Air-cooled screw chiller controller · BACnet points list

Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) BACnet points list

Updated 28 October 2026

Short answer

The 30XV Carrier Controller has native BACnet IP on Ethernet-0 (J15) and BACnet MS/TP on RS485-4 (J8), with about 765 objects: AVs, BVs and a few MVs named after their CCN table and point. Commands are separate _rd (read) and _wr (write) objects; the writable copies are BV 123-129 and AV 552-554, plus the setpoint AVs 545-551. Each alarm has its own read-only BV (ALM_...).

This page lists 765 BACnet objects for the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Equipment
Air-cooled screw chiller controller
Equipment type
Chillers
BACnet objects
765 (20 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Carrier Controller software version 9.x
Default device instance
1600001
Also known as
30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed
Source document
AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier PIC6.1 Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP and MS/TP Points) · 30XV-6T · rev. 5-26
Download CSV 765 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)

Integration in brief

Enable BACnet (bacena), pick BACnet IP or MS/TP in the BACnet configuration menu, set the identifier and network number, then select the Network machine control method with the Start/Stop button. Command through the _wr objects (start/stop, occupancy, control point, demand limit, emergency stop) and read run status, water temperatures, capacity and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 123GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 129GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
AV 552GENUNIT_CTRL_PNT_wrLeaving water control point from the BMSWrite
AV 553GENUNIT_DEM_LIM_wrDemand limit commandWrite
AV 20GENUNIT_CTRL_TYPControl type: Local, Network or RemoteRead
AV 21GENUNIT_STATUSRunning statusRead
AV 30TEMP_COOL_LWTLeaving chilled water temperatureRead
AV 29TEMP_COOL_EWTEntering chilled water temperatureRead
AV 24GENUNIT_CAP_TPercent total capacityRead
AV 109ALARMRST_ALMUnit alarm stateRead

Enable & remote start

Select the Network machine control method with the Start/Stop button; the unit then follows network commands and ignores the remote control contacts and the Enable-Off-Remote switch (SW1). Start/stop and occupancy are written to the _wr objects. In Local On, Local Schedule or Remote the unit ignores network commands except emergency stop.

Heartbeat & communication loss

The manual says that if communication with the network is lost while under network control, the machine starts and is controlled locally.

Network setup

Watch out for

Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

765 of 765 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) BACnet Points List
DescriptionStates
AV1GENCONF_prio_cirCir Priority SequenceRead
AV2GENCONF_off_on_dUnit Off to On DelayRead
AV3GENCONF_lim_selDemand Limit Type SelectRead
AV4GENCONF_nh_startNight Mode Start HourRead
AV5GENCONF_nh_endNight Mode End HourRead
AV6GENCONF_nh_limitNight Capacity LimitRead
AV7PUMPCONF_cpumpseqEvap Pumps SequenceRead
AV8PUMPCONF_pump_delPump Auto Rotation DelayRead
AV9USERCONF_use_passUser PasswordWrite
AV10RESETCFG_cr_selCooling Reset SelectRead
AV11RESETCFG_oat_crnoOAT No Reset ValueRead
AV12RESETCFG_oat_crfuOAT Full Reset ValueRead
AV13RESETCFG_dt_cr_noDelta T No Reset ValueRead
AV14RESETCFG_dt_cr_fuDelta T Full Reset ValueRead
AV15RESETCFG_v_cr_noCurrent No Reset ValueRead
AV16RESETCFG_v_cr_fuCurrent Full Reset ValueRead
AV17RESETCFG_spacr_noSpace T No Reset ValueRead
AV18RESETCFG_spacr_fuSpace T Full Reset ValueRead
AV19RESETCFG_cr_degCooling Reset Deg. ValueRead
AVmin20GENUNIT_CTRL_TYPLocal=0 Net.=1 Remote=2Read
AVmin21GENUNIT_STATUSRun StatusRead
AV22GENUNIT_min_leftMinutes Left for StartRead
AV23GENUNIT_SP_SEL_rdSetpoint SelectRead
AVmin24GENUNIT_CAP_TPercent Total CapacityRead
AV25GENUNIT_SPCurrent SetpointRead
AV26GENUNIT_CTRL_PNT_rdControl PointRead
AV27GENUNIT_DEM_LIM_rdActive Demand Limit ValRead
AV28GENUNIT_min_limDemand Limit MinimumRead
AVmin29TEMP_COOL_EWTEvap Entering FluidRead
AVmin30TEMP_COOL_LWTEvap Leaving FluidRead
AV31TEMP_OATOutdoor Air TemperatureRead
AV32TEMP_SCT_ASaturated Cond Tmp Cir ARead
AV33TEMP_SST_ASaturated Suction Temp ARead
AV34TEMP_SLT_ASaturated Liquid Temp ARead
AV35TEMP_SUCT_ACompressor Suction Tmp ARead
AV36TEMP_DGT_ADischarge Gas Temp Cir ARead
AV37TEMP_CP_TMP_AMotor Temperature Cir ARead
AV38TEMP_ECO_T_AEXV Eco. Tmp Cir ARead
AV39TEMP_LIQ_T_ALiquid Temperature ARead
AV40TEMP_SCT_BSaturated Cond Tmp Cir BRead
AV41TEMP_SST_BSaturated Suction Temp BRead
AV42TEMP_SLT_BSaturated Liquid Temp BRead
AV43TEMP_SUCT_BCompressor Suction Tmp BRead
AV44TEMP_DGT_BDischarge Gas Temp Cir BRead
AV45TEMP_CP_TMP_BMotor Temperature Cir BRead
AV46TEMP_ECO_T_BEXV Eco. Tmp Cir BRead
AV47TEMP_LIQ_T_BLiquid Temperature BRead
AV48TEMP_SPACETMPSpace Temp (Opt.)Read
AV49TEMP_CHWSTEMPChill Water Temp (Opt.)Read
AV50PRESSURE_DP_ADischarge Pressure ARead
AV51PRESSURE_SP_AMain Suction Pressure ARead
AV52PRESSURE_OP_AOil Pressure ARead
AV53PRESSURE_DOP_ADelta Oil Pressure ARead
AV54PRESSURE_ECO_P_AEconomizer Pressure ARead
AV55PRESSURE_LIQ_P_ALiquid Pressure ARead
AV56PRESSURE_DP_BDischarge Pressure BRead
AV57PRESSURE_SP_BMain Suction Pressure BRead
AV58PRESSURE_OP_BOil Pressure BRead
AV59PRESSURE_DOP_BDelta Oil Pressure BRead
AV60PRESSURE_ECO_P_BEconomizer Pressure BRead
AV61PRESSURE_LIQ_P_BLiquid Pressure BRead
AV62INPUTS_SP_RESETRemote Reset SetpointRead
AV63INPUTS_LIM_ANALRemote Dem. LimitRead
AV64INPUTS_leak_vLeakage Detector 1Read
AV65INPUTS_leak_2_vLeakage Detector 2Read
AV66OUTPUTS_CAPT010ACapacity Signal Cir ARead
AV67OUTPUTS_VFAN_AVariFan Speed ARead
AV68OUTPUTS_CAPT010BCapacity Signal Cir BRead
AV69OUTPUTS_VFAN_BVariFan Speed BRead
AV70OUTPUTS_CAPT_010Chiller Capacity SignalRead
AV71RUNTIME_HR_MACHMachine Operating HoursRead
AV72RUNTIME_st_machMachine StartsRead
AV73RUNTIME_HR_CP_ACompressor A HoursRead
AV74RUNTIME_st_cp_aCompressor A StartsRead
AV75RUNTIME_HR_CP_BCompressor B HoursRead
AV76RUNTIME_st_cp_bCompressor B StartsRead
AV77RUNTIME_hr_cpum1Evap Pump #1 HoursRead
AV78RUNTIME_hr_cpum2Evap Pump #2 HoursRead
AV79RUNTIME_VIctAVI Cycle Count ARead
AV80RUNTIME_VIctBVI Cycle Count BRead
AV81RUNTIME_hrfana01Circuit A Fan #1 HoursRead
AV82RUNTIME_hrfana02Circuit A Fan #2 HoursRead
AV83RUNTIME_hrfana03Circuit A Fan #3 HoursRead
AV84RUNTIME_hrfana04Circuit A Fan #4 HoursRead
AV85RUNTIME_hrfana05Circuit A Fan #5 HoursRead
AV86RUNTIME_hrfana06Circuit A Fan #6 HoursRead
AV87RUNTIME_hrfana07Circuit A Fan #7 HoursRead
AV88RUNTIME_hrfana08Circuit A Fan #8 HoursRead
AV89RUNTIME_hrfana09Circuit A Fan #9 HoursRead
AV90RUNTIME_hrfana10Circuit A Fan #10 HoursRead
AV91RUNTIME_hrfana11Circuit A Fan #11 HoursRead
AV92RUNTIME_hrfana12Circuit A Fan #12 HoursRead
AV93RUNTIME_hrfana13Circuit A Fan #13 HoursRead
AV94RUNTIME_hrfana14Circuit A Fan #14 HoursRead
AV95RUNTIME_hrfanb01Circuit B Fan #1 HoursRead
AV96RUNTIME_hrfanb02Circuit B Fan #2 HoursRead
AV97RUNTIME_hrfanb03Circuit B Fan #3 HoursRead
AV98RUNTIME_hrfanb04Circuit B Fan #4 HoursRead
AV99RUNTIME_hrfanb05Circuit B Fan #5 HoursRead
AV100RUNTIME_hrfanb06Circuit B Fan #6 HoursRead
AV101RUNTIME_hrfanb07Circuit B Fan #7 HoursRead
AV102RUNTIME_hrfanb08Circuit B Fan #8 HoursRead
AV103RUNTIME_hrfanb09Circuit B Fan #9 HoursRead
AV104RUNTIME_hrfanb10Circuit B Fan #10 HoursRead
AV105RUNTIME_hrfanb11Circuit B Fan #11 HoursRead
AV106RUNTIME_hrfanb12Circuit B Fan #12 HoursRead
AV107RUNTIME_hrfanb13Circuit B Fan #13 HoursRead
AV108RUNTIME_hrfanb14Circuit B Fan #14 HoursRead
AVmin109ALARMRST_ALMAlarm StateRead
AV110ALARMRST_alarm_1Jbus Current Alarm 1Read
AV111ALARMRST_alarm_2Jbus Current Alarm 2Read
AV112ALARMRST_alarm_3Jbus Current Alarm 3Read
AV113ALARMRST_alarm_4Jbus Current Alarm 4Read
AV114ALARMRST_alarm_5Jbus Current Alarm 5Read
AV115VLT_DRV_drv_pwraCir A Drive PowerRead
AV116VLT_DRV_drv_IaCir A Drive AmpsRead
AV117VLT_DRV_drv_VaCir A Drive VoltageRead
AV118VLT_DRV_drv_SaCir A Drive SpeedRead
AV119VLT_DRV_drv_FaCir A Drive FrequencyRead
AV120VLT_DRV_drv_TaCir A Drive TorqueRead
AV121VLT_DRV_drv_DCVaCir A Drive DC Link VoltRead
AV122VLT_DRV_drv_HSTaCir A Drive Heat Sink TRead
AV123VLT_DRV_drv_CCTaCir A Drive Ctrl Card TRead
AV124VLT_DRV_drv_HTRaCir A Drive HeaterRead
AV125VLT_DRV_drv_pwrbCir B Drive PowerRead
AV126VLT_DRV_drv_IbCir B Drive AmpsRead
AV127VLT_DRV_drv_VbCir B Drive VoltageRead
AV128VLT_DRV_drv_SbCir B Drive SpeedRead
AV129VLT_DRV_drv_FbCir B Drive FrequencyRead
AV130VLT_DRV_drv_TbCir B Drive TorqueRead
AV131VLT_DRV_drv_DCVbCir B Drive DC Link VoltRead
AV132VLT_DRV_drv_HSTbCir B Drive Heat Sink TRead
AV133VLT_DRV_drv_CCTbCir B Drive Ctrl Card TRead
AV134VLT_DRV_drv_HTRbCir B Drive HeaterRead
AV135LAST_POR_date_on1Power On 1 :day-mon-yearRead
AV136LAST_POR_time_on1Power On 1 :hour-minuteRead
AV137LAST_POR_date_of1PowerDown 1:day-mon-yearRead
AV138LAST_POR_time_of1PowerDown 1:hour-minuteRead
AV139LAST_POR_date_on2Power On 2 :day-mon-yearRead
AV140LAST_POR_time_on2Power On 2 :hour-minuteRead
AV141LAST_POR_date_of2PowerDown 2:day-mon-yearRead
AV142LAST_POR_time_of2PowerDown 2:hour-minuteRead
AV143LAST_POR_date_on3Power On 3 :day-mon-yearRead
AV144LAST_POR_time_on3Power On 3 :hour-minuteRead
AV145LAST_POR_date_of3PowerDown 3:day-mon-yearRead
AV146LAST_POR_time_of3PowerDown 3:hour-minuteRead
AV147LAST_POR_date_on4Power On 4 :day-mon-yearRead
AV148LAST_POR_time_on4Power On 4 :hour-minuteRead
AV149LAST_POR_date_of4PowerDown 4:day-mon-yearRead
AV150LAST_POR_time_of4PowerDown 4:hour-minuteRead
AV151LAST_POR_date_on5Power On 5 :day-mon-yearRead
AV152LAST_POR_time_on5Power On 5 :hour-minuteRead
AV153LAST_POR_date_of5PowerDown 5:day-mon-yearRead
AV154LAST_POR_time_of5PowerDown 5:hour-minuteRead
AV155EXV_CTRL_ov_exv_aEXV Override Circuit ARead
AV156EXV_CTRL_EXV_AEXV Position (Pct) ARead
AV157EXV_CTRL_DSH_ADischarge Superheat ARead
AV158EXV_CTRL_dsh_spaDis. Superheat Setpnt ARead
AV159EXV_CTRL_SH_ASuction Superheat ARead
AV160EXV_CTRL_sh_sp_aSuct. Superheat Setpnt ARead
AV161EXV_CTRL_pinch_aEvap ExchangeDT Cir ARead
AV162EXV_CTRL_subcoolaSubcooling Circuit ARead
AV163EXV_CTRL_subc_spaSubcooling Setpoint ARead
AV164EXV_CTRL_exv_staEXV State ARead
AV165EXV_CTRL_exv_lstaEXV Previous State ARead
AV166EXV_CTRL_exvwposaEXV Wished Position ARead
AV167EXV_CTRL_ov_exv_bEXV Override Circuit BRead
AV168EXV_CTRL_EXV_BEXV Position (Pct) BRead
AV169EXV_CTRL_DSH_BDischarge Superheat BRead
AV170EXV_CTRL_dsh_spbDis. Superheat Setpnt BRead
AV171EXV_CTRL_SH_BSuction Superheat BRead
AV172EXV_CTRL_sh_sp_bSuct. Superheat Setpnt BRead
AV173EXV_CTRL_pinch_bEvap ExchangeDT Cir BRead
AV174EXV_CTRL_subcoolbSubcooling Circuit BRead
AV175EXV_CTRL_subc_spbSubcooling Setpoint BRead
AV176EXV_CTRL_exv_stbEXV State BRead
AV177EXV_CTRL_exv_lstbEXV Previous State BRead
AV178EXV_CTRL_exvwposbEXV Wished Position BRead
AV179M_MSTSLV_slv_statSlave Chiller StateRead
AV180M_MSTSLV_slv_captSlave Chiller Total CapRead
AV181M_MSTSLV_l_strt_dLag Start DelayRead
AV182M_MSTSLV_ll_hr_dLead/lag Hours DeltaRead
AV183M_MSTSLV_ms_errorMaster/Slave ErrorRead
AV184M_MSTSLV_lagstatSlave lagstatRead
AV185M_MSTSLV_slav_hrSlave Operating HoursRead
AV186M_MSTSLV_slav_ewtSlave Evap Ent. FluidRead
AV187M_MSTSLV_slav_lwtSlave Evap Leav. FluidRead
AV188CAPACTRL_ctrl_wtControled Water TempRead
AV189CAPACTRL_cwt_rateCtrl Water Temp, Deg/MinRead
AV190CAPACTRL_cap_limCurrent Capacity LimitRead
AV191CAPACTRL_drvcmdaWished Comp. Frequency ARead
AV192CAPACTRL_capmodaCapa Ctrl Stat Nb ARead
AV193CAPACTRL_lcapmodaLast Capa Ctrl Stat Nb ARead
AV194CAPACTRL_overridaOverride Capacity Nb ARead
AV195CAPACTRL_cap_pc_aEstimated Capacity ARead
AV196CAPACTRL_drvcmdbWished Comp. Frequency BRead
AV197CAPACTRL_capmodbCapacity Ctrl Stat Nb BRead
AV198CAPACTRL_lcapmodbLast Capa Ctrl Stat Nb BRead
AV199CAPACTRL_overridbOverride Capacity Nb BRead
AV200CAPACTRL_cap_pc_bEstimated Capacity BRead
AV201CAPACTRL_cMaxFrqAMax Comp. Frequency ARead
AV202CAPACTRL_cMaxFrqBMax Comp. Frequency BRead
AV203CAPACTRL_viCmdAComp. VI Cmd ARead
AV204CAPACTRL_viCmdBComp. VI Cmd BRead
AV205CAPACTRL_resetReset AmountRead
AV206CAPACTRL_CirRunNbCircuit Running NumberRead
AV207CAPACTRL_StatCirAState of Circuit ARead
AV208CAPACTRL_StatCirBState of Circuit BRead
AV209CAPACTRL_DualMastDual Circuit MasterRead
AV210CAPACTRL_xSpdHighTransfer Spd, add cirRead
AV211CAPACTRL_xSpdLowTransfer Spd, remove cirRead
AV212LIMITS_dshactaEXV_dsh_act ARead
AV213LIMITS_dshstpaEXV_dsh_stp ARead
AV214LIMITS_elspactaEXV_lsp_act ARead
AV215LIMITS_elspstpaEXV_lsp_stp ARead
AV216LIMITS_chdpactaENV comp high dp act ARead
AV217LIMITS_chdpstpaENV comp high dp stp ARead
AV218LIMITS_fhdpactaENV fan high dp act ARead
AV219LIMITS_fhdpstpaENV fan high dp stp ARead
AV220LIMITS_ldpactaENV low dp act ARead
AV221LIMITS_ldpstpaENV low dp stp ARead
AV222LIMITS_hspactaENV high sp act ARead
AV223LIMITS_hspstpaENV high sp stp ARead
AV224LIMITS_lspactaENV low sp act ARead
AV225LIMITS_lspstpaENV low sp stp ARead
AV226LIMITS_dgtactadgt act ARead
AV227LIMITS_dgtstpadgt stp ARead
AV228LIMITS_dshactbEXV_dsh_act BRead
AV229LIMITS_dshstpbEXV_dsh_stp BRead
AV230LIMITS_elspactbEXV_lsp_act BRead
AV231LIMITS_elspstpbEXV_lsp_stp BRead
AV232LIMITS_chdpactbENV comp high dp act BRead
AV233LIMITS_chdpstpbENV comp high dp stp BRead
AV234LIMITS_fhdpactbENV fan high dp act BRead
AV235LIMITS_fhdpstpbENV fan high dp stp BRead
AV236LIMITS_ldpactbENV low dp act BRead
AV237LIMITS_ldpstpbENV low dp stp BRead
AV238LIMITS_hspactbENV high sp act BRead
AV239LIMITS_hspstpbENV high sp stp BRead
AV240LIMITS_lspactbENV low sp act BRead
AV241LIMITS_lspstpbENV low sp stp BRead
AV242LIMITS_dgtactbdgt_act BRead
AV243LIMITS_dgtstpbdgt_stp BRead
AV244ECO_CTRL_eco_aEXV Eco Pos. (Pct) ARead
AV245ECO_CTRL_eco_bEXV Eco Pos. (Pct) BRead
AV246FAN_CTRL_fan_f_aFan Freq Cir ARead
AV247FAN_CTRL_fan_staFan State ARead
AV248FAN_CTRL_fan_lstaFan Previous State ARead
AV249FAN_CTRL_wfan_f_aFan Wished Freq ARead
AV250FAN_CTRL_fan_modaFan Mode ARead
AV251FAN_CTRL_fan_txtaFan Mode Text ARead
AV252FAN_CTRL_ftotpowaFan Tot Pwr Filtered ARead
AV253FAN_CTRL_fcont_aFan Contactors On ARead
AV254FAN_CTRL_fan_f_bFan Freq Cir BRead
AV255FAN_CTRL_fan_stbFan State BRead
AV256FAN_CTRL_fan_lstbFan Previous State BRead
AV257FAN_CTRL_wfan_f_bFan Wished Freq BRead
AV258FAN_CTRL_fan_modbFan Mode BRead
AV259FAN_CTRL_fan_txtbFan Mode Text BRead
AV260FAN_CTRL_ftotpowbFan Tot Pwr Filtered BRead
AV261FAN_CTRL_fcont_bFan Contactors On BRead
AV262FAN_DRV_fd_pwra1Fan Drive Power A1Read
AV263FAN_DRV_fd_Ia1Fan Drive Amps A1Read
AV264FAN_DRV_fd_Va1Fan Drive Voltage A1Read
AV265FAN_DRV_fd_Sa1Fan Drive Speed A1Read
AV266FAN_DRV_fd_Fa1Fan Drive Frequency A1Read
AV267FAN_DRV_fd_Ta1Fan Drive Torque A1Read
AV268FAN_DRV_fd_DCVa1Fan Drv DC Link Volt A1Read
AV269FAN_DRV_fd_HSTa1Fan Drive Heat Sink T A1Read
AV270FAN_DRV_fd_CCTa1Fan Drive Ctrl Card T A1Read
AV271FAN_DRV_fd_pwra2Fan Drive Power A2Read
AV272FAN_DRV_fd_Ia2Fan Drive Amps A2Read
AV273FAN_DRV_fd_Va2Fan Drive Voltage A2Read
AV274FAN_DRV_fd_Sa2Fan Drive Speed A2Read
AV275FAN_DRV_fd_Fa2Fan Drive Frequency A2Read
AV276FAN_DRV_fd_Ta2Fan Drive Torque A2Read
AV277FAN_DRV_fd_DCVa2Fan Drv DC Link Volt A2Read
AV278FAN_DRV_fd_HSTa2Fan Drive Heat Sink T A2Read
AV279FAN_DRV_fd_CCTa2Fan Drive Ctrl Card T A2Read
AV280FAN_DRV_fd_pwra3Fan Drive Power A3Read
AV281FAN_DRV_fd_Ia3Fan Drive Amps A3Read
AV282FAN_DRV_fd_Va3Fan Drive Voltage A3Read
AV283FAN_DRV_fd_Sa3Fan Drive Speed A3Read
AV284FAN_DRV_fd_Fa3Fan Drive Frequency A3Read
AV285FAN_DRV_fd_Ta3Fan Drive Torque A3Read
AV286FAN_DRV_fd_DCVa3Fan Drv DC Link Volt A3Read
AV287FAN_DRV_fd_HSTa3Fan Drive Heat Sink T A3Read
AV288FAN_DRV_fd_CCTa3Fan Drive Ctrl Card T A3Read
AV289FAN_DRV_fd_pwrb1Fan Drive Power B1Read
AV290FAN_DRV_fd_Ib1Fan Drive Amps B1Read
AV291FAN_DRV_fd_Vb1Fan Drive Voltage B1Read
AV292FAN_DRV_fd_Sb1Fan Drive Speed B1Read
AV293FAN_DRV_fd_Fb1Fan Drive Frequency B1Read
AV294FAN_DRV_fd_Tb1Fan Drive Torque B1Read
AV295FAN_DRV_fd_DCVb1Fan Drv DC Link Volt B1Read
AV296FAN_DRV_fd_HSTb1Fan Drive Heat Sink T B1Read
AV297FAN_DRV_fd_CCTb1Fan Drive Ctrl Card T B1Read
AV298FAN_DRV_fd_pwrb2Fan Drive Power B2Read
AV299FAN_DRV_fd_Ib2Fan Drive Amps B2Read
AV300FAN_DRV_fd_Vb2Fan Drive Voltage B2Read
AV301FAN_DRV_fd_Sb2Fan Drive Speed B2Read
AV302FAN_DRV_fd_Fb2Fan Drive Frequency B2Read
AV303FAN_DRV_fd_Tb2Fan Drive Torque B2Read
AV304FAN_DRV_fd_DCVb2Fan Drv DC Link Volt B2Read
AV305FAN_DRV_fd_HSTb2Fan Drive Heat Sink T B2Read
AV306FAN_DRV_fd_CCTb2Fan Drive Ctrl Card T B2Read
AV307FAN_DRV_fd_pwrb3Fan Drive Power B3Read
AV308FAN_DRV_fd_Ib3Fan Drive Amps B3Read
AV309FAN_DRV_fd_Vb3Fan Drive Voltage B3Read
AV310FAN_DRV_fd_Sb3Fan Drive Speed B3Read
AV311FAN_DRV_fd_Fb3Fan Drive Frequency B3Read
AV312FAN_DRV_fd_Tb3Fan Drive Torque B3Read
AV313FAN_DRV_fd_DCVb3Fan Drv DC Link Volt B3Read
AV314FAN_DRV_fd_HSTb3Fan Drive Heat Sink T B3Read
AV315FAN_DRV_fd_CCTb3Fan Drive Ctrl Card T B3Read
AV316FACTORY_unitsizeUnit CapacityRead
AV317FACTORY_voltagePower Supply VoltageRead
AV318FACTORY_mfg_tierTier 0=STD, 1=MID, 2=HIRead
AV319FACTORY_cpass_nbEvap Pass NumberRead
AV320FACTORY_fac_passFactory PasswordRead
AV321FACTORY_fMaxOvrAMax Frequency Override ARead
AV322FACTORY_fMaxOvrBMax Frequency Override BRead
AV323FACTORY_fan_factFan Freq Factor(0.7-1.1)Read
AV324FACTORY_fMinOvrMin Frequency OverrideRead
AV325FACTORY_lastspdaLow Amb. Start Spd ARead
AV326FACTORY_lastspdbLow Amb. Start Spd BRead
AV327FACTORY2_exvmax_aEXV A Maximum Steps NumbRead
AV328FACTORY2_exvmax_bEXV B Maximum Steps NumbRead
AV329FACTORY2_eco_cnfaEconomizer A Steps NumbRead
AV330FACTORY2_eco_cnfbEconomizer B Steps NumbRead
AV331FACTORY2_vfd_cmpNb VFD CompressorRead
AV332FACTORY2_vfd_fanaNb Fan Drive Cir ARead
AV333FACTORY2_vfd_fanbNb Fan Drive Cir BRead
AV334SERVICE1_flui_typEvaporator Fluid TypeRead
AV335SERVICE1_freezespBrine Freeze SetpointRead
AV336SERVICE1_mini_lwtBrine Minimum Fluid TempRead
AV337SERVICE1_fastcaprFast Capacity RecoveryRead
AV338SERVICE1_ewt_cirAEWT Probe on Cir A SideRead
AV339SERVICE1_leak_thrLeakage Charge ThresholdRead
AV340SERVICE1_leak_tmrLeakage Charge TimerRead
AV341SERVICE1_heaterspEvap Heater Delta SptRead
AV342SERVICE1_freez_ovFreeze Override OffsetRead
AV343SERVICE1_ViPwrChkVI Self-Test ThresholdWrite
AV344SERVICE1_odtrspdOil Delta Trigger SpeedRead
AV345SERVICE1_otrigtimOil Trigger TimeRead
AV346SERVICE1_odrecspdOil Delta Recover SpeedRead
AV347SERVICE1_orectimOil Recover TimeRead
AV348SERVICE1_wateesysWater Temp HysteresisRead
AV349SERVICE1_vistrtdtHigh VI Time at StartRead
AV350SERVICE1_vistrtenEnable High VI at StartRead
AV351UPDTHOUR_hr_machMachine Operating HoursRead
AV352UPDTHOUR_st_machMachine Starts NumberRead
AV353UPDTHOUR_hr_cp_aCompressor A HoursRead
AV354UPDTHOUR_st_cp_aCompressor A StartsRead
AV355UPDTHOUR_hr_cp_bCompressor B HoursRead
AV356UPDTHOUR_st_cp_bCompressor B StartsRead
AV357UPDTHOUR_hr_cpum1Evap Pump #1 HoursRead
AV358UPDTHOUR_hr_cpum2Evap Pump #2 HoursRead
AV359UPDTHOUR_VIctAVI Cycle Count ARead
AV360UPDTHOUR_VIctBVI Cycle Count BRead
AV361UPDTHOUR_hrfana01Circuit A Fan #1 HoursRead
AV362UPDTHOUR_hrfana02Circuit A Fan #2 HoursRead
AV363UPDTHOUR_hrfana03Circuit A Fan #3 HoursRead
AV364UPDTHOUR_hrfana04Circuit A Fan #4 HoursRead
AV365UPDTHOUR_hrfana05Circuit A Fan #5 HoursRead
AV366UPDTHOUR_hrfana06Circuit A Fan #6 HoursRead
AV367UPDTHOUR_hrfana07Circuit A Fan #7 HoursRead
AV368UPDTHOUR_hrfana08Circuit A Fan #8 HoursRead
AV369UPDTHOUR_hrfana09Circuit A Fan #9 HoursRead
AV370UPDTHOUR_hrfana10Circuit A Fan #10 HoursRead
AV371UPDTHOUR_hrfana11Circuit A Fan #11 HoursRead
AV372UPDTHOUR_hrfana12Circuit A Fan #12 HoursRead
AV373UPDTHOUR_hrfana13Circuit A Fan #13 HoursRead
AV374UPDTHOUR_hrfana14Circuit A Fan #14 HoursRead
AV375UPDTHOUR_hrfanb01Circuit B Fan #1 HoursRead
AV376UPDTHOUR_hrfanb02Circuit B Fan #2 HoursRead
AV377UPDTHOUR_hrfanb03Circuit B Fan #3 HoursRead
AV378UPDTHOUR_hrfanb04Circuit B Fan #4 HoursRead
AV379UPDTHOUR_hrfanb05Circuit B Fan #5 HoursRead
AV380UPDTHOUR_hrfanb06Circuit B Fan #6 HoursRead
AV381UPDTHOUR_hrfanb07Circuit B Fan #7 HoursRead
AV382UPDTHOUR_hrfanb08Circuit B Fan #8 HoursRead
AV383UPDTHOUR_hrfanb09Circuit B Fan #9 HoursRead
AV384UPDTHOUR_hrfanb10Circuit B Fan #10 HoursRead
AV385UPDTHOUR_hrfanb11Circuit B Fan #11 HoursRead
AV386UPDTHOUR_hrfanb12Circuit B Fan #12 HoursRead
AV387UPDTHOUR_hrfanb13Circuit B Fan #13 HoursRead
AV388UPDTHOUR_hrfanb14Circuit B Fan #14 HoursRead
AV389MST_SLV_ms_selMaster/Slave SelectRead
AV390MST_SLV_ms_ctrlMaster Control TypeRead
AV391MST_SLV_slv_addrSlave AddressRead
AV392MST_SLV_lead_selLead Lag SelectRead
AV393MST_SLV_ll_bal_dLead/Lag Balance DeltaRead
AV394MST_SLV_lstr_timLead/Lag Start TimerRead
AV395MST_SLV_lead_pulLead Pulldown TimeRead
AV396MST_SLV_start_dtStart If Error HigherRead
AV397MST_SLV_lag_miniLag Minimum Running TimeRead
AV398MST_SLV_lag_pumpLag Unit Pump ControlRead
AV429EXV_CFG_fixeddshFixed DSH SetpointRead
AV430EXV_CFG_scsp_maxSubcooling Setpoint MaxRead
AV431EXV_CFG_scsp_minSubcooling Setpoint MinRead
AV432EXV_CFG_sh_sp_aSuperheat Setpoint ARead
AV433EXV_CFG_sh_sp_bSuperheat Setpoint BRead
AV434EXV_CFG_apr_stpApproach SetpointRead
AV435EXV_CFG_sbc_kp_aSubcool PI, Kp Cir ARead
AV436EXV_CFG_sbc_ti_aSubcool PI, Ti Cir ARead
AV437EXV_CFG_sbc_ni_aSubcool PI, NI Cir ARead
AV438EXV_CFG_dsh_kp_aDSH PI, Kp Cir ARead
AV439EXV_CFG_dsh_ti_aDSH PI, Ti Cir ARead
AV440EXV_CFG_dsh_ni_aDSH PI, NI Cir ARead
AV441EXV_CFG_hsp_kp_aHigh SP PI, Kp Cir ARead
AV442EXV_CFG_hsp_ti_aHigh SP PI, Ti Cir ARead
AV443EXV_CFG_hsp_ni_aHigh SP PI, NI Cir ARead
AV444EXV_CFG_lsp_kp_aLow SP PI, Kp Cir ARead
AV445EXV_CFG_lsp_ti_aLow SP PI, Ti Cir ARead
AV446EXV_CFG_lsp_ni_aLow SP PI, NI Cir ARead
AV447EXV_CFG_dop_kp_aDop PI, Kp Cir ARead
AV448EXV_CFG_dop_ti_aDop PI, Ti Cir ARead
AV449EXV_CFG_dop_ni_aDop PI, NI Cir ARead
AV450EXV_CFG_ssh_kp_aSuction SH PI, Kp Cir ARead
AV451EXV_CFG_ssh_ti_aSuction SH PI, Ti Cir ARead
AV452EXV_CFG_ssh_ni_aSuction SH PI, NI Cir ARead
AV453EXV_CFG_sbc_kp_bSubcool PI, Kp Cir BRead
AV454EXV_CFG_sbc_ti_bSubcool PI, Ti Cir BRead
AV455EXV_CFG_sbc_ni_bSubcool PI, NI Cir BRead
AV456EXV_CFG_dsh_kp_bDSH PI, Kp Cir BRead
AV457EXV_CFG_dsh_ti_bDSH PI, Ti Cir BRead
AV458EXV_CFG_dsh_ni_bDSH PI, NI Cir BRead
AV459EXV_CFG_hsp_kp_bHigh SP PI, Kp Cir BRead
AV460EXV_CFG_hsp_ti_bHigh SP PI, Ti Cir BRead
AV461EXV_CFG_hsp_ni_bHigh SP PI, NI Cir BRead
AV462EXV_CFG_lsp_kp_bLow SP PI, Kp Cir BRead
AV463EXV_CFG_lsp_ti_bLow SP PI, Ti Cir BRead
AV464EXV_CFG_lsp_ni_bLow SP PI, NI Cir BRead
AV465EXV_CFG_dop_kp_bDop PI, Kp Cir BRead
AV466EXV_CFG_dop_ti_bDop PI, Ti Cir BRead
AV467EXV_CFG_dop_ni_bDop PI, NI Cir BRead
AV468EXV_CFG_ssh_kp_bSuction SH PI, Kp Cir BRead
AV469EXV_CFG_ssh_ti_bSuction SH PI, Ti Cir BRead
AV470EXV_CFG_ssh_ni_bSuction SH PI, NI Cir BRead
AV471EXV_CFG_apr_kp_aAppr. PI, Kp Cir ARead
AV472EXV_CFG_apr_ti_aAppr. PI, Ti Cir ARead
AV473EXV_CFG_apr_ni_aAppr. PI, NI Cir ARead
AV474EXV_CFG_apr_kp_bAppr. PI, Kp Cir BRead
AV475EXV_CFG_apr_ti_bAppr. PI, Ti Cir BRead
AV476EXV_CFG_apr_ni_bAppr. PI, NI Cir BRead
AV477DELTA_wateesyswater_t_hysteresisRead
AV478DELTA_chdp_hyscmp high dp hysteresisRead
AV479DELTA_chdtdactcmp high dt act offsetRead
AV480DELTA_chdtdsptcmp high dt stp offsetRead
AV481DELTA_fhdp_hysfan high dp hysteresisRead
AV482DELTA_fhdtdactfan high dt act offsetRead
AV483DELTA_fhdtdstpfan high dt stp offsetRead
AV484DELTA_ldp_hyslow dp hysteresisRead
AV485DELTA_ldtdactlow dt act offsetRead
AV486DELTA_ldtdsptlow dt stp offsetRead
AV487DELTA_hsp_hysthigh sp hysteresisRead
AV488DELTA_hstdacthigh st act offsetRead
AV489DELTA_hstdspthigh st stp offsetRead
AV490DELTA_lsp_hystlow sp hysteresisRead
AV491DELTA_lstdactlow st act offsetRead
AV492DELTA_lstdsptlow st stp offsetRead
AV493DELTA_lstdcpadeltat lstEXV vs lstCAPARead
AV494DELTA_mt_hystmotor temp hysteresisRead
AV495DELTA_mt_dactmotor temp act offsetRead
AV496DELTA_mt_dsptmotor temp stp offsetRead
AV497DELTA_dgt_hystdgt hysteresisRead
AV498DELTA_dgt_actdgt limit act offsetRead
AV499DELTA_dgt_sptdgt limit spt offsetRead
AV500DELTA_dsh_hystdsh hysteresisRead
AV501DELTA_dsh_actdsh act offsetRead
AV502DELTA_dshdelayexv_no_dsh_delayRead
AV503DELTA_mopdelayexv_no_mop_delayRead
AV504DELTA_sbc_hyssubcool hysteresisRead
AV505DELTA_sbc_actsubcool act offsetRead
AV506DELTA_sbc_sptSubcooling SetpointRead
AV507DELTA_cramprtCompressor Ramp RateRead
AV508BACNET_networkNetworkRead
AV509BACNET_identIdentifierRead
AV510BACNET_bbmdBACnet Management DeviceRead
AV511FAN_CFG_fldp_kpaFan Low DP PI, Kp, Cir ARead
AV512FAN_CFG_fldp_tiaFan Low DP PI, Ti Cir ARead
AV513FAN_CFG_fldp_niaFan Low DP PI, NI Cir ARead
AV514FAN_CFG_fldp_kpbFan Low DP PI, Kp, Cir BRead
AV515FAN_CFG_fldp_tibFan Low DP PI, Ti Cir BRead
AV516FAN_CFG_fldp_nibFan Low DP PI, NI Cir BRead
AV517FAN_CFG_fan_hlimFan Max FrequencyRead
AV518FAN_CFG_fan_llimFan Min FrequencyRead
AV519FAN_CFG_sync_KpSychronizing Output KpRead
AV520FAN_CFG_n_coilsACir Cond Coil Number ARead
AV521FAN_CFG_n_coilsBCir Cond Coil Number BRead
AV522FAN_CFG_cp_factACompressor Factor ARead
AV523FAN_CFG_cp_factBCompressor Factor BRead
AV524FAN_CFG_fldtfactFan Low Dis. FactorRead
AV525FAN_CFG_xt_s_smpStablility Sample NbRead
AV526FAN_CFG_xt_in_tlOpt. Deviation ToleranceRead
AV527FAN_CFG_os_d_ampOpt. Disturbance Ampl.Read
AV528FAN_CFG_os_d_perOpt. Disturbance PeriodRead
AV529FAN_CFG_os_f_powOpt. Freeze Power Tol.Read
AV530FAN_CFG_xtos_fltOpt. Filter TimeRead
AV531FAN_CFG_sct_biasSCT bias at startRead
AV532FAN_CFG_sct_timTotal SCT bias timeRead
AV533FAN_CFG_sct_decrDecrement SCT bias timeRead
AV534ECO_PI_ecsh_kpaEXV Eco. SH Kp, Cir ARead
AV535ECO_PI_ecsh_tiaEXV Eco. SH Ti Cir ARead
AV536ECO_PI_ecsh_niaEXV Eco. SH NI Cir ARead
AV537ECO_PI_ecsh_kpbEXV Eco. SH Kp, Cir BRead
AV538ECO_PI_ecsh_tibEXV Eco. SH Ti Cir BRead
AV539ECO_PI_ecsh_nibEXV Eco. SH NI Cir BRead
AV540ECO_PI_eco_minEXV Eco. Min PositionRead
AV541ECO_PI_eco_maxEXV Eco. Max PositionRead
AV542ECO_PI_capa_limCapacity Lim Disable EcoRead
AV543ECO_PI_ecoshspaEco Superheat Setpoint ARead
AV544ECO_PI_ecoshspbEco Superheat Setpoint BRead
AV545SETPOINT_csp1Cooling Setpoint 1Write
AV546SETPOINT_csp2Cooling Setpoint 2Write
AV547SETPOINT_ice_spCooling Ice SetpointWrite
AV548SETPOINT_cramp_spCooling Ramp LoadingWrite
AV549SETPOINT_lim_sp1Switch Limit Setpoint 1Write
AV550SETPOINT_lim_sp2Switch Limit Setpoint 2Write
AV551SETPOINT_lim_sp3Switch Limit Setpoint 3Write
AVmin552GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin553GENUNIT_DEM_LIM_wrDemand LimitWrite
AV554GENUNIT_SP_SEL_wrSetpoint SelectWrite
AV555SERVICE1_apr_enApproach Ctrl at Start?Read
AV556FAN_DRV_fd_pwrTotal Fan Drive PowerRead
AV557VLT_DRV_drv_pwrTotal Comp Drive PowerRead
AV558LIMITS_lspdcpaENV low sp delta ARead
AV559LIMITS_lspdcpbENV low sp delta BRead
AV562tab621_chilstatFSM chiler statusRead
AV563tab621_chil_capFSM Percent unit total capacityRead
AV564tab621_cap_max_flagFSM unit capacity fully loadedRead
BV1GENCONF_ramp_selRamp Loading EnableRead
BV2GENCONF_ice_cnfgIce Mode EnableRead
BV3GENCONF_shortcycShort Cycle ManagementRead
BV4PUMPCONF_pump_perPump Sticking ProtectionRead
BV5PUMPCONF_pump_locFlow Checked If Pump OffRead
BV6GENUNIT_CHIL_S_S_rdNet.: Cmd Start/StopRead
BV7GENUNIT_CHIL_OCC_rdNet.: Cmd OccupiedRead
BV8GENUNIT_SP_OCC_rdSetpoint Occupied?Read
BV9GENUNIT_EMSTOP_rdEmergency StopRead
BV10INPUTS_ONOFF_SWRemote On/Off SwitchRead
BV11INPUTS_SETP_SWRemote Setpoint SwitchRead
BV12INPUTS_LIM_SW1Limit Switch 1Read
BV13INPUTS_LIM_SW2Limit Switch 2Read
BV14INPUTS_OIL_L_AOil Level Input ARead
BV15INPUTS_OIL_L_BOil Level Input BRead
BV16INPUTS_REM_LOCKCustomer InterlockRead
BV17INPUTS_ICE_SWIce Done Storage SwitchRead
BV18INPUTS_OCC_OVSWOccupied Override SwitchRead
BV19INPUTS_HEATR_SWEvap Heater DetectorRead
BV20OUTPUTS_LABEL_ACIRCUIT ARead
BV21OUTPUTS_CP_ACompressor ARead
BV22OUTPUTS_OIL_SL_AOil Solenoid Output ARead
BV23OUTPUTS_VI_AVI Solenoid Output ARead
BV24OUTPUTS_ISO_OP_ARef Iso Relay Energize ARead
BV25OUTPUTS_ISO_POSARef Iso Valve State ARead
BV26OUTPUTS_OIL_HT_AOil Heater Output ARead
BV27OUTPUTS_LABEL_BCIRCUIT BRead
BV28OUTPUTS_CP_BCompressor BRead
BV29OUTPUTS_OIL_SL_BOil Solenoid Output BRead
BV30OUTPUTS_VI_BVI Solenoid Output BRead
BV31OUTPUTS_ISO_OP_BRef Iso Relay Energize BRead
BV32OUTPUTS_ISO_POSBRef Iso Valve State BRead
BV33OUTPUTS_OIL_HT_BOil Heater Output BRead
BV34OUTPUTS_ALARMAlarm Relay StatusRead
BV35OUTPUTS_RUNNINGRunning Relay StatusRead
BV36OUTPUTS_ALERTAlert Relay StateRead
BV37OUTPUTS_SHUTDOWNShutdown Indicator StateRead
BV38OUTPUTS_C_HEATEREvap Heater OutputRead
BV39OUTPUTS_FCA1Fan Contactor 1ARead
BV40OUTPUTS_FCA2Fan Contactor 2ARead
BV41OUTPUTS_FCA3Fan Contactor 3ARead
BV42OUTPUTS_FCA4Fan Contactor 4ARead
BV43OUTPUTS_FCA5Fan Contactor 5ARead
BV44OUTPUTS_FCA6Fan Contactor 6ARead
BV45OUTPUTS_FCA7Fan Contactor 7ARead
BV46OUTPUTS_FCA8Fan Contactor 8ARead
BV47OUTPUTS_FCB1Fan Contactor 1BRead
BV48OUTPUTS_FCB2Fan Contactor 2BRead
BV49OUTPUTS_FCB3Fan Contactor 3BRead
BV50OUTPUTS_FCB4Fan Contactor 4BRead
BV51OUTPUTS_FCB5Fan Contactor 5BRead
BV52OUTPUTS_FCB6Fan Contactor 6BRead
BV53OUTPUTS_FCB7Fan Contactor 7BRead
BV54OUTPUTS_FCB8Fan Contactor 8BRead
BV55OUTPUTS_VFD_EN_AComp. HW Enable ARead
BV56OUTPUTS_VFD_EN_BComp. HW Enable BRead
BV57OUTPUTS_BOX_HTRControl Box HeaterRead
BV58PUMPSTAT_CPUMP_1_rdEvap Pump #1 CommandRead
BV59PUMPSTAT_CPUMP_2_rdEvap Pump #2 CommandRead
BV60PUMPSTAT_ROTCPUMP_rdRotate Evap Pumps ?Read
BV61PUMPSTAT_FLOW_SWEvap Flow Switch #1Read
BV62PUMPSTAT_FLOW_SWBEvap Flow Switch #2Read
BV63MODES_m_delayStart Up Delay In EffectRead
BV64MODES_m_2stptSecond Setpoint In UseRead
BV65MODES_m_resetReset In EffectRead
BV66MODES_m_demlimDemand Limit ActiveRead
BV67MODES_m_pmprotEvaporator Pump RotationRead
BV68MODES_m_pmpperPump Periodic StartRead
BV69MODES_m_nightNight Low Noise ActiveRead
BV70MODES_m_slaveMaster Slave ActiveRead
BV71MODES_m_iceIce Mode In EffectRead
BV72ALARMRST_RST_ALMAlarm ResetRead
BV73VLT_DRV_SET_DRVADrive A AttachRead
BV74VLT_DRV_SET_DRVBDrive B AttachRead
BV75VLT_DRV_VLT_COMAComm with Drive A OkRead
BV76VLT_DRV_VLT_COMBComm with Drive B OkRead
BV77M_MSTSLV_ms_activMaster/Slave Ctrl ActiveRead
BV78M_MSTSLV_lead_selLead Unit is the:Read
BV79M_MSTSLV_ll_changLead/lag Changeover?Read
BV80M_MSTSLV_ll_pullLead Pulldown ?Read
BV81M_MSTSLV_cap_maxMax Available Capacity ?Read
BV82FAN_DRV2_SET_FDA1Fan Drive A1 AttachRead
BV83FAN_DRV2_SET_FDA2Fan Drive A2 AttachRead
BV84FAN_DRV2_SET_FDA3Fan Drive A3 AttachRead
BV85FAN_DRV2_SET_FDB1Fan Drive B1 AttachRead
BV86FAN_DRV2_SET_FDB2Fan Drive B2 AttachRead
BV87FAN_DRV2_SET_FDB3Fan Drive B3 AttachRead
BV88FAN_DRV2_FD_COMA1Comm Fan Drive A1 OkRead
BV89FAN_DRV2_FD_COMA2Comm Fan Drive A2 OkRead
BV90FAN_DRV2_FD_COMA3Comm Fan Drive A3 OkRead
BV91FAN_DRV2_FD_COMB1Comm Fan Drive B1 OkRead
BV92FAN_DRV2_FD_COMB2Comm Fan Drive B2 OkRead
BV93FAN_DRV2_FD_COMB3Comm Fan Drive B3 OkRead
BV94FAN_DRV2_stopfanaStop Cir A Fan DriveRead
BV95FAN_DRV2_stopfanbStop Cir B Fan DriveRead
BV96FACTORY_freq_60H60Hz Sel (No=50, Yes=60)Read
BV97FACTORY_probrineProcess Brine EvapRead
BV98FACTORY_heat_selEvap Heater InstalledRead
BV99FACTORY_mst_slvMaster Slave SetupRead
BV100FACTORY_emm_nrcpEnergy Management ModuleRead
BV101FACTORY_loamboptLow Ambient Option (STD)Read
BV102FACTORY_leak_chkLeakage Charge DetectionRead
BV103FACTORY_fMaxEnAEnable Max Frequency ARead
BV104FACTORY_fMaxEnBEnable Max Frequency BRead
BV105SERVICE1_ewt_optEntering Fluid ControlRead
BV106SERVICE1_ser_passService PasswordRead
BV107SERVICE1_RFI_confCompressor RFI Filter EnRead
BV108SERVICE1_metricMetric Units? (Blackbox)Read
BV109SERVICE1_fdrv_cfgSend fan drive config?Read
BV110SERVICE1_cdrv_cfgSend comp. drive config?Read
BV111SERVICE1_auto_smAuto Start When SM LostRead
BV112SERVICE1_ViChkEnVI Self-Test EnableWrite
BV113SERVICE1_AntiFrzPump Rot. AntiFrz ProtecRead
BV116MST_SLV_ll_serieChiller In SeriesRead
BV117BACNET_bacenaBACnet EnableRead
BV118BACNET_bacunitMetric UnitRead
BV119FAN_CFG_fan_ctrlFan Ctrl Type (Vari,Fix)Read
BV120FAN_CFG_xt_enablOptimization EnableRead
BV121CP_ENABL_en_cp_aCompressor A DisableRead
BV122CP_ENABL_en_cp_bCompressor B DisableRead
BVmin123GENUNIT_CHIL_S_S_wrChiller Start/StopWrite
BV124PUMPSTAT_CPUMP_1_wrEvaporator pump 1Write
BV125PUMPSTAT_CPUMP_2_wrEvaporator pump 2Write
BV126GENUNIT_EMSTOP_wrEmergency StopWrite
BV127PUMPSTAT_ROTCPUMP_wrRotate Evap Pumps ?Write
BV128GENUNIT_SP_OCC_wrSetpoint Occupied?Write
BVmin129GENUNIT_CHIL_OCC_wrChiller occupied?Write
BV130ALM_COOL_EWT_FCOOL_EWT_FRead
BV131ALM_COOL_LWT_FCOOL_LWT_FRead
BV132ALM_OAT_FOAT_FRead
BV133ALM_CHWSTEMP_FCHWSTEMP_FRead
BV134ALM_SUCTION_T_A_FSUCTION_T_A_FRead
BV135ALM_SUCTION_T_B_FSUCTION_T_B_FRead
BV136ALM_DGT_A_T_FDGT_A_T_FRead
BV137ALM_DGT_B_T_FDGT_B_T_FRead
BV138ALM_LIQUID_T_A_FLIQUID_T_A_FRead
BV139ALM_LIQUID_T_B_FLIQUID_T_B_FRead
BV140ALM_CP_TMP_A_FCP_TMP_A_FRead
BV141ALM_CP_TMP_B_FCP_TMP_B_FRead
BV142ALM_ECO_T_A_FECO_T_A_FRead
BV143ALM_ECO_T_B_FECO_T_B_FRead
BV144ALM_SPACE_TEMP_FSPACE_TEMP_FRead
BV145ALM_DP_A_FDP_A_FRead
BV146ALM_DP_B_FDP_B_FRead
BV147ALM_SP_A_FSP_A_FRead
BV148ALM_SP_B_FSP_B_FRead
BV149ALM_OIL_P_A_FOIL_P_A_FRead
BV150ALM_OIL_P_B_FOIL_P_B_FRead
BV151ALM_ECO_P_A_FECO_P_A_FRead
BV152ALM_ECO_P_B_FECO_P_B_FRead
BV153ALM_LIQUID_P_A_FLIQUID_P_A_FRead
BV154ALM_LIQUID_P_B_FLIQUID_P_B_FRead
BV155ALM_SIOB1_COM_FSIOB1_COM_FRead
BV156ALM_SIOB2_COM_FSIOB2_COM_FRead
BV157ALM_AUX1_1_COM_FAUX1_1_COM_FRead
BV158ALM_AUX1_2_COM_FAUX1_2_COM_FRead
BV159ALM_AUX1_3_COM_FAUX1_3_COM_FRead
BV160ALM_AUX1_4_COM_FAUX1_4_COM_FRead
BV161ALM_EMM_BRD_COM_FEMM_BOARD_COM_FRead
BV162ALM_VLT_DRIVE1_COM_FVLT_DRIVE1_COM_FRead
BV163ALM_VLT_DRIVE2_COM_FVLT_DRIVE2_COM_FRead
BV164ALM_FAN_DRIVEA1_COM_FFAN_DRIVEA1_COM_FRead
BV165ALM_FAN_DRIVEA2_COM_FFAN_DRIVEA2_COM_FRead
BV166ALM_FAN_DRIVEA3_COM_FFAN_DRIVEA3_COM_FRead
BV167ALM_FAN_DRIVEB1_COM_FFAN_DRIVEB1_COM_FRead
BV168ALM_FAN_DRIVEB2_COM_FFAN_DRIVEB2_COM_FRead
BV169ALM_FAN_DRIVEB3_COM_FFAN_DRIVEB3_COM_FRead
BV170ALM_COOLER_FREEZE_FCOOLER_FREEZE_FRead
BV171ALM_LOW_SUCTION_A_FLOW_SUCTION_A_FRead
BV172ALM_LOW_SUCTION_B_FLOW_SUCTION_B_FRead
BV173ALM_LOCK_FLOCK_FRead
BV174ALM_LOSS_COM_MS_FLOSS_COM_MS_FRead
BV175ALM_LOW_OIL_A_P_FLOW_OIL_A_P_FRead
BV176ALM_LOW_OIL_B_P_FLOW_OIL_B_P_FRead
BV177ALM_OIL_FILT_A_P_FOIL_FILT_A_P_FRead
BV178ALM_OIL_FILT_B_P_FOIL_FILT_B_P_FRead
BV179ALM_OIL_DROP_A_P_FOIL_DROP_A_P_FRead
BV180ALM_OIL_DROP_B_P_FOIL_DROP_B_P_FRead
BV181ALM_LOW_OIL_LEVEL_A_FLOW_OIL_LEVEL_A_FRead
BV182ALM_LOW_OIL_LEVEL_B_FLOW_OIL_LEVEL_B_FRead
BV183ALM_M_S_CONFIG_FM_S_CONFIG_FRead
BV184ALM_INI_FACT_CONF_FINI_FACT_CONF_FRead
BV185ALM_ILL_FACT_CONF_FILL_FACT_CONF_FRead
BV186ALM_CCN_EMSTOP_FCCN_EMSTOP_FRead
BV187ALM_COOL_PUMP1_FCOOL_PUMP1_FRead
BV188ALM_COOL_PUMP2_FCOOL_PUMP2_FRead
BV189ALM_SCT_OUT_OF_CP_M_A_FSCT_OUT_OF_CP_MAP_A_FRead
BV190ALM_SCT_OUT_OF_CP_M_B_FSCT_OUT_OF_CP_MAP_B_FRead
BV191ALM_REFRIG_ESCAPE_FREFRIGERANT_ESCAPE_FRead
BV192ALM_HIGH_DGT_A_FHIGH_DGT_A_FRead
BV193ALM_HIGH_DGT_B_FHIGH_DGT_B_FRead
BV194ALM_SUCT_VALV_CLOSD_A_FSUCT_VALV_CLOSED_A_FRead
BV195ALM_SUCT_VALV_CLOSD_B_FSUCT_VALV_CLOSED_B_FRead
BV196ALM_COOLER_FLOW_FCOOLER_FLOW_FRead
BV197ALM_SENSORS_SWAP_FSENSORS_SWAP_FRead
BV198ALM_SST_OUT_OF_CP_M_A_FSST_OUT_OF_CP_MAP_A_FRead
BV199ALM_SST_OUT_OF_CP_M_B_FSST_OUT_OF_CP_MAP_B_FRead
BV200ALM_VLT_DRIVE_A_FVLT_DRIVE_A_FRead
BV201ALM_VLT_DRIVE_B_FVLT_DRIVE_B_FRead
BV202ALM_FAN_DRIVE_A1_FFAN_DRIVE_A1_FRead
BV203ALM_FAN_DRIVE_A2_FFAN_DRIVE_A2_FRead
BV204ALM_FAN_DRIVE_A3_FFAN_DRIVE_A3_FRead
BV205ALM_FAN_DRIVE_B1_FFAN_DRIVE_B1_FRead
BV206ALM_FAN_DRIVE_B2_FFAN_DRIVE_B2_FRead
BV207ALM_FAN_DRIVE_B3_FFAN_DRIVE_B3_FRead
BV208ALM_VLT_DRIVE_A_ALERTVLT_DRIVE_A_ALERTRead
BV209ALM_VLT_DRIVE_B_ALERTVLT_DRIVE_B_ALERTRead
BV210ALM_FAN_DRIVE_A1_ALERTFAN_DRIVE_A1_ALERTRead
BV211ALM_FAN_DRIVE_A2_ALERTFAN_DRIVE_A2_ALERTRead
BV212ALM_FAN_DRIVE_A3_ALERTFAN_DRIVE_A3_ALERTRead
BV213ALM_FAN_DRIVE_B1_ALERTFAN_DRIVE_B1_ALERTRead
BV214ALM_FAN_DRIVE_B2_ALERTFAN_DRIVE_B2_ALERTRead
BV215ALM_FAN_DRIVE_B3_ALERTFAN_DRIVE_B3_ALERTRead
BV216ALM_HIGH_CP_TMP_A_FHIGH_CP_TMP_A_FRead
BV217ALM_HIGH_CP_TMP_B_FHIGH_CP_TMP_B_FRead
BV218ALM_HP_SWITCH_A_FHP_SWITCH_A_FRead
BV219ALM_HP_SWITCH_B_FHP_SWITCH_B_FRead
BV220ALM_DATABASE_FDATABASE_FRead
BV221ALM_LENSCAN_FLENSCAN_FRead
BV222ALM_STEPPER_EXV_A_FSTEPPER_EXV_A_FRead
BV223ALM_STEPPER_EXV_B_FSTEPPER_EXV_B_FRead
BV224ALM_STEPPER_ECO_A_FSTEPPER_ECO_A_FRead
BV225ALM_STEPPER_ECO_B_FSTEPPER_ECO_B_FRead
BV226ALM_VI_DIAG_A_ALERTVI_DIAG_A_ALERTRead
BV227ALM_VI_DIAG_B_ALERTVI_DIAG_B_ALERTRead
BV228ALM_LOSS_REF_FLOW_A_FLOSS_REF_FLOW_A_FRead
BV229ALM_LOSS_REF_FLOW_B_FLOSS_REF_FLOW_B_FRead
MV21UNIT_StatusUNIT_StatusRead
MV109Alarm_StateAlarm StateRead
MV250FAN_BACNET_fan_modaFan Mode ARead
MV251FAN_BACNET_fan_txtaFan Mode Text ARead
MV258FAN_BACNET_fan_modbFan Mode BRead
MV259FAN_BACNET_fan_txtbFan Mode Text BRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)

How many BACnet points does the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) have?

This list has 765 BACnet objects: 532 analog values, 227 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) BACnet points are writable?

20 of the 765 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) BACnet documentation?

The source is AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier PIC6.1 Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP and MS/TP Points) (30XV-6T), revision 5-26, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/00/30XV-6T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)?

Start with BV 123 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 129 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 552 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 553 GENUNIT_DEM_LIM_wr (Demand limit command); AV 20 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 21 GENUNIT_STATUS (Running status); AV 30 TEMP_COOL_LWT (Leaving chilled water temperature); AV 29 TEMP_COOL_EWT (Entering chilled water temperature); AV 24 GENUNIT_CAP_T (Percent total capacity); AV 109 ALARMRST_ALM (Unit alarm state).

How do I enable BMS control of the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)?

Select the Network machine control method with the Start/Stop button; the unit then follows network commands and ignores the remote control contacts and the Enable-Off-Remote switch (SW1). Start/stop and occupancy are written to the _wr objects. In Local On, Local Schedule or Remote the unit ignores network commands except emergency stop.

Does the Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller) need a BACnet heartbeat or have a communication timeout?

The manual says that if communication with the network is lost while under network control, the machine starts and is controlled locally.

How do I check these points on the real AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaForce 30XV140-500, Series B Variable Speed Air-Cooled Liquid Chillers with Greenspeed Intelligence and Carrier PIC6.1 Controller - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix E, BACnet IP and MS/TP Points) · 30XV-6T · rev. 5-26. Object names, instances and units are reproduced as published; descriptions are our own.