- AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Air-cooled scroll chiller controller (BACnet option) · BACnet points list
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet points list
Updated 28 October 2026
On the 30RAP, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. Its list has about 160 objects: AVs, BVs and a few multistate values (MSV) for start/stop, emergency stop, control point, demand limit, setpoints, water temperatures, pressures, compressor and pump status, run hours, service counters and alarm state.
This page lists 161 BACnet objects for the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaSnap 30RAP 010-150 (UPC Open BACnet option)
- Equipment
- Air-cooled scroll chiller controller (BACnet option)
- Equipment type
- Chillers
- BACnet objects
- 161 (34 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
- Also known as
- 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink
BMS integration notes: Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Address the UPC Open, set the MS/TP DIP switches, and set the chiller control method to CCN (Configuration > OPT2 > CTRL = 3). The BMS then starts and stops the unit with BV 4 (CHIL_S_S) and can write control point and demand limit; read control mode, leaving fluid temperature, capacity and alarm state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 4 | chil_s_s_1 | Network start/stop | Write |
| BV 6 | emstop_1 | Emergency stop command | Write |
| AV 5 | ctrl_pnt_1 | Control point (leaving fluid setpoint) | Write |
| AV 2 | dem_lim_1 | Demand limit, 0-100 % | Write |
| AV 8 | stat_1 | Control mode code | Read |
| AV 31 | cool_lwt_1 | Cooler leaving fluid temperature | Read |
| AV 30 | cool_ewt_1 | Cooler entering fluid temperature | Read |
| AV 3 | cap_t_1 | Percent total capacity | Read |
| MV 1 | alm_msv_1 | Alarm state: 1 Normal, 2 Alert, 3 Alarm | Read |
Enable & remote start
Set the control method to CCN (Configuration > OPT2 > CTRL = 3). An external CCN device then forces CHIL_S_S (BV 4) between start and stop.
Network setup
- The BACnet option adds a UPC Open controller; it speaks BACnet MS/TP at 9600, 19.2k, 38.4k or 76.8k (Carrier default 76.8k), set on BAS port DIP switches DS1-DS2.
- For MS/TP set DS3 to enable, DS4 to E1-485 and the protocol switches DS5-DS8 to MSTP; the EIA-485 jumpers must be set to EIA-485 and 2W.
- MAC address from the two rotary switches (tens and ones); the controller reads switches and DIP settings only at power-up.
- Device instance is auto-generated as the network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120; change it with i-Vu Tools or a BACview.
- Fit a BT485 terminator on the first and last controller of the MS/TP segment.
Watch out for
- Several points (pumps, head pressure, Greenspeed fan drive) depend on unit options.
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 2 | dem_lim_1 | Active Demand Limit | % | Write | |
| AVmin | 3 | cap_t_1 | Percent Total Capacity | % | Read | |
| AV | 4 | sp_1 | Active Setpoint | °F | Read | |
| AVmin | 5 | ctrl_pnt_1 | Control Point | °F | Write | |
| AV | 6 | ewt_1 | Entering Fluid Temp | °F | Read | |
| AV | 7 | lwt_1 | Leaving Fluid Temp - Prime Variable | °F | Read | |
| AVmin | 8 | stat_1 | Control Mode | Read | ||
| AV | 9 | stage_1 | Requested Stage | Read | ||
| AV | 11 | capa_t_1 | Percent Total Capacity (circuit A) | % | Read | |
| AV | 12 | capa_a_1 | Percent Available Cap. (circuit A) | % | Read | |
| AV | 13 | dp_a_1 | Discharge Pressure (circuit A) | psig | Read | |
| AV | 14 | sp_a_1 | Suction Pressure (circuit A) | psig | Read | |
| AV | 15 | disgas_1 | Discharge Gas Temp | °F | Read | |
| AV | 16 | tmp_scta_1 | Saturated Condensing Tmp (circuit A) | °F | Read | |
| AV | 17 | tmp_ssta_1 | Saturated Suction Temp (circuit A) | °F | Read | |
| AV | 18 | exv_a_1 | EXV% Open (circuit A) | % | Read | |
| AV | 19 | vhp_act_1 | Var Head Press Output | mA | Read | |
| AV | 20 | tmp_rgta_1 | Compr Return Gas Temp (circuit A) | °F | Read | |
| AV | 21 | capb_t_1 | Percent Total Capacity (circuit B) | % | Read | |
| AV | 22 | capb_a_1 | Percent Available Cap. (circuit A) | % | Read | |
| AV | 23 | dp_b_1 | Discharge Pressure (circuit B) | psig | Read | |
| AV | 24 | sp_b_1 | Suction Pressure (circuit B) | psig | Read | |
| AV | 25 | tmp_sctb_1 | Saturated Condensing Tmp (circuit B) | °F | Read | |
| AV | 26 | tmp_sstb_1 | Saturated Suction Temp (circuit B) | °F | Read | |
| AV | 27 | exv_b_1 | EXV% Open (circuit B) | % | Read | |
| AV | 28 | tmp_rgtb_1 | Compr Return Gas Temp (circuit B) | °F | Read | |
| AV | 29 | hsp_1 | Head Setpoint | °F | Read | |
| AVmin | 30 | cool_ewt_1 | Cooler Entering Fluid | °F | Read | |
| AVmin | 31 | cool_lwt_1 | Cooler Leaving Fluid | °F | Read | |
| AV | 32 | dual_ | Lead/Lag Leaving Fluid | °F | Read | |
| AV | 33 | rst_ma_1 | 4-20 mA Reset Signal | °F | Read | |
| AV | 34 | min_left_1 | Minutes Left for Start | min | Read | |
| AV | 36 | lmt_ma_1 | 4-20 mA Demand Signal | mA | Read | |
| AV | 38 | lwt_sp_1 | Cooler LWT Setpoint | °F | Read | |
| AV | 39 | pmp_dlta_1 | Pump Changeover Hours | hr | Write | |
| AV | 40 | pmp_slct_1 | Cooler Pump Select | Write | ||
| AV | 41 | pump_dly_1 | Cooler Pump Shutdown Dly | min | Write | |
| AV | 42 | delay_1 | Minutes Off Time | min | Write | |
| AV | 43 | lead_typ_1 | Lead/Lag Circuit Select | Read | ||
| AV | 44 | sh_a_1 | Suction Superheat Temp (circuit A) | °F (delta) | Read | |
| AV | 45 | sh_b_1 | Suction Superheat Temp (circuit B) | °F (delta) | Read | |
| AV | 46 | p1_cdown_1 | Pump 1 Service Countdown | hr | Read | |
| AV | 47 | p2_cdown_1 | Pump 2 Service Countdown | hr | Read | |
| AV | 48 | si_pumps_1 | Pump Service Interval | hr | Write | |
| AV | 49 | cl_cdown_1 | Coil Service Countdown | hr | Read | |
| AV | 50 | si_coil_1 | Coil Cleaning Srvc Inter | hr | Write | |
| AV | 51 | si_strnr_1 | Strainer Srvc Interval | hr | Write | |
| AV | 52 | st_cdown_1 | Strainer Srvc Countdown | hr | Read | |
| AV | 53 | csp1_1 | Cooling Setpoint 1 | °F | Write | |
| AV | 54 | csp2_1 | Cooling Setpoint 2 | °F | Write | |
| AV | 55 | csp3_1 | Ice Setpoint | °F | Write | |
| AV | 56 | cramp_1 | Cooling Ramp Loading | Write | ||
| AV | 57 | hr_mach_1 | Machine Operating Hours | hr | Read | |
| AV | 58 | cy_mach_1 | Machine Starts | Read | ||
| AV | 59 | hr_cira_1 | Circuit A Run Hours | hr | Read | |
| AV | 60 | hr_a1_1 | Compressor A1 Run Hours | hr | Read | |
| AV | 61 | hr_a2_1 | Compressor A2 Run Hours | hr | Read | |
| AV | 62 | hr_a3_1 | Compressor A3 Run Hours | hr | Read | |
| AV | 63 | hr_cirb_1 | Circuit B Run Hours | hr | Read | |
| AV | 64 | hr_b1_1 | Compressor B1 Run Hours | hr | Read | |
| AV | 65 | hr_b2_1 | Compressor B2 Run Hours | hr | Read | |
| AV | 66 | hr_b3_1 | Compressor B3 Run Hours | hr | Read | |
| AV | 67 | cy_cira_1 | Circuit A Starts | Read | ||
| AV | 68 | cy_a1_1 | Compressor A1 Starts | Read | ||
| AV | 69 | cy_a2_1 | Compressor A2 Starts | Read | ||
| AV | 70 | cy_a3_1 | Compressor A3 Starts | Read | ||
| AV | 71 | cy_cirb_1 | Circuit B Starts | Read | ||
| AV | 72 | cy_b1_1 | Compressor B1 Starts | Read | ||
| AV | 73 | cy_b2_1 | Compressor B2 Starts | Read | ||
| AV | 74 | cy_b3_1 | Compressor B3 Starts | Read | ||
| AV | 75 | hr_pump1_1 | Pump 1 Run Hours | hr | Read | |
| AV | 76 | hr_pump2_1 | Pump 2 Run Hours | hr | Read | |
| AV | 77 | seq_type_1 | Loading Sequence Select | Read | ||
| AV | 78 | a1unltme_1 | Comp A1 Unload Time | Read | ||
| AV | 80 | dmv_lvl_1_perct_1 | Demand Level 1 | % | Write | |
| AV | 81 | dmv_lvl_2_perct_1 | Demand Level 2 | % | Write | |
| AV | 82 | dmv_lvl_3_perct_1 | Demand Level 3 | % | Write | |
| AV | 84 | calctons_1 | Available Cap Nominal Tons | TONS | Read | |
| AV | 1003 | oat_1 | Outdoor Air Temperature | °F | Write | |
| AV | 2901 | user_analog_1_1 | User Defined Analog 1 | sq m | Write | |
| AV | 2902 | user_analog_2_1 | User Defined Analog 2 | sq m | Write | |
| AV | 2903 | user_analog_3_1 | User Defined Analog 3 | sq m | Write | |
| AV | 2904 | user_analog_4_1 | User Defined Analog 4 | sq m | Write | |
| AV | 2905 | user_analog_5_1 | User Defined Analog 5 | sq m | Write | |
| AV | 9006 | cool_demand_level_1 | System Cooling Demand Level | Read | ||
| BV | 2 | lsactive_1 | Low Sound Active | Read | ||
| BVmin | 4 | chil_s_s_1 | CCN Chiller | Write | Start/Stop | |
| BV | 5 | mode_1 | Override Modes in Effect | Read | ||
| BVmin | 6 | emstop_1 | Emergency Stop | Write | Enabled/Emstop | |
| BV | 7 | coolpmp1_1 | Cooler Pump Relay 1 | Read | ||
| BV | 8 | coolpmp2_1 | Cooler Pump Relay 2 | Read | ||
| BV | 9 | pmp1_fbk_1 | Cooler Pump 1 Interlock | Read | ||
| BV | 10 | pmp2_fbk_1 | Cooler Pump 2 Interlock | Read | ||
| BV | 11 | coolflow_1 | Cooler Flow Switch | Read | ||
| BV | 12 | rot_pump_1 | Rotate Cooler Pumps Now | Write | No/Yes | |
| BV | 13 | k_a1_rly_1 | Compressor A1 Relay | Read | ||
| BV | 14 | k_a2_rly_1 | Compressor A2 Relay | Read | ||
| BV | 15 | k_a3_rly_1 | Compressor A3 Relay | Read | On/Off | |
| BV | 16 | k_a1_fbk_1 | Compressor A1 Feedback | Read | ||
| BV | 17 | k_a2_fbk_1 | Compressor A2 Feedback | Read | ||
| BV | 18 | k_a3_fbk_1 | Compressor A3 Feedback | Read | On/Off | |
| BV | 19 | k_b1_rly_1 | Compressor B1 Relay | Read | ||
| BV | 20 | k_b2_rly_1 | Compressor B2 Relay | Read | ||
| BV | 21 | k_b3_rly_1 | Compressor B3 Relay | Read | On/Off | |
| BV | 22 | k_b1_fbk_1 | Compressor B1 Feedback | Read | ||
| BV | 23 | k_b2_fbk_1 | Compressor B2 Feedback | Read | ||
| BV | 24 | k_b3_fbk_1 | Compressor B3 Feedback | Read | On/Off | |
| BV | 25 | dmd_sw1_1 | Demand Limit Switch 1 | Read | ||
| BV | 26 | dmd_sw2_1 | Demand Limit Switch 2 | Read | ||
| BV | 27 | ice_done_1 | Ice Done | Read | ||
| BV | 28 | heat_req_1 | Heat Request | Read | ||
| BV | 29 | dual_in_1 | Dual Setpoint Switch | Read | ||
| BV | 30 | mode_1_1 | CSM Controlling Chiller | Read | ||
| BV | 31 | mode_2_1 | WSM Controlling Chiller | Read | ||
| BV | 32 | mode_3_1 | Master/Slave Control | Read | ||
| BV | 33 | mode_5_1 | Ramp Load Limited | Read | ||
| BV | 34 | mode_6_1 | Timed Override In Effect | Read | ||
| BV | 35 | mode_7_1 | Low Cooler Suction Temp A | Read | ||
| BV | 36 | mode_8_1 | Low Cooler Suction Temp B | Read | ||
| BV | 37 | mode_9_1 | Slow Change Override | Read | ||
| BV | 38 | mode_10_1 | Minimum OFF Time Active | Read | ||
| BV | 39 | mode_13_1 | Dual Setpoint | Read | ||
| BV | 40 | mode_14_1 | Temperature Reset | Read | ||
| BV | 41 | mode_15_1 | Demand/Sound Limited | Read | ||
| BV | 42 | mode_16_1 | Cooler Freeze Protection | Read | ||
| BV | 43 | mode_17_1 | Low Temperature Cooling | Read | ||
| BV | 44 | mode_18_1 | High Temperature Cooling | Read | ||
| BV | 45 | mode_19_1 | Making ICE | Read | ||
| BV | 46 | mode_20_1 | Storing ICE | Read | ||
| BV | 47 | mode_21_1 | High SCT Circuit A | Read | ||
| BV | 48 | mode_22_1 | High SCT Circuit B | Read | ||
| BV | 49 | mode_23_1 | Minimum Comp. On Time | Read | ||
| BV | 50 | mode_24_1 | Pump Off Delay Time | Read | ||
| BV | 51 | mode_25_1 | Low Sound Mode | Read | ||
| BV | 52 | p1_maint_1 | Pump 1 Maintenance Done | Write | Yes/No | |
| BV | 53 | p2_maint_1 | Pump 2 Maintenance Done | Write | Yes/No | |
| BV | 54 | cl_maint_1 | Coil Cleaning Maint.Done | Write | Yes/No | |
| BV | 55 | st_maint_1 | Strainer Maint. Done | Write | Yes/No | |
| BV | 59 | cool_htr_1 | Cooler/Pump Heater | Read | ||
| BV | 60 | fan_1_1 | Fan Relay 1 | Read | ||
| BV | 61 | fan_2_1 | Fan Relay 2 | Read | ||
| BV | 62 | fan_3_1 | Fan Relay 3 | Read | ||
| BV | 63 | fan_4_1 | Fan Relay 4 | Read | ||
| BV | 64 | fan_5_1 | Fan Relay 5 | Read | ||
| BV | 65 | fan_6_1 | Fan Relay 6 | Read | ||
| BV | 66 | fan_7_1 | Fan Relay 7 | Read | ||
| BV | 67 | fan_8_1 | Fan Relay 8 | Read | ||
| BV | 79 | mlv_rly_1 | Minimum Load Valve Relay | Read | ||
| BV | 83 | dem_lmt_act_1 | System Demand Limiting | Read | ||
| BV | 2008 | occ_status | Occupancy Status | Read | ||
| BV | 2911 | user_binary_1_1 | User Defined Binary 1 | Write | ||
| BV | 2912 | user_binary_2_1 | User Defined Binary 2 | Write | ||
| BV | 2913 | user_binary_3_1 | User Defined Binary 3 | Write | ||
| BV | 2914 | user_binary_4_1 | User Defined Binary 4 | Write | ||
| BV | 2915 | user_binary_5_1 | User Defined Binary 5 | Write | ||
| BV | 2999 | element_stat_1 | Element Comm Status | Read | ||
| MVmin | 1 | alm_msv_1 | Alarm State | Read | 1 = Normal, 2 = Alert, 3 = Alarm | |
| MV | 5 | control_msv_1 | Control Method | Read | 1 = Switch, 3 = Occupancy, 4 = CCN | |
| MV | 7 | crst_typ1_msv_1 | Cooling Reset Type | Read | 1 = No Reset, 2 = 4-20mA Input, 3 = External Temp- OAT, 4 = Return Fluid, 5 = External Temp- SPT | |
| MV | 8 | dmd_ctrl_msv_1 | Demand Limit Select | Read | 1 = None, 2 = External Sw. Input, 3 = 4-20mA Input, 4 = Loadshed | |
| MV | 9 | leadpump_msv_1 | Lead Pump | Read | 1 = Automatic, 2 = Pump 1, 3 = Pump 2, 4 = No Configuration |
No points match these filters.
Integration notes
- BACnet comes from the optional UPC Open controller, mounted in the main control box; object names end in _1.
- The Network Points List gives a point description, CCN name, read/write, units, default and range for each object; descriptions here are the printed point descriptions.
- The table lists multistate values as MSV (mapped as MV here), e.g. MV 1 Alarm State and MV 5 Control Method.
- AV 8 Control Mode codes: 1 Test, 2 Local Off, 3 CCN Off, 4 Clock Off, 5 Emergency Stop, 6 Local On, 7 CCN On, 8 Clock On, 9 Heat Enabled, 10 Pump Delay.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RAP 010-150 (UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
How many BACnet points does the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) have?
This list has 161 BACnet objects: 85 analog values, 71 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet points are writable?
34 of the 161 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet documentation?
The source is AquaSnap 30RAP010-150 Air-Cooled Chillers and 30RAP011-060 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix D, BACnet Communication Option, Network Points List) (30RAP-8T), revision 3-23, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0E/30RAP-8T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)?
Start with BV 4 chil_s_s_1 (Network start/stop); BV 6 emstop_1 (Emergency stop command); AV 5 ctrl_pnt_1 (Control point (leaving fluid setpoint)); AV 2 dem_lim_1 (Demand limit, 0-100 %); AV 8 stat_1 (Control mode code); AV 31 cool_lwt_1 (Cooler leaving fluid temperature); AV 30 cool_ewt_1 (Cooler entering fluid temperature); AV 3 cap_t_1 (Percent total capacity); MV 1 alm_msv_1 (Alarm state: 1 Normal, 2 Alert, 3 Alarm).
How do I enable BMS control of the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)?
Set the control method to CCN (Configuration > OPT2 > CTRL = 3). An external CCN device then forces CHIL_S_S (BV 4) between start and stop.
How do I check these points on the real AquaSnap 30RAP 010-150 (UPC Open BACnet option)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaSnap 30RAP010-150 Air-Cooled Chillers and 30RAP011-060 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix D, BACnet Communication Option, Network Points List) · 30RAP-8T · rev. 3-23. Object names, instances and units are reproduced as published; descriptions are our own.