Air-cooled scroll chiller controller (BACnet option) · BACnet points list

Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet points list

Updated 28 October 2026

Short answer

On the 30RAP, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. Its list has about 160 objects: AVs, BVs and a few multistate values (MSV) for start/stop, emergency stop, control point, demand limit, setpoints, water temperatures, pressures, compressor and pump status, run hours, service counters and alarm state.

This page lists 161 BACnet objects for the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Equipment
Air-cooled scroll chiller controller (BACnet option)
Equipment type
Chillers
BACnet objects
161 (34 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
Also known as
30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink
Source document
AquaSnap 30RAP010-150 Air-Cooled Chillers and 30RAP011-060 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix D, BACnet Communication Option, Network Points List) · 30RAP-8T · rev. 3-23
Download CSV 161 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)

Integration in brief

Address the UPC Open, set the MS/TP DIP switches, and set the chiller control method to CCN (Configuration > OPT2 > CTRL = 3). The BMS then starts and stops the unit with BV 4 (CHIL_S_S) and can write control point and demand limit; read control mode, leaving fluid temperature, capacity and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 4chil_s_s_1Network start/stopWrite
BV 6emstop_1Emergency stop commandWrite
AV 5ctrl_pnt_1Control point (leaving fluid setpoint)Write
AV 2dem_lim_1Demand limit, 0-100 %Write
AV 8stat_1Control mode codeRead
AV 31cool_lwt_1Cooler leaving fluid temperatureRead
AV 30cool_ewt_1Cooler entering fluid temperatureRead
AV 3cap_t_1Percent total capacityRead
MV 1alm_msv_1Alarm state: 1 Normal, 2 Alert, 3 AlarmRead

Enable & remote start

Set the control method to CCN (Configuration > OPT2 > CTRL = 3). An external CCN device then forces CHIL_S_S (BV 4) between start and stop.

Network setup

Watch out for

Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

161 of 161 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet Points List
DescriptionStates
AVmin2dem_lim_1Active Demand Limit%Write
AVmin3cap_t_1Percent Total Capacity%Read
AV4sp_1Active Setpoint°FRead
AVmin5ctrl_pnt_1Control Point°FWrite
AV6ewt_1Entering Fluid Temp°FRead
AV7lwt_1Leaving Fluid Temp - Prime Variable°FRead
AVmin8stat_1Control ModeRead
AV9stage_1Requested StageRead
AV11capa_t_1Percent Total Capacity (circuit A)%Read
AV12capa_a_1Percent Available Cap. (circuit A)%Read
AV13dp_a_1Discharge Pressure (circuit A)psigRead
AV14sp_a_1Suction Pressure (circuit A)psigRead
AV15disgas_1Discharge Gas Temp°FRead
AV16tmp_scta_1Saturated Condensing Tmp (circuit A)°FRead
AV17tmp_ssta_1Saturated Suction Temp (circuit A)°FRead
AV18exv_a_1EXV% Open (circuit A)%Read
AV19vhp_act_1Var Head Press OutputmARead
AV20tmp_rgta_1Compr Return Gas Temp (circuit A)°FRead
AV21capb_t_1Percent Total Capacity (circuit B)%Read
AV22capb_a_1Percent Available Cap. (circuit A)%Read
AV23dp_b_1Discharge Pressure (circuit B)psigRead
AV24sp_b_1Suction Pressure (circuit B)psigRead
AV25tmp_sctb_1Saturated Condensing Tmp (circuit B)°FRead
AV26tmp_sstb_1Saturated Suction Temp (circuit B)°FRead
AV27exv_b_1EXV% Open (circuit B)%Read
AV28tmp_rgtb_1Compr Return Gas Temp (circuit B)°FRead
AV29hsp_1Head Setpoint°FRead
AVmin30cool_ewt_1Cooler Entering Fluid°FRead
AVmin31cool_lwt_1Cooler Leaving Fluid°FRead
AV32dual_Lead/Lag Leaving Fluid°FRead
AV33rst_ma_14-20 mA Reset Signal°FRead
AV34min_left_1Minutes Left for StartminRead
AV36lmt_ma_14-20 mA Demand SignalmARead
AV38lwt_sp_1Cooler LWT Setpoint°FRead
AV39pmp_dlta_1Pump Changeover HourshrWrite
AV40pmp_slct_1Cooler Pump SelectWrite
AV41pump_dly_1Cooler Pump Shutdown DlyminWrite
AV42delay_1Minutes Off TimeminWrite
AV43lead_typ_1Lead/Lag Circuit SelectRead
AV44sh_a_1Suction Superheat Temp (circuit A)°F (delta)Read
AV45sh_b_1Suction Superheat Temp (circuit B)°F (delta)Read
AV46p1_cdown_1Pump 1 Service CountdownhrRead
AV47p2_cdown_1Pump 2 Service CountdownhrRead
AV48si_pumps_1Pump Service IntervalhrWrite
AV49cl_cdown_1Coil Service CountdownhrRead
AV50si_coil_1Coil Cleaning Srvc InterhrWrite
AV51si_strnr_1Strainer Srvc IntervalhrWrite
AV52st_cdown_1Strainer Srvc CountdownhrRead
AV53csp1_1Cooling Setpoint 1°FWrite
AV54csp2_1Cooling Setpoint 2°FWrite
AV55csp3_1Ice Setpoint°FWrite
AV56cramp_1Cooling Ramp LoadingWrite
AV57hr_mach_1Machine Operating HourshrRead
AV58cy_mach_1Machine StartsRead
AV59hr_cira_1Circuit A Run HourshrRead
AV60hr_a1_1Compressor A1 Run HourshrRead
AV61hr_a2_1Compressor A2 Run HourshrRead
AV62hr_a3_1Compressor A3 Run HourshrRead
AV63hr_cirb_1Circuit B Run HourshrRead
AV64hr_b1_1Compressor B1 Run HourshrRead
AV65hr_b2_1Compressor B2 Run HourshrRead
AV66hr_b3_1Compressor B3 Run HourshrRead
AV67cy_cira_1Circuit A StartsRead
AV68cy_a1_1Compressor A1 StartsRead
AV69cy_a2_1Compressor A2 StartsRead
AV70cy_a3_1Compressor A3 StartsRead
AV71cy_cirb_1Circuit B StartsRead
AV72cy_b1_1Compressor B1 StartsRead
AV73cy_b2_1Compressor B2 StartsRead
AV74cy_b3_1Compressor B3 StartsRead
AV75hr_pump1_1Pump 1 Run HourshrRead
AV76hr_pump2_1Pump 2 Run HourshrRead
AV77seq_type_1Loading Sequence SelectRead
AV78a1unltme_1Comp A1 Unload TimeRead
AV80dmv_lvl_1_perct_1Demand Level 1%Write
AV81dmv_lvl_2_perct_1Demand Level 2%Write
AV82dmv_lvl_3_perct_1Demand Level 3%Write
AV84calctons_1Available Cap Nominal TonsTONSRead
AV1003oat_1Outdoor Air Temperature°FWrite
AV2901user_analog_1_1User Defined Analog 1sq mWrite
AV2902user_analog_2_1User Defined Analog 2sq mWrite
AV2903user_analog_3_1User Defined Analog 3sq mWrite
AV2904user_analog_4_1User Defined Analog 4sq mWrite
AV2905user_analog_5_1User Defined Analog 5sq mWrite
AV9006cool_demand_level_1System Cooling Demand LevelRead
BV2lsactive_1Low Sound ActiveRead
BVmin4chil_s_s_1CCN ChillerWriteStart/Stop
BV5mode_1Override Modes in EffectRead
BVmin6emstop_1Emergency StopWriteEnabled/Emstop
BV7coolpmp1_1Cooler Pump Relay 1Read
BV8coolpmp2_1Cooler Pump Relay 2Read
BV9pmp1_fbk_1Cooler Pump 1 InterlockRead
BV10pmp2_fbk_1Cooler Pump 2 InterlockRead
BV11coolflow_1Cooler Flow SwitchRead
BV12rot_pump_1Rotate Cooler Pumps NowWriteNo/Yes
BV13k_a1_rly_1Compressor A1 RelayRead
BV14k_a2_rly_1Compressor A2 RelayRead
BV15k_a3_rly_1Compressor A3 RelayReadOn/Off
BV16k_a1_fbk_1Compressor A1 FeedbackRead
BV17k_a2_fbk_1Compressor A2 FeedbackRead
BV18k_a3_fbk_1Compressor A3 FeedbackReadOn/Off
BV19k_b1_rly_1Compressor B1 RelayRead
BV20k_b2_rly_1Compressor B2 RelayRead
BV21k_b3_rly_1Compressor B3 RelayReadOn/Off
BV22k_b1_fbk_1Compressor B1 FeedbackRead
BV23k_b2_fbk_1Compressor B2 FeedbackRead
BV24k_b3_fbk_1Compressor B3 FeedbackReadOn/Off
BV25dmd_sw1_1Demand Limit Switch 1Read
BV26dmd_sw2_1Demand Limit Switch 2Read
BV27ice_done_1Ice DoneRead
BV28heat_req_1Heat RequestRead
BV29dual_in_1Dual Setpoint SwitchRead
BV30mode_1_1CSM Controlling ChillerRead
BV31mode_2_1WSM Controlling ChillerRead
BV32mode_3_1Master/Slave ControlRead
BV33mode_5_1Ramp Load LimitedRead
BV34mode_6_1Timed Override In EffectRead
BV35mode_7_1Low Cooler Suction Temp ARead
BV36mode_8_1Low Cooler Suction Temp BRead
BV37mode_9_1Slow Change OverrideRead
BV38mode_10_1Minimum OFF Time ActiveRead
BV39mode_13_1Dual SetpointRead
BV40mode_14_1Temperature ResetRead
BV41mode_15_1Demand/Sound LimitedRead
BV42mode_16_1Cooler Freeze ProtectionRead
BV43mode_17_1Low Temperature CoolingRead
BV44mode_18_1High Temperature CoolingRead
BV45mode_19_1Making ICERead
BV46mode_20_1Storing ICERead
BV47mode_21_1High SCT Circuit ARead
BV48mode_22_1High SCT Circuit BRead
BV49mode_23_1Minimum Comp. On TimeRead
BV50mode_24_1Pump Off Delay TimeRead
BV51mode_25_1Low Sound ModeRead
BV52p1_maint_1Pump 1 Maintenance DoneWriteYes/No
BV53p2_maint_1Pump 2 Maintenance DoneWriteYes/No
BV54cl_maint_1Coil Cleaning Maint.DoneWriteYes/No
BV55st_maint_1Strainer Maint. DoneWriteYes/No
BV59cool_htr_1Cooler/Pump HeaterRead
BV60fan_1_1Fan Relay 1Read
BV61fan_2_1Fan Relay 2Read
BV62fan_3_1Fan Relay 3Read
BV63fan_4_1Fan Relay 4Read
BV64fan_5_1Fan Relay 5Read
BV65fan_6_1Fan Relay 6Read
BV66fan_7_1Fan Relay 7Read
BV67fan_8_1Fan Relay 8Read
BV79mlv_rly_1Minimum Load Valve RelayRead
BV83dem_lmt_act_1System Demand LimitingRead
BV2008occ_statusOccupancy StatusRead
BV2911user_binary_1_1User Defined Binary 1Write
BV2912user_binary_2_1User Defined Binary 2Write
BV2913user_binary_3_1User Defined Binary 3Write
BV2914user_binary_4_1User Defined Binary 4Write
BV2915user_binary_5_1User Defined Binary 5Write
BV2999element_stat_1Element Comm StatusRead
MVmin1alm_msv_1Alarm StateRead1 = Normal, 2 = Alert, 3 = Alarm
MV5control_msv_1Control MethodRead1 = Switch, 3 = Occupancy, 4 = CCN
MV7crst_typ1_msv_1Cooling Reset TypeRead1 = No Reset, 2 = 4-20mA Input, 3 = External Temp- OAT, 4 = Return Fluid, 5 = External Temp- SPT
MV8dmd_ctrl_msv_1Demand Limit SelectRead1 = None, 2 = External Sw. Input, 3 = 4-20mA Input, 4 = Loadshed
MV9leadpump_msv_1Lead PumpRead1 = Automatic, 2 = Pump 1, 3 = Pump 2, 4 = No Configuration

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RAP 010-150 (UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)

How many BACnet points does the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) have?

This list has 161 BACnet objects: 85 analog values, 71 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet points are writable?

34 of the 161 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet documentation?

The source is AquaSnap 30RAP010-150 Air-Cooled Chillers and 30RAP011-060 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix D, BACnet Communication Option, Network Points List) (30RAP-8T), revision 3-23, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0E/30RAP-8T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)?

Start with BV 4 chil_s_s_1 (Network start/stop); BV 6 emstop_1 (Emergency stop command); AV 5 ctrl_pnt_1 (Control point (leaving fluid setpoint)); AV 2 dem_lim_1 (Demand limit, 0-100 %); AV 8 stat_1 (Control mode code); AV 31 cool_lwt_1 (Cooler leaving fluid temperature); AV 30 cool_ewt_1 (Cooler entering fluid temperature); AV 3 cap_t_1 (Percent total capacity); MV 1 alm_msv_1 (Alarm state: 1 Normal, 2 Alert, 3 Alarm).

How do I enable BMS control of the Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)?

Set the control method to CCN (Configuration > OPT2 > CTRL = 3). An external CCN device then forces CHIL_S_S (BV 4) between start and stop.

How do I check these points on the real AquaSnap 30RAP 010-150 (UPC Open BACnet option)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaSnap 30RAP010-150 Air-Cooled Chillers and 30RAP011-060 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix D, BACnet Communication Option, Network Points List) · 30RAP-8T · rev. 3-23. Object names, instances and units are reproduced as published; descriptions are our own.