Networked room thermostat · BACnet points list
Carrier ComfortVu BACnet Thermostat BACnet points list
Updated 28 October 2026
The ComfortVu is a touchscreen room thermostat that can talk BACnet MS/TP on an RS-485 bus (a DIP switch selects BACnet or Modbus). Its object list mixes live values (temperatures, outputs, occupancy) with the technician settings, so many installer parameters are writable over the network. Several object instances are reused with different names depending on whether the thermostat is set up for a fan coil (FC) or an AC/heat pump (AC) system, so expect only one of each pair to exist on a given unit.
This page lists 165 BACnet objects for the Carrier ComfortVu BACnet Thermostat — 115 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- ComfortVu BACnet Thermostat
- Equipment
- Networked room thermostat
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 165 (115 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ComfortVu, Carrier ComfortVu, 11-808-726-01
BMS integration notes: Carrier ComfortVu BACnet Thermostat
Put the thermostat on BACnet MS/TP, then command it like a wall stat: turn it on/off with OnOff, pick the mode and fan speed, and write the cooling and heating setpoints. Read back the effective setpoint, mode, fan and occupancy to confirm what the thermostat is actually doing. The points list gives no network timeout and no network space-temperature input.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | OnOff | Turns the thermostat on or off | Write |
| AV 4 | Mode | Selects fan only, cool, heat or auto | Write |
| BV 28 | UnoccupiedByNetwork | Occupancy command; 1 = unoccupied, 0 = occupied | Write |
| AV 0 | SetPoint_SetPointCool | Cooling setpoint, 5-35 °C (41-95 °F) | Write |
| AV 1 | SetPointHeat | Heating setpoint, 5-35 °C (41-95 °F) | Write |
| AV 6 | FanSpeed | Fan auto/low/medium/high | Write |
| AV 5 | ModeEffective | Mode actually running | Read |
| AV 13 | OccupancyEffectiveHVAC | Resulting occupancy state | Read |
| AV 3 | ReturnAirSensorEffective | Temperature the thermostat controls to | Read |
Enable & remote start
BV0 OnOff turns the thermostat on/off over the network. BI10 S1_8_UseBacnet shows whether the DIP switch has it set to BACnet (1) or Modbus (0).
Network setup
- MS/TP at 9600, 19200, 38400 or 76800 baud, no parity, 8 data bits, 1 stop bit.
- A DIP switch selects BACnet or Modbus; read it back on BI10 S1_8_UseBacnet.
- The device instance is AV42 BacnetDeviceInstanceNumber, writable, range 10000 to 4000193.
- DIP switches also set AC vs fan coil (FC) system type, which changes which objects exist.
Watch out for
- Mode, fan speed and occupancy are integer-coded Analog Values, not Multistate objects.
- Several instances are reused: the same BI/BO number has an AC name and an FC name, and only one applies.
- Many writable AVs are the thermostat's technician (P) settings, so writing them changes the installer configuration.
Carrier ComfortVu BACnet Thermostat BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 3 | T1_Ext_TemperatureSensor | Range -20°C... 100°C (-4...212°F) | °C/°F | Read | |
| AI | 4 | IN1_AIN | Range -20°C... 100°C (-4...212°F) | °C/°F | Read | |
| AO | 0 | AO_Cool (cool/heat valve) | Range 0...100%; fan coil systems only | % | Read | |
| AO | 1 | AO_Heat | Range 0...100%; fan coil systems only | % | Read | |
| AO | 2 | AO_Fan | Range 0...100% | % | Read | |
| AO | 3 | AO_Humidifier | Range 0...100% | % | Read | |
| AO | 4 | AO_DeHumidifier | Range 0...100% | % | Read | |
| AVmin | 0 | SetPoint_SetPointCool | Range 5...35°C (41...95°F) | °C/°F | Write | |
| AVmin | 1 | SetPointHeat | Range 5...35°C (41...95°F) | °C/°F | Write | |
| AV | 2 | SetPointEffective | Range 5...35°C (41...95°F) | °C/°F | Read | |
| AVmin | 3 | ReturnAirSensorEffective | Range 0...100°C (32...212°F) | °C/°F | Read | |
| AVmin | 4 | Mode | Write | 0 - Fan Only; 1 - Cool; 2 - Heat; 3 - Auto | ||
| AVmin | 5 | ModeEffective | Read | 0 - Fan Only; 1 - Cool; 2 - Heat; 4 - Off | ||
| AVmin | 6 | FanSpeed | Write | 0 - Auto; 1 - Low; 2 - Medium; 3 - High | ||
| AV | 7 | FanEffective | Read | 1 - Low; 2 - Medium; 3 - High; 4 - Off | ||
| AV | 8 | ReturnAirSensorCalibration | Range -6...6°C (-9...9°F); tech setting P01 | °C/°F | Write | |
| AV | 9 | SetPointLimitCool | Range 5...35°C (41...95°F); tech setting P02 | °C/°F | Write | |
| AV | 10 | SetPointLimitHeat | Range 5...35°C (41...95°F); tech setting P03 | °C/°F | Write | |
| AV | 11 | EconomySetPointInCool | Range 5...35°C (41...95°F); tech setting P25 | °C/°F | Write | |
| AV | 12 | EconomySetPointInHeat | Range 5...35°C (41...95°F); tech setting P26 | °C/°F | Write | |
| AVmin | 13 | OccupancyEffectiveHVAC | Read | 0 - Unoccupied; 1 - Occupied; 2 - Temporary occupied | ||
| AV | 14 | OccupancySensorAuthority | tech setting P16 | Read | 0 – Occupancy sensor logic not used; 1 – Occupancy sensor logic controls HVAC | |
| AV | 15 | OccupancySensorFunction | tech setting P15 | Write | 0 - On/Off logic; 1 - Start/Stop logic; 2 - Change setpoint logic; 3 - Unoccupancy Dehumidified logic | |
| AV | 16 | OccupancySensorHVACDelayTime | Range 0...900 minutes; tech setting P17 | min | Write | |
| AV | 17 | TimeSwitchingToOccupiedMode | Range 0...999 seconds | s | Write | |
| AV | 18 | T1_Function | tech setting P08 | Write | 0 - Not used; 1 - External sensor (T1); 2 - Soft start sensor (T3).; 3 – Door switch – Door switch (Hotel configuration of occupancy logic is active); 4 – Key tag | |
| AV | 19 | IN1_Function | tech setting P09 | Write | 0 - Not used; 1- Auto changeover sensor (T2); 2 - Soft start sensor (T3); 3 – window contact(remote switch On/Off); 4 – window contact (remote switch EC On/EC Off → change SetpointEffective in according to objects AV11, AV12); 5 – Auxiliary Occupancy sensor. | |
| AV | 20 | WindowContactDelayTime | Range 0...999 seconds; tech setting P11 | s | Write | |
| AV | 21 | DoorSwitchDelayTime | Range 0...999 seconds; tech setting P13 | s | Write | |
| AV | 25 | T2_Effective | Range 0...99°C (32...210°F); tech setting P83 | °C/°F | Read | |
| AV | 26 | T3_Effective | Range 0...99°C (32...210°F); tech setting P84 | °C/°F | Read | |
| AV | 27 | CoolFanOnDelay | Range 0...600 sec; tech setting P31; fan coil systems only | s | Write | |
| AV | 28 | CoolFanOffDelay | Range 0...600 sec; tech setting P32 | s | Write | |
| AV | 29 | HeatFanOnDelay | Range 0...600 sec; tech setting P33; fan coil systems only | s | Write | |
| AV | 30 | HeatFanOffDelay | Range 0...600 sec; tech setting P34 | s | Write | |
| AV | 31 | FreezeProtectionCutInSetpoint | Range 8... 15°C (46...59°F); tech setting P36 | °C/°F | Write | |
| AV | 32 | FreezeProtectionCutOutSetpoint | Range 10... 17°C (50...63°F); tech setting P37 | °C/°F | Write | |
| AV | 33 | FilterCounter | Range 0... 999 hours; tech setting P38 | h | Read | |
| AV | 34 | FilterAlarmTimeDelay | Range 0... 999 hours; tech setting P42 | h | Write | |
| AV | 35 | CoolDifferentialBand | Range 0... 5°C (0...10°F); tech setting P45 | °C/°F | Write | |
| AV | 36 | CoolDifferentialBandOffset | Range -5... 5°C (-9...9°F); tech setting P46 | °C/°F | Write | |
| AV | 37 | HeatDifferentialBand | Range 0... 5°C (0...10°F); tech setting P47 | °C/°F | Write | |
| AV | 38 | HeatDifferentialBandOffset | Range -5... 5°C (-9...9°F); tech setting P48 | °C/°F | Write | |
| AV | 39 | ShiftBetweenCoolAndHeat | Range 0...10°C (0...20°F); tech setting P49 | °C/°F | Write | |
| AV | 40 | ShiftBetweenCoolStages | Range 0...10°C (0...20°F); tech setting P50; AC systems only | °C/°F | Write | |
| AV | 41 | ShiftBetweenHeatStages | Range 0...10°C (0...20°F); tech setting P51 | °C/°F | Write | |
| AV | 42 | BacnetDeviceInstanceNumber | Range 10000...4000193 | Write | ||
| AV | 43 | TimeDelayOnNextCoolStage | Range 0...600 sec; tech setting P63; AC systems only | s | Write | |
| AV | 44 | TimeDelayOnNextHeatStage | Range 0...600 sec; tech setting P27 | s | Write | |
| AV | 45 | TimeDelayOffNextCoolStage | Range 0...600 sec; tech setting P64; AC systems only | s | Write | |
| AV | 46 | TimeDelayOffNextHeatStage | Range 0...600 sec; tech setting P28 | s | Write | |
| AV | 47 | CompressorStandbyDelay | Range 0...360 sec; AC systems only | s | Write | |
| AV | 48 | DeiceInCoolCutInTemperature | Range -9.5...8°C (15...46°F); tech setting P85; AC systems only | °C/°F | Write | |
| AV | 49 | DeiceInCoolCutOutTemperature | Range 2...20°C (36...68°F); tech setting P86; AC systems only | °C/°F | Write | |
| AV | 50 | DeiceInHeatTime | Range 120...420 sec; tech setting P87; AC systems only | s | Write | |
| AV | 51 | DeiceInHeatBreakTime | Range 600...1800 sec; tech setting P88; AC systems only | s | Write | |
| AV | 52 | DeiceInHeatCutInTemperature | Range -9.5...8°C (15...46°F); tech setting P89; AC systems only | °C/°F | Write | |
| AV | 53 | DeiceInHeatCutOutTemperature | Range 2...20°C (36...68°F); tech setting P90; AC systems only | °C/°F | Write | |
| AV | 54 | BackLightDimTime | Range 0...99 min; tech setting P101 | min | Write | |
| AV | 55 | BackLightDimValue | Range 1...90 %; tech setting P102 | % | Write | |
| AV | 56 | BackLightBrightness | Range 50...100%; tech setting P105 | % | Write | |
| AV | 57 | FanSoftStartInHeatCutInTemperature | Range 14....37°C (57...99°F); tech setting P43; fan coil systems only | °C/°F | Write | |
| AV | 58 | FanSoftStartInHeatCutOutTemperature | Range 12...35°C (54...95°F); tech setting P44; fan coil systems only | °C/°F | Write | |
| AV | 59 | DifferentialOnOffFanSpeeds | Range 0.3...2°C (0.6...4°F); fan coil systems only | °C/°F | Write | |
| AV | 60 | OutputsTresholdTimeCool | Range 0...100 sec; tech setting P122; fan coil systems only | s | Write | |
| AV | 61 | OutputsTresholdTimeHeat | Range 0...100 sec; tech setting P123; fan coil systems only | s | Write | |
| AV | 62 | Kp_PIDCool | Range 0...100; tech setting P114; fan coil systems only | Write | ||
| AV | 63 | Kp_PIDHeat | Range 0...100; tech setting P115; fan coil systems only | Write | ||
| AV | 64 | Ki_PIDCool | Range 0...100; tech setting P116; fan coil systems only | Write | ||
| AV | 65 | Ki_PIDHeat | Range 0...100; tech setting P117; fan coil systems only | Write | ||
| AV | 66 | Kd_PIDCool | Range 0...100; tech setting P118; fan coil systems only | Write | ||
| AV | 67 | Kd_PIDHeat | Range 0...100; tech setting P119; fan coil systems only | Write | ||
| AV | 68 | CoolValveProportionalBand | Range 2...10°C; tech setting P52; fan coil systems only | °C/°F | Write | |
| AV | 69 | CoolProportionalLowLimit | Range 0...100%; tech setting P53; fan coil systems only | % | Write | |
| AV | 70 | CoolProportionalHighLimit | Range 0...100%; tech setting P54; fan coil systems only | % | Write | |
| AV | 71 | HeatValveProportionalBand | Range 2...10°C; tech setting P55; fan coil systems only | °C/°F | Write | |
| AV | 72 | HeatProportionalLowLimit | Range 0...100%; tech setting P56; fan coil systems only | % | Write | |
| AV | 73 | HeatProportionalHighLimit | Range 0...100%; tech setting P57; fan coil systems only | % | Write | |
| AV | 75 | ProportionalOnPercent | Range 0...30%; tech setting P60; fan coil systems only | % | Write | |
| AV | 76 | ProportionalOffPercent | Range 0...20%; tech setting P61; fan coil systems only | % | Write | |
| AV | 77 | CoolVFSProportionalBand | Range 2...10°C; tech setting P65 | °C/°F | Write | |
| AV | 78 | HeatVFSProportionalBand | Range 2...10°C; tech setting P66 | °C/°F | Write | |
| AV | 79 | CoolVFSLowSpeedPercent | Range 0...30%; tech setting P67 | % | Write | |
| AV | 80 | CoolVFSMediumSpeedPercent | Range 30...60%; tech setting P68 | % | Write | |
| AV | 81 | CoolVFSHighSpeedPercent | Range 60...100%; tech setting P69 | % | Write | |
| AV | 82 | HeatVFSLowSpeedPercent | Range 0...30%; tech setting P70 | % | Write | |
| AV | 83 | HeatlVFSMediumSpeedPercent | Range 30...60%; tech setting P71 | % | Write | |
| AV | 84 | HeatlVFSHighSpeedPercent | Range 60...100%; tech setting P72 | % | Write | |
| AV | 86 | VFSMediumSpeedDiff | Range 10...50%; tech setting P74 | % | Write | |
| AV | 87 | VFSHighSpeedDiff | Range 10...50%; tech setting P75 | % | Write | |
| AV | 88 | CoolVFSLowLimit | Range 0...100%; tech setting P76 | % | Write | |
| AV | 89 | CoolVFSHighLimit | Range 0...100%; tech setting P77 | % | Write | |
| AV | 90 | HeatVFSLowLimit | Range 0...100%; tech setting P78 | % | Write | |
| AV | 91 | HeatVFSHighLimit | Range 0...100%; tech setting P79 | % | Write | |
| AV | 94 | Humidity_Value | Range 0...100% | % | Read | |
| AV | 95 | Humidity_Offset | Range -9...9%; tech setting P195 | % | Write | |
| AV | 98 | HumiditySetPoint | Range 20...100%; tech setting P197 | % | Write | |
| AV | 99 | HumidityDeadZone | Range 0...100%; tech setting P196 | % | Write | |
| AV | 101 | HumidityDifferentialBand | Range 2...20%; tech setting P194 | % | Write | |
| AV | 102 | RoomTemperatureDisableHumidity | Range 10...30°C (50...86°F); tech setting P188 | °C/°F | Write | |
| AV | 103 | DehumidityCycle | Range 0...600 min; tech setting P189 | min | Write | |
| AV | 104 | DehumidityBreakTime | Range 0...900 min; tech setting P190 | min | Write | |
| AV | 105 | DoorSwitchOrKeyTag_Function | tech setting P18 | Write | 0 – Thermostat turns off when unoccupied; 1 – Thermostat use economy; 2 – Fan Low keeps running | |
| AV | 106 | DehumiditySetPointInCool | Range 10...30°C (50...86°F); tech setting P192 | °C/°F | Write | |
| AV | 113 | DayProgSchdeduler | tech setting P107 | Write | 0 - Disable Scheduler,; 1 - All days with same schedule; 2 - One schedule for M- F and anothed for Sat & Sun; 3 - One schedule for M- F and another for Sat , Sun schedule individually; 4 - Schedule each day individually. | |
| AV | 114 | DayPeriods | tech setting P108 | Write | 0 - 2 periods, 1 – 4 periods. | |
| AV | 115 | DayPeriodsType | tech setting P109 | Write | 0 - USA, 1 - Europe | |
| AV | 121 | LockConfiguration | Range 0 ...15; tech setting P04 P05 P06 P07 | Write | 0 – non Lock; 1 –Mode; 2 –Fan; 3 –Mode+Fan; 4 – On/Off; 5 – On/Off + Mode; 6 – On/Off + Fan; 7 – On/Off + Fan+Mode; 8 - SP; 9 – SP+Mode; 10 – SP+Fan; 11 – SP+Mode+Fan; 12 – SP+On/Off; 13 – SP+On/Off + Mode; 14 – SP+On/Off + Fan; 15 – SP+On/Off + Fan+Mode | |
| AV | 129 | TEconomizerEffective | Range 0...99°C (32...210°F) | °C/°F | Write | |
| AV | 130 | MinimumTimeCompressorOn | Range 0...20 min; tech setting P160; AC systems only | min | Write | |
| AV | 131 | MinimumTimeCompressorOff | Range 0...20 min; tech setting P161; AC systems only | min | Write | |
| AV | 134 | EconomizerOA_LowLimitTemp | Range 9...27°C (48...80°F); tech setting P170 | °C/°F | Write | |
| BI | 0 | S1_1_FanSpeeds | Read | 1-On,0-Off | ||
| BI | 1 | S1_2_FanSpeeds | Read | 1-On,0-Off | ||
| BI | 2 | S1_3_Config4pipe | fan coil systems only | Read | 1-On,0-Off | |
| BI | 2 | S1_3_ConfigHCHP | AC systems only | Read | 1-On,0-Off | |
| BI | 3 | S1_4_ElectricalHeater | fan coil systems only | Read | 1-On,0-Off | |
| BI | 3 | S1_4_AC | AC systems only | Read | 1-On,0-Off | |
| BI | 7 | S1_5_ChilledBeam | fan coil systems only | Read | 1-On,0-Off | |
| BI | 7 | S1_5_Compressor Delay | AC systems only | Read | 1-On,0-Off | |
| BI | 8 | S1_6_FloorHeater | fan coil systems only | Read | 1-On,0-Off | |
| BI | 8 | S1_6_ElectricalHeater2Stage | AC systems only | Read | 1-On,0-Off | |
| BI | 9 | S1_7_AC_FC_System | Read | 0-AC,1-FC | ||
| BI | 10 | S1_8_UseBacnet | Read | 1-Bacnet ,0-Modbus | ||
| BI | 11 | S2_1_CoolProportional | fan coil systems only | Read | 1- Cool Proportional, 0 - relay | |
| BI | 12 | S2_2_HeatProportional | fan coil systems only | Read | 1- Heat Proportional, 0 – relay | |
| BI | 13 | S2_3_Dehumidifier Or Reheat | AC systems only | Read | 1- Dehumidifier, 0- Reheat | |
| BI | 14 | S2_4_Cool Only | AC systems only | Read | 1-On,0-Off | |
| BO | 0 | HeatOnOffValve | fan coil systems only | Read | 1-On,0-Off | |
| BO | 0 | HeatElement 1 | AC systems only | Read | 1-On,0-Off | |
| BO | 1 | HeatElement | fan coil systems only | Read | 1-On,0-Off | |
| BO | 1 | HeatElement 2 | AC systems only | Read | 1-On,0-Off | |
| BO | 2 | HeatElement 3 | AC systems only | Read | 1-On,0-Off | |
| BO | 3 | CoolOnOffValve | fan coil systems only | Read | 1-On,0-Off | |
| BO | 3 | Compressor 1 | AC systems only | Read | 1-On,0-Off | |
| BO | 4 | Compressor 2 | AC systems only | Read | 1-On,0-Off | |
| BO | 5 | FanOnOffLow | Read | 1-On,0-Off | ||
| BO | 6 | FanOnOffMedium | Read | 1-On,0-Off | ||
| BO | 7 | FanOnOffHigh | Read | 1-On,0-Off | ||
| BO | 8 | HPOnOff | AC systems only | Read | 1-On,0-Off | |
| BO | 14 | Economizer | Read | 1-On,0-Off | ||
| BVmin | 0 | OnOff | Write | 1-On,0-Off | ||
| BV | 1 | AutoFan | Write | 1-On,0-Off | ||
| BV | 2 | C_F_Scale | Write | 1-On (C) ,0-Off (F) | ||
| BV | 7 | One_TwoSetpoints | tech setting P99 | Write | (2 set points), (1 set point) | |
| BV | 8 | FilterAlarm | Read | 1-Alarm, 0-Normal | ||
| BV | 9 | FilterReset | tech setting P41 | Write | 1-Reset, 0-Normal | |
| BV | 10 | AutoModeEnable | tech setting P14 | Write | 1-Enable, 0-Disable | |
| BV | 11 | BackLightDimEnable | tech setting P100 | Write | 1-Enable, 0-Disable | |
| BV | 12 | BeeperEnable | tech setting P30 | Write | 1-Enable, 0-Disable | |
| BV | 13 | FreezeProtectionEnable | tech setting P35 | Write | 1-Enable, 0-Disable | |
| BV | 14 | WindowContact | Write | 1-Open, 0-Closed | ||
| BV | 15 | WindowContactPolarity | tech setting P10 | Write | 1-NC (Normally closes), 0- NO (Normally open) | |
| BV | 16 | UnoccupancyByPIR | Read | 1-Unoccupied, 0-Occupied | ||
| BV | 17 | UnoccupancyByAuxOccSensor | Read | 1-Unoccupied, 0-Occupied | ||
| BV | 18 | AuxOccupancySensorPolarity | tech setting P19 | Write | 1-NC (Normally closes), 0- NO (Normally open) | |
| BV | 19 | DoorSwitchOpen | Read | 1-Open, 0-Closed | ||
| BV | 20 | DoorSwitchPolarity | tech setting P12 | Write | 1-NC (Normally closes), 0- NO (Normally open) | |
| BV | 25 | RestoreDefault | tech setting P200 | Write | 1-On,0-Off | |
| BV | 24 | EmergencyHeat (in HC always Off) | AC systems only | Write | 1-On,0-Off | |
| BVmin | 28 | UnoccupiedByNetwork | Write | 1-Unoccupied, 0-Occupied | ||
| BV | 30 | DayProgramEnable | Write | 1-Disable, 0-Enable | ||
| BV | 36 | SetLock | Write | 1-On,0-Off | ||
| BV | 40 | EnableShowHumidityFromSettings | tech setting P187 | Write | 1-Enable, 0-Disable | |
| BV | 41 | SetAlarm | Write | 1-Show,0-Hide |
No points match these filters.
Integration notes
- MS/TP baud rates 9600, 19200, 38400 or 76800, 8N1.
- DIP switch configuration (AC vs FC system) decides which objects exist; some instances appear twice in the list with an AC name and an FC name.
- Mode, fan speed and similar enumerations are Analog Values carrying integer codes, not Multistate objects.
- The device instance itself can be changed by writing AV42 (BacnetDeviceInstanceNumber).
- Many writable AVs mirror the thermostat's technician (P) settings.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ComfortVu BACnet Thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier ComfortVu BACnet Thermostat
How many BACnet points does the Carrier ComfortVu BACnet Thermostat have?
This list has 165 BACnet objects: 2 analog inputs, 5 analog outputs, 105 analog values, 16 binary inputs, 13 binary outputs, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier ComfortVu BACnet Thermostat BACnet points are writable?
115 of the 165 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier ComfortVu BACnet Thermostat BACnet documentation?
The source is ComfortVu BACnet Thermostat Points List and Technician Settings (11-808-726-01), published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/06/11-808-726-01.pdf.
What are the minimum BACnet points to integrate the Carrier ComfortVu BACnet Thermostat?
Start with BV 0 OnOff (Turns the thermostat on or off); AV 4 Mode (Selects fan only, cool, heat or auto); BV 28 UnoccupiedByNetwork (Occupancy command; 1 = unoccupied, 0 = occupied); AV 0 SetPoint_SetPointCool (Cooling setpoint, 5-35 °C (41-95 °F)); AV 1 SetPointHeat (Heating setpoint, 5-35 °C (41-95 °F)); AV 6 FanSpeed (Fan auto/low/medium/high); AV 5 ModeEffective (Mode actually running); AV 13 OccupancyEffectiveHVAC (Resulting occupancy state); AV 3 ReturnAirSensorEffective (Temperature the thermostat controls to).
How do I enable BMS control of the Carrier ComfortVu BACnet Thermostat?
BV0 OnOff turns the thermostat on/off over the network. BI10 S1_8_UseBacnet shows whether the DIP switch has it set to BACnet (1) or Modbus (0).
How do I check these points on the real ComfortVu BACnet Thermostat?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: ComfortVu BACnet Thermostat Points List and Technician Settings · 11-808-726-01. Object names, instances and units are reproduced as published; descriptions are our own.