Water-cooled centrifugal chiller controller · BACnet points list
Carrier AquaEdge 19MV (PIC6) BACnet points list
Updated 28 October 2026
The 19MV's PIC6 controller offers BACnet MS/TP on RS-485 port J8 or BACnet IP on Ethernet port J15, with about 300 AV, BV and MV objects named after their CCN table and point. Commands use paired read (_rd) and write (_wr) objects for start/stop, occupancy, control point, demand limit, emergency stop, free cooling and heat/cool select. It repeats 228 of the 19DV PIC6 objects (all but the BACnet dongle input) and adds about 70 more, mostly magnetic bearing controller (MBC) points plus UPS battery, EXV and liquid bypass points.
This page lists 299 BACnet objects for the Carrier AquaEdge 19MV (PIC6) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaEdge 19MV (PIC6)
- Equipment
- Water-cooled centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 299 (14 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller
BMS integration notes: Carrier AquaEdge 19MV (PIC6)
Enable BACnet in the CONNECT (BMS Protocol) menu: J8 option for MS/TP or BACnet Enable for BACnet IP. Set the identifier and network, and put the chiller in NETWORK control mode. The chiller then starts when both BV 66 start/stop and BV 68 occupancy are true; write control point and demand limit through the _wr objects and read status, water temperatures and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 66 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 68 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| BV 67 | GENUNIT_EMSTOP_wr | Emergency stop command | Write |
| AV 147 | GENUNIT_CTRL_PNT_wr | Control point command | Write |
| AV 148 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| MV 1 | GENUNIT_ctl_mode | Control mode: Local, Network, Remote, Local Sched | Read |
| AV 7 | GENUNIT_ch_state | Chiller status code | Read |
| AV 9 | TEMP_LCW | Leaving chilled water temperature | Read |
| AV 8 | TEMP_ECW | Entering chilled water temperature | Read |
| AV 85 | ALARMRST_alarm_1 | Current alarm 1 | Read |
Enable & remote start
In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP or the HMI to shut it down.
Network setup
- CONNECT menu: Port J8 option 0 = None, 1 = BACnet MS/TP, 2 = Modbus RTU; BACnet Enable (bacena) defaults to disabled. The menu needs the Service password.
- Defaults: BACnet network 1600, identifier 1600001, MS/TP MAC 1, MS/TP baud option 2 (38400), Max Master 3.
- BACnet IP and Modbus TCP use Ethernet port J15 (default IP 169.254.0.1, mask 255.255.0.0).
- BACnet MS/TP and BACnet IP are mutually exclusive, as are BACnet MS/TP and Modbus RTU. Changing the protocol reboots the PIC6.
- After changing the IP address, reboot or power-cycle the PIC6 to rebuild the BACnet stack.
Watch out for
- Write the _wr objects; the _rd objects only echo the current value.
- Configuration parameters are generally read-only over BACnet; setpoints are read/write.
Carrier AquaEdge 19MV (PIC6) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AV | 2 | GENUNIT_reset | Control Point Reset | Read | ||
| AV | 3 | GENUNIT_setpoint | Actual Setpoint | Read | ||
| AV | 4 | GENUNIT_AMPS_P | Percent Current | Read | ||
| AV | 5 | GENUNIT_KW_P | Motor Percent Kilowatts | Read | ||
| AV | 6 | GENUNIT_DEM_LIM_rd | Actual Demand Limit | Read | ||
| AVmin | 7 | GENUNIT_ch_state | Chiller Status Code | Read | ||
| AVmin | 8 | TEMP_ECW | Entering Chilled Water | Read | ||
| AVmin | 9 | TEMP_LCW | Leaving Chilled Water | Read | ||
| AV | 10 | TEMP_ECDW | Entering Condenser Water | Read | ||
| AV | 11 | TEMP_LCDW | Leaving Condenser Water | Read | ||
| AV | 12 | TEMP_HR_EWT | Heat Recl Entering Temp | Read | ||
| AV | 13 | TEMP_HR_LWT | Heat Recl Leaving Temp | Read | ||
| AV | 14 | TEMP_EVAP_SAT | Evap Sat Refrig Temp | Read | ||
| AV | 15 | TEMP_EVAP_T | Evap Refrig Liquid Temp | Read | ||
| AV | 16 | TEMP_evap_app | Evaporator Approach | Read | ||
| AV | 17 | TEMP_cond_app | Condenser Approach | Read | ||
| AV | 18 | TEMP_COND_SAT | Cond Sat Refrig Temp | Read | ||
| AV | 19 | TEMP_DGT | Comp Discharge Temp | Read | ||
| AV | 20 | TEMP_DSH | Discharge Superheat | Read | ||
| AV | 21 | TEMP_MTRB_OIL | Thrust Bearing Oil Temp | Read | ||
| AV | 22 | TEMP_MTRB | Thrust Bearing Temp | Read | ||
| AV | 23 | TEMP_MTRB1 | Low Speed ME Brg Temp | Read | ||
| AV | 24 | TEMP_MTRB2 | Low Speed CE Brg Temp | Read | ||
| AV | 25 | TEMP_MTRB3 | High Speed ME Brg Temp | Read | ||
| AV | 26 | TEMP_MTRB4 | High Speed CE Brg Temp | Read | ||
| AV | 27 | TEMP_MTRW1 | Motor Winding 1 Temp | Read | ||
| AV | 28 | TEMP_MTRW2 | Motor Winding 2 Temp | Read | ||
| AV | 29 | TEMP_MTRW3 | Motor Winding 3 Temp | Read | ||
| AV | 30 | TEMP_OILT_SMP | Oil Sump Temp | Read | ||
| AV | 31 | TEMP_OILT_DIS | Oil Supply Temp | Read | ||
| AV | 32 | TEMP_PGC_SUCT | Purge Comp Suction Temp | Read | ||
| AV | 33 | TEMP_CBH1_T | 1st Stage Bearing Temp | Read | ||
| AV | 34 | TEMP_CBH2_T | 2nd Stage Bearing Temp | Read | ||
| AV | 36 | PRESSURE_EVAP_P | Evaporator Pressure | Read | ||
| AV | 37 | PRESSURE_COND_P | Condenser Pressure | Read | ||
| AV | 38 | PRESSURE_ECON_P | Economizer Pressure | Read | ||
| AV | 39 | PRESSURE_OIL_PD | Oil Pump Delta P | Read | ||
| AV | 40 | PRESSURE_DIFF_P | Diffuser Pressure | Read | ||
| AV | 41 | PRESSURE_HEAD_P | Head Pressure Reference | Read | ||
| AV | 42 | PRESSURE_REF_PD | Bearing Delta P | Read | ||
| AV | 43 | PRESSURE_PUMP_PD | Ref Pump Delta P | Read | ||
| AV | 44 | INPUTS_GV1_ACT | Guide Vane 1 Actual Pos | Read | ||
| AV | 45 | INPUTS_GV2_ACT | Guide Vane 2 Actual Pos | Read | ||
| AV | 46 | INPUTS_VFD_ACT | Actual VFD Speed Per | Read | ||
| AV | 47 | INPUTS_DIFF_ACT | Diffuser Actual Pos | Read | ||
| AV | 48 | INPUTS_HGBPACTP | Actual ECV Pos Per | Read | ||
| AV | 49 | OUTPUTS_DIFF_OUT | Diffuser Output mA | Read | ||
| AV | 50 | OUTPUTS_HDPV_OUT | Head Pres Output mA | Read | ||
| AV | 51 | OUTPUTS_CHST_OUT | Chiller Stat Output mA | Read | ||
| AV | 52 | OUTPUTS_VFD_OUT | VFD Speed Output mA | Read | ||
| AV | 53 | OUTPUTS_EXV_OUT | Oil EXV Output mA | Read | ||
| AV | 54 | OUTPUTS_llc_exvt | Liquid Level EXV Target | Read | ||
| AV | 55 | OUTPUTS_op_vfd_t | Oil Pump VFD Target | Read | ||
| AV | 56 | OUTPUTS_GV1_OUT | Guide Vane1 Output | Read | ||
| AV | 57 | OUTPUTS_GV2_OUT | Guide Vane2 Output | Read | ||
| AV | 58 | HYDRLIC_CDW_FV | Cond Water Flow Value | Read | ||
| AV | 59 | HYDRLIC_cdw_pd | Condenser Water Delta P | Read | ||
| AV | 60 | HYDRLIC_CHW_FV | Chilled Water Flow Value | Read | ||
| AV | 61 | HYDRLIC_chw_pd | Chilled Water Delta P | Read | ||
| AV | 62 | HYDRLIC_ctrlw_dt | Controlled Water DT | Read | ||
| AV | 63 | RUNTIME_C_STARTS | Compressor Starts Num | Read | ||
| AV | 64 | RUNTIME_COMP_HRS | Compressor Running Hrs | Read | ||
| AV | 65 | RUNTIME_SRV_HRS | After Service Hrs | Read | ||
| AV | 66 | POWER_I_AMPS_A_I | Actual Line Current | Read | ||
| AV | 67 | POWER_I_AMPS_P_I | Percent Line Current | Read | ||
| AV | 68 | POWER_I_VOLT_A | Actual Line Voltage | Read | ||
| AV | 69 | POWER_I_VOLT_P | Percent Line Voltage | Read | ||
| AV | 70 | POWER_I_KW | Line Kilowatts | Read | ||
| AV | 71 | POWER_I_POW_FACT | Line Power Factor | Read | ||
| AV | 72 | POWER_I_ln_imb_v | Line Voltage Imbalance% | Read | ||
| AV | 73 | POWER_O_VFD_LOAD | VFD Load Current | Read | ||
| AV | 74 | POWER_O_amps_p_o | Percent VFD Load Current | Read | ||
| AV | 75 | POWER_O_MOT_FREQ | Motor Actual Frequency | Read | ||
| AV | 76 | POWER_O_bus_volt | DC Bus Voltage | Read | ||
| AV | 77 | POWER_O_vfd_act | Actual VFD Speed Per | Read | ||
| AV | 78 | POWER_O_motor_pf | Motor Power Factor | Read | ||
| AV | 79 | POWER_O_motor_kw | Motor Kilowatts | Read | ||
| AV | 80 | POWER_O_motorkwh | Motor Kilowatt-Hours | Read | ||
| AV | 81 | POWER_O_enc_temp | VFD Enclosure Temp | Read | ||
| AV | 82 | POWER_O_inv_temp | Inverter Temperature | Read | ||
| AV | 83 | POWER_O_rec_temp | Rectifier Temperature | Read | ||
| AV | 84 | POWER_O_alm_code | VFD Alarm Code | Read | ||
| AVmin | 85 | ALARMRST_alarm_1 | Jbus Current Alarm 1 | Read | ||
| AV | 86 | ALARMRST_alarm_2 | Jbus Current Alarm 2 | Read | ||
| AV | 87 | ALARMRST_alarm_3 | Jbus Current Alarm 3 | Read | ||
| AV | 88 | ALARMRST_alarm_4 | Jbus Current Alarm 4 | Read | ||
| AV | 89 | ALARMRST_alarm_5 | Jbus Current Alarm 5 | Read | ||
| AV | 90 | CAPACTRL_ctrl_wt | Controlled Water Temp | Read | ||
| AV | 91 | CAPACTRL_gv1_tgt | Target GV1 Pos | Read | ||
| AV | 92 | CAPACTRL_gv2_tgt | Target GV2 Pos | Read | ||
| AV | 93 | CAPACTRL_vfd_tgt | Target VFD Speed Per | Read | ||
| AV | 94 | CAPACTRL_hgbp_tp | EXCSV Surge Pro Target | Read | ||
| AV | 95 | CAPACTRL_cm_stat1 | Comp1 Run State Val | Read | ||
| AV | 96 | MAISURGE_act_reg | Surge Region | Read | ||
| AV | 97 | MAISURGE_dts_act | Actual Delta Tsat | Read | ||
| AV | 98 | MAISURGE_dts_cal | Calc Ref Delta Tsat | Read | ||
| AV | 99 | MAISURGE_sc | Surge Counts | Read | ||
| AV | 100 | MAISURGE_spc | Surge Protection Counts | Read | ||
| AV | 101 | MAISURGE_surg_act | Surge Prevention Active | Read | ||
| AV | 102 | MAISURGE_surg_pro | Surge Protection Active | Read | ||
| AV | 103 | MAISURGE_dts_maxc | Cal Surge Delta Tsmax | Read | ||
| AV | 104 | MAISURGE_dts_minc | Cal Surge Delta Tsmin | Read | ||
| AV | 105 | MAISURGE_dts_medc | Cal Surge Delta Tsmed | Read | ||
| AV | 106 | MAISURGE_gv1_sful | IGV1 Full Load Position | Read | ||
| AV | 107 | MAISURGE_gv1_smin | IGV1 Minimum Position | Read | ||
| AV | 108 | MAISURGE_gv1_smed | Opti-Sound IGV1 Position | Read | ||
| AV | 109 | MAISURGE_enlp_opt | Envelope Line Optimized | Read | ||
| AV | 110 | QCK_TEST_Q_GV1ACT | Guide Vane 1 Actual Pos | Read | ||
| AV | 111 | QCK_TEST_Q_DIFTGT | Diffuser Target Pos | Read | ||
| AV | 112 | MAIN_SRD_diff_tgt | Diffuser Target Pos | Read | ||
| AV | 113 | MAIN_SRD_lift_a | Actual Lift | Read | ||
| AV | 114 | MAIN_SRD_lift_1 | VDO High Lift Load Line | Read | ||
| AV | 115 | MAIN_SRD_lift_2 | VDO Low Lift Load Line | Read | ||
| AV | 116 | MAIN_MS_lead_lag | Unit is Lead or Lag | Read | ||
| AV | 117 | MAIN_MS_ms_ctrl | Primary Control Type | Read | ||
| AV | 118 | MAIN_MS_sl_ctrl | Secondary Control Type | Read | ||
| AV | 119 | MAIN_MS_ll_fault | Primary Secondary Fault | Read | ||
| AV | 120 | MAIN_MS_lagstat | Secondary Run Status | Read | ||
| AV | 121 | MAIN_MS_lagstart | Lag Start Timer | Read | ||
| AV | 122 | MAIN_MS_lagstop | Lag Stop Timer | Read | ||
| AV | 123 | MAIN_MS_preflt | Prestart Fault Timer | Read | ||
| AV | 124 | MAIN_MS_pulltime | Pulldown Timer | Read | ||
| AV | 125 | MAIN_MS_ll_hr_d | Lead/Lag Hours Delta | Read | ||
| AV | 126 | CFGSURGE_gv1_pmin | IGV1 Minimum Position | Read | ||
| AV | 127 | CFGSURGE_gv1_pful | IGV1 Full Load Position | Read | ||
| AV | 128 | CFGSURGE_sgl_off | Surge Line Offset | Read | ||
| AV | 129 | CFGSURGE_sgl_loff | Surge Line Lower DB | Read | ||
| AV | 130 | CFGSURGE_sgl_hoff | Surge Line Upper DB | Read | ||
| AV | 131 | CFGSURGE_sgl_shfh | Surge Line Shape Factor | Read | ||
| AV | 132 | CFGSURGE_sgl_shfl | Sound Line Shape Factor | Read | ||
| AV | 133 | CFGSURGE_sgl_spdf | Surge Line Speed Factor | Read | ||
| AV | 134 | CFGSURGE_sgl_pro | Surge Profile Offset | Read | ||
| AV | 135 | CONF_PRG_oil_qly | Oil Quality | Read | ||
| AV | 136 | CONF_PRG_oil_flt | Oil Filter Failure | Read | ||
| AV | 137 | CONF_PRG_tran_dev | Transducer Deviation | Read | ||
| AV | 138 | CONF_PRG_ref_chg | Refrig Charge Status | Read | ||
| AV | 139 | CONNECT_network | BACnet Network | Read | ||
| AV | 140 | CONNECT_bac_id | BACnet Identifier | Read | ||
| AV | 141 | SETPOINT_ecw_sp | Cooling ECW Setpoint | Write | ||
| AV | 142 | SETPOINT_lcw_sp | Cooling LCW Setpoint | Write | ||
| AV | 143 | SETPOINT_ecdw_sp | Heating ECDW Setpoint | Write | ||
| AV | 144 | SETPOINT_lcdw_sp | Heating LCDW Setpoint | Write | ||
| AV | 145 | SETPOINT_ice_sp | Ice Build Setpoint | Write | ||
| AV | 146 | SETPOINT_dem_base | Base Demand Limit | Write | ||
| AVmin | 147 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 148 | GENUNIT_DEM_LIM_wr | Demand Limit | Write | ||
| AV | 149 | GENUNIT_HC_SEL_wr | Heatcool Select | Write | ||
| AV | 150 | BACnet_PRIME_V | Value of Prime variable | Read | ||
| AV | 151 | RUNTIME_ST_CNT12 | Starts Num in 12 Hours | Read | ||
| AV | 152 | POWER_I_ln_imb_i | Line Current Imbalance% | Read | ||
| AV | 153 | RUNTIME_PGP_NO | Total Pumpout Numbers | Read | ||
| AV | 154 | RUNTIME_PGP_TM | Total Pumpout Time | Read | ||
| AV | 155 | RUNTIME_pgp_tm_w | Avg Daily Purge in 7 Day | Read | ||
| AV | 160 | INPUTS_COND_LS | Liquid Level Cond | Read | ||
| AV | 161 | OUTPUTS_LQBPtgtV | EXCSV Target Pos volt | Read | ||
| AV | 162 | EXVCTRL_MEXV_CMD | Main EXV Position Cmd | Read | ||
| AV | 163 | EXVCTRL_EEXV_CMD | ECO EXV Position Cmd | Read | ||
| AV | 165 | MBC_RPM | Rotational Shaft Speed | Read | ||
| AV | 166 | MBC_SpeedHZ0 | Sync Speen (Hz) | Read | ||
| AV | 167 | MBC_jAvGpChg | J Average Gap Change | Read | ||
| AV | 168 | MBC_hAvGpChg | H Average Gap Change | Read | ||
| AV | 169 | MBC_kAvGpChg | K Average Gap Change | Read | ||
| AV | 170 | MBC_jxAvg | J Average Position X | Read | ||
| AV | 171 | MBC_jyAvg | J Average Position Y | Read | ||
| AV | 172 | MBC_hzAvg | H Average Position | Read | ||
| AV | 173 | MBC_kxAvg | K Average Position X | Read | ||
| AV | 174 | MBC_kyAvg | K Average Position Y | Read | ||
| AV | 175 | MBC_tempC01 | J Bearing Coil Temp | Read | ||
| AV | 176 | MBC_tempC02 | H Outboard Coil Temp | Read | ||
| AV | 177 | MBC_tempC03 | H Inboard Coil Temp | Read | ||
| AV | 178 | MBC_tempC04 | K Bearing Coil Temp | Read | ||
| AV | 179 | MBC_tempC05 | Coldplate Temp | Read | ||
| AV | 180 | MBC_j1Imeas | J1 Coil Current | Read | ||
| AV | 181 | MBC_j2Imeas | J2 Coil Current | Read | ||
| AV | 182 | MBC_j3Imeas | J3 Coil Current | Read | ||
| AV | 183 | MBC_j4Imeas | J4 Coil Current | Read | ||
| AV | 184 | MBC_k1Imeas | K1 Coil Current | Read | ||
| AV | 185 | MBC_k2Imeas | K2 Coil Current | Read | ||
| AV | 186 | MBC_k3Imeas | K3 Coil Current | Read | ||
| AV | 187 | MBC_k4Imeas | K4 Coil Current | Read | ||
| AV | 188 | MBC_h1meas | H1 Coil Current | Read | ||
| AV | 189 | MBC_h2meas | H2 Coil Current | Read | ||
| AV | 190 | MBC5_j1R0 | J Coil 1 R0 | Read | ||
| AV | 191 | MBC5_j2R0 | J Coil 2 R0 | Read | ||
| AV | 192 | MBC5_j3R0 | J Coil 3 R0 | Read | ||
| AV | 193 | MBC5_j4R0 | J Coil 4 R0 | Read | ||
| AV | 194 | MBC5_jSCal1 | J Sensor Gap S1 | Read | ||
| AV | 195 | MBC5_jTCal1 | J Sensor Gap T1 | Read | ||
| AV | 196 | MBC5_jSCal2 | J Sensor Gap S2 | Read | ||
| AV | 197 | MBC5_jTCal2 | J Sensor Gap T2 | Read | ||
| AV | 198 | MBC5_k1R0 | K Coil 1 R0 | Read | ||
| AV | 199 | MBC5_k2R0 | K Coil 2 R0 | Read | ||
| AV | 200 | MBC5_k3R0 | K Coil 3 R0 | Read | ||
| AV | 201 | MBC5_k4R0 | K Coil 4 R0 | Read | ||
| AV | 202 | MBC5_kSCal1 | K Sensor Gap S1 | Read | ||
| AV | 203 | MBC5_kTCal1 | K Sensor Gap T1 | Read | ||
| AV | 204 | MBC5_kSCal2 | K Sensor Gap S2 | Read | ||
| AV | 205 | MBC5_kTCal2 | K Sensor Gap T2 | Read | ||
| AV | 206 | MBC5_h1R0 | H Coil 1 R0 | Read | ||
| AV | 207 | MBC5_h2R0 | H Coil 2 R0 | Read | ||
| AV | 208 | MBC5_hSCal1 | H Sensor Gap S1 | Read | ||
| AV | 209 | MBC5_hSCal2 | H Sensor Gap S2 | Read | ||
| AV | 210 | MBC3_jFDC_cur | J Fast Drop Count Now | Read | ||
| AV | 211 | MBC3_hFDC_cur | H Fast Drop Count Now | Read | ||
| AV | 212 | MBC3_kFDC_cur | K Fast Drop Count Now | Read | ||
| AV | 213 | MBC3_jFDC_lim | J Fast Drop Count Limit | Read | ||
| AV | 214 | MBC3_hFDC_lim | H Fast Drop Count Limit | Read | ||
| AV | 215 | MBC3_kFDC_lim | K Fast Drop Count Limit | Read | ||
| AV | 216 | QCK_EOL_cfgidst | MBC ID Status Value | Read | ||
| AV | 217 | MAIN_UPS_chg_lvl | Battery Charge Level | Read | ||
| AV | 218 | MAIMETER_CMECONDL | Calc Cond Level SP | Read | ||
| AV | 219 | MAIMETER_MEXV_TGT | Main EXV Tgt Position | Read | ||
| AV | 220 | MAIMETER_EEXV_TGT | Eco EXV Tgt Position | Read | ||
| AV | 221 | OUTPUTS_LQBP_TGT | EXCSV Target Pos Per | Read | ||
| BV | 1 | GENUNIT_statstop | Deter Start Stop Command | Read | ||
| BV | 2 | GENUNIT_CHIL_S_S_rd | Network:Cmd Start/Stop | Read | ||
| BV | 3 | GENUNIT_CHIL_OCC_rd | Network:Cmd Occupied | Read | ||
| BV | 4 | GENUNIT_HC_SEL_rd | Cooling/Heating Select | Read | ||
| BV | 5 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 6 | GENUNIT_loc_occ | Local Schedule Occupied | Read | ||
| BV | 7 | GENUNIT_ice_occ | Ice Schedule Occupied | Read | ||
| BV | 8 | GENUNIT_FC_START_rd | Start Free Cooling | Read | ||
| BV | 9 | GENUNIT_BAC_OCC | BACnet Occupied | Read | ||
| BV | 10 | INPUTS_STAR_AUX | Compressor Start Contact | Read | ||
| BV | 11 | INPUTS_HP_SW | High Pressure Switch | Read | ||
| BV | 12 | INPUTS_REM_CON | Remote Contact | Read | ||
| BV | 13 | INPUTS_E_STOP | Emergency Stop Contact | Read | ||
| BV | 14 | INPUTS_ICE_CON | Ice Build Contact | Read | ||
| BV | 15 | INPUTS_REM_LOCK | Chiller Lockout | Read | ||
| BV | 16 | INPUTS_SAFETY | Spare Safety Input | Read | ||
| BV | 17 | INPUTS_STARTFLT | Starter Fault Feedback | Read | ||
| BV | 18 | INPUTS_FS_LOCK | Fire Security Interlock | Read | ||
| BV | 19 | INPUTS_TRIPR | ISM Trip Relay Status | Read | ||
| BV | 21 | INPUTS_PGLE_LO | Purge Level Switch Low | Read | ||
| BV | 22 | INPUTS_PGLE_HI | Purge Level Switch High | Read | ||
| BV | 23 | INPUTS_HF_LS | Liquid Level Switch | Read | ||
| BV | 24 | OUTPUTS_ALM | Alarm Relay | Read | ||
| BV | 25 | OUTPUTS_ALE | Alert Relay | Read | ||
| BV | 26 | OUTPUTS_COMP_SR | Compressor Start Relay | Read | ||
| BV | 27 | OUTPUTS_GV1_DEC | Guide Vane 1 Decrease | Read | ||
| BV | 28 | OUTPUTS_GV1_INC | Guide Vane 1 Increase | Read | ||
| BV | 29 | OUTPUTS_OIL_HEAT | Oil Heater Relay | Read | ||
| BV | 30 | OUTPUTS_OIL_PUMP | Oil Pump Relay | Read | ||
| BV | 31 | OUTPUTS_TFR_HIGH | Tower Fan Relay High | Read | ||
| BV | 32 | OUTPUTS_TFR_LOW | Tower Fan Relay Low | Read | ||
| BV | 33 | OUTPUTS_ECON_IV | Economizer Isolation VLV | Read | ||
| BV | 34 | OUTPUTS_COND_CV | Condenser Control Valve | Read | ||
| BV | 35 | OUTPUTS_EVAP_CV | Evaporator Control Valve | Read | ||
| BV | 36 | OUTPUTS_EVAP_DCV | Evaporator Drain Valve | Read | ||
| BV | 37 | OUTPUTS_COND_DCV | Condenser Drain Valve | Read | ||
| BV | 38 | OUTPUTS_COND_PSV | Purge Cond Valve | Read | ||
| BV | 39 | OUTPUTS_COMP_PSV | Purge Comp Valve | Read | ||
| BV | 40 | OUTPUTS_DRASVON | Purge Drainage Valve | Read | ||
| BV | 41 | OUTPUTS_REG_PSV | Purge Regeneration Valve | Read | ||
| BV | 42 | OUTPUTS_DIS_PSV | Purge Discharge Valve | Read | ||
| BV | 43 | OUTPUTS_PGAPUMP | Purge Vacuum Pump | Read | ||
| BV | 44 | OUTPUTS_PG_COMP | Purge Compressor | Read | ||
| BV | 45 | OUTPUTS_PG_HEAT | Purge Heater | Read | ||
| BV | 46 | OUTPUTS_VS_SV | Vapor Source SV | Read | ||
| BV | 47 | OUTPUTS_FC_VALVE | Free Cooling Valve | Read | ||
| BV | 48 | OUTPUTS_COND_FCV | Condenser Filling Valve | Read | ||
| BV | 49 | HYDRLIC_CDWP | Condenser Water Pump | Read | ||
| BV | 50 | HYDRLIC_CDW_FLOW | Condenser Water Flow | Read | ||
| BV | 51 | HYDRLIC_CHWP | Chilled Water Pump | Read | ||
| BV | 52 | HYDRLIC_CHW_FLOW | Chilled Water Flow | Read | ||
| BV | 53 | POWER_O_prech_fd | Precharge Feedback | Read | ||
| BV | 54 | POWER_O_lrtem_sw | LR Temp Switch | Read | ||
| BV | 55 | POWER_O_spd_fd | SPD Feedback | Read | ||
| BV | 56 | POWER_O_VFDC_HI | High VFD Current | Read | ||
| BV | 57 | MAIN_SRD_diffault | Diffuser Fault | Read | ||
| BV | 58 | MAIN_SRD_diff_alm | SRD Rotating Stall Alarm | Read | ||
| BV | 59 | MAIN_MS_ll_comm | Lead Lag Communication | Read | ||
| BV | 60 | MAIN_MS_lag_s_s | Secondary Start/Stop | Read | ||
| BV | 61 | LABONLY_gv1_fc | GV1 Forced | Read | ||
| BV | 62 | LABONLY_gv2_fc | GV2 Forced | Read | ||
| BV | 63 | CONNECT_bacena | BACnet/IP Enable | Read | ||
| BV | 64 | CONNECT_bacunit | BACnet Metric Unit | Read | ||
| BV | 65 | SETPOINT_EWT_OPT | EWT Control Option | Write | ||
| BVmin | 66 | GENUNIT_CHIL_S_S_wr | Chiller Start/Stop | Write | ||
| BVmin | 67 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| BVmin | 68 | GENUNIT_CHIL_OCC_wr | Chiller Occupied? | Write | ||
| BV | 69 | GENUNIT_FC_START_wr | Start Free Cooling | Write | ||
| BV | 70 | OUTPUTS_RUN_STAT | Chiller Status (Discrete) | Read | ||
| BV | 75 | MBC_Alert | General Alert for MBC | Read | ||
| BV | 76 | MBC_Alarm | General Alarm for MBC | Read | ||
| BV | 77 | MAIN_UPS_charging | Battery Charging | Read | ||
| BV | 78 | MAIN_UPS_bat_full | Battery Fully Charged | Read | ||
| MVmin | 1 | GENUNIT_ctl_mode | Control Mode | Read | ||
| MV | 2 | INPUTS_DMP_ACT | Damper Valve Status | Read | ||
| MV | 3 | INPUTS_HGBP_ACT | EC Valve Status | Read | ||
| MV | 4 | FACTORY_chil_typ | Chiller Type | Read | ||
| MV | 5 | FACTORY_vfd_opt | VFD/Starter Option | Read | ||
| MV | 6 | CONF_OPT_hgbp_opt | EXVSV Valve Option | Read | ||
| MV | 7 | CONF_OPT_hgbp_sel | EXVSV Selection | Read | ||
| MV | 8 | BACnet_COLOR | Operation Status Color | Read | ||
| MV | 9 | MODES_cm_stat1 | Comp1 Run State Val | Read | ||
| MV | 10 | MBC_flags0 | MBC Levitate Status | Read | ||
| MV | 11 | FACTORY_lub_typ | Lubrication Type | Read |
No points match these filters.
Integration notes
- Objects marked Read/Write in the PV ACCESS column are mapped as writable; everything else is read-only.
- No units column; values follow the BACnet Metric Unit setting (bacunit, default No).
- The manual codes equipment status as a number (AV 7 GENUNIT_ch_state, "Chiller Status Code", appears to carry it): 1 Off, 2 Control Test, 3 Pumpdown, 4 Lockout, 5 Recycle, 6 Tripout, 7 Timeout, 8 Prestart, 9 Start-up, 10 Autorst, 11 Ramping, 12 Running, 13 Override, 14 Demand, 15 Shutdown, 16 Freecool, 17 Condflsh.
- Alarm state codes per the manual: 0 Normal, 1 Partial (Alert), 2 Shutdown (Alarm).
- The protocol appendix text refers to the "19XR PIC6"; the object table is the one printed in the 19MV manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19MV (PIC6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaEdge 19MV (PIC6)
How many BACnet points does the Carrier AquaEdge 19MV (PIC6) have?
This list has 299 BACnet objects: 215 analog values, 73 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaEdge 19MV (PIC6) BACnet points are writable?
14 of the 299 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaEdge 19MV (PIC6) BACnet documentation?
The source is AquaEdge 19MV Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed Intelligence, PIC6 Controls - Controls Operation and Troubleshooting (Appendix C, Table C BACnet Object Table) (19MV-CLT-3T), revision 7-25, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/09/19MV-CLT-3T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaEdge 19MV (PIC6)?
Start with BV 66 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 68 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 67 GENUNIT_EMSTOP_wr (Emergency stop command); AV 147 GENUNIT_CTRL_PNT_wr (Control point command); AV 148 GENUNIT_DEM_LIM_wr (Demand limit command); MV 1 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 7 GENUNIT_ch_state (Chiller status code); AV 9 TEMP_LCW (Leaving chilled water temperature); AV 8 TEMP_ECW (Entering chilled water temperature); AV 85 ALARMRST_alarm_1 (Current alarm 1).
How do I enable BMS control of the Carrier AquaEdge 19MV (PIC6)?
In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP or the HMI to shut it down.
How do I check these points on the real AquaEdge 19MV (PIC6)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaEdge 19MV Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed Intelligence, PIC6 Controls - Controls Operation and Troubleshooting (Appendix C, Table C BACnet Object Table) · 19MV-CLT-3T · rev. 7-25. Object names, instances and units are reproduced as published; descriptions are our own.