Applied rooftop unit controller · BACnet points list

Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet points list

Updated 28 October 2026

Short answer

The SmartVu touchscreen control with PIC 6.1 hardware runs Carrier's 48/50K and 48/50V applied rooftop units. It speaks BACnet MS/TP on port J8 or BACnet IP on either Ethernet port, plus CCN; Modbus is not offered for BAS use. Almost every object is an analog, binary or multistate value, grouped into setpoints, sensor readings, network inputs, unit states, outputs, runtimes and a large set of configuration and alert-limit values.

This page lists 715 BACnet objects for the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) — 393 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Equipment
Applied rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
715 (393 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Software 2.5.0 (versions before 2.4.0 may use different instances and names)
Also known as
SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T
Source document
SmartVu Controls Version 2.X for Applied Rooftop Integration Guide (Appendix A: BACnet and CCN Network Points) · 48-50-ART-SVU-1T · rev. 2025-03
Download CSV 715 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)

Integration in brief

On the SmartVu Controller Config screens (user password 1111) set Primary BAS Network to BACnet and BACnet Enable to MS/TP or BACnet IP, then reboot. Occupancy comes from BACnet schedule objects or the Network Occupancy point (AV 363); write the occupied setpoints directly and read unit states, temperatures and the alarm relay. Check the numeric codes of configuration AVs on the touchscreen before writing them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 363GENUNIT_NETOCCNetwork occupancy; Primary BAS Network must be BACnetWrite
AV 195COOLSTP_CLSP_OCCOccupied cooling setpointWrite
AV 313HEATSTP_HTSP_OCCOccupied heating setpointWrite
BV 1ALARMRST_RST_ALMAlarm reset commandWrite
MV 22STATES_IDFNUMIndoor fan state; 5 = runningRead
AV 289GENUNIT_OCCUPIEDConfirms occupied/unoccupiedRead
AV 7AIRTEMP_SPTSpace temperatureRead
AV 4AIRTEMP_SATSupply air temperatureRead
BV 83DISCOUT_ALMOUTCommon alarm relay outputRead

Enable & remote start

Primary BAS Network selects the network that drives occupancy; it must be BACnet to use the Network Occupancy point (GENUNIT_NETOCC, AV 363) when BACnet schedule objects are not used. The guide does not say what the 0-2 values of AV 363 mean (default 2). Occupancy Source (MV 26) shows where occupancy currently comes from.

Sensors & values from the BMS

The Network Inputs group has writable objects for BMS values, e.g. Net SPT (AV 360), Net OAT (AV 362), Net SPRH (AV 347), Net Indoor Air Quality (AV 357), Net Building Pressure (AV 352), and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them or give any refresh timeout.

Network setup

Watch out for

Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

715 of 715 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet Points List
DescriptionStates
AV3AIRPRESS_BPBuilding Pressure (BP)in. w.c.Read
AV15AIRTEMP_DXLATDirect Expansion LAT°FRead
AV14AIRTEMP_EFF_CPEffective Control Point°FRead
AV11AIRTEMP_EATExhaust Air Temp (EAT)°FRead
AV10AIRTEMP_MATMixed Air Temp (MAT)°FRead
AV120AIRTEMP_OADPOutside Air Dew Point°FRead
AV9AIRTEMP_OATOutside Air Temp (OAT)°FRead
AV1AIRPRESS_RAPReturn Air Pressurein. w.c.Read
AV6AIRTEMP_RATReturn Air Temp (RAT)°FRead
AVmin7AIRTEMP_SPTSpace Temp (SPT)°FRead
AV8AIRTEMP_SPTOSpace Temp Offset°FRead
AV13AIRTEMP_LATStaged Gas LAT°FRead
AV12AIRTEMP_LSTStaged Gas Limit Temp°FRead
AV123AIRTEMP_SADPSupply Air Dew Point°FRead
AVmin4AIRTEMP_SATSupply Air Temp (SAT)°FRead
AV5AIRTEMP_SATOSupply Air Temp Offset°FRead
AV2AIRPRESS_SDPSupply Pressure (SP)in. w.c.Read
BVmin1ALARMRST_RST_ALMAlarm ResetWrite1=NO; 2=YES
AV35ALERTCFG_BP_HLMTBP High Limit (default 0.1, 0 to 0.15)in. w.c.Write
AV34ALERTCFG_BP_LLMTBP Low Limit (default -0.1, -0.15 to 0)in. w.c.Write
AV74ALERTCFG_COFS_ACTCOFS Action (default 0)Write
AV76ALERTCFG_COFS_TMECOFS Time (default 5, 1 to 20)hWrite
AV75ALERTCFG_COFS_TRPCOFS Trips (default 5, 1 to 20)Write
AV60ALERTCFG_CP_C_THComp Cycling Threshold (default 200)minWrite
AV54ALERTCFG_CMPCMD_TCompressor Cmd Time (default 15, 1 to 30)sWrite
AV45ALERTCFG2_ERV_ALRTERV Frost Alert Limit (default 35, 25 to 40)°FWrite
AV59ALERTCFG_POSTFLFinal Filter Reminder (default 2880, 0 to 43200)Write
AV48ALERTCFG_HIGH_SSTHigh SST Time (default 10)minWrite
AV40ALERTCFG_IAQ_HLMTIAQ High Limit (default 1200, 0 to 5000)ppmWrite
BV4ALERTCFG_LOCK_OUTLockout NotificationWrite1=OFF; 2=ON
BV448LPALMENLow Power Alarm EnableWrite1=DISABLE; 2=ENABLE
AV575LPALMHYSLow Power Hysteresis (mS) (default 500, 0 to 2000)Write
AV72ALERTCFG_LPRLLow Press Ratio Limit (default 1.3, 1 to 2)psigWrite
AV65ALERTCFG_SSHALOWLow SSH A Alert (default 4, 2 to 10)°FWrite
AV67ALERTCFG_SSHAFLLOLow SSH A Full Load Alrt (default 4, 2 to 10)°FWrite
AV66ALERTCFG_SSHAPLLOLow SSH A Part Load Alrt (default 9, 7 to 15)°FWrite
AV71ALERTCFG_LSSHTIMELow SSH Alert Time (default 30, 5 to 120)sWrite
AV68ALERTCFG_SSHBLOWLow SSH B Alert (default 4, 2 to 10)°FWrite
AV70ALERTCFG_SSHBFLLOLow SSH B Full Load Alrt (default 4, 2 to 10)°FWrite
AV69ALERTCFG_SSHBPLLOLow SSH B Part Load Alrt (default 9, 7 to 15)°FWrite
AV63ALERTCFG_LSST1TLow SST 1Min Threshold (default 0, -30 to 40)°FWrite
AV64ALERTCFG_LSST20sTLow SST 20Sec Threshold (default -20, -30 to 40)°FWrite
AV62ALERTCFG_LSST2TLow SST 2Min Threshold (default 10, -30 to 40)°FWrite
AV61ALERTCFG_LSST4TLow SST 4Min Threshold (default 20, -30 to 40)°FWrite
AV50ALERTCFG_MINDISAMin Disc Chg Cir A (default 11, 0 to 99)psigWrite
AV52ALERTCFG_MINDISBMin Disc Chg Cir B (default 11, 0 to 99)psigWrite
AV49ALERTCFG_MINSUCAMin Suc Chg Cir A (default 20, 0 to 99)psigWrite
AV51ALERTCFG_MINSUCBMin Suc Chg Cir B (default 20, 0 to 99)psigWrite
AV56ALERTCFG_ECMINCFMOAD Min CFM (default 0)cfmWrite
AV39ALERTCFG_OAT_HLMTOAT High Limit (default 150)°FWrite
AV38ALERTCFG_OAT_LLMTOAT Low Limit (default -40)°FWrite
AV53ALERTCFG_OFF_PRESOff Press Ratio (default -0.2, -1 to 1)psigWrite
AV55ALERTCFG_OCFMSENSOutdoor Air CFM (default 0, 0 to 1)cfmWrite
AV41ALERTCFG_MAINFLTPre-Filter Change Time (default 2000, 168 to 8760)hWrite
AV31ALERTCFG_RARH_HTRARH High Limit (default 100, 0 to 100)%Write
AV30ALERTCFG_RARH_LTRARH Low Limit (default 0, 0 to 100)%Write
AV27ALERTCFG_RATHLMTORAT High Occu Limit (default 90, -40 to 245)°FWrite
AV28ALERTCFG_RATHLMTURAT High Unoc Limit (default 100, -40 to 245)°FWrite
AV26ALERTCFG_RATLLMTORAT Low Occu Limit (default 60, -40 to 245)°FWrite
AV29ALERTCFG_RATLLMTURAT Low Unoc Limit (default 40, -40 to 245)°FWrite
AV37ALERTCFG_SAT_HTMPSAT High Limit (default 130, 105 to 160)°FWrite
AV23ALERTCFG_SATHLMTOSAT High Occu Limit (default 130, 105 to 160)°FWrite
AV25ALERTCFG_SATHLMTUSAT High Unoc Limit (default 130, 105 to 160)°FWrite
AV36ALERTCFG_SAT_LTMPSAT Low Limit (default 45, 0 to 50)°FWrite
AV22ALERTCFG_SATLLMTOSAT Low Occu Limit (default 40, 0 to 45)°FWrite
AV24ALERTCFG_SATLLMTUSAT Low Unoc Limit (default 40, 0 to 45)°FWrite
AV33ALERTCFG_SP_HLMTSP High Limit (default 2, 1.5 to 2.2)in. w.c.Write
AV32ALERTCFG_SP_LLMTSP Low Limit (default 0.1, 0 to 0.5)in. w.c.Write
AV16ALERTCFG_SPRHHLSPRH High Limit (default 80, 0 to 100)%Write
AV17ALERTCFG_SPRHLLSPRH Low Limit (default 20, 0 to 100)%Write
AV19ALERTCFG_SPTHLMTOSPT High Occu Limit (default 85, -10 to 245)°FWrite
AV21ALERTCFG_SPTHLMTUSPT High Unoc Limit (default 100, -10 to 245)°FWrite
AV18ALERTCFG_SPTLLMTOSPT Low Occu Limit (default 60, -10 to 245)°FWrite
AV20ALERTCFG_SPTLLMTUSPT Low Unoc Limit (default 45, -10 to 245)°FWrite
AV86ALERTCFG_MSDPTStatic Duct Press Limit (default 3, 0 to 5)in. w.c.Write
BV5ALERTCFG_T24ENABT24 DiagnosticWrite1=DISABLE; 2=ENABLE
AV83ALERTCFG_T24ECMAXT24 Econ Max Pos (default 85, 50 to 100)%Write
AV82ALERTCFG_T24ECMINT24 Econ Min Pos (default 15, 0 to 50)%Write
AV84ALERTCFG_HCDELAYT24 Heat-Cool Delay (default 25, 0 to 60)minWrite
AV80ALERTCFG_MOVEDTECT24 Move Detect (default 1, 1 to 10)%Write
AV77ALERTCFG_OARADIFFT24 OA RA diff (default 15, 5 to 20)°FWrite
AV79ALERTCFG_SATCHNGET24 Sat Change (default 0.2, 0 to 5)°FWrite
AV78ALERTCFG_SATMOVET24 SAT Move Chk (default 10, 10 to 20)%Write
AV81ALERTCFG_SASETTLET24 SAT Settle (default 120, 5 to 450)sWrite
AV135ANALOGIN_ODF1SPDCF 1 SpeedHzRead
AV136ANALOGIN_ODF2SPDCF 2 SpeedHzRead
AV137ANALOGIN_ODF3SPDCF 3 SpeedHzRead
AV131ANALOGIN_CMPA1SPDComp A1 SpeedHzRead
AV132ANALOGIN_CMPA2SPDComp A2 SpeedHzRead
AV133ANALOGIN_CMPB1SPDComp B1 SpeedHzRead
AV134ANALOGIN_CMPB2SPDComp B2 SpeedHzRead
AV146ANALOGIN_DLCDemand Limit ControlRead
AV114ANALOGIN_EF3P_CMDEXF 3rd Party Modulation%Read
AV140ANALOGIN_EFSPDExhaust Fan Speed%Read
AV141ANALOGIN_EXV_A1EXV A1%Read
AV142ANALOGIN_EXV_A2EXV A2%Read
AV143ANALOGIN_EXV_B1EXV B1%Read
AV144ANALOGIN_EXV_B2EXV B2%Read
AV148ANALOGIN_FFPDFinal Filt Press Dropin. w.c.Read
AV130ANALOGIN_HMD2HGRH Valve 2 Feedback%Read
AV129ANALOGIN_HMDHGRH Valve Feedback%Read
AV116ANALOGIN_IAQOPRSTIAQ OAD Pos Reset%Read
AV115ANALOGIN_SF3P_CMDIDF 3rd Party Modulation%Read
AV138ANALOGIN_IDFSPDIDF Speed%Read
AV139ANALOGIN_IDFRPMIDF Speed RPMrpmRead
AV117ANALOGIN_IAQIndoor Air QualityppmRead
AV125ANALOGIN_MARHMixed Air RH (MARH)%Read
AV113ANALOGIN_OD3P_CMDOAD 3rd Party Modulation%Read
AV127ANALOGIN_DAMPPOSOAD Feedback%Read
AV111ANALOGIN_OACFMOutdoor Air CFMcfmRead
AV112ANALOGIN_OACFMRSTOutdoor Air CFM ResetcfmRead
AV149ANALOGIN_OA_ENTHOutdoor Air EnthalpyBTU/lbRead
AV118ANALOGIN_OAQOutdoor Air QualityppmRead
AV119ANALOGIN_OARHOutdoor Air RH (OARH)%Read
AV147ANALOGIN_PFPDPre Filt Press DropRead
AV128ANALOGIN_DAMPPOS2RAD Feedback%Read
AV150ANALOGIN_RA_ENTHReturn Air EnthalpyBTU/lbRead
AV121ANALOGIN_RARHReturn Air RH (RARH)%Read
AV124ANALOGIN_SPRHSpace RH (SPRH)%Read
AV145ANALOGIN_SPSRStatic Pressure Stpt Rstin. w.c.Read
AV122ANALOGIN_SARHSupply Air RH (SARH)%Read
AV126ANALOGIN_ZDPZone Damper Position%Read
AV94ANALGOUT_HEATCMDActual heat command%Read
AV104ANALGOUT_ODF1CMDCF 1 Command%Read
AV105ANALGOUT_ODF2CMDCF 2 Command%Read
AV106ANALGOUT_ODF3CMDCF 3 Command%Read
AV99ANALGOUT_CMPA1CMDComp A1 Command%Read
AV100ANALGOUT_CMPA2CMDComp A2 Command%Read
AV101ANALGOUT_CMPB1CMDComp B1 Command%Read
AV102ANALGOUT_CMPB2CMDComp B2 Command%Read
AV98ANALGOUT_ERV_OAFERV Outdoor Air Fan%Read
AV97ANALGOUT_EFCMDExhaust Fan Cmd%Read
AV107ANALGOUT_EXVA1CMDEXV A1 Cmd%Read
AV108ANALGOUT_EXVA2CMDEXV A2 Cmd%Read
AV109ANALGOUT_EXVB1CMDEXV B1 Cmd%Read
AV110ANALGOUT_EXVB2CMDEXV B2 Cmd%Read
AV96ANALGOUT_HMV2HGRH 2 Command%Read
AV95ANALGOUT_HMVHGRH Command%Read
AV103ANALGOUT_IDFCMDIDF1 Control Command%Read
AV92ANALGOUT_DAMPCMDOAD Command%Read
AV93ANALGOUT_DAMPCMD2RAD Cmd%Read
AV295BACNET_loc_occLocal Sched Occ RequestRead
MV27BACNET_ALC_COLOROperation Status ColorRead1=Gray; 2=Red; 3=DarkBlue; 4=LightBlue; 5=Green; 6=LightGreen; 7=Yellow; 8=Orange; 9=Red; 10=White; 13=Coral; 14=Charcoal; 15=Purple
AV294BACNET_SCH_ObjjSched Linked BACnet ObjRead
AV573BACNET_ALC_PRIMEValue of Prime variable°FRead
AV193COOLCFG_GAP_CLHTCool Heat Gap Config (default 5, 2 to 10)°FWrite
BV7COOLCFG_TMPDVNTCool Tempered VentingWrite1=DISABLE; 2=ENABLE
AV191COOLCFG_CLTRENDCool Trend Level (default 0.2, 0.1 to 5)°FWrite
AV192COOLCFG_CLTNDTMCool Trend Time (default 2, 1 to 5)minWrite
AV186COOLCFG_DEMANDCool/Heat Demand Source (default 3, 0 to 5)Write
AV483COOLCFG_SATHI_DBSAT High Deadband (default 5, 2.5 to 10)°FWrite
AV482COOLCFG_SATLO_DBSAT Lo Deadband (default 10, 5 to 15)°FWrite
AV190COOLCFG_RSTLMITSAT Reset Limit (default 10, 0 to 20)Write
AV189COOLCFG_RSTRTIOSAT Reset Ratio (default 3, 0 to 10)Write
AV188COOLCFG_TPCTLRSTSAT Reset Source (default 0, 0 to 5)Write
AV187COOLCFG_SPLYDBVent Deadband (default 15, 10 to 30)°FWrite
AV296COOLSTP_HODACLSP100% OA Cool SAT°FRead
AV200COOLSTP_HODAHCL100% OA High Cool SAT (default 70, 55 to 75)°FWrite
AV199COOLSTP_HODALCL100% OA Low Cool SAT (default 75, 55 to 75)°FWrite
AV224COOLSTP_CAPLIMS1Cool Capacity Limit S1 (default 50, 0 to 100)%Write
AV225COOLSTP_CAPLIMS2Cool Capacity Limit S2 (default 0, 0 to 100)%Write
AV233COOLSTP_DMDRSTCLDmd Reset Cool Adjust (default 4, 0 to 10)°FWrite
AV203COOLCFG_DOHICLONHi Cool On DB (default 1, 0.5 to 20)°FWrite
AV198COOLSTP_SAHICLSPHi Cool SAT (default 55, 55 to 75)°FWrite
AV202COOLCFG_DOLOCLOFLo Cool Off DB (default 1, 0.5 to 2)°FWrite
AV201COOLCFG_DOLOCLONLo Cool On DB (default 1, 0 to 2)°FWrite
AV197COOLSTP_SALOCLSPLo Cool SAT (default 65, 55 to 75)°FWrite
AVmin195COOLSTP_CLSP_OCCOccupied Cooling (default 73, 55 to 80)°FWrite
AV527COOLSTP_ACTV_SPSAT Setpt°FRead
AV196COOLSTP_CLSP_UNOUnoccupied Cooling (default 83, 55 to 110)°FWrite
AV206COOLCFG_DOVAVCOFVAV Cool Off DB (default 2, 1 to 25)°FWrite
AV205COOLCFG_DOVAVCONVAV Cool On DB (default 3.5, 0 to 25)°FWrite
AV204COOLSTP_VAVCLSPVAV Cooling SAT (default 55, 45 to 75)°FWrite
AV207COOLSTP_SPLYAVSPVent SAT (default 70, 55 to 85)°FWrite
AV218DHUMSTP_CCTSTPDehum CCT (default 55)°FWrite
AV484DHUMCFG_DHUMMODEDehum Control Mode (default 0, 0 to 3)Write
AV208DHUMCFG_DMD_SRCDehum Demand Source (default 3, 0 to 8)Write
AV215DHUMSTP_DHUMRHSPDehum RH (default 55, 40 to 100)%Write
AV217DHUMCFG_RLOS_OFFDehum RH Off DB (default 5, 1 to 20)%Write
AV216DHUMCFG_RLOS_ONDehum RH On DB (default 5, 0 to 20)%Write
AV302DHUMSTP_DHUMSADPDehum SADP°FRead
BV13DHUMCFG_DHUMHICLHigh Cool DehumWrite1=DISABLE; 2=ENABLE
BV15DHUMCFG_DHUMHIHTHigh Heat DehumWrite1=DISABLE; 2=ENABLE
BV14DHUMCFG_DHUMLOCLLow Cool DehumWrite1=DISABLE; 2=ENABLE
BV16DHUMCFG_DHUMLOHTLow Heat DehumWrite1=DISABLE; 2=ENABLE
BV18DHUMCFG_OFDHUMENOccupied Free DehumWrite1=DISABLE; 2=ENABLE
BV10DHUMCFG_SUPPHEATSupplemental HeatWrite1=DISABLE; 2=ENABLE
BV9DHUMCFG_UNOCENABUnoccupied DehumWrite1=DISABLE; 2=ENABLE
BV19DHUMCFG_UFDHUMENUnoccupied Free DehumWrite1=DISABLE; 2=ENABLE
BV12DHUMCFG_DHUMVAVVAV Cool DehumWrite1=DISABLE; 2=ENABLE
BV11DHUMCFG_DHUMVENTVent/None DehumWrite1=DISABLE; 2=ENABLE
AV152COMMADDR_AUX1AUXRead
AV159COMMADDR_COMP_A1Compressor A1Read
AV153COMMADDR_NGC1NGC IOB 1Read
AV166COMMADDR_ODF_1ODF 1Read
AV167COMMADDR_ODF_2ODF 2Read
AV168COMMADDR_ODF_3ODF 3Read
AV154COMMADDR_PD4_EXV1PD4 EXVRead
AV171COMMADDR_PWREXH_1Power Exhaust 1Read
AV172COMMADDR_PWREXH_2Power Exhaust 2Read
AV169COMMADDR_RF_1Return Fan 1Read
AV170COMMADDR_RF_2Return Fan 2Read
AV155COMMADDR_SIOB1SIOB 1Read
AV156COMMADDR_SIOB2SIOB 2Read
AV157COMMADDR_SIOB3SIOB 3Read
AV160COMMADDR_IDF_1Supply Fan 1Read
AV161COMMADDR_IDF_2Supply Fan 2Read
AV162COMMADDR_IDF_3Supply Fan 3Read
AV163COMMADDR_IDF_4Supply Fan 4Read
AV164COMMADDR_IDF_5Supply Fan 5Read
AV165COMMADDR_IDF_6Supply Fan 6Read
AV158COMMADDR_SYSTEMVUZIOBRead
BV39DISCIN_HPSACir A HPS SwitchRead1=OPEN; 2=CLOSE
BV40DISCIN_HPSBCir B HPS SwitchRead1=OPEN; 2=CLOSE
BV33DISCIN_CNDOSWCOFSRead1=OPEN; 2=CLOSE
BV35DISCIN_CMPFBKA1Comp A1 FeedbackRead1=OFF; 2=ON
BV36DISCIN_CMPFBKA2Comp A2 FeedbackRead1=OFF; 2=ON
BV37DISCIN_CMPFBKB1Comp B1 FeedbackRead1=OFF; 2=ON
BV38DISCIN_CMPFBKB2Comp B2 FeedbackRead1=OFF; 2=ON
BV34DISCIN_DEHUMSWDehumidify SwitchRead1=OPEN; 2=CLOSE
BV45DISCIN_DLS1DemandLimSwitch1Read1=OFF; 2=ON
BV46DISCIN_DLS2DemandLimSwitch2Read1=OFF; 2=ON
BV42DISCIN_ERV_FRSTERV Frost IndicatorRead1=OFF; 2=ON
BV43DISCIN_WHEEL_STERV Motion SensorRead1=OFF; 2=ON
BV44DISCIN_ERVFSSERV OD Filt Stat SwitchRead1=OFF; 2=ON
BV30DISCIN_FILTSTATFilter SwitchRead1=CLEAN; 2=DIRTY
BV49DISCIN_PRESSSWFire Press SwitchRead1=OFF; 2=ON
BV25DISCIN_FIRESWFire Shutdown SwitchRead1=OPEN; 2=CLOSE
BV32DISCIN_HT_ALARMHeat AlarmRead1=OPEN; 2=CLOSE
BV22DISCIN_TSTAT_Y2Hi Cool Input (Y2)Read1=OPEN; 2=CLOSE
BV24DISCIN_TSTAT_W2Hi Heat Input (W2)Read1=OPEN; 2=CLOSE
BV51DISCIN_FRZSWHydronic Freeze SwitchRead1=OFF; 2=ON
BV53DISCIN_IAQSWIAQ SwitchRead1=OFF; 2=ON
BV47DISCIN_IGCFANSWIGC IDF SwitchRead1=OFF; 2=ON
BV20DISCIN_TSTAT_GIndoor Fan Input (G)Read1=OPEN; 2=CLOSE
BV31DISCIN_IDF_LSMIndoor Fan Limit SwitchRead1=OPEN; 2=CLOSE
BV58DISCIN_INRFGLKIndoor RFG Sensor ALMRead1=NORMAL; 2=ALARM
BV21DISCIN_TSTAT_Y1Lo Cool Input (Y1)Read1=OPEN; 2=CLOSE
BV23DISCIN_TSTAT_W1Lo Heat Input (W1)Read1=OPEN; 2=CLOSE
BV56DISCIN_ENEGPRESOAD Neg PressureRead1=OFF; 2=ON
BV54DISCIN_OAQSWOAQ SwitchRead1=OFF; 2=ON
BV55DISCIN_ODENTHSWOutdoor EnthalpyRead1=OFF; 2=ON
BV59DISCIN_OUTRFGLKOutdoor RFG Sensor ALMRead1=NORMAL; 2=ALARM
BV28DISCIN_PMR_STATPhase MonitorRead1=OPEN; 2=CLOSE
BV48DISCIN_PFPSSPre Filter SwitchRead1=OFF; 2=ON
BV52DISCIN_PPSSPressure SafetyRead1=OFF; 2=ON
BV41DISCIN_RESWRemote SwitchRead1=OPEN; 2=CLOSE
BV29DISCIN_SHTDWNSWShutdown SwitchRead1=OFF; 2=ON
BV26DISCIN_SMOKESWSmoke DetectorRead1=OPEN; 2=CLOSE
BV50DISCIN_EVACSWSmoke Evac SwitchRead1=OFF; 2=ON
BV27DISCIN_SMKPRGSWSmoke Purge SwitchRead1=OPEN; 2=CLOSE
BV57DISCIN_VSOLSWAVS Oil Level Switch ARead1=OFF; 2=ON
BV73DISCOUT_RH3PRLY3rd Party Reheat RelayRead1=OFF; 2=ON
BVmin83DISCOUT_ALMOUTAlarmRead1=OFF; 2=ON
BV70DISCOUT_CCHRACCH ARead1=OFF; 2=ON
BV71DISCOUT_CCHRBCCH BRead1=OFF; 2=ON
BV67DISCOUT_ODF1CF 1 RelayRead1=OFF; 2=ON
BV68DISCOUT_ODF2CF 2 RelayRead1=OFF; 2=ON
BV69DISCOUT_ODF3CF 3 RelayRead1=OFF; 2=ON
BV61DISCOUT_CMPRELA1Comp A1 Modulation RLYRead1=OPEN; 2=CLOSE
BV63DISCOUT_CMPRELA2Comp A2 Modulation RLYRead1=OPEN; 2=CLOSE
BV60DISCOUT_CPA1Compressor A1Read1=OFF; 2=ON
BV62DISCOUT_CPA2Compressor A2Read1=OFF; 2=ON
BV64DISCOUT_CPB1Compressor B1Read1=OFF; 2=ON
BV65DISCOUT_CPB2Compressor B2Read1=OFF; 2=ON
BV81DISCOUT_BYP_DAMPERV Bypass DamperRead1=OFF; 2=ON
BV74DISCOUT_ERVWHEELERV WheelRead1=OFF; 2=ON
BV90DISCOUT_AUTOADDRFan Auto AddressRead1=OFF; 2=ON
BV75DISCOUT_STGHEAT1Heat Enable 1Read1=OFF; 2=ON
BV76DISCOUT_STGHEAT2Heat Enable 2Read1=OFF; 2=ON
BV77DISCOUT_STGHEAT3Heat Enable 3Read1=OFF; 2=ON
BV78DISCOUT_STGHEAT4Heat Enable 4Read1=OFF; 2=ON
BV79DISCOUT_STGHEAT5Heat Enable 5Read1=OFF; 2=ON
BV80DISCOUT_STGHEAT6Heat Enable 6Read1=OFF; 2=ON
BV84DISCOUT_HIRHeat Interlock RelayRead1=OFF; 2=ON
BV86DISCOUT_HRRHeat ReclaimRead1=OFF; 2=ON
BV85DISCOUT_HMFRHumidifierRead1=OFF; 2=ON
BV66DISCOUT_IDFBYRELIDF VFD Bypass RelayRead1=OFF; 2=ON
BV87DISCOUT_PEAPower Exh ARead1=OFF; 2=ON
BV88DISCOUT_PEBPower Exh BRead1=OFF; 2=ON
BV89DISCOUT_PECPower Exh CRead1=OFF; 2=ON
AV219DISCOUT_POWEXH1Power Exhaust EnableRead
BV72DISCOUT_HMSReheat 3-way valveRead1=OFF; 2=ON
BV445DISCOUT_VSCA1_SSVSC A1 Safe StopRead1=OFF; 2=ON
BV82DISCOUT_ZDORZone Damper Override RLYRead1=OFF; 2=ON
AV260ERVCFG_CHKTYPEERV Check Type (default 0, 0 to 2)Write
AV262ERVCFG_ENTTOLERV Enthalpy Tolerance (default 2, 0 to 2)BTU/lbWrite
AV265ERVCFG_ERVMINPSERV Fan Damper Min Pos (default 10, 0 to 100)%Write
AV264ERVCFG_MAXBYPCLERV Fan Max Bypass Close (default 100, 0 to 100)%Write
AV263ERVCFG_MAXBYPOPERV Fan Max Bypass Open (default 100, 0 to 100)%Write
AV269ERVCFG_OFFENTDBERV Off Enthalpy DB (default 0.5, 0 to 2)BTU/lbWrite
AV268ERVCFG_OFFTMPDBERV Off Temp DB (default 5, 0 to 10)Δ°FWrite
AV261ERVCFG_TMPTOLERV Temp Tolerance (default 10, 0 to 20)Δ°FWrite
AV267ERVCFG_ERVEFMINERV Wheel Exh Min Speed (default 0, 0 to 100)%Write
AV266ERVCFG_WHMINPOSERV Wheel-Minimum Pos (default 10, 0 to 100)%Write
BV108EQUIPCFG_RH3PEN3rd Party Reheat EnableWrite1=DISABLE; 2=ENABLE
BV101EQUIPCFG_ALARMENAlarm OutputWrite1=DISABLE; 2=ENABLE
AV256EQUIPCFG_AUXRELAYAux Relay (default 0, 0 to 2)Write
BV123EQUIPCFG_CONDENCOFSWrite1=DISABLE; 2=ENABLE
BV122EQUIPCFG_DMDRSTENDemand Reset SwitchWrite1=DISABLE; 2=ENABLE
BV93EQUIPCFG_DMDLIMDemand/Capacity Anlg InWrite1=DISABLE; 2=ENABLE
BV102EQUIPCFG_EATENEAT SensorWrite1=DISABLE; 2=ENABLE
BV117EQUIPCFG_ECONENEconomizer (OAD)Write1=DISABLE; 2=ENABLE
BV99EQUIPCFG_SHTDWNENEmergency Shutdown EnWrite1=DISABLE; 2=ENABLE
BV124EQUIPCFG_ENTHSWENEnthalpy SwitchWrite1=DISABLE; 2=ENABLE
BV110EQUIPCFG_ERVENERVWrite1=DISABLE; 2=ENABLE
BV112EQUIPCFG_ERVBYPENERV Bypass DamperWrite1=DISABLE; 2=ENABLE
BV111EQUIPCFG_ERVOAFENERV OAFWrite1=DISABLE; 2=ENABLE
BV114EQUIPCFG_EVACENEvacuation SwitchWrite1=DISABLE; 2=ENABLE
BV107EQUIPCFG_EF3PENEXF 3rd Party ModWrite1=DISABLE; 2=ENABLE
BV116EQUIPCFG_EFENExhaust FanWrite1=DISABLE; 2=ENABLE
BV113EQUIPCFG_FIRESWENFire SwitchWrite1=DISABLE; 2=ENABLE
AV303EQUIPCFG_FRZSWENFreeze SwitchRead
BV118EQUIPCFG_HT1ENHeat Stage 1 RelayWrite1=DISABLE; 2=ENABLE
BV119EQUIPCFG_HT2ENHeat Stage 2 RelayWrite1=DISABLE; 2=ENABLE
BV120EQUIPCFG_HT3ENHeat Stage 3 RelayWrite1=DISABLE; 2=ENABLE
BV121EQUIPCFG_HT4ENHeat Stage 4 RelayWrite1=DISABLE; 2=ENABLE
BV96EQUIPCFG_HUMSWENHumidistatWrite1=DISABLE; 2=ENABLE
BV127EQUIPCFG_IAQSWENIAQ SwitchWrite1=DISABLE; 2=ENABLE
AV257EQUIPCFG_SIO1AI10IAQ/OAD Input Config (default 0, 0 to 5)Write
BV125EQUIPCFG_IAQORENIAQ-OD Pos Reset EnableWrite1=DISABLE; 2=ENABLE
BV105EQUIPCFG_SF3PENIDF 3rd Party ModWrite1=DISABLE; 2=ENABLE
BV104EQUIPCFG_IDFVFDBYIDF VFD BypassWrite1=DISABLE; 2=ENABLE
BV103EQUIPCFG_OACFMENOACFM SensorWrite1=DISABLE; 2=ENABLE
BV109EQUIPCFG_OAD3PENOAD 3rd Party ModWrite1=DISABLE; 2=ENABLE
BV126EQUIPCFG_OAQSWENOAQ SwitchWrite1=DISABLE; 2=ENABLE
BV98EQUIPCFG_PMRENPhase MonitorWrite1=DISABLE; 2=ENABLE
BV97EQUIPCFG_FILTSWENPre-Filter SwitchWrite1=DISABLE; 2=ENABLE
BV115EQUIPCFG_PRESSENPressurization SwitchWrite1=DISABLE; 2=ENABLE
AV255EQUIPCFG_RESWENRemote Input (default 0, 0 to 2)Write
AV574EQUIPCFG_SIO3DI7Select IAQ or OAQ Switch (default 0, 0 to 2)Write
BV94EQUIPCFG_SMOKEENSmoke DetectorWrite1=DISABLE; 2=ENABLE
BV106EQUIPCFG_SPSRENSPSR SensorWrite1=DISABLE; 2=ENABLE
BV95EQUIPCFG_TSTATENThermostatWrite1=DISABLE; 2=ENABLE
BV100EQUIPCFG_ZDORENZDORWrite1=DISABLE; 2=ENABLE
AV235EFCFG_CONTROLEXF Control Config (default 0, 0 to 3)Write
AV249EFCFG_EXFEVACEXF Evacuation Speed (default 0, 0 to 100)%Write
AV237EFCFG_MAXSPDEXF Max Speed (default 50, 20 to 100)%Write
AV236EFCFG_MINSPDEXF Min Speed (default 10, 0 to 100)%Write
AV240EFCFG_DAMPPOS1EXF OAD Pos 1 (default 50, 0 to 100)%Write
AV241EFCFG_DAMPPOS2EXF OAD Pos 2 (default 100, 0 to 100)%Write
AV242EFCFG_PEOAD1EXF OAD Position 1 (default 25, 0 to 100)%Write
AV243EFCFG_PEOAD2EXF OAD Position 2 (default 50, 0 to 100)%Write
AV244EFCFG_PEOAD3EXF OAD Position 3 (default 75, 0 to 100)%Write
AV245EFCFG_PEOAD4EXF OAD Position 4 (default 100, 0 to 100)%Write
AV246EFCFG_PEOAD5EXF OAD Position 5 (default 100, 0 to 100)%Write
AV247EFCFG_PEOAD6EXF OAD Position 6 (default 100, 0 to 100)%Write
AV248EFCFG_EXFPURGEEXF Smoke Purge Speed (default 0, 0 to 100)%Write
AV238EFCFG_SPEED1EXF Speed OAD Pos 1 (default 25, 0 to 100)%Write
AV239EFCFG_SPEED2EXF Speed OAD Pos 2 (default 50, 0 to 100)%Write
AV85EFCFG_RAP_THRet Air Press Threshold (default -0.4, -1 to 1)in. w.c.Write
AV250EFSTP_EFBPSPTBuilding Pressure (default 0.05, -0.3 to 0.3)in. w.c.Write
AV278FRECLCFG_CHNGSELChangeover Select (default 0, 0 to 3)Write
AV282FRECLCFG_DIFFDBTHDiff Dry Bulb Threshold (default 0, 0 to 10)°FWrite
AV279FRECLCFG_DIFFENTHDiff Enthalpy Threshold (default 0.5, 0 to 2)BTU/lbWrite
BV132FRECLCFG_DRYBLBDry Bulb Chngeover (OAT)Write1=DISABLE; 2=ENABLE
AV473FRECLCFG_FCOOL_TGFree Cool Timeguard (default 5, 0 to 30)minWrite
AV283FRECLCFG_IAQOADRSIAQ Switch OAD Pos Reset (default -10, -100 to 0)%Write
BV133FRECLCFG_DEWLIMOADP Limit CheckWrite1=DISABLE; 2=ENABLE
AV281FRECLCFG_DEWLIMTHOADP Threshold (default 55, 50 to 62)°FWrite
BV147FRECLCFG_ODAIRQOAQ CheckWrite1=DISABLE; 2=ENABLE
AV395FRECLCFG_ODAIRQTHOAQ Lockout (default 1300, 1000 to 2000)ppmWrite
AV280FRECLCFG_DRYBLBTHOAT Dry Bulb Threshold (default 75, -40 to 120)°FWrite
BV130FRECLCFG_FREECLENOcc Free CoolWrite1=DISABLE; 2=ENABLE
BV131FRECLCFG_UFCUnocc Free CoolingWrite1=DISABLE; 2=ENABLE
AV309HEATCFG_HT2DTGHeat 2Stage Dn Timeguard (default 120, 30 to 300)sWrite
AV310HEATCFG_HT2UTGHeat 2Stage Up Timeguard (default 120, 30 to 300)sWrite
AV312HEATCFG_HEAT_FODHeat Fan Off Delay Timer (default 45, 30 to 120)sWrite
BV135HEATCFG_HTTEMPCLHeat Tempered CoolingWrite1=DISABLE; 2=ENABLE
AV306HEATCFG_HEATTTDBHeat Tempered Cooling DB (default 0)Write
BV134HEATCFG_HTMPDVNTHeat Tempered VentingWrite1=DISABLE; 2=ENABLE
AV307HEATCFG_HTTRENDHeat Trend Level (default 0.1, 0.1 to 5)°FWrite
AV308HEATCFG_HTTNDTMHeat Trend Time (default 120, 30 to 600)sWrite
BV137HEATCFG_HEAT_EBLMorning Warmup OnlyWrite1=DISABLE; 2=ENABLE
AV318HEATSTP_HODAHHT100% OA High Heat SAT (default 85, 65 to 125)°FWrite
AV317HEATSTP_HODALHT100% OA Low Heat SAT (default 75, 65 to 125)°FWrite
AV321HEATCFG_DOHIHTONHi Heat On DB (default 1, 0.5 to 20)°FWrite
AV316HEATSTP_SAHIHTSPHi Heat SAT (default 95, 60 to 125)°FWrite
AV320HEATCFG_DOLOHTOFLo Heat Off DB (default 1, 0.5 to 2)°FWrite
AV319HEATCFG_DOLOHTONLo Heat On DB (default 1, 0 to 2)°FWrite
AV315HEATSTP_SALOHTSPLo Heat SAT (default 85, 60 to 125)°FWrite
AVmin313HEATSTP_HTSP_OCCOccupied Heating (default 68, 55 to 80)°FWrite
AV314HEATSTP_HTSP_UNOUnoccupied Heating (default 58, 40 to 99)°FWrite
AV328IDFCFG_IDFCSPD2Hi Cool IDF Speed (default 100, 0 to 100)%Write
AV333IDFCFG_IDFHSPD2Hi Heat IDF Speed (default 100, 0 to 100)%Write
AV322IDFCFG_OPSELECTIDF Control (default 1, 0 to 8)Write
AV336IDFCFG_IDFEVACIDF Evacuation Speed (default 34, 0 to 100)%Write
AV335IDFCFG_IDFPRESSIDF Pressurization Speed (default 34, 0 to 100)%Write
AV334IDFCFG_IDFPURGEIDF PURGE Speed (default 34, 0 to 100)%Write
AV325IDFCFG_IDFMXSPDIndoor Fan Max Speed (default 100, 0 to 100)%Write
AV324IDFCFG_IDFMNSPDIndoor Fan Min Speed (default 34, 0 to 100)%Write
AV326IDFCFG_IDFCSPD1Lo Cool IDF Speed (default 66, 0 to 100)%Write
AV332IDFCFG_IDFHSPD1Lo Heat IDF Speed (default 66, 0 to 100)%Write
AV327IDFCFG_IDFMCSPDMed Cool IDF Speed (default 88, 0 to 100)%Write
AV337IDFCFG_OCCUCFGOccupied Fan (default 0, 0 to 1)Write
AV331IDFCFG_SAVHCCTHSAV High Cool Cap Thresh (default 90, 0 to 100)%Write
AV329IDFCFG_SAVLCCTHSAV Low Cool Cap Thresh (default 70, 0 to 100)%Write
AV330IDFCFG_SAVMCCTHSAV Med Cool Cap Thresh (default 75, 0 to 100)%Write
AV323IDFCFG_SAVTYPESAV Mode Selection (default 0, 0 to 1)Write
AV341IDFCFG_SDPRTIMESDP Reset Time (default 15, 5 to 30)minWrite
AV342IDFCFG_SDPRZDPSDP Reset ZDP Threshold (default 85, 40 to 100)%Write
AV288IDFCFG_SDPRLMITSP Reset Limitin. w.c.Read
AV340IDFCFG_SDPRRTIOSP Reset Ratio (default 0.2, 0 to 3)in. w.c.Write
AV339IDFCFG_SDPRSSP Reset Source (default 0, 0 to 5)Write
AV338IDFCFG_UNOCCFGUnoccupied Fan (default 0, 0 to 1)Write
AV345IDFSTP_AIRFLOWAir Flow Setpoint (default 1200, 0 to 50000)cfmWrite
AV343IDFSTP_CO2LVLCO2 Level (default 2000, 0 to 2000)ppmWrite
AV344IDFSTP_DUCTSETSupply Pressure (default 1.5, 0 to 2.5)in. w.c.Write
AV287IDFSTP_ZPSETPTZone Pressurein. w.c.Read
AV221DMDLMCFG_AICLSELAnalog Limit Mode (default 0, 0 to 2)Write
AV305DMDLMCFG_DMDCPENCapacity Limit EnableRead
AV222DMDLMCFG_CAPLMSRCCapacity Limit Source (default 0, 0 to 3)Write
AV226COOLSTP_DMDLIMS1Cool Demand Limit S1 (default 4, 0 to 10)Δ°FWrite
AV227COOLSTP_DMDLIMS2Cool Demand Limit S2 (default 6, 0 to 10)Δ°FWrite
AV304DMDLMCFG_DMDLMENDemand Limit EnableRead
AV220DMDLMCFG_DMDLMSRCDemand Limit Source (default 0, 0 to 3)Write
BV91DMDLMCFG_DLSWSENDemand Switch EnableWrite1=DISABLE; 2=ENABLE
AV234HEATSTP_DMDRSTHTDmd Reset Heat Adjust (default 4, 0 to 10)°FWrite
AV229HEATSTP_CAPLIMS1Heat Capacity Limit S1 (default 50, 0 to 100)%Write
AV230HEATSTP_CAPLIMS2Heat Capacity Limit S2 (default 0, 0 to 100)%Write
AV231HEATSTP_DMDLIMS1Heat Demand Limit S1 (default 4, 0 to 10)Δ°FWrite
AV232HEATSTP_DMDLIMS2Heat Demand Limit S2 (default 6, 0 to 10)Δ°FWrite
AV223COOLSTP_CLCAPSTPMax Cool Capacity (default 100, 50 to 100)%Write
AV228HEATSTP_HTCAPSTPMax Heat Capacity (default 100, 50 to 100)%Write
MV7MDESTS_ODF1MDNCF 1 ModeRead1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH
MV8MDESTS_ODF2MDNCF 2 ModeRead1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH
MV9MDESTS_ODF3MDNCF 3 ModeRead1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH
MV1MDESTS_CIRCAMDNCircuit A ModeRead1=NORMAL; 2=TEST
MV2MDESTS_CIRCBMDNCircuit B ModeRead1=NORMAL; 2=TEST
MV3MDESTS_CMPA1MDNComp A1 ModeRead1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF
MV4MDESTS_CMPA2MDNComp A2 ModeRead1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF
MV5MDESTS_CMPB1MDNComp B1 ModeRead1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF
MV6MDESTS_CMPB2MDNComp B2 ModeRead1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF
AV290MDESTS_DMD_DETDemand DeterminationRead
BV138MDESTS_ERVCHECKERV Check StatusRead1=FALSE; 2=TRUE
MV11MDESTS_HEATRMDNHeater ModeRead1=NONE; 2=SAT; 3=RAT; 4=ZONE; 5=MAT; 6=EXTERNAL, MANUAL; 7=SAT; 8=RAT; 9=ZONE; 10=MAT; 11=EXTERNAL, MANUAL
MV10MDESTS_IDFMDNUMIndoor Fan ModeRead1=NONE; 2=MANUAL; 3=SDP_NOM; 4=SDP_HIGH; 5=SDP_LOW; 6=CO2_NOM; 7=CO2_LOW; 8=CTLFLUID; 9=SST_LOW; 10=ST_LOW; 11=FLOW_NOM; 12=BP_NOM; 13=BP_HIGH, BP_LOW, TRACK, ON
MV12MDESTS_ECONMNUMOAD ModeRead1=NONE; 2=MANUAL; 3=AMB_FLOW; 4=MNAIRQLY; 5=NOM_TRAC; 6=SAT; 7=IAQ_OVR; 8=AMBFLWSW
AV291MDESTS_OP_STATEOperational StateRead
BV139MDESTS_DHUMPURGReheat Oil PurgeRead1=OFF; 2=ON
BV177MDESTS_MODETCSTTemp Compensated StartRead1=OFF; 2=ON
AV353ANALOGIN_EF3P_NETNet 3rd Party EXF (default 0)%Write
AV355ANALOGIN_SF3P_NETNet 3rd Party IDF (default 0)%Write
AV354ANALOGIN_OD3P_NETNet 3rd Party OAD (default 0)%Write
AV352AIRPRESS_BPNETNet Building Pressure (default 0)in. w.c.Write
AV351ANALOGIN_IAQORNETNet IAQ OAD Pos Reset (default 0)%Write
AV358ANALOGIN_IAQRNETNet IAQ Reset (default 0)ppmWrite
AV357ANALOGIN_IAQNETNet Indoor Air Quality (default 0)ppmWrite
AV350ANALOGIN_OCFMRNETNet OA CFM Reset (default 0)cfmWrite
AV362AIRTEMP_OATNETNet OAT (default 0)°FWrite
AV349ANALOGIN_OACFMNETNet Outdoor Air CFM (default 0)cfmWrite
AV356ANALOGIN_OAQNETNet Outdoor Air Quality (default 0)ppmWrite
AV348ANALOGIN_RARHNETNet RARH (default 0)%Write
AV364ANALOGIN_SPSR_NETNet SP Reset (default 0, 0 to 5)in. w.c.Write
AV361AIRTEMP_SPTONETNet Space Temp Offset (default 0)°FWrite
AV347ANALOGIN_SPRHNETNet SPRH (default 0)%Write
AV360AIRTEMP_SPTNETNet SPT (default 0)°FWrite
AV365ANALOGIN_ZDPNETNet Zone Damper Position (default 0)%Write
BV145NETIN_G_NETNetwork GWrite1=OFF; 2=ON
BV146NETIN_HSTATNETNetwork HSTATWrite1=OFF; 2=ON
AV359AIRPRESS_SDP_NETNetwork Supply Pressure (default 0)in. w.c.Write
BV143NETIN_W1_NETNetwork W1Write1=OFF; 2=ON
BV144NETIN_W2_NETNetwork W2Write1=OFF; 2=ON
BV141NETIN_Y1_NETNetwork Y1Write1=OFF; 2=ON
BV142NETIN_Y2_NETNetwork Y2Write1=OFF; 2=ON
AV398OADCFG_OABPORDBBld Pressure Deadband (default 0.01, 0 to 0.05)in. w.c.Write
AV396OADCFG_OABPORENBld Pressure Override En (default 0, 0 to 1)Write
AV397OADCFG_OABPORTHBld Pressure Threshold (default 0.02, 0 to 0.2)in. w.c.Write
AV392OADCFG_IAQCFMRSIAQ OA CFM Reset (default 0, -40000 to 0)cfmWrite
AV369OADCFG_IAQOCFGIAQ Override Conf (default 0, 0 to 2)Write
AV384OADCFG_IAQODBIAQ Override Deadband (default 200, 100 to 1000)ppmWrite
AV385OADCFG_IAQOPOSIAQ Override Position (default 50, 0 to 100)%Write
AV383OADCFG_IAQOTHIAQ Override Threshold (default 1200, 400 to 2000)ppmWrite
BV149OADCFG_IAQPOPIAQ Pre-Occ PurgeWrite1=DISABLE; 2=ENABLE
AV386OADCFG_IAQPDURIAQ Purge Duration (default 15, 5 to 60)minWrite
AV391OADCFG_IAQPHITPIAQ Purge Hi Temp Pos (default 35, 0 to 100)%Write
AV390OADCFG_IAQPLOTPIAQ Purge Lo Temp Pos (default 10, 0 to 100)%Write
AV387OADCFG_IAQPLOCKIAQ Purge Lockout (default 50, 35 to 70)°FWrite
AV389OADCFG_IAQPRGHLIAQ Purge OAT Hi Lockout (default 95, 85 to 115)°FWrite
AV388OADCFG_IAQPRGLLIAQ Purge OAT Lo Lockout (default 45, 0 to 50)°FWrite
AV382OADCFG_IAQRESETIAQ Reset Source (default 0, 0 to 3)Write
BV148OADCFG_IAQSBVENIAQ Vent Standby DemandWrite1=DISABLE; 2=ENABLE
AV374IDFCFG_VENTSPD1IDF Vent Speed 1 (default 66, 0 to 100)%Write
AV375IDFCFG_VENTSPD2IDF Vent Speed 2 (default 70, 0 to 100)%Write
AV376IDFCFG_VENTSPD3IDF Vent Speed 3 (default 80, 0 to 100)%Write
AV377IDFCFG_VENTSPD4IDF Vent Speed 4 (default 100, 0 to 100)%Write
AV372OADCFG_MINOADCPMin OAD Control Point (default 75, 0 to 100)%Write
AV378OADCFG_OADPOS1OA Damper Vent Pos 1 (default 60, 0 to 100)%Write
AV379OADCFG_OADPOS2OA Damper Vent Pos 2 (default 38, 0 to 100)%Write
AV380OADCFG_OADPOS3OA Damper Vent Pos 3 (default 30, 0 to 100)%Write
AV381OADCFG_OADPOS4OA Damper Vent Pos 4 (default 0, 0 to 100)%Write
BV17OADCFG_OADHUMENOA Dehum EnableWrite1=DISABLE; 2=ENABLE
AV399OADCFG_CFMSPOACFM Setpoint (default 780, 0 to 20000)cfmWrite
AV57OADCFG_FLTGAPOAD Fault Detect Gap (default 5, 2 to 100)%Write
AV58OADCFG_FLTTIMEOAD Fault Detect Time (default 20, 10 to 240)sWrite
AV371OADCFG_MAXPOSOAD Max Position (default 100, 0 to 100)%Write
AV370OADCFG_MINPOSOAD Min Position (default 10, 0 to 100)%Write
AV373OADCFG_OADEVACOAD Smoke Evac Speed (default 0, 0 to 100)%Write
AV394OADCFG_PRGLONGPurge Long Duration (default 60, 10 to 60)minWrite
AV393OADCFG_PRGSHORTPurge Short Duration (default 20, 5 to 30)minWrite
AV368OADCFG_ECONCTRLVentilation Control (default 0, 0 to 5)Write
BV207UNITCFG_AUTRSTAuto RestartWrite1=OFF; 2=ON
AV259UNITCFG_OCC_OTOccupancy Override Time (default 2, 0 to 4)hWrite
BV179OCCSBOccupied StandbyRead1=DISABLE; 2=ENABLE
BV92OCCSB_ENOccupied Standby EnableWrite1=DISABLE; 2=ENABLE
AV366OCCSBNETOccupied Standby Net (default 0)Write
AV258OCCSTNDTOccupied Standby Time (default 5, 5 to 30)minWrite
AV367ZS_OCCSBOccupied Standby ZS (default 0)Write
AV453RUNTIME_CCHRA_RTCCH A MinutesRead
AV455RUNTIME_CCHRA_RCCCH A Reset CountRead
AV454RUNTIME_CCHRA_SCCCH A Start CountRead
AV456RUNTIME_CCHRB_RTCCH B MinutesRead
AV458RUNTIME_CCHRB_RCCCH B Reset CountRead
AV457RUNTIME_CCHRB_SCCCH B Start CountRead
AV429RUNTIME_CND1_RTCF 1 MinutesRead
AV431RUNTIME_CND1_RCCF 1 Reset CountRead
AV430RUNTIME_CND1_SCCF 1 Start CountRead
AV432RUNTIME_CND2_RTCF 2 MinutesRead
AV434RUNTIME_CND2_RCCF 2 Reset CountRead
AV433RUNTIME_CND2_SCCF 2 Start CountRead
AV435RUNTIME_CND3_RTCF 3 MinutesRead
AV437RUNTIME_CND3_RCCF 3 Reset CountRead
AV436RUNTIME_CND3_SCCF 3 Start CountRead
AV417RUNTIME_COMPA1RTComp A1 MinutesRead
AV419RUNTIME_COMPA1RCComp A1 Reset CountRead
AV418RUNTIME_COMPA1SCComp A1 Start CountRead
AV420RUNTIME_COMPA2RTComp A2 MinutesRead
AV422RUNTIME_COMPA2RCComp A2 Reset CountRead
AV421RUNTIME_COMPA2SCComp A2 Start CountRead
AV423RUNTIME_COMPB1RTComp B1 MinutesRead
AV425RUNTIME_COMPB1RCComp B1 Reset CountRead
AV424RUNTIME_COMPB1SCComp B1 Start CountRead
AV426RUNTIME_COMPB2RTComp B2 MinutesRead
AV428RUNTIME_COMPB2RCComp B2 Reset CountRead
AV427RUNTIME_COMPB2SCComp B2 Start CountRead
AV441RUNTIME_EFAN_RTExhaust Fan MinutesRead
AV443RUNTIME_EFAN_RCExhaust Fan Reset CountRead
AV442RUNTIME_EFAN_SCExhaust Fan Start CountRead
AV446RUNTIME_SHEAT_RCHeat Reset CountRead
AV444RUNTIME_SHEAT_RTHeat MinutesRead
AV445RUNTIME_SHEAT_SCHeat Start CountRead
AV447RUNTIME_HMVLV_RTHGRH Valve MinutesRead
AV449RUNTIME_HMVLV_RCHGRH Valve Reset CountRead
AV448RUNTIME_HMVLV_SCHGRH Valve Start CountRead
AV465RUNTIME_HUMPUSCHumdimizer Cycle CntRead
AV438RUNTIME_IDF_RTIndoor Fan MinutesRead
AV440RUNTIME_IDF_RCIndoor Fan Reset CountRead
AV439RUNTIME_IDF_SCIndoor Fan Start CountRead
AV450RUNTIME_DAMP_RTOAD MinutesRead
AV452RUNTIME_DAMP_RCOAD Reset CountRead
AV451RUNTIME_DAMP_SCOAD Start CountRead
AV459RUNTIME_OILACYSCOil Cir A CountRead
AV460RUNTIME_OILBCYSCOil Cir B CountRead
AV274EXVSTP_EXVSTA1A1 Start Pos (default 35, 0 to 100)%Write
AV270EXVSTP_SupHtA1A1 Superheat Setpoint (default 0)°FWrite
AV408RFGTEMP_SSHA1A1 Superheat Temp°FRead
AV275EXVSTP_EXVSTA2A2 Start Pos (default 35, 0 to 100)%Write
AV271EXVSTP_SupHtA2A2 Superheat Setpoint (default 0)°FWrite
AV409RFGTEMP_SSHA2A2 Superheat Temp°FRead
AV276EXVSTP_EXVSTB1B1 Start Pos (default 35, 0 to 100)%Write
AV272EXVSTP_SupHtB1B1 Superheat Setpoint (default 0)°FWrite
AV410RFGTEMP_SSHB1B1 Superheat Temp°FRead
AV277EXVSTP_EXVSTB2B2 Start Pos (default 35, 0 to 100)%Write
AV273EXVSTP_SupHtB2B2 Superheat Setpoint (default 0)°FWrite
AV411RFGTEMP_SSHB2B2 Superheat Temp°FRead
AV471COOLCFG_CCHTHACCH A OAT Lockout (default 80, 50 to 90)°FWrite
AV472COOLCFG_CCHTHBCCH B OAT Lockout (default 80, 50 to 90)°FWrite
AV497COOLCFG_CFSPDMX1CF Speed MAX (default 100)%Write
AV496COOLCFG_CFSPDMN1CF Speed MIN (default 0)%Write
BV172CNDSTP_SPDStpENCF User Start Spd EnabWrite1=DISABLE; 2=ENABLE
AV498COOLCFG_CFSTSPD1CF User Start Speed (default 0)%Write
AV402RFGPRESS_DPACir A Discharge PressurepsigRead
AV462CMPASTS_ORTMLFTACir A Oil Rec Time LeftsRead
AV400RFGPRESS_SPACir A Suction PressurepsigRead
AV346CMPASTS_BOOSTSTACir A VSC Boost StateRead
AV403RFGPRESS_DPBCir B Discharge PressurepsigRead
AV464CMPBSTS_ORTMLFTBCir B Oil Rec Time LeftsRead
AV401RFGPRESS_SPBCir B Suction PressurepsigRead
AV474COOLSTP_CMPMAXA1Cmp Nominal Spd Max A1 (default 100)%Write
AV476COOLSTP_CMPMAXA2Cmp Nominal Spd Max A2 (default 100)%Write
AV478COOLSTP_CMPMAXB1Cmp Nominal Spd Max B1 (default 100)%Write
AV480COOLSTP_CMPMAXB2Cmp Nominal Spd Max B2 (default 100)%Write
AV475COOLSTP_CMPMINA1Cmp Nominal Spd Min A1 (default 0)%Write
AV477COOLSTP_CMPMINA2Cmp Nominal Spd Min A2 (default 0)%Write
AV479COOLSTP_CMPMINB1Cmp Nominal Spd Min B1 (default 0)%Write
AV481COOLSTP_CMPMINB2Cmp Nominal Spd Min B2 (default 0)%Write
AV88CMPFLRTMCompressor Failure Timer (default 5, 2 to 20)sWrite
AV87CMPSTKTMCompressor Stuck On Time (default 4, 2 to 20)sWrite
AV212DHUMCFG_CCBYPTMECon Coil Bypass Time (default 0)minWrite
AV213DHUMCFG_CCPRGPOSCond Coil Purge Pos (default 50)%Write
AV214DHUMCFG_CCPRGTMECond Coil Purge Time (default 10)minWrite
AV293RFGTEMP_CCTCooling Coil Temp°FRead
AV506DHUMCFG_OILTIMEDehum Oil Recov Time (default 60, 0 to 120)minWrite
AV300RFGTEMP_DGTADischarge Gas Temp A°FRead
AV523OUTPUTS_EXVA1OBJEXV A1 ObjectiveRead
AV524OUTPUTS_EXVA2OBJEXV A2 ObjectiveRead
AV525OUTPUTS_EXVB1OBJEXV B1 ObjectiveRead
AV526OUTPUTS_EXVB2OBJEXV B2 ObjectiveRead
AV89HEATSINK_HSCTRLOFHeat Sink Ctrl Offset (default 10, 0 to 20)°FWrite
AV211DHUMCFG_RHTCLTMEHGRH Coil Closed Time (default 45, 5 to 120)minWrite
AV210DHUMCFG_RHTOPTMEHGRH Coil Open Time (default 2, 1 to 5)minWrite
AV489DHUMCFG_RHSTARTHGRH Start Pos (default 5, 0 to 100)%Write
AV490DHUMCFG_RHTIMEHGRH Startup Time (default 30, 0 to 120)sWrite
AV488DHUMCFG_RHMAXPOSHGRH Valve Max Pos (default 99, 50 to 100)%Write
AV487DHUMCFG_RHMINPOSHGRH Valve Min Pos (default 1, 0 to 50)%Write
AV91HEATSINK_HSHTEMPHigh Heat Sink Temp (default 200, 100 to 250)°FWrite
AV90HEATSINK_HSHTMPDBHigh Heat Sink Temp DB (default 8, 0 to 20)°FWrite
AV209DHUMCFG_DHMATLCKHigh MT Dehum Lockout (default 105, 90 to 115)°FWrite
AV301HMZR_CONDPURGHumidizer PurgeRead
AV519CMPA1STS_LOADREQLoad Request Comp A1Read
AV520CMPA2STS_LOADREQLoad Request Comp A2Read
AV521CMPB1STS_LOADREQLoad Request Comp B1Read
AV522CMPB2STS_LOADREQLoad Request Comp B2Read
BV174COOLCFG_LCRCOLow Cap Req Comp OnWrite1=NO; 2=YES
AV73LPRTIMELow Pressure Ratio Time (default 30, 5 to 120)sWrite
BV129EXVSTP_EXVSTENBManual Start Pos EnableWrite1=DISABLE; 2=ENABLE
AV505DHUMCFG_OILHITHOil Recov High Thld (default 50, 0 to 100)%Write
AV504DHUMCFG_OILLOWTHOil Recov Low Thld (default 20, 0 to 100)%Write
AV461CMPASTS_OILRECACOil Recovery Actv Cir ARead
AV463CMPBSTS_OILRECACOil Recovery Actv Cir BRead
AV416RFGTEMP_OILTSMPAOil Sump Temp°FRead
AV406RFGTEMP_SDTASaturated Discharge CirA°FRead
AV407RFGTEMP_SDTBSaturated Discharge CirB°FRead
AV404RFGTEMP_SSTASaturated Suction A°FRead
AV405RFGTEMP_SSTBSaturated Suction B°FRead
AV485COOLCFG_SCT_HLIMSCT High Limit (default 115, 100 to 140)°FWrite
AV486COOLCFG_SCT_LLIMSCT Low Limit (default 80, 40 to 90)°FWrite
AV539CMPASTS_SDTABSMXSDT Abs Max Cir ARead
AV543CMPBSTS_SDTABSMXSDT Abs Max Cir BRead
AV538CMPASTS_SDTABSMNSDT Abs Min Cir ARead
AV542CMPBSTS_SDTABSMNSDT Abs Min Cir BRead
AV535CMPBSTS_SDTENVMXSDT Env Max Cir BRead
AV531CMPASTS_SDTENVMXSDT Env Max CirARead
AV534CMPBSTS_SDTENVMNSDT Env Min Cir BRead
AV530CMPASTS_SDTENVMNSDT Env Min CirARead
AV493CNDSTP_SDTTEMP1SDT Setpoint 1 (default 0)°FWrite
AV494CNDSTP_SDTTEMP2SDT Setpoint 2 (default 0)°FWrite
AV495CNDSTP_SDTTEMP3SDT Setpoint 3 (default 0)°FWrite
BV171CNDSTP_SDTStpEnSDT Setpoint EnableWrite1=DISABLE; 2=ENABLE
AV541CMPBSTS_SSTABSMXSST Abs Max Cir BRead
AV537CMPASTS_SSTABSMXSST Abs Max CirARead
AV540CMPBSTS_SSTABSMNSST Abs Min Cir BRead
AV536CMPASTS_SSTABSMNSST Abs Min CirARead
AV533CMPBSTS_SSTENVMXSST Env Max Cir BRead
AV529CMPASTS_SSTENVMXSST Env Max CirARead
AV532CMPBSTS_SSTENVMNSST Env Min Cir BRead
AV528CMPASTS_SSTENVMNSST Env Min CirARead
AV299RFGTEMP_SGT1Suction Gas Temp 1°FRead
AV412RFGTEMP_SGTA1Suction Gas Temp Cir A1°FRead
AV413RFGTEMP_SGTA2Suction Gas Temp Cir A2°FRead
AV414RFGTEMP_SGTB1Suction Gas Temp Cir B1°FRead
AV415RFGTEMP_SGTB2Suction Gas Temp Cir B2°FRead
BV128EXVSTP_SETPTENBUser Setpoint EnableWrite1=DISABLE; 2=ENABLE
BV175COOLCFG_VSCFS_ORVSC Fixed Speed OverrideWrite1=DISABLE; 2=ENABLE
BV136SVCOUT_CMTRNDAHAdd Heat Comfort TrendWrite1=DISABLE; 2=ENABLE
MV20STATES_ODF2STNCF 2 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV21STATES_ODF3STNCF 3 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV13STATES_CIRCASTNCircuit A StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV14STATES_CIRCBSTNCircuit B StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV15STATES_CMPA1STNComp A1 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV16STATES_CMPA2STNComp A2 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV17STATES_CMPB1STNComp B1 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV18STATES_CMPB2STNComp B2 StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
BV8SVCOUT_CMTRNDACCool Comfort TrendingWrite1=DISABLE; 2=ENABLE
BV176STATES_OKTOFRCLFree Cooling AvailableRead1=YES; 2=NO
BV180STATES_OKTOFDHMFree Dehum StatusRead1=DISABLE; 2=ENABLE
MV24STATES_HEATRSTNHeater StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV23STATES_RHTSTNUMHGRH StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MVmin22STATES_IDFNUMIndoor Fan StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV25STATES_ECONNUMOAD StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
MV26STATES_OCCSRNUMOccupancy SourceRead1=DefaultSchedule; 2=LocalSchedule; 3=BMSSchedule; 4=RemoteSwitch; 5=TimedOverride; 6=Linkage; 7=Forced; 8=MotionSensing
MV19STATES_ODF1STNODF A StateRead1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT
BV178STATES_PURGEACTPre-Occ Purge StateRead1=OFF; 2=ON
AV516STATES_MINTILOCTime Until Next OccupiedminRead
BV206SWTCHCFG_ALARMINVAlarm RelayWrite1=NORMAL; 2=INVERTED
BV200SWTCHCFG_CMPA1INVCompressor A1Write1=NORMAL; 2=INVERTED
BV201SWTCHCFG_CMPA2INVCompressor A2Write1=NORMAL; 2=INVERTED
BV182SWTCHCFG_CNDSWINVCondensate Ovrflw SwitchWrite1=NORMAL; 2=INVERTED
BV202SWTCHCFG_CCHRAINVCrankcase Heater AWrite1=NORMAL; 2=INVERTED
BV199SWTCHCFG_DORINVDamper Override RelayWrite1=NORMAL; 2=INVERTED
BV204SWTCHCFG_EVBYPINVERV Bypass DamperWrite1=NORMAL; 2=INVERTED
BV196SWTCHCFG_FRSTINVERV Frost IndicationWrite1=NORMAL; 2=INVERTED
BV205SWTCHCFG_ERVINVERV WheelWrite1=NORMAL; 2=INVERTED
BV197SWTCHCFG_WHLSTINVERV Wheel Motion SensorWrite1=NORMAL; 2=INVERTED
BV203SWTCHCFG_PEENINVEXF EnableWrite1=NORMAL; 2=INVERTED
BV192SWTCHCFG_FLTSWINVFilter Status SwitchWrite1=NORMAL; 2=INVERTED
BV195SWTCHCFG_FRESWINVFire ShutdownWrite1=NORMAL; 2=INVERTED
BV181SWTCHCFG_HTALMINVHeat Alarm/Limit SwitchWrite1=NORMAL; 2=INVERTED
BV198SWTCHCFG_HTENINVHeat EnableWrite1=NORMAL; 2=INVERTED
BV185SWTCHCFG_HPSAINVHigh Pressure SwitchWrite1=NORMAL; 2=INVERTED
BV189SWTCHCFG_DHMSWINVHumidistat SwitchWrite1=NORMAL; 2=INVERTED
BV184SWTCHCFG_IDFSWINVIndoor Fan Limit SwitchWrite1=NORMAL; 2=INVERTED
BV194SWTCHCFG_PMRSWINVPhase MonitorWrite1=NORMAL; 2=INVERTED
BV193SWTCHCFG_RESWINVRemote InputWrite1=NORMAL; 2=INVERTED
BV183SWTCHCFG_SMKSWINVSmoke DetectorWrite1=NORMAL; 2=INVERTED
BV186SWTCHCFG_TSTGINVThermostat GWrite1=NORMAL; 2=INVERTED
BV190SWTCHCFG_TSTW1INVThermostat W1Write1=NORMAL; 2=INVERTED
BV191SWTCHCFG_TSTW2INVThermostat W2Write1=NORMAL; 2=INVERTED
BV187SWTCHCFG_TSTY1INVThermostat Y1Write1=NORMAL; 2=INVERTED
BV188SWTCHCFG_TSTY2INVThermostat Y2Write1=NORMAL; 2=INVERTED
AV286HCSTATUS_CAPACTCooling CapacityRead
AV466GENUINIT_FILT_RTFilter MinutesRead
AV297FILTER_STATUSFilter StatusRead
AV284HCSTATUS_HEATREQHeat Request from UI%Read
AV292GENUNIT_HEATCOOLHeat/Cool statusRead
BV6IDFFDBK_STATUSIDF Feedback StatusRead1=DISABLE; 2=ENABLE
BV140LINK_ACTLinkage ActiveRead1=NO; 2=YES
AVmin363GENUNIT_NETOCCNetwork Occupancy (default 2, 0 to 2)Write
AVmin289GENUNIT_OCCUPIEDOccupiedRead
AV43GENUNIT_PREFLTR_LIMPre-Filter Press Limit (default 1.5, 0.5 to 5)in. w.c.Write
AV42GENUNIT_PREFLTR_SRCPre-Filter Source (default 0, 0 to 3)Write
BV167GENUNIT_FLTR_RSTReset Filter HoursWrite1=NO; 2=YES
AV285HCSTATUS_SATCTLPTSupply Air Temp Cntrl PtRead
AV567GENUNIT_SMAXCCAPSys Max Cool Cap%Read
AV568GENUNIT_SMAXHCAPSys Max Heat Cap%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)

How many BACnet points does the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) have?

This list has 715 BACnet objects: 502 analog values, 186 binary values, 27 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet points are writable?

393 of the 715 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet documentation?

The source is SmartVu Controls Version 2.X for Applied Rooftop Integration Guide (Appendix A: BACnet and CCN Network Points) (48-50-ART-SVU-1T), revision 2025-03, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0F/48-50-ART-SVU-1T.pdf.

What are the minimum BACnet points to integrate the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?

Start with AV 363 GENUNIT_NETOCC (Network occupancy; Primary BAS Network must be BACnet); AV 195 COOLSTP_CLSP_OCC (Occupied cooling setpoint); AV 313 HEATSTP_HTSP_OCC (Occupied heating setpoint); BV 1 ALARMRST_RST_ALM (Alarm reset command); MV 22 STATES_IDFNUM (Indoor fan state; 5 = running); AV 289 GENUNIT_OCCUPIED (Confirms occupied/unoccupied); AV 7 AIRTEMP_SPT (Space temperature); AV 4 AIRTEMP_SAT (Supply air temperature); BV 83 DISCOUT_ALMOUT (Common alarm relay output).

How do I enable BMS control of the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?

Primary BAS Network selects the network that drives occupancy; it must be BACnet to use the Network Occupancy point (GENUNIT_NETOCC, AV 363) when BACnet schedule objects are not used. The guide does not say what the 0-2 values of AV 363 mean (default 2). Occupancy Source (MV 26) shows where occupancy currently comes from.

Can the BMS supply sensor values to the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?

The Network Inputs group has writable objects for BMS values, e.g. Net SPT (AV 360), Net OAT (AV 362), Net SPRH (AV 347), Net Indoor Air Quality (AV 357), Net Building Pressure (AV 352), and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them or give any refresh timeout.

How do I check these points on the real 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: SmartVu Controls Version 2.X for Applied Rooftop Integration Guide (Appendix A: BACnet and CCN Network Points) · 48-50-ART-SVU-1T · rev. 2025-03. Object names, instances and units are reproduced as published; descriptions are our own.