Water-cooled centrifugal chiller controller · BACnet points list

Carrier AquaEdge 19MV (PIC6) BACnet points list

Updated 28 October 2026

Short answer

The 19MV's PIC6 controller offers BACnet MS/TP on RS-485 port J8 or BACnet IP on Ethernet port J15, with about 300 AV, BV and MV objects named after their CCN table and point. Commands use paired read (_rd) and write (_wr) objects for start/stop, occupancy, control point, demand limit, emergency stop, free cooling and heat/cool select. It repeats 228 of the 19DV PIC6 objects (all but the BACnet dongle input) and adds about 70 more, mostly magnetic bearing controller (MBC) points plus UPS battery, EXV and liquid bypass points.

This page lists 299 BACnet objects for the Carrier AquaEdge 19MV (PIC6) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaEdge 19MV (PIC6)
Equipment
Water-cooled centrifugal chiller controller
Equipment type
Chillers
BACnet objects
299 (14 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
1600001
Also known as
19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller
Source document
AquaEdge 19MV Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed Intelligence, PIC6 Controls - Controls Operation and Troubleshooting (Appendix C, Table C BACnet Object Table) · 19MV-CLT-3T · rev. 7-25
Download CSV 299 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaEdge 19MV (PIC6)

Integration in brief

Enable BACnet in the CONNECT (BMS Protocol) menu: J8 option for MS/TP or BACnet Enable for BACnet IP. Set the identifier and network, and put the chiller in NETWORK control mode. The chiller then starts when both BV 66 start/stop and BV 68 occupancy are true; write control point and demand limit through the _wr objects and read status, water temperatures and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 66GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 68GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
BV 67GENUNIT_EMSTOP_wrEmergency stop commandWrite
AV 147GENUNIT_CTRL_PNT_wrControl point commandWrite
AV 148GENUNIT_DEM_LIM_wrDemand limit commandWrite
MV 1GENUNIT_ctl_modeControl mode: Local, Network, Remote, Local SchedRead
AV 7GENUNIT_ch_stateChiller status codeRead
AV 9TEMP_LCWLeaving chilled water temperatureRead
AV 8TEMP_ECWEntering chilled water temperatureRead
AV 85ALARMRST_alarm_1Current alarm 1Read

Enable & remote start

In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP or the HMI to shut it down.

Network setup

Watch out for

Carrier AquaEdge 19MV (PIC6) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

299 of 299 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaEdge 19MV (PIC6) BACnet Points List
DescriptionStates
AV1GENUNIT_CTRL_PNT_rdControl PointRead
AV2GENUNIT_resetControl Point ResetRead
AV3GENUNIT_setpointActual SetpointRead
AV4GENUNIT_AMPS_PPercent CurrentRead
AV5GENUNIT_KW_PMotor Percent KilowattsRead
AV6GENUNIT_DEM_LIM_rdActual Demand LimitRead
AVmin7GENUNIT_ch_stateChiller Status CodeRead
AVmin8TEMP_ECWEntering Chilled WaterRead
AVmin9TEMP_LCWLeaving Chilled WaterRead
AV10TEMP_ECDWEntering Condenser WaterRead
AV11TEMP_LCDWLeaving Condenser WaterRead
AV12TEMP_HR_EWTHeat Recl Entering TempRead
AV13TEMP_HR_LWTHeat Recl Leaving TempRead
AV14TEMP_EVAP_SATEvap Sat Refrig TempRead
AV15TEMP_EVAP_TEvap Refrig Liquid TempRead
AV16TEMP_evap_appEvaporator ApproachRead
AV17TEMP_cond_appCondenser ApproachRead
AV18TEMP_COND_SATCond Sat Refrig TempRead
AV19TEMP_DGTComp Discharge TempRead
AV20TEMP_DSHDischarge SuperheatRead
AV21TEMP_MTRB_OILThrust Bearing Oil TempRead
AV22TEMP_MTRBThrust Bearing TempRead
AV23TEMP_MTRB1Low Speed ME Brg TempRead
AV24TEMP_MTRB2Low Speed CE Brg TempRead
AV25TEMP_MTRB3High Speed ME Brg TempRead
AV26TEMP_MTRB4High Speed CE Brg TempRead
AV27TEMP_MTRW1Motor Winding 1 TempRead
AV28TEMP_MTRW2Motor Winding 2 TempRead
AV29TEMP_MTRW3Motor Winding 3 TempRead
AV30TEMP_OILT_SMPOil Sump TempRead
AV31TEMP_OILT_DISOil Supply TempRead
AV32TEMP_PGC_SUCTPurge Comp Suction TempRead
AV33TEMP_CBH1_T1st Stage Bearing TempRead
AV34TEMP_CBH2_T2nd Stage Bearing TempRead
AV36PRESSURE_EVAP_PEvaporator PressureRead
AV37PRESSURE_COND_PCondenser PressureRead
AV38PRESSURE_ECON_PEconomizer PressureRead
AV39PRESSURE_OIL_PDOil Pump Delta PRead
AV40PRESSURE_DIFF_PDiffuser PressureRead
AV41PRESSURE_HEAD_PHead Pressure ReferenceRead
AV42PRESSURE_REF_PDBearing Delta PRead
AV43PRESSURE_PUMP_PDRef Pump Delta PRead
AV44INPUTS_GV1_ACTGuide Vane 1 Actual PosRead
AV45INPUTS_GV2_ACTGuide Vane 2 Actual PosRead
AV46INPUTS_VFD_ACTActual VFD Speed PerRead
AV47INPUTS_DIFF_ACTDiffuser Actual PosRead
AV48INPUTS_HGBPACTPActual ECV Pos PerRead
AV49OUTPUTS_DIFF_OUTDiffuser Output mARead
AV50OUTPUTS_HDPV_OUTHead Pres Output mARead
AV51OUTPUTS_CHST_OUTChiller Stat Output mARead
AV52OUTPUTS_VFD_OUTVFD Speed Output mARead
AV53OUTPUTS_EXV_OUTOil EXV Output mARead
AV54OUTPUTS_llc_exvtLiquid Level EXV TargetRead
AV55OUTPUTS_op_vfd_tOil Pump VFD TargetRead
AV56OUTPUTS_GV1_OUTGuide Vane1 OutputRead
AV57OUTPUTS_GV2_OUTGuide Vane2 OutputRead
AV58HYDRLIC_CDW_FVCond Water Flow ValueRead
AV59HYDRLIC_cdw_pdCondenser Water Delta PRead
AV60HYDRLIC_CHW_FVChilled Water Flow ValueRead
AV61HYDRLIC_chw_pdChilled Water Delta PRead
AV62HYDRLIC_ctrlw_dtControlled Water DTRead
AV63RUNTIME_C_STARTSCompressor Starts NumRead
AV64RUNTIME_COMP_HRSCompressor Running HrsRead
AV65RUNTIME_SRV_HRSAfter Service HrsRead
AV66POWER_I_AMPS_A_IActual Line CurrentRead
AV67POWER_I_AMPS_P_IPercent Line CurrentRead
AV68POWER_I_VOLT_AActual Line VoltageRead
AV69POWER_I_VOLT_PPercent Line VoltageRead
AV70POWER_I_KWLine KilowattsRead
AV71POWER_I_POW_FACTLine Power FactorRead
AV72POWER_I_ln_imb_vLine Voltage Imbalance%Read
AV73POWER_O_VFD_LOADVFD Load CurrentRead
AV74POWER_O_amps_p_oPercent VFD Load CurrentRead
AV75POWER_O_MOT_FREQMotor Actual FrequencyRead
AV76POWER_O_bus_voltDC Bus VoltageRead
AV77POWER_O_vfd_actActual VFD Speed PerRead
AV78POWER_O_motor_pfMotor Power FactorRead
AV79POWER_O_motor_kwMotor KilowattsRead
AV80POWER_O_motorkwhMotor Kilowatt-HoursRead
AV81POWER_O_enc_tempVFD Enclosure TempRead
AV82POWER_O_inv_tempInverter TemperatureRead
AV83POWER_O_rec_tempRectifier TemperatureRead
AV84POWER_O_alm_codeVFD Alarm CodeRead
AVmin85ALARMRST_alarm_1Jbus Current Alarm 1Read
AV86ALARMRST_alarm_2Jbus Current Alarm 2Read
AV87ALARMRST_alarm_3Jbus Current Alarm 3Read
AV88ALARMRST_alarm_4Jbus Current Alarm 4Read
AV89ALARMRST_alarm_5Jbus Current Alarm 5Read
AV90CAPACTRL_ctrl_wtControlled Water TempRead
AV91CAPACTRL_gv1_tgtTarget GV1 PosRead
AV92CAPACTRL_gv2_tgtTarget GV2 PosRead
AV93CAPACTRL_vfd_tgtTarget VFD Speed PerRead
AV94CAPACTRL_hgbp_tpEXCSV Surge Pro TargetRead
AV95CAPACTRL_cm_stat1Comp1 Run State ValRead
AV96MAISURGE_act_regSurge RegionRead
AV97MAISURGE_dts_actActual Delta TsatRead
AV98MAISURGE_dts_calCalc Ref Delta TsatRead
AV99MAISURGE_scSurge CountsRead
AV100MAISURGE_spcSurge Protection CountsRead
AV101MAISURGE_surg_actSurge Prevention ActiveRead
AV102MAISURGE_surg_proSurge Protection ActiveRead
AV103MAISURGE_dts_maxcCal Surge Delta TsmaxRead
AV104MAISURGE_dts_mincCal Surge Delta TsminRead
AV105MAISURGE_dts_medcCal Surge Delta TsmedRead
AV106MAISURGE_gv1_sfulIGV1 Full Load PositionRead
AV107MAISURGE_gv1_sminIGV1 Minimum PositionRead
AV108MAISURGE_gv1_smedOpti-Sound IGV1 PositionRead
AV109MAISURGE_enlp_optEnvelope Line OptimizedRead
AV110QCK_TEST_Q_GV1ACTGuide Vane 1 Actual PosRead
AV111QCK_TEST_Q_DIFTGTDiffuser Target PosRead
AV112MAIN_SRD_diff_tgtDiffuser Target PosRead
AV113MAIN_SRD_lift_aActual LiftRead
AV114MAIN_SRD_lift_1VDO High Lift Load LineRead
AV115MAIN_SRD_lift_2VDO Low Lift Load LineRead
AV116MAIN_MS_lead_lagUnit is Lead or LagRead
AV117MAIN_MS_ms_ctrlPrimary Control TypeRead
AV118MAIN_MS_sl_ctrlSecondary Control TypeRead
AV119MAIN_MS_ll_faultPrimary Secondary FaultRead
AV120MAIN_MS_lagstatSecondary Run StatusRead
AV121MAIN_MS_lagstartLag Start TimerRead
AV122MAIN_MS_lagstopLag Stop TimerRead
AV123MAIN_MS_prefltPrestart Fault TimerRead
AV124MAIN_MS_pulltimePulldown TimerRead
AV125MAIN_MS_ll_hr_dLead/Lag Hours DeltaRead
AV126CFGSURGE_gv1_pminIGV1 Minimum PositionRead
AV127CFGSURGE_gv1_pfulIGV1 Full Load PositionRead
AV128CFGSURGE_sgl_offSurge Line OffsetRead
AV129CFGSURGE_sgl_loffSurge Line Lower DBRead
AV130CFGSURGE_sgl_hoffSurge Line Upper DBRead
AV131CFGSURGE_sgl_shfhSurge Line Shape FactorRead
AV132CFGSURGE_sgl_shflSound Line Shape FactorRead
AV133CFGSURGE_sgl_spdfSurge Line Speed FactorRead
AV134CFGSURGE_sgl_proSurge Profile OffsetRead
AV135CONF_PRG_oil_qlyOil QualityRead
AV136CONF_PRG_oil_fltOil Filter FailureRead
AV137CONF_PRG_tran_devTransducer DeviationRead
AV138CONF_PRG_ref_chgRefrig Charge StatusRead
AV139CONNECT_networkBACnet NetworkRead
AV140CONNECT_bac_idBACnet IdentifierRead
AV141SETPOINT_ecw_spCooling ECW SetpointWrite
AV142SETPOINT_lcw_spCooling LCW SetpointWrite
AV143SETPOINT_ecdw_spHeating ECDW SetpointWrite
AV144SETPOINT_lcdw_spHeating LCDW SetpointWrite
AV145SETPOINT_ice_spIce Build SetpointWrite
AV146SETPOINT_dem_baseBase Demand LimitWrite
AVmin147GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin148GENUNIT_DEM_LIM_wrDemand LimitWrite
AV149GENUNIT_HC_SEL_wrHeatcool SelectWrite
AV150BACnet_PRIME_VValue of Prime variableRead
AV151RUNTIME_ST_CNT12Starts Num in 12 HoursRead
AV152POWER_I_ln_imb_iLine Current Imbalance%Read
AV153RUNTIME_PGP_NOTotal Pumpout NumbersRead
AV154RUNTIME_PGP_TMTotal Pumpout TimeRead
AV155RUNTIME_pgp_tm_wAvg Daily Purge in 7 DayRead
AV160INPUTS_COND_LSLiquid Level CondRead
AV161OUTPUTS_LQBPtgtVEXCSV Target Pos voltRead
AV162EXVCTRL_MEXV_CMDMain EXV Position CmdRead
AV163EXVCTRL_EEXV_CMDECO EXV Position CmdRead
AV165MBC_RPMRotational Shaft SpeedRead
AV166MBC_SpeedHZ0Sync Speen (Hz)Read
AV167MBC_jAvGpChgJ Average Gap ChangeRead
AV168MBC_hAvGpChgH Average Gap ChangeRead
AV169MBC_kAvGpChgK Average Gap ChangeRead
AV170MBC_jxAvgJ Average Position XRead
AV171MBC_jyAvgJ Average Position YRead
AV172MBC_hzAvgH Average PositionRead
AV173MBC_kxAvgK Average Position XRead
AV174MBC_kyAvgK Average Position YRead
AV175MBC_tempC01J Bearing Coil TempRead
AV176MBC_tempC02H Outboard Coil TempRead
AV177MBC_tempC03H Inboard Coil TempRead
AV178MBC_tempC04K Bearing Coil TempRead
AV179MBC_tempC05Coldplate TempRead
AV180MBC_j1ImeasJ1 Coil CurrentRead
AV181MBC_j2ImeasJ2 Coil CurrentRead
AV182MBC_j3ImeasJ3 Coil CurrentRead
AV183MBC_j4ImeasJ4 Coil CurrentRead
AV184MBC_k1ImeasK1 Coil CurrentRead
AV185MBC_k2ImeasK2 Coil CurrentRead
AV186MBC_k3ImeasK3 Coil CurrentRead
AV187MBC_k4ImeasK4 Coil CurrentRead
AV188MBC_h1measH1 Coil CurrentRead
AV189MBC_h2measH2 Coil CurrentRead
AV190MBC5_j1R0J Coil 1 R0Read
AV191MBC5_j2R0J Coil 2 R0Read
AV192MBC5_j3R0J Coil 3 R0Read
AV193MBC5_j4R0J Coil 4 R0Read
AV194MBC5_jSCal1J Sensor Gap S1Read
AV195MBC5_jTCal1J Sensor Gap T1Read
AV196MBC5_jSCal2J Sensor Gap S2Read
AV197MBC5_jTCal2J Sensor Gap T2Read
AV198MBC5_k1R0K Coil 1 R0Read
AV199MBC5_k2R0K Coil 2 R0Read
AV200MBC5_k3R0K Coil 3 R0Read
AV201MBC5_k4R0K Coil 4 R0Read
AV202MBC5_kSCal1K Sensor Gap S1Read
AV203MBC5_kTCal1K Sensor Gap T1Read
AV204MBC5_kSCal2K Sensor Gap S2Read
AV205MBC5_kTCal2K Sensor Gap T2Read
AV206MBC5_h1R0H Coil 1 R0Read
AV207MBC5_h2R0H Coil 2 R0Read
AV208MBC5_hSCal1H Sensor Gap S1Read
AV209MBC5_hSCal2H Sensor Gap S2Read
AV210MBC3_jFDC_curJ Fast Drop Count NowRead
AV211MBC3_hFDC_curH Fast Drop Count NowRead
AV212MBC3_kFDC_curK Fast Drop Count NowRead
AV213MBC3_jFDC_limJ Fast Drop Count LimitRead
AV214MBC3_hFDC_limH Fast Drop Count LimitRead
AV215MBC3_kFDC_limK Fast Drop Count LimitRead
AV216QCK_EOL_cfgidstMBC ID Status ValueRead
AV217MAIN_UPS_chg_lvlBattery Charge LevelRead
AV218MAIMETER_CMECONDLCalc Cond Level SPRead
AV219MAIMETER_MEXV_TGTMain EXV Tgt PositionRead
AV220MAIMETER_EEXV_TGTEco EXV Tgt PositionRead
AV221OUTPUTS_LQBP_TGTEXCSV Target Pos PerRead
BV1GENUNIT_statstopDeter Start Stop CommandRead
BV2GENUNIT_CHIL_S_S_rdNetwork:Cmd Start/StopRead
BV3GENUNIT_CHIL_OCC_rdNetwork:Cmd OccupiedRead
BV4GENUNIT_HC_SEL_rdCooling/Heating SelectRead
BV5GENUNIT_EMSTOP_rdEmergency StopRead
BV6GENUNIT_loc_occLocal Schedule OccupiedRead
BV7GENUNIT_ice_occIce Schedule OccupiedRead
BV8GENUNIT_FC_START_rdStart Free CoolingRead
BV9GENUNIT_BAC_OCCBACnet OccupiedRead
BV10INPUTS_STAR_AUXCompressor Start ContactRead
BV11INPUTS_HP_SWHigh Pressure SwitchRead
BV12INPUTS_REM_CONRemote ContactRead
BV13INPUTS_E_STOPEmergency Stop ContactRead
BV14INPUTS_ICE_CONIce Build ContactRead
BV15INPUTS_REM_LOCKChiller LockoutRead
BV16INPUTS_SAFETYSpare Safety InputRead
BV17INPUTS_STARTFLTStarter Fault FeedbackRead
BV18INPUTS_FS_LOCKFire Security InterlockRead
BV19INPUTS_TRIPRISM Trip Relay StatusRead
BV21INPUTS_PGLE_LOPurge Level Switch LowRead
BV22INPUTS_PGLE_HIPurge Level Switch HighRead
BV23INPUTS_HF_LSLiquid Level SwitchRead
BV24OUTPUTS_ALMAlarm RelayRead
BV25OUTPUTS_ALEAlert RelayRead
BV26OUTPUTS_COMP_SRCompressor Start RelayRead
BV27OUTPUTS_GV1_DECGuide Vane 1 DecreaseRead
BV28OUTPUTS_GV1_INCGuide Vane 1 IncreaseRead
BV29OUTPUTS_OIL_HEATOil Heater RelayRead
BV30OUTPUTS_OIL_PUMPOil Pump RelayRead
BV31OUTPUTS_TFR_HIGHTower Fan Relay HighRead
BV32OUTPUTS_TFR_LOWTower Fan Relay LowRead
BV33OUTPUTS_ECON_IVEconomizer Isolation VLVRead
BV34OUTPUTS_COND_CVCondenser Control ValveRead
BV35OUTPUTS_EVAP_CVEvaporator Control ValveRead
BV36OUTPUTS_EVAP_DCVEvaporator Drain ValveRead
BV37OUTPUTS_COND_DCVCondenser Drain ValveRead
BV38OUTPUTS_COND_PSVPurge Cond ValveRead
BV39OUTPUTS_COMP_PSVPurge Comp ValveRead
BV40OUTPUTS_DRASVONPurge Drainage ValveRead
BV41OUTPUTS_REG_PSVPurge Regeneration ValveRead
BV42OUTPUTS_DIS_PSVPurge Discharge ValveRead
BV43OUTPUTS_PGAPUMPPurge Vacuum PumpRead
BV44OUTPUTS_PG_COMPPurge CompressorRead
BV45OUTPUTS_PG_HEATPurge HeaterRead
BV46OUTPUTS_VS_SVVapor Source SVRead
BV47OUTPUTS_FC_VALVEFree Cooling ValveRead
BV48OUTPUTS_COND_FCVCondenser Filling ValveRead
BV49HYDRLIC_CDWPCondenser Water PumpRead
BV50HYDRLIC_CDW_FLOWCondenser Water FlowRead
BV51HYDRLIC_CHWPChilled Water PumpRead
BV52HYDRLIC_CHW_FLOWChilled Water FlowRead
BV53POWER_O_prech_fdPrecharge FeedbackRead
BV54POWER_O_lrtem_swLR Temp SwitchRead
BV55POWER_O_spd_fdSPD FeedbackRead
BV56POWER_O_VFDC_HIHigh VFD CurrentRead
BV57MAIN_SRD_diffaultDiffuser FaultRead
BV58MAIN_SRD_diff_almSRD Rotating Stall AlarmRead
BV59MAIN_MS_ll_commLead Lag CommunicationRead
BV60MAIN_MS_lag_s_sSecondary Start/StopRead
BV61LABONLY_gv1_fcGV1 ForcedRead
BV62LABONLY_gv2_fcGV2 ForcedRead
BV63CONNECT_bacenaBACnet/IP EnableRead
BV64CONNECT_bacunitBACnet Metric UnitRead
BV65SETPOINT_EWT_OPTEWT Control OptionWrite
BVmin66GENUNIT_CHIL_S_S_wrChiller Start/StopWrite
BVmin67GENUNIT_EMSTOP_wrEmergency StopWrite
BVmin68GENUNIT_CHIL_OCC_wrChiller Occupied?Write
BV69GENUNIT_FC_START_wrStart Free CoolingWrite
BV70OUTPUTS_RUN_STATChiller Status (Discrete)Read
BV75MBC_AlertGeneral Alert for MBCRead
BV76MBC_AlarmGeneral Alarm for MBCRead
BV77MAIN_UPS_chargingBattery ChargingRead
BV78MAIN_UPS_bat_fullBattery Fully ChargedRead
MVmin1GENUNIT_ctl_modeControl ModeRead
MV2INPUTS_DMP_ACTDamper Valve StatusRead
MV3INPUTS_HGBP_ACTEC Valve StatusRead
MV4FACTORY_chil_typChiller TypeRead
MV5FACTORY_vfd_optVFD/Starter OptionRead
MV6CONF_OPT_hgbp_optEXVSV Valve OptionRead
MV7CONF_OPT_hgbp_selEXVSV SelectionRead
MV8BACnet_COLOROperation Status ColorRead
MV9MODES_cm_stat1Comp1 Run State ValRead
MV10MBC_flags0MBC Levitate StatusRead
MV11FACTORY_lub_typLubrication TypeRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19MV (PIC6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaEdge 19MV (PIC6)

How many BACnet points does the Carrier AquaEdge 19MV (PIC6) have?

This list has 299 BACnet objects: 215 analog values, 73 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaEdge 19MV (PIC6) BACnet points are writable?

14 of the 299 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaEdge 19MV (PIC6) BACnet documentation?

The source is AquaEdge 19MV Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed Intelligence, PIC6 Controls - Controls Operation and Troubleshooting (Appendix C, Table C BACnet Object Table) (19MV-CLT-3T), revision 7-25, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/09/19MV-CLT-3T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaEdge 19MV (PIC6)?

Start with BV 66 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 68 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 67 GENUNIT_EMSTOP_wr (Emergency stop command); AV 147 GENUNIT_CTRL_PNT_wr (Control point command); AV 148 GENUNIT_DEM_LIM_wr (Demand limit command); MV 1 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 7 GENUNIT_ch_state (Chiller status code); AV 9 TEMP_LCW (Leaving chilled water temperature); AV 8 TEMP_ECW (Entering chilled water temperature); AV 85 ALARMRST_alarm_1 (Current alarm 1).

How do I enable BMS control of the Carrier AquaEdge 19MV (PIC6)?

In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP or the HMI to shut it down.

How do I check these points on the real AquaEdge 19MV (PIC6)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaEdge 19MV Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed Intelligence, PIC6 Controls - Controls Operation and Troubleshooting (Appendix C, Table C BACnet Object Table) · 19MV-CLT-3T · rev. 7-25. Object names, instances and units are reproduced as published; descriptions are our own.