

165 of 165 shown
Type
Access
Show
Carrier ComfortVu BACnet Thermostat BACnet Points List
DescriptionStates
AI3T1_Ext_TemperatureSensorRange -20°C... 100°C (-4...212°F)°C/°FRead
AI4IN1_AINRange -20°C... 100°C (-4...212°F)°C/°FRead
AO0AO_Cool (cool/heat valve)Range 0...100%; fan coil systems only%Read
AO1AO_HeatRange 0...100%; fan coil systems only%Read
AO2AO_FanRange 0...100%%Read
AO3AO_HumidifierRange 0...100%%Read
AO4AO_DeHumidifierRange 0...100%%Read
AVmin0SetPoint_SetPointCoolRange 5...35°C (41...95°F)°C/°FWrite
AVmin1SetPointHeatRange 5...35°C (41...95°F)°C/°FWrite
AV2SetPointEffectiveRange 5...35°C (41...95°F)°C/°FRead
AVmin3ReturnAirSensorEffectiveRange 0...100°C (32...212°F)°C/°FRead
AVmin4ModeWrite0 - Fan Only; 1 - Cool; 2 - Heat; 3 - Auto
AVmin5ModeEffectiveRead0 - Fan Only; 1 - Cool; 2 - Heat; 4 - Off
AVmin6FanSpeedWrite0 - Auto; 1 - Low; 2 - Medium; 3 - High
AV7FanEffectiveRead1 - Low; 2 - Medium; 3 - High; 4 - Off
AV8ReturnAirSensorCalibrationRange -6...6°C (-9...9°F); tech setting P01°C/°FWrite
AV9SetPointLimitCoolRange 5...35°C (41...95°F); tech setting P02°C/°FWrite
AV10SetPointLimitHeatRange 5...35°C (41...95°F); tech setting P03°C/°FWrite
AV11EconomySetPointInCoolRange 5...35°C (41...95°F); tech setting P25°C/°FWrite
AV12EconomySetPointInHeatRange 5...35°C (41...95°F); tech setting P26°C/°FWrite
AVmin13OccupancyEffectiveHVACRead0 - Unoccupied; 1 - Occupied; 2 - Temporary occupied
AV14OccupancySensorAuthoritytech setting P16Read0 – Occupancy sensor logic not used; 1 – Occupancy sensor logic controls HVAC
AV15OccupancySensorFunctiontech setting P15Write0 - On/Off logic; 1 - Start/Stop logic; 2 - Change setpoint logic; 3 - Unoccupancy Dehumidified logic
AV16OccupancySensorHVACDelayTimeRange 0...900 minutes; tech setting P17minWrite
AV17TimeSwitchingToOccupiedModeRange 0...999 secondssWrite
AV18T1_Functiontech setting P08Write0 - Not used; 1 - External sensor (T1); 2 - Soft start sensor (T3).; 3 – Door switch – Door switch (Hotel configuration of occupancy logic is active); 4 – Key tag
AV19IN1_Functiontech setting P09Write0 - Not used; 1- Auto changeover sensor (T2); 2 - Soft start sensor (T3); 3 – window contact(remote switch On/Off); 4 – window contact (remote switch EC On/EC Off → change SetpointEffective in according to objects AV11, AV12); 5 – Auxiliary Occupancy sensor.
AV20WindowContactDelayTimeRange 0...999 seconds; tech setting P11sWrite
AV21DoorSwitchDelayTimeRange 0...999 seconds; tech setting P13sWrite
AV25T2_EffectiveRange 0...99°C (32...210°F); tech setting P83°C/°FRead
AV26T3_EffectiveRange 0...99°C (32...210°F); tech setting P84°C/°FRead
AV27CoolFanOnDelayRange 0...600 sec; tech setting P31; fan coil systems onlysWrite
AV28CoolFanOffDelayRange 0...600 sec; tech setting P32sWrite
AV29HeatFanOnDelayRange 0...600 sec; tech setting P33; fan coil systems onlysWrite
AV30HeatFanOffDelayRange 0...600 sec; tech setting P34sWrite
AV31FreezeProtectionCutInSetpointRange 8... 15°C (46...59°F); tech setting P36°C/°FWrite
AV32FreezeProtectionCutOutSetpointRange 10... 17°C (50...63°F); tech setting P37°C/°FWrite
AV33FilterCounterRange 0... 999 hours; tech setting P38hRead
AV34FilterAlarmTimeDelayRange 0... 999 hours; tech setting P42hWrite
AV35CoolDifferentialBandRange 0... 5°C (0...10°F); tech setting P45°C/°FWrite
AV36CoolDifferentialBandOffsetRange -5... 5°C (-9...9°F); tech setting P46°C/°FWrite
AV37HeatDifferentialBandRange 0... 5°C (0...10°F); tech setting P47°C/°FWrite
AV38HeatDifferentialBandOffsetRange -5... 5°C (-9...9°F); tech setting P48°C/°FWrite
AV39ShiftBetweenCoolAndHeatRange 0...10°C (0...20°F); tech setting P49°C/°FWrite
AV40ShiftBetweenCoolStagesRange 0...10°C (0...20°F); tech setting P50; AC systems only°C/°FWrite
AV41ShiftBetweenHeatStagesRange 0...10°C (0...20°F); tech setting P51°C/°FWrite
AV42BacnetDeviceInstanceNumberRange 10000...4000193Write
AV43TimeDelayOnNextCoolStageRange 0...600 sec; tech setting P63; AC systems onlysWrite
AV44TimeDelayOnNextHeatStageRange 0...600 sec; tech setting P27sWrite
AV45TimeDelayOffNextCoolStageRange 0...600 sec; tech setting P64; AC systems onlysWrite
AV46TimeDelayOffNextHeatStageRange 0...600 sec; tech setting P28sWrite
AV47CompressorStandbyDelayRange 0...360 sec; AC systems onlysWrite
AV48DeiceInCoolCutInTemperatureRange -9.5...8°C (15...46°F); tech setting P85; AC systems only°C/°FWrite
AV49DeiceInCoolCutOutTemperatureRange 2...20°C (36...68°F); tech setting P86; AC systems only°C/°FWrite
AV50DeiceInHeatTimeRange 120...420 sec; tech setting P87; AC systems onlysWrite
AV51DeiceInHeatBreakTimeRange 600...1800 sec; tech setting P88; AC systems onlysWrite
AV52DeiceInHeatCutInTemperatureRange -9.5...8°C (15...46°F); tech setting P89; AC systems only°C/°FWrite
AV53DeiceInHeatCutOutTemperatureRange 2...20°C (36...68°F); tech setting P90; AC systems only°C/°FWrite
AV54BackLightDimTimeRange 0...99 min; tech setting P101minWrite
AV55BackLightDimValueRange 1...90 %; tech setting P102%Write
AV56BackLightBrightnessRange 50...100%; tech setting P105%Write
AV57FanSoftStartInHeatCutInTemperatureRange 14....37°C (57...99°F); tech setting P43; fan coil systems only°C/°FWrite
AV58FanSoftStartInHeatCutOutTemperatureRange 12...35°C (54...95°F); tech setting P44; fan coil systems only°C/°FWrite
AV59DifferentialOnOffFanSpeedsRange 0.3...2°C (0.6...4°F); fan coil systems only°C/°FWrite
AV60OutputsTresholdTimeCoolRange 0...100 sec; tech setting P122; fan coil systems onlysWrite
AV61OutputsTresholdTimeHeatRange 0...100 sec; tech setting P123; fan coil systems onlysWrite
AV62Kp_PIDCoolRange 0...100; tech setting P114; fan coil systems onlyWrite
AV63Kp_PIDHeatRange 0...100; tech setting P115; fan coil systems onlyWrite
AV64Ki_PIDCoolRange 0...100; tech setting P116; fan coil systems onlyWrite
AV65Ki_PIDHeatRange 0...100; tech setting P117; fan coil systems onlyWrite
AV66Kd_PIDCoolRange 0...100; tech setting P118; fan coil systems onlyWrite
AV67Kd_PIDHeatRange 0...100; tech setting P119; fan coil systems onlyWrite
AV68CoolValveProportionalBandRange 2...10°C; tech setting P52; fan coil systems only°C/°FWrite
AV69CoolProportionalLowLimitRange 0...100%; tech setting P53; fan coil systems only%Write
AV70CoolProportionalHighLimitRange 0...100%; tech setting P54; fan coil systems only%Write
AV71HeatValveProportionalBandRange 2...10°C; tech setting P55; fan coil systems only°C/°FWrite
AV72HeatProportionalLowLimitRange 0...100%; tech setting P56; fan coil systems only%Write
AV73HeatProportionalHighLimitRange 0...100%; tech setting P57; fan coil systems only%Write
AV75ProportionalOnPercentRange 0...30%; tech setting P60; fan coil systems only%Write
AV76ProportionalOffPercentRange 0...20%; tech setting P61; fan coil systems only%Write
AV77CoolVFSProportionalBandRange 2...10°C; tech setting P65°C/°FWrite
AV78HeatVFSProportionalBandRange 2...10°C; tech setting P66°C/°FWrite
AV79CoolVFSLowSpeedPercentRange 0...30%; tech setting P67%Write
AV80CoolVFSMediumSpeedPercentRange 30...60%; tech setting P68%Write
AV81CoolVFSHighSpeedPercentRange 60...100%; tech setting P69%Write
AV82HeatVFSLowSpeedPercentRange 0...30%; tech setting P70%Write
AV83HeatlVFSMediumSpeedPercentRange 30...60%; tech setting P71%Write
AV84HeatlVFSHighSpeedPercentRange 60...100%; tech setting P72%Write
AV86VFSMediumSpeedDiffRange 10...50%; tech setting P74%Write
AV87VFSHighSpeedDiffRange 10...50%; tech setting P75%Write
AV88CoolVFSLowLimitRange 0...100%; tech setting P76%Write
AV89CoolVFSHighLimitRange 0...100%; tech setting P77%Write
AV90HeatVFSLowLimitRange 0...100%; tech setting P78%Write
AV91HeatVFSHighLimitRange 0...100%; tech setting P79%Write
AV94Humidity_ValueRange 0...100%%Read
AV95Humidity_OffsetRange -9...9%; tech setting P195%Write
AV98HumiditySetPointRange 20...100%; tech setting P197%Write
AV99HumidityDeadZoneRange 0...100%; tech setting P196%Write
AV101HumidityDifferentialBandRange 2...20%; tech setting P194%Write
AV102RoomTemperatureDisableHumidityRange 10...30°C (50...86°F); tech setting P188°C/°FWrite
AV103DehumidityCycleRange 0...600 min; tech setting P189minWrite
AV104DehumidityBreakTimeRange 0...900 min; tech setting P190minWrite
AV105DoorSwitchOrKeyTag_Functiontech setting P18Write0 – Thermostat turns off when unoccupied; 1 – Thermostat use economy; 2 – Fan Low keeps running
AV106DehumiditySetPointInCoolRange 10...30°C (50...86°F); tech setting P192°C/°FWrite
AV113DayProgSchdedulertech setting P107Write0 - Disable Scheduler,; 1 - All days with same schedule; 2 - One schedule for M- F and anothed for Sat & Sun; 3 - One schedule for M- F and another for Sat , Sun schedule individually; 4 - Schedule each day individually.
AV114DayPeriodstech setting P108Write0 - 2 periods, 1 – 4 periods.
AV115DayPeriodsTypetech setting P109Write0 - USA, 1 - Europe
AV121LockConfigurationRange 0 ...15; tech setting P04 P05 P06 P07Write0 – non Lock; 1 –Mode; 2 –Fan; 3 –Mode+Fan; 4 – On/Off; 5 – On/Off + Mode; 6 – On/Off + Fan; 7 – On/Off + Fan+Mode; 8 - SP; 9 – SP+Mode; 10 – SP+Fan; 11 – SP+Mode+Fan; 12 – SP+On/Off; 13 – SP+On/Off + Mode; 14 – SP+On/Off + Fan; 15 – SP+On/Off + Fan+Mode
AV129TEconomizerEffectiveRange 0...99°C (32...210°F)°C/°FWrite
AV130MinimumTimeCompressorOnRange 0...20 min; tech setting P160; AC systems onlyminWrite
AV131MinimumTimeCompressorOffRange 0...20 min; tech setting P161; AC systems onlyminWrite
AV134EconomizerOA_LowLimitTempRange 9...27°C (48...80°F); tech setting P170°C/°FWrite
BI0S1_1_FanSpeedsRead1-On,0-Off
BI1S1_2_FanSpeedsRead1-On,0-Off
BI2S1_3_Config4pipefan coil systems onlyRead1-On,0-Off
BI2S1_3_ConfigHCHPAC systems onlyRead1-On,0-Off
BI3S1_4_ElectricalHeaterfan coil systems onlyRead1-On,0-Off
BI3S1_4_ACAC systems onlyRead1-On,0-Off
BI7S1_5_ChilledBeamfan coil systems onlyRead1-On,0-Off
BI7S1_5_Compressor DelayAC systems onlyRead1-On,0-Off
BI8S1_6_FloorHeaterfan coil systems onlyRead1-On,0-Off
BI8S1_6_ElectricalHeater2StageAC systems onlyRead1-On,0-Off
BI9S1_7_AC_FC_SystemRead0-AC,1-FC
BI10S1_8_UseBacnetRead1-Bacnet ,0-Modbus
BI11S2_1_CoolProportionalfan coil systems onlyRead1- Cool Proportional, 0 - relay
BI12S2_2_HeatProportionalfan coil systems onlyRead1- Heat Proportional, 0 – relay
BI13S2_3_Dehumidifier Or ReheatAC systems onlyRead1- Dehumidifier, 0- Reheat
BI14S2_4_Cool OnlyAC systems onlyRead1-On,0-Off
BO0HeatOnOffValvefan coil systems onlyRead1-On,0-Off
BO0HeatElement 1AC systems onlyRead1-On,0-Off
BO1HeatElementfan coil systems onlyRead1-On,0-Off
BO1HeatElement 2AC systems onlyRead1-On,0-Off
BO2HeatElement 3AC systems onlyRead1-On,0-Off
BO3CoolOnOffValvefan coil systems onlyRead1-On,0-Off
BO3Compressor 1AC systems onlyRead1-On,0-Off
BO4Compressor 2AC systems onlyRead1-On,0-Off
BO5FanOnOffLowRead1-On,0-Off
BO6FanOnOffMediumRead1-On,0-Off
BO7FanOnOffHighRead1-On,0-Off
BO8HPOnOffAC systems onlyRead1-On,0-Off
BO14EconomizerRead1-On,0-Off
BVmin0OnOffWrite1-On,0-Off
BV1AutoFanWrite1-On,0-Off
BV2C_F_ScaleWrite1-On (C) ,0-Off (F)
BV7One_TwoSetpointstech setting P99Write(2 set points), (1 set point)
BV8FilterAlarmRead1-Alarm, 0-Normal
BV9FilterResettech setting P41Write1-Reset, 0-Normal
BV10AutoModeEnabletech setting P14Write1-Enable, 0-Disable
BV11BackLightDimEnabletech setting P100Write1-Enable, 0-Disable
BV12BeeperEnabletech setting P30Write1-Enable, 0-Disable
BV13FreezeProtectionEnabletech setting P35Write1-Enable, 0-Disable
BV14WindowContactWrite1-Open, 0-Closed
BV15WindowContactPolaritytech setting P10Write1-NC (Normally closes), 0- NO (Normally open)
BV16UnoccupancyByPIRRead1-Unoccupied, 0-Occupied
BV17UnoccupancyByAuxOccSensorRead1-Unoccupied, 0-Occupied
BV18AuxOccupancySensorPolaritytech setting P19Write1-NC (Normally closes), 0- NO (Normally open)
BV19DoorSwitchOpenRead1-Open, 0-Closed
BV20DoorSwitchPolaritytech setting P12Write1-NC (Normally closes), 0- NO (Normally open)
BV25RestoreDefaulttech setting P200Write1-On,0-Off
BV24EmergencyHeat (in HC always Off)AC systems onlyWrite1-On,0-Off
BVmin28UnoccupiedByNetworkWrite1-Unoccupied, 0-Occupied
BV30DayProgramEnableWrite1-Disable, 0-Enable
BV36SetLockWrite1-On,0-Off
BV40EnableShowHumidityFromSettingstech setting P187Write1-Enable, 0-Disable
BV41SetAlarmWrite1-Show,0-Hide

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ComfortVu BACnet Thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier ComfortVu BACnet Thermostat

How many BACnet points does the Carrier ComfortVu BACnet Thermostat have?

This list has 165 BACnet objects: 2 analog inputs, 5 analog outputs, 105 analog values, 16 binary inputs, 13 binary outputs, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier ComfortVu BACnet Thermostat BACnet points are writable?

115 of the 165 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier ComfortVu BACnet Thermostat BACnet documentation?

The source is ComfortVu BACnet Thermostat Points List and Technician Settings (11-808-726-01), published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/06/11-808-726-01.pdf.

What are the minimum BACnet points to integrate the Carrier ComfortVu BACnet Thermostat?

Start with BV 0 OnOff (Turns the thermostat on or off); AV 4 Mode (Selects fan only, cool, heat or auto); BV 28 UnoccupiedByNetwork (Occupancy command; 1 = unoccupied, 0 = occupied); AV 0 SetPoint_SetPointCool (Cooling setpoint, 5-35 °C (41-95 °F)); AV 1 SetPointHeat (Heating setpoint, 5-35 °C (41-95 °F)); AV 6 FanSpeed (Fan auto/low/medium/high); AV 5 ModeEffective (Mode actually running); AV 13 OccupancyEffectiveHVAC (Resulting occupancy state); AV 3 ReturnAirSensorEffective (Temperature the thermostat controls to).

How do I enable BMS control of the Carrier ComfortVu BACnet Thermostat?

BV0 OnOff turns the thermostat on/off over the network. BI10 S1_8_UseBacnet shows whether the DIP switch has it set to BACnet (1) or Modbus (0).