Air-cooled scroll chiller controller (BACnet option) · BACnet points list

Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet points list

Updated 28 October 2026

Short answer

On the 30RB, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. It publishes about 300 AV and BV objects (names ending in _1) covering start/stop, emergency stop, control point, demand limit, heat/cool select, setpoints, temperatures, pressures, compressor and fan status for up to three circuits, run hours and alarm state.

This page lists 302 BACnet objects for the Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaSnap 30RB 060-390 (UPC Open BACnet option)
Equipment
Air-cooled scroll chiller controller (BACnet option)
Equipment type
Chillers
BACnet objects
302 (36 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
Also known as
30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink
Source document
AquaSnap 30RB060-390 Air-Cooled Chillers and 30RB080-390 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix F, BACnet Communication Option, Network Points List) · 30RB-8T Rev. B · rev. 12-23
Download CSV 302 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)

Integration in brief

Address the UPC Open (rotary switches), set the MS/TP baud and protocol DIP switches, and configure the chiller for CCN control. The BMS then starts and stops the chiller with BV 1500 (CCN Chiller Start/Stop) and can write control point, demand limit and heat/cool select; read run status, leaving water temperature, capacity and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1500chil_s_s_1Network start/stop (Enable/Disable)Write
BV 68emstop_1Emergency stop commandWrite
AV 110hc_sel_1Heat/cool select: 0 Cool, 1 Heat, 2 AutoWrite
AV 96ctrl_pnt_1Control point (leaving water setpoint)Write
AV 1dem_lim_1Demand limit, 0-100 %Write
AV 137status_1Run status codeRead
AV 151lwt_1Leaving water temperatureRead
AV 1700cap_t_1Percent total capacityRead
AV 2alm_1Alarm state: 0 Normal, 1 Partial, 2 ShutdownRead

Enable & remote start

Set the Operating Control Type to 2 (CCN Control). An external CCN device then forces CHIL_S_S (BV 1500) between start and stop. The Status Unit Control Type reads 2 (CCN) when the Enable/Off/Remote Contact switch is On and 0 (Local Off) when it is Off.

Network setup

Watch out for

Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

302 of 302 shown
Type
AnalogBinary
Access
Show
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet Points List
DescriptionStates
AVmin1dem_lim_1Active Demand Limit Val%Write
AVmin2alm_1Alarm StateRead
AV3capt_010_1Chiller Capacity SignalvoltsRead
AV4cpa1_cur_1Cir A Crank Heater Current Cp1ampsRead
AV5cpa2_cur_1Cir A Crank Heater Current Cp2ampsRead
AV6cpa3_cur_1Cir A Crank Heater Current Cp3ampsRead
AV7cpa4_cur_1Cir A Crank Heater Current Cp4ampsRead
AV8exv_a_1Cir A EXV Position%Read
AV9fan_st_a_1Cir A Fan Staging NumberRead
AV10hd_pos_a_1Cir A Head Press Actuator Pos%Read
AV11cpa1_tmp_1Cir A Motor Thermistor Comp 1ohmsRead
AV12cpa2_tmp_1Cir A Motor Thermistor Comp 2ohmsRead
AV13cpa3_tmp_1Cir A Motor Thermistor Comp 3ohmsRead
AV14cpa4_tmp_1Cir A Motor Thermistor Comp 4ohmsRead
AV15capa_t_1Cir A Percent Total Capacity%Read
AV16suct_t_a_1Cir A Suction Gas Temperature°FRead
AV17sh_a_1Cir A Suction Superheat Temp°F (delta)Read
AV18cpb1_cur_1Cir B Crank Heater Current Cp1ampsRead
AV19cpb2_cur_1Cir B Crank Heater Current Cp2ampsRead
AV20cpb3_cur_1Cir B Crank Heater Current Cp3ampsRead
AV21cpb4_cur_1Cir B Crank Heater Current Cp4ampsRead
AV22exv_b_1Cir B EXV Position%Read
AV23fan_st_b_1Cir B Fan Staging NumberRead
AV24hd_pos_b_1Cir B Head Press Actuator Pos%Read
AV25cpb1_tmp_1Cir B Motor Thermistor Comp 1ohmsRead
AV26cpb2_tmp_1Cir B Motor Thermistor Comp 2ohmsRead
AV27cpb3_tmp_1Cir B Motor Thermistor Comp 3ohmsRead
AV28cpb4_tmp_1Cir B Motor Thermistor Comp 4ohmsRead
AV29capb_t_1Cir B Percent Total Capacity%Read
AV30sct_b_1Cir B Saturated Condensing Tmp°FRead
AV31sst_b_1Cir B Saturated Suction Temp°FRead
AV32suct_t_b_1Cir B Suction Gas Temperature°FRead
AV33sp_b_1Cir B Suction PressurepsiRead
AV34sh_b_1Cir B Suction Superheat TemppsiRead
AV35cpc1_cur_1Cir C Crank Heater Current Cp1ampsRead
AV36cpc2_cur_1Cir C Crank Heater Current Cp2ampsRead
AV37cpc3_cur_1Cir C Crank Heater Current Cp3ampsRead
AV38cpc4_cur_1Cir C Crank Heater Current Cp4ampsRead
AV39exv_c_1Cir C EXV Position%Read
AV40fan_st_c_1Cir C Fan Staging NumberRead
AV41hd_pos_c_1Cir C Head Press Actuator Pos%Read
AV42cpc1_tmp_1Cir C Motor Thermistor Comp 1ohmsRead
AV43cpc2_tmp_1Cir C Motor Thermistor Comp 2ohmsRead
AV44cpc3_tmp_1Cir C Motor Thermistor Comp 3ohmsRead
AV45cpc4_tmp_1Cir C Motor Thermistor Comp 4ohmsRead
AV46capc_t_1Cir C Percent Total Capacity%Read
AV47sct_c_1Cir C Saturated Condensing Tmp°FRead
AV48sst_c_1Cir C Saturated Suction Temp°FRead
AV49suct_t_c_1Cir C Suction Gas Temperature°FRead
AV50sp_c_1Cir C Suction PressurepsiRead
AV51sh_c_1Cir C Suction Superheat Temp°F (delta)Read
AV52hr_fana1_1Circuit A Fan #1 HourshoursRead
AV53hr_fana2_1Circuit A Fan #2 HourshoursRead
AV54hr_fana3_1Circuit A Fan #3 HourshoursRead
AV55hr_fana4_1Circuit A Fan #4 HourshoursRead
AV56hr_fana5_1Circuit A Fan #5 HourshoursRead
AV57hr_fana6_1Circuit A Fan #6 HourshoursRead
AV58hr_fanb1_1Circuit B Fan #1 HourshoursRead
AV59hr_fanb2_1Circuit B Fan #2 HourshoursRead
AV60hr_fanb3_1Circuit B Fan #3 HourshoursRead
AV61hr_fanb4_1Circuit B Fan #4 HourshoursRead
AV62hr_fanb5_1Circuit B Fan #5 HourshoursRead
AV63hr_fanb6_1Circuit B Fan #6 HourshoursRead
AV64hr_fanc1_1Circuit C Fan #1 HourshoursRead
AV65hr_fanc2_1Circuit C Fan #2 HourshoursRead
AV66hr_fanc3_1Circuit C Fan #3 HourshoursRead
AV67hr_fanc4_1Circuit C Fan #4 HourshoursRead
AV68hr_fanc5_1Circuit C Fan #5 HourshoursRead
AV69hr_fanc6_1Circuit C Fan #6 HourshoursRead
AV70lead_cir_1Circuit Loading SequenceWrite
AV71hr_cp_a1_1Compressor A1 HourshoursRead
AV72st_cp_a1_1Compressor A1 StartsRead
AV73hr_cp_a2_1Compressor A2 HourshoursRead
AV74st_cp_a2_1Compressor A2 StartsRead
AV75hr_cp_a3_1Compressor A3 HourshoursRead
AV76st_cp_a3_1Compressor A3 StartsRead
AV77hr_cp_a4_1Compressor A4 HourshoursRead
AV78st_cp_a4_1Compressor A4 StartsRead
AV79hr_cp_b1_1Compressor B1 HourshoursRead
AV80st_cp_b1_1Compressor B1 StartsRead
AV81hr_cp_b2_1Compressor B2 HourshoursRead
AV82st_cp_b2_1Compressor B2 StartsRead
AV83hr_cp_b3_1Compressor B3 HourshoursRead
AV84st_cp_b3_1Compressor B3 StartsRead
AV85hr_cp_b4_1Compressor B4 HourshoursRead
AV86st_cp_b4_1Compressor B4 StartsRead
AV87hr_cp_c1_1Compressor C1 HourshoursRead
AV88st_cp_c1_1Compressor C1 StartsRead
AV89hr_cp_c2_1Compressor C2 HourshoursRead
AV90st_cp_c2_1Compressor C2 StartsRead
AV91hr_cp_c3_1Compressor C3 HourshoursRead
AV92st_cp_c3_1Compressor C3 StartsRead
AV93hr_cp_c4_1Compressor C4 HourshoursRead
AV94st_cp_c4_1Compressor C4 StartsRead
AV95ctrl_wt_1Controlled Water Temp°FRead
AVmin96ctrl_pnt_1Control Point°FWrite
AV97flui_typ_1Cooler Fluid TypeRead
AV98pump_seq_1Cooler Pumps SequenceWrite
AV99ice_sp_1Cooling Ice Setpoint°FWrite
AV100cramp_sp_1Cooling Ramp Loading°F (delta)Write
AV101cr_deg_1Cooling Reset Deg. Value°FWrite
AV102csp1_1Cooling Setpoint 1°FWrite
AV103csp2_1Cooling Setpoint 2°FWrite
AV104v_cr_fu_1Current Full Reset ValuemaWrite
AV105v_cr_no_1Current No Reset ValuemaWrite
AV106dt_cr_fu_1Delta T Full Reset Value°F (delta)Write
AV107dt_cr_no_1Delta T No Reset Value°F (delta)Write
AV108lim_sel_1Demand Limit Type SelectWrite
AV109oat_1External Temperature°FRead
AVmin110hc_sel_1Heat/Cool SelectWrite
AV111heatcool_1Heat/Cool StatusRead
AV112hr_hpump_1Heat Reclaim Pump HourshoursRead
AV113lag_lim_1Lag Capacity Limit Value%Read
AV114lim_anal_1Limit 4-20mA SignalmaRead
AV115hr_mach_1Machine Operating HourshoursRead
AV116st_mach_1Machine Starts NumberRead
AV117lim_ze_1mA For 0% Demand LimitmAWrite
AV118lim_mx_1mA For 100% Demand LimitmAWrite
AV119ms_sel_1Master/Slave SelectWrite
AV120min_left_1Minutes Left for StartminRead
AV121oatcr_fu_1OAT Full Reset Value°FWrite
AV122oatcr_no_1OAT No Reset Value°FWrite
AV123spacetmp_1Optional Space Temp°FRead
AV124pump_del_1Pump Auto Rotation DelayhoursWrite
AV125pd_p_a_1Pumpdown Pressure Cir ApsiRead
AV126pd_p_b_1Pumpdown Pressure Cir BpsiRead
AV127hr_sat_a_1Pumpdown Saturated Tmp A°FRead
AV128hr_sat_b_1Pumpdown Saturated Tmp B°FRead
AV129hr_deadb_1Reclaim Deadband°F (delta)Write
AV130hr_ewt_1Reclaim Entering Fluid°FRead
AV131hr_lwt_1Reclaim Leaving Fluid°FRead
AV132rsp_1Reclaim Setpoint°FWrite
AV133hrstat_a_1Reclaim Status Circuit ARead
AV134hrstat_b_1Reclaim Status Circuit BRead
AV135hr_v_pos_1Reclaim Valve Position%Read
AV136sp_reset_1Reset/Setpoint 4-20mA InmaRead
AVmin137status_1Run StatusRead
AV138spacr_fu_1Space T Full Reset Value°FRead
AV139spacr_no_1Space T No Reset Value°FRead
AV140st_cp_av_1Starts/hr From Last 24 hRead
AV141st_cp_mx_1Starts Max During 1 HourRead
AV142hr_subta_1Sub Condenser Temp Cir A°FRead
AV143hr_subtb_1Sub Condenser Temp Cir B°FRead
AV144hr_subca_1Subcooling Temperature A°FRead
AV145hr_subcb_1Subcooling Temperature B°FRead
AV146lim_sp1_1Switch Limit Setpoint 1%Write
AV147lim_sp2_1Switch Limit Setpoint 2%Write
AV148lim_sp3_1Switch Limit Setpoint 3%Write
AV149off_on_d_1Unit Off to On DelayminWrite
AV150ewt_1Water Exchanger Entering Temp°FRead
AVmin151lwt_1Water Exchanger Leaving Temp°FRead
AV152hr_cpum1_1Water Pump #1 HourshoursRead
AV153hr_cpum2_1Water Pump #2 HourshoursRead
AV1600sp_a_1Cir A Suction PressurepsiRead
AV1601dp_a_1Cir A Discharge PressurepsiRead
AV1602sct_a_1Cir A Saturated Condensing Tmp°FRead
AV1603sst_a_1Cir A Saturated Suction Temp°FRead
AV1605dp_b_1Cir B Discharge PressurepsiRead
AV1609dp_c_1Cir C Discharge PressurepsiRead
AV1612chwstemp_1CHWS Temperature - Prime Variable°FRead
AVmin1700cap_t_1Percent Total Capacity%Read
AV2901user_analog_1_1User Defined Analog 1Read
AV2902user_analog_2_1User Defined Analog 2Read
AV2903user_analog_3_1User Defined Analog 3Read
AV2904user_analog_4_1User Defined Analog 4Read
AV2905user_analog_5_1User Defined Analog 5Read
AV3500chws_sp_1Current Setpoint°FRead
AV9006cool_demand_level_1System Cooling Demand LevelRead
AV80001mstr_oa_temp_1System OAT MasterRead
BV2schedule_1Local ScheduleRead
BV3dem_lmt_act_1System Demand LimitingRead
BV4hr_ea_a_1Air Cond Entering Valv AReadOn/Off
BV5hr_ea_b_1Air Cond Entering Valv BReadOn/Off
BV6hr_la_a_1Air Cond Leaving Valve AReadOn/Off
BV7hr_la_b_1Air Cond Leaving Valve BReadOn/Off
BV8alarmout_1Alarm Relay StatusReadOn/Off
BV9alert_1Alert Relay StatusReadOn/Off
BV10mode_12_1Auto Changeover ActiveReadYes/No
BV11mode_17_1Boiler ActiveReadYes/No
BV12boiler_1Boiler CommandReadOn/Off
BV13cp_a1_ht_1Cir A Compressor 1 Heater OutReadOn/Off
BV14cp_a1_1Cir A Compressor 1 OutputReadOn/Off
BV15cp_a2_ht_1Cir A Compressor 2 Heater OutReadOn/Off
BV16cp_a2_1Cir A Compressor 2 OutputReadOn/Off
BV17cp_a3_ht_1Cir A Compressor 3 Heater OutReadOn/Off
BV18cp_a3_1Cir A Compressor 3 OutputReadOn/Off
BV19cp_a4_ht_1Cir A Compressor 4 Heater OutReadOn/Off
BV20cp_a4_1Cir A Compressor 4 OutputReadOn/Off
BV21fan_a1_1Cir A Fan Output DO # 1ReadOn/Off
BV22fan_a2_1Cir A Fan Output DO # 2ReadOn/Off
BV23fan_a3_1Cir A Fan Output DO # 3ReadOn/Off
BV24fan_a4_1Cir A Fan Output DO # 4ReadOn/Off
BV25fan_a5_1Cir A Fan Output DO # 5ReadOn/Off
BV26fan_a6_1Cir A Fan Output DO # 6ReadOn/Off
BV27hgbp_v_a_1Cir A Hot Gas Bypass OutputReadOn/Off
BV28cp_b1_ht_1Cir B Compressor 1 Heater OutReadOn/Off
BV29cp_b1_1Cir B Compressor 1 OutputReadOn/Off
BV30cp_b2_ht_1Cir B Compressor 2 Heater OutReadOn/Off
BV31cp_b2_1Cir B Compressor 2 OutputReadOn/Off
BV32cp_b3_ht_1Cir B Compressor 3 Heater OutReadOn/Off
BV33cp_b3_1Cir B Compressor 3 OutputReadOn/Off
BV34cp_b4_ht_1Cir B Compressor 4 Heater OutReadOn/Off
BV35cp_b4_1Cir B Compressor 4 OutputReadOn/Off
BV36fan_b1_1Cir B Fan Output DO # 1ReadOn/Off
BV37fan_b2_1Cir B Fan Output DO # 2ReadOn/Off
BV38fan_b3_1Cir B Fan Output DO # 3ReadOn/Off
BV39fan_b4_1Cir B Fan Output DO # 4ReadOn/Off
BV40fan_b5_1Cir B Fan Output DO # 5ReadOn/Off
BV41fan_b6_1Cir B Fan Output DO # 6ReadOn/Off
BV42hgbp_v_b_1Cir B Hot Gas Bypass OutputReadOn/Off
BV43cp_c1_ht_1Cir C Compressor 1 Heater OutReadOn/Off
BV44cp_c1_1Cir C Compressor 1 OutputReadOn/Off
BV45cp_c2_ht_1Cir C Compressor 2 Heater OutReadOn/Off
BV46cp_c2_1Cir C Compressor 2 OutputReadOn/Off
BV47cp_c3_ht_1Cir C Compressor 3 Heater OutReadOn/Off
BV48cp_c3_1Cir C Compressor 3 OutputReadOn/Off
BV49cp_c4_ht_1Cir C Compressor 4 Heater OutReadOn/Off
BV50cp_c4_1Cir C Compressor 4 OutputReadOn/Off
BV51fan_c1_1Cir C Fan Output DO # 1ReadOn/Off
BV52fan_c2_1Cir C Fan Output DO # 2ReadOn/Off
BV53fan_c3_1Cir C Fan Output DO # 3ReadOn/Off
BV54fan_c4_1Cir C Fan Output DO # 4ReadOn/Off
BV55fan_c5_1Cir C Fan Output DO # 5ReadOn/Off
BV56fan_c6_1Cir C Fan Output DO # 6ReadOn/Off
BV57hgbp_v_c_1Cir C Hot Gas Bypass OutputReadOn/Off
BV58mode_06_1Cooler Heater ActiveReadYes/No
BV59coolheat_1Cooler Heater CommandReadOn/Off
BV60mode_07_1Cooler Pumps RotationReadYes/No
BV61critical_1Critical Alarm StatusReadOn/Off
BV62mode_19_1Defrost Active On Cir AReadYes/No
BV63mode_20_1Defrost Active On Cir BReadYes/No
BV64mode_04_1Demand Limit ActiveReadYes/No
BV65elec_box_1Electrical Box SafetyReadYes/No
BV66ehs_step_1Electrical Heat StageReadOpen/Close
BV67mode_15_1Electric Heat ActiveRead
BVmin68emstop_1Emergency StopWriteEnable/Disable
BV69pump_loc_1Flow Checked if Pump OffWriteYes/No
BV70mode_13_1Free Cooling ActiveReadYes/No
BV71fc_dsble_1Free Cooling Disable?ReadYes/No
BV72fc_sw_1Free Cooling Disable Sw.ReadYes/No
BV73mode_16_1Heating Low EWT LockoutReadYes/No
BV74recl_sel_1Heat Reclaim SelectWriteYes/No
BV75mode_24_1High DGT Circuit AReadYes/No
BV76mode_25_1High DGT Circuit BReadYes/No
BV77mode_26_1High DGT Circuit CReadYes/No
BV78mode_27_1High Pres Override Cir AReadYes/No
BV79mode_28_1High Pres Override Cir BReadYes/No
BV80mode_29_1High Pres Override Cir CReadYes/No
BV81ice_sw_1Ice Done Storage SwitchReadOpen/Close
BV82mode_18_1Ice Mode in EffectReadYes/No
BV83lock_1_1Interlock StatusReadOpen/Close
BV84lim_sw1_1Limit Switch 1 StatusReadOpen/Close
BV85lim_sw2_1Limit Switch 2 StatusReadOpen/Close
BV86mode_21_1Low Suction Circuit AReadYes/No
BV87mode_22_1Low Suction Circuit BReadYes/No
BV88mode_23_1Low Suction Circuit CReadYes/No
BV89mode_09_1Night Low Noise ActiveReadYes/No
BV90occ_ovsw_1Occupied Override SwitchReadOpen/Close
BV91onoff_sw_1On/Off - Remote SwitchReadOpen/Close
BV92all_pass_1Pass For All User ConfigWriteNo/Yes
BV93mode_08_1Pump Periodic StartReadYes/No
BV94pump_def_1Pump Run StatusReadOpen/Close
BV95pump_per_1Pump Sticking ProtectionWriteNo/Yes
BV96mode_05_1Ramp Loading ActiveReadYes/No
BV97ramp_sel_1Ramp Loading SelectWriteNo/Yes
BV98ready_1Ready or Running StatusReadOn/Off
BV99mode_14_1Reclaim ActiveReadYes/No
BV100condflow_1Reclaim Condenser FlowReadOn/Off
BV101cond_htr_1Reclaim Condenser HeaterReadOn/Off
BV102condpump_1Reclaim Condenser PumpReadOn/Off
BV103cond_pmp_1Reclaim Condenser PumpReadOn/Off
BV104hc_sw_1Remote Heat/Cool SwitchReadOpen/Close
BV105rem_lock_1Remote Interlock StatusReadOpen/Close
BV106recl_sw_1Remote Reclaim SwitchReadOpen/Close
BV107setp_sw_1Remote Setpoint SwitchReadOpen/Close
BV108mode_03_1Reset in EffectReadYes/No
BV109rot_pump_1Rotate Pumps Now?WriteYes/No
BV110running_1Running StatusReadOn/Off
BV111mode_02_1Second Setpoint in UseReadYes/No
BV112sp_occ_1Setpoint Occupied?ReadYes/No
BV113shutdown_1Shutdown Indicator StateReadOn/Off
BV114seq_typ_1Staged Loading SequenceWriteNo/Yes
BV115mode_01_1Startup Delay in EffectReadYes/No
BV116mode_30_1Superheat Override Cir AReadYes/No
BV117mode_31_1Superheat Override Cir BReadYes/No
BV118mode_32_1Superheat Override Cir CReadYes/No
BV119mode_10_1System Manager ActiveReadYes/No
BV120hr_ew_a_1Water Cond Enter Valve AReadOn/Off
BV121hr_ew_b_1Water Cond Enter Valve BReadOn/Off
BV122hr_lw_a_1Water Cond Leaving Val AReadOn/Off
BV123hr_lw_b_1Water Cond Leaving Val BReadOn/Off
BV124cpump_1_1Water Pump #1 CommandReadOn/Off
BV125cpump_2_1Water Pump #2 CommandReadOn/Off
BV146element_alarm_1Equipment AlarmRead
BVmin1500chil_s_s_1CCN Chiller Start/StopWriteEnable/Disable
BV1501chil_occ_1Chiller Occupied?ReadYes/No
BV2911user_binary_1_1User Defined Binary 1Read
BV2912user_binary_2_1User Defined Binary 2Read
BV2913user_binary_3_1User Defined Binary 3Read
BV2914user_binary_4_1User Defined Binary 4Read
BV2915user_binary_5_1User Defined Binary 5Read
BV2999element_stat_1Element Comm StatusRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RB 060-390 (UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)

How many BACnet points does the Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) have?

This list has 302 BACnet objects: 169 analog values, 133 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet points are writable?

36 of the 302 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet documentation?

The source is AquaSnap 30RB060-390 Air-Cooled Chillers and 30RB080-390 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix F, BACnet Communication Option, Network Points List) (30RB-8T Rev. B), revision 12-23, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/05/30RB-8T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)?

Start with BV 1500 chil_s_s_1 (Network start/stop (Enable/Disable)); BV 68 emstop_1 (Emergency stop command); AV 110 hc_sel_1 (Heat/cool select: 0 Cool, 1 Heat, 2 Auto); AV 96 ctrl_pnt_1 (Control point (leaving water setpoint)); AV 1 dem_lim_1 (Demand limit, 0-100 %); AV 137 status_1 (Run status code); AV 151 lwt_1 (Leaving water temperature); AV 1700 cap_t_1 (Percent total capacity); AV 2 alm_1 (Alarm state: 0 Normal, 1 Partial, 2 Shutdown).

How do I enable BMS control of the Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)?

Set the Operating Control Type to 2 (CCN Control). An external CCN device then forces CHIL_S_S (BV 1500) between start and stop. The Status Unit Control Type reads 2 (CCN) when the Enable/Off/Remote Contact switch is On and 0 (Local Off) when it is Off.

How do I check these points on the real AquaSnap 30RB 060-390 (UPC Open BACnet option)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaSnap 30RB060-390 Air-Cooled Chillers and 30RB080-390 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix F, BACnet Communication Option, Network Points List) · 30RB-8T Rev. B · rev. 12-23. Object names, instances and units are reproduced as published; descriptions are our own.