Water-cooled centrifugal chiller controller · BACnet points list

Carrier AquaEdge 19DV (PIC6) BACnet points list

Updated 28 October 2026

Short answer

The 19DV's PIC6 controller speaks BACnet MS/TP on RS-485 port J8 or BACnet IP on Ethernet, plus Modbus RTU/TCP. Commands use paired read (_rd) and write (_wr) objects; the write copies (start/stop, occupancy, control point, demand limit, emergency stop, free cooling, heat/cool select) are marked CMD. The list also includes temperatures, pressures, guide-vane and VFD data, surge and alarm points.

This page lists 229 BACnet objects for the Carrier AquaEdge 19DV (PIC6) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaEdge 19DV (PIC6)
Equipment
Water-cooled centrifugal chiller controller
Equipment type
Chillers
BACnet objects
229 (14 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
1600001
Also known as
19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller
Source document
AquaEdge 19DV Two-Stage High-Efficiency Centrifugal Chiller - Controls Operation and Troubleshooting (Appendix D) · 19DV-CLT-3T · rev. 2020-02
Download CSV 229 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaEdge 19DV (PIC6)

Integration in brief

Enable BACnet in the BMS Protocol menu (J8 option for MS/TP or BACnet/IP Enable), set the identifier and network, and enable Network start. The chiller then starts when both BV 66 start/stop and BV 68 occupancy are true; write control point and demand limit through the _wr objects and read status, water temperatures and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 66GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 68GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
BV 67GENUNIT_EMSTOP_wrEmergency stop commandWrite
AV 147GENUNIT_CTRL_PNT_wrControl point commandWrite
AV 148GENUNIT_DEM_LIM_wrDemand limit commandWrite
MV 1GENUNIT_ctl_modeControl mode: Local, Network, Remote, Local SchedRead
AV 7GENUNIT_ch_stateChiller status codeRead
AV 9TEMP_LCWLeaving chilled water temperatureRead
AV 8TEMP_ECWEntering chilled water temperatureRead
AV 85ALARMRST_alarm_1Current alarm 1Read

Enable & remote start

In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a quick shutdown. A STOP OVERRIDE point in GENUNIT, if enabled, prevents starting.

Network setup

Watch out for

Carrier AquaEdge 19DV (PIC6) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

229 of 229 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaEdge 19DV (PIC6) BACnet Points List
DescriptionStates
AVmin85ALARMRST_alarm_1Current Alarm 1Read
AV86ALARMRST_alarm_2Current Alarm 2Read
AV87ALARMRST_alarm_3Current Alarm 3Read
AV88ALARMRST_alarm_4Current Alarm 4Read
AV89ALARMRST_alarm_5Current Alarm 5Read
MV8BACnet_COLORStart Free CoolingRead
AV150BACnet_PRIME_VStart Free CoolingRead
AV95CAPACTRL_cm_stat1Comp1 Run State ValRead
AV90CAPACTRL_ctrl_wtControlled Water TempRead
AV91CAPACTRL_gv1_tgtTarget GV1 PosRead
AV92CAPACTRL_gv2_tgtTarget GV2 PosRead
AV94CAPACTRL_hgbp_tpECV Target PercentRead
AV93CAPACTRL_vfd_tgtTarget VFD Speed PerRead
AV127CFGSURGE_gv1_pfulIGV1 Full Load PositionRead
AV126CFGSURGE_gv1_pminIGV1 Minimum PositionRead
AV130CFGSURGE_sgl_hoffSurge Line Upper DBRead
AV129CFGSURGE_sgl_loffSurge Line Lower DBRead
AV128CFGSURGE_sgl_offSurge Line OffsetRead
AV134CFGSURGE_sgl_proSurge Profile OffsetRead
AV131CFGSURGE_sgl_shfhSurge Line Shape FactorRead
AV132CFGSURGE_sgl_shflSound Line Shape FactorRead
AV133CFGSURGE_sgl_spdfSurge Line Speed FactorRead
MV6CONF_OPT_hgbp_optEC Valve OptionReadNo=0, Cont.=1, ON/OFF=2, mA=3
MV7CONF_OPT_hgbp_selEC Valve SelectionReadDisable=0, Surge=1, Low Load=2, Comb=3
AV136CONF_PRG_oil_fltOil Filter FailureRead
AV135CONF_PRG_oil_qlyOil QualityRead
AV138CONF_PRG_ref_chgRefrig Charge StatusRead
AV137CONF_PRG_tran_devTransducer DeviationRead
AV140CONNECT_bac_idBACnet IdentifierRead
BV63CONNECT_bacenaBACnet/IP EnableRead
BV64CONNECT_bacunitBACnet Metric UnitRead
AV139CONNECT_networkBACnet NetworkRead
MV4FACTORY_chil_typChiller TypeRead19XR6/7=0, 19XR2~E/D/V=1, 19DV=2
MV5FACTORY_vfd_optVFD OptionReadNo=0, FS VFD=1, Carrier=2, Rockwell LF2=3, Eaton=4, Rockwell STD=5
AV4GENUNIT_AMPS_PPercent CurrentRead
BV9GENUNIT_BAC_OCCBACnet OccupiedRead
AVmin7GENUNIT_ch_stateChiller Status CodeRead
BV3GENUNIT_CHIL_OCC_rdNetwork:Cmd OccupiedRead
BVmin68GENUNIT_CHIL_OCC_wrNetwork:Cmd OccupiedWrite
BV2GENUNIT_CHIL_S_S_rdNetwork:Cmd Start/StopRead
BVmin66GENUNIT_CHIL_S_S_wrNetwork:Cmd Start/StopWriteLocal=0, Network=1, Remote=2, Local Sched=3
AV1GENUNIT_CTRL_PNT_rdControl PointRead
AVmin147GENUNIT_CTRL_PNT_wrControl PointWrite
MVmin1GENUNIT_ctl_modeControl ModeReadLocal=0, Network=1, Remote=2, Local Sched=3
AV6GENUNIT_DEM_LIM_rdActual Demand LimitRead
AVmin148GENUNIT_DEM_LIM_wrActual Demand LimitWrite
BV5GENUNIT_EMSTOP_rdEmergency StopRead
BVmin67GENUNIT_EMSTOP_wrEmergency StopWrite
BV8GENUNIT_FC_START_rdStart Free CoolingRead
BV69GENUNIT_FC_START_wrStart Free CoolingWrite
BV4GENUNIT_HC_SEL_rdCooling/Heating SelectRead
AV149GENUNIT_HC_SEL_wrCooling/Heating SelectWrite
BV7GENUNIT_ice_occIce Schedule OccupiedRead
AV5GENUNIT_KW_PMotor Percent KilowattsRead
BV6GENUNIT_loc_occLocal Schedule OccupiedRead
AV2GENUNIT_resetControl Point ResetRead
AV3GENUNIT_setpointActual SetpointRead
BV1GENUNIT_statstopDeter Start Stop CommandRead
BV50HYDRLIC_CDW_FLOWCondenser Water FlowRead
AV58HYDRLIC_CDW_FVCond Water Flow ValueRead
AV59HYDRLIC_cdw_pdCondenser Water Delta PRead
BV49HYDRLIC_CDWPCondenser Water PumpRead
BV52HYDRLIC_CHW_FLOWChilled Water FlowRead
AV60HYDRLIC_CHW_FVChilled Water Flow ValueRead
AV61HYDRLIC_chw_pdChilled Water Delta PRead
BV51HYDRLIC_CHWPChilled Water PumpRead
AV62HYDRLIC_ctrlw_dtControlled Water DTRead
BV20INPUTS_bacdonglBACnet DongleRead
AV47INPUTS_DIFF_ACTDiffuser Actual PosRead
MV2INPUTS_DMP_ACTDamper Valve StatusRead
BV13INPUTS_E_STOPEmergency Stop ContactRead
BV18INPUTS_FS_LOCKFire Security InterlockRead
AV44INPUTS_GV1_ACTGuide Vane 1 Actual PosRead
AV45INPUTS_GV2_ACTGuide Vane 2 Actual PosRead
BV23INPUTS_HF_LSLiquid Level SwitchRead
MV3INPUTS_HGBP_ACTEC Valve StatusRead
AV48INPUTS_HGBPACTPActual ECV Pos PerRead
BV11INPUTS_HP_SWHigh Pressure SwitchRead
BV14INPUTS_ICE_CONIce Build ContactRead
BV22INPUTS_PGLE_HIPurge Level Switch HighRead
BV21INPUTS_PGLE_LOPurge Level Switch LowRead
BV12INPUTS_REM_CONRemote ContactRead
BV15INPUTS_REM_LOCKChiller LockoutRead
BV16INPUTS_SAFETYSpare Safety InputRead
BV10INPUTS_STAR_AUXCompressor Start ContactRead
BV17INPUTS_STARTFLTStarter Fault FeedbackRead
BV19INPUTS_TRIPRISM Trip Relay StatusRead
AV46INPUTS_VFD_ACTActual VFD Speed PerRead
BV61LABONLY_gv1_fcGV1 ForcedRead
BV62LABONLY_gv2_fcGV2 ForcedRead
BV60MAIN_MS_lag_s_sSlave Start/StopRead
AV121MAIN_MS_lagstartLag Start TimerRead
AV120MAIN_MS_lagstatSlave Run StatusRead
AV122MAIN_MS_lagstopLag Stop TimerRead
AV116MAIN_MS_lead_lagUnit is Lead or LagRead
BV59MAIN_MS_ll_commLead Lag CommunicationRead
AV119MAIN_MS_ll_faultMaster Slave FaultReadNo Fault=0, Master=1, Slave=2, Both=3
AV125MAIN_MS_ll_hr_dLead/Lag Hours DeltaRead
AV117MAIN_MS_ms_ctrlMaster Control TypeRead
AV123MAIN_MS_prefltPrestart Fault TimerRead
AV124MAIN_MS_pulltimePulldown TimerRead
AV118MAIN_MS_sl_ctrlSlave Control TypeReadLocal=0, Network=1, Remote=2, Local Sched=3
BV58MAIN_SRD_diff_almSRD Rotating Stall AlarmRead
AV112MAIN_SRD_diff_tgtDiffuser Target PosRead
BV57MAIN_SRD_diffaultDiffuser FaultRead
AV114MAIN_SRD_lift_1VDO High Lift Load LineRead
AV115MAIN_SRD_lift_2VDO Low Lift Load LineRead
AV113MAIN_SRD_lift_aActual LiftRead
AV96MAISURGE_act_regSurge RegionReadNo=0, Low=1, High=2, Deadband=3, Noise=4
AV97MAISURGE_dts_actActual Delta TsatRead
AV98MAISURGE_dts_calCalc Ref Delta TsatRead
AV103MAISURGE_dts_maxcCal Surge Delta TsmaxRead
AV105MAISURGE_dts_medcCal Surge Delta TsmedRead
AV104MAISURGE_dts_mincCal Surge Delta TsminRead
AV109MAISURGE_enlp_optEnvelope Line OptimizedRead
AV106MAISURGE_gv1_sfulIGV1 Full Load PositionRead
AV108MAISURGE_gv1_smedOpti-Sound IGV1 PositionRead
AV107MAISURGE_gv1_sminIGV1 Minimum PositionRead
AV99MAISURGE_scSurge CountsRead
AV100MAISURGE_spcSurge Protection CountsRead
AV101MAISURGE_surg_actSurge Prevention ActiveRead
AV102MAISURGE_surg_proSurge Protection ActiveRead
MV9MODES_cm_stat1Comp1 Run State StatusRead0=OFF, 1=CTLTEST, 2=PUMPDOWN, 3=LOCKOUT, 4=RECYCLE, 5=TRIPOUT, 6=TIMEOUT, 7=PRESTART, 8=STARTUP, 9=AUTORST, 10=RAMPING, 11=RUNNING, 12=OVERRIDE, 13=DEMAND, 14=SHUTDOWN, 15=FREECOOL, 16=CONDFLSH
BV25OUTPUTS_ALEAlert RelayRead
BV24OUTPUTS_ALMAlarm RelayRead
AV51OUTPUTS_CHST_OUTChiller Stat Output mARead
BV39OUTPUTS_COMP_PSVPurge Comp ValveRead
BV26OUTPUTS_COMP_SRCompressor Start RelayRead
BV34OUTPUTS_COND_CVCondenser Control ValveRead
BV37OUTPUTS_COND_DCVCondenser Drain ValveRead
BV48OUTPUTS_COND_FCVCondenser Filling ValveRead
BV38OUTPUTS_COND_PSVPurge Cond ValveRead
AV49OUTPUTS_DIFF_OUTDiffuser Output mARead
BV42OUTPUTS_DIS_PSVPurge Discharge ValveRead
BV40OUTPUTS_DRASVONPurge Drainage ValveRead
BV33OUTPUTS_ECON_IVEconomizer Isolation VLVRead
BV35OUTPUTS_EVAP_CVEvaporator Control ValveRead
BV36OUTPUTS_EVAP_DCVEvaporator Drain ValveRead
AV53OUTPUTS_EXV_OUTOil EXV Output mARead
BV47OUTPUTS_FC_VALVEFree Cooling ValveRead
BV27OUTPUTS_GV1_DECGuide Vane 1 DecreaseRead
BV28OUTPUTS_GV1_INCGuide Vane 1 IncreaseRead
AV56OUTPUTS_GV1_OUTGuide Vane1 OutputRead
AV57OUTPUTS_GV2_OUTGuide Vane2 OutputRead
AV50OUTPUTS_HDPV_OUTHead Pres Output mARead
AV54OUTPUTS_llc_exvtLiquid Level EXV TargetRead
BV29OUTPUTS_OIL_HEATOil Heater RelayRead
BV30OUTPUTS_OIL_PUMPOil Pump RelayRead
AV55OUTPUTS_op_vfd_tOil Pump VFD TargetRead
BV44OUTPUTS_PG_COMPPurge CompressorRead
BV45OUTPUTS_PG_HEATPurge HeaterRead
BV43OUTPUTS_PGAPUMPPurge Vacuum PumpRead
BV41OUTPUTS_REG_PSVPurge Regeneration ValveRead
BV31OUTPUTS_TFR_HIGHTower Fan Relay HighRead
BV32OUTPUTS_TFR_LOWTower Fan Relay LowRead
AV52OUTPUTS_VFD_OUTVFD Speed Output mARead
BV46OUTPUTS_VS_SVVapor Source SVRead
AV66POWER_I_AMPS_A_IActual Line CurrentRead
AV67POWER_I_AMPS_P_IPercent Line CurrentRead
AV70POWER_I_KWMotor KilowattsRead
AV72POWER_I_ln_imb_vLine Voltage Imbalance%Read
AV71POWER_I_POW_FACTMotor Power FactorRead
AV68POWER_I_VOLT_AActual Line VoltageRead
AV69POWER_I_VOLT_PPercent Line VoltageRead
AV84POWER_O_alm_codeVFD Alarm CodeRead
AV74POWER_O_amps_p_oPercent VFD Load CurrentRead
AV76POWER_O_bus_voltDC Bus VoltageRead
AV81POWER_O_enc_tempVFD Enclosure TempRead
AV82POWER_O_inv_tempInverter TemperatureRead
BV54POWER_O_lrtem_swLR Temp SwitchRead
AV75POWER_O_MOT_FREQMotor Actual FrequencyRead
AV79POWER_O_motor_kwMotor KilowattsRead
AV78POWER_O_motor_pfMotor Power FactorRead
AV80POWER_O_motorkwhMotor Kilowatt-HoursRead
BV53POWER_O_prech_fdPrecharge FeedbackRead
AV83POWER_O_rec_tempRectifier TemperatureRead
BV55POWER_O_spd_fdSPD FeedbackRead
AV77POWER_O_vfd_actActual VFD Speed PerRead
AV73POWER_O_VFD_LOADVFD Load CurrentRead
BV56POWER_O_VFDC_HIHigh VFD CurrentRead
AV37PRESSURE_COND_PCondenser PressureRead
AV40PRESSURE_DIFF_PDiffuser PressureRead
AV38PRESSURE_ECON_PEconomizer PressureRead
AV36PRESSURE_EVAP_PEvaporator PressureRead
AV41PRESSURE_HEAD_PHead Pressure ReferenceRead
AV39PRESSURE_OIL_PDOil Pump Delta PRead
AV43PRESSURE_PUMP_PDRef Pump Delta PRead
AV42PRESSURE_REF_PDBearing Delta PRead
AV111QCK_TEST_Q_DIFTGTDiffuser Target PosRead
AV110QCK_TEST_Q_GV1ACTGuide Vane 1 Actual PosRead
AV63RUNTIME_C_STARTSCompressor Starts NumRead
AV64RUNTIME_COMP_HRSCompressor Running HrsRead
AV153RUNTIME_PGP_NOTotal Pumpout NumbersRead
AV65RUNTIME_SRV_HRSAfter Service HrsRead
AV151RUNTIME_ST_CNT12Start Num in 12 hoursRead
AV146SETPOINT_dem_baseBase Demand LimitWrite
AV143SETPOINT_ecdw_spHeating ECDW SetpointWrite
AV141SETPOINT_ecw_spCooling ECW SetpointWrite
BV65SETPOINT_EWT_OPTEWT Control OptionWrite
AV145SETPOINT_ice_spIce Build SetpointWrite
AV144SETPOINT_lcdw_spHeating LCDW SetpointWrite
AV142SETPOINT_lcw_spCooling LCW SetpointWrite
AV33TEMP_CBH1_T1st Stage Bearing TempRead
AV34TEMP_CBH2_T2nd Stage Bearing TempRead
AV17TEMP_cond_appCondenser ApproachRead
AV18TEMP_COND_SATCond Sat Refrig TempRead
AV19TEMP_DGTComp Discharge TempRead
AV20TEMP_DSHDischarge SuperheatRead
AV10TEMP_ECDWEntering Condenser WaterRead
AVmin8TEMP_ECWEntering Chilled WaterRead
AV16TEMP_evap_appEvaporator ApproachRead
AV14TEMP_EVAP_SATEvap Sat Refrig TempRead
AV15TEMP_EVAP_TEvap Refrig Liquid TempRead
AV12TEMP_HR_EWTHeat Recl Entering TempRead
AV13TEMP_HR_LWTHeat Recl Leaving TempRead
AV11TEMP_LCDWLeaving Condenser WaterRead
AVmin9TEMP_LCWLeaving Chilled WaterRead
AV22TEMP_MTRBThrust Bearing TempRead
AV21TEMP_MTRB_OILThrust Bearing Oil TempRead
AV23TEMP_MTRB1Low Speed ME Brg TempRead
AV24TEMP_MTRB2Low Speed CE Brg TempRead
AV25TEMP_MTRB3High Speed ME Brg TempRead
AV26TEMP_MTRB4High Speed CE Brg TempRead
AV27TEMP_MTRW1Motor Winding 1 TempRead
AV28TEMP_MTRW2Motor Winding 2 TempRead
AV29TEMP_MTRW3Motor Winding 3 TempRead
AV31TEMP_OILT_DISOil Supply TempRead
AV30TEMP_OILT_SMPOil Sump TempRead
AV32TEMP_PGC_SUCTPurge Comp Suction TempRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19DV (PIC6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaEdge 19DV (PIC6)

How many BACnet points does the Carrier AquaEdge 19DV (PIC6) have?

This list has 229 BACnet objects: 151 analog values, 69 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaEdge 19DV (PIC6) BACnet points are writable?

14 of the 229 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaEdge 19DV (PIC6) BACnet documentation?

The source is AquaEdge 19DV Two-Stage High-Efficiency Centrifugal Chiller - Controls Operation and Troubleshooting (Appendix D) (19DV-CLT-3T), revision 2020-02, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0D/19DV-CLT-3T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaEdge 19DV (PIC6)?

Start with BV 66 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 68 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 67 GENUNIT_EMSTOP_wr (Emergency stop command); AV 147 GENUNIT_CTRL_PNT_wr (Control point command); AV 148 GENUNIT_DEM_LIM_wr (Demand limit command); MV 1 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 7 GENUNIT_ch_state (Chiller status code); AV 9 TEMP_LCW (Leaving chilled water temperature); AV 8 TEMP_ECW (Entering chilled water temperature); AV 85 ALARMRST_alarm_1 (Current alarm 1).

How do I enable BMS control of the Carrier AquaEdge 19DV (PIC6)?

In NETWORK control mode the chiller starts and stops from the CHIL_S_S and CHIL_OCC points written over the network (both must be true). Use EMSTOP for a quick shutdown. A STOP OVERRIDE point in GENUNIT, if enabled, prevents starting.

How do I check these points on the real AquaEdge 19DV (PIC6)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaEdge 19DV Two-Stage High-Efficiency Centrifugal Chiller - Controls Operation and Troubleshooting (Appendix D) · 19DV-CLT-3T · rev. 2020-02. Object names, instances and units are reproduced as published; descriptions are our own.