Water-cooled screw chiller controller (BACnet option) · BACnet points list

Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet points list

Updated 28 October 2026

Short answer

On the 30HX, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. Its list has about 250 AVs, BVs and three multistate values covering start/stop, control point, demand limit, setpoints, cooler and condenser water temperatures, refrigerant pressures, compressor currents and run hours, and alarm state.

This page lists 252 BACnet objects for the Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Equipment
Water-cooled screw chiller controller (BACnet option)
Equipment type
Chillers
BACnet objects
252 (16 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
Also known as
30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller
Source document
30HXA,HXC076-271 Condenserless and Water-Cooled Chillers with ComfortLink Controls 50/60 Hz, Series 9 - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix H, BACnet Communication Option, Network Points List) · 30HX-2T · rev. 8-24
Download CSV 252 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)

Integration in brief

Address the UPC Open, set the MS/TP DIP switches, and set the control method (OPT2 > CTRL) to CCN. The BMS then starts and stops the chiller with BV 3 (CHIL_S_S) and can write control point and demand limit; read control mode, leaving fluid temperature, capacity and alarm state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3chil_s_s_1Network start/stopWrite
AV 59ctrl_pnt_1Control point (leaving fluid setpoint)Write
AV 16dem_lim_1Demand limit, 0-100 %Write
MV 5stat_msv_1Control modeRead
AV 62cool_lwt_1Cooler leaving fluid temperatureRead
AV 61cool_ewt_1Cooler entering fluid temperatureRead
AV 120cap_t_1Percent total capacityRead
MV 2alm_msv_1Alarm state: 1 Normal, 2 Alert, 3 AlarmRead

Enable & remote start

Set the control method (OPT2 > CTRL) to CCN = CCN Control; CHIL_S_S (BV 3) then starts and stops the chiller from the network.

Network setup

Watch out for

Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

252 of 252 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet Points List
DescriptionStates
AV1dmv_lvl_1_perct_1Demand Level 1%Read
AV2dmv_lvl_2_perct_1Demand Level 2%Read
AV3dmv_lvl_3_perct_1Demand Level 3%Read
AV4csp_in_14-20 ma Cooling SetpointmARead
AV5lmt_ma_14-20 ma Demand SignalmARead
AV6hsp_in_14-20 ma Heating SetpointmARead
AV7rst_ma_14-20 ma Reset SignalmARead
AV8tmtr_a1_1A1 Motor Temperature°FRead
AV9fltp_a1_1A1 Oil Filter Diff.PressPSIRead
AV10op_a1_1A1 Oil PressurePSIGRead
AV11dop_a1_1A1 Oil Pressure Diff.PSIRead
AV12tmtr_a2_1A2 Motor Temperature°FRead
AV13fltp_a2_1A2 Oil Filter Diff.PressPSIRead
AV14op_a2_1A2 Oil PressurePSIGRead
AV15dop_a2_1A2 Oil Pressure Diff.PSIRead
AVmin16dem_lim_1Active Demand Limit%Write
AV17sp_1Active Setpoint°FRead
AV18alrmcnfg_1Alarm Relay UsageRead
AV19alm_1Alarm StateRead
AV20aprch_sp_1Approach Setpoint°FRead
AV21tmtr_b1_1B1 Motor Temperature°FRead
AV22fltp_b1_1B1 Oil Filter Diff.PressPSIRead
AV23op_b1_1B1 Oil PressurePSIRead
AV24dop_b1_1B1 Oil Pressure Diff.PSIRead
AV25tmtr_b2_1B2 Motor Temperature°FRead
AV26fltp_b2_1B2 Oil Filter Diff.PressPSIRead
AV27op_b2_1B2 Oil PressurePSIRead
AV28dop_b2_1B2 Oil Pressure Diff.PSIRead
AV29mop_spa_1Calculated MOP Circuit A°FRead
AV30mop_spb_1Calculated MOP Circuit B°FRead
AV31dl_stat_1CCN Loadshed SignalRead
AV32hr_cira_1Circuit A Run HourshrRead
AV33cy_cira_1Circuit A StartsRead
AV34hr_cirb_1Circuit B Run HourshrRead
AV35cy_cirb_1Circuit B StartsRead
AV36a_curr_1Circuit Running CurrentARead
AV37b_curr_1Circuit Running CurrentARead
AV38a1_mta_1Comp A1 % Must Trip Amps%Read
AV39a1_curr_1Comp A1 Running CurrentARead
AV40a2_mta_1Comp A2 % Must Trip Amps%Read
AV41a2_curr_1Comp A2 Running CurrentARead
AV42b1_mta_1Comp B1 % Must Trip Amps%Read
AV43b1_curr_1Comp B1 Running CurrentARead
AV44b2_mta_1Comp B2 % Must Trip Amps%Read
AV45b2_curr_1Comp B2 Running CurrentARead
AV46hr_a1_1Compressor A1 Run HourshrRead
AV47cy_a1_1Compressor A1 StartsRead
AV48hr_a2_1Compressor A2 Run HourshrRead
AV49cy_a2_1Compressor A2 StartsRead
AV50hr_b1_1Compressor B1 Run HourshrRead
AV51cy_b1_1Compressor B1 StartsRead
AV52hr_b2_1Compressor B2 Run HourshrRead
AV53cy_b2_1Compressor B2 StartsRead
AV54comp_seq_1Compressor SequenceWrite
AV55cond_ewt_1Condenser Entering Fluid°FRead
AV56cond_lwt_1Condenser Leaving Fluid°FRead
AV57cnpc_1Condenser Pump ControlRead
AV58stat_1Control ModeRead
AVmin59ctrl_pnt_1Control Point°FWrite
AV60coolewts_1Cool Entering Fluid-Slave°FRead
AVmin61cool_ewt_1Cooler Entering Fluid°FRead
AVmin62cool_lwt_1Cooler Leaving Fluid°FRead
AV63cramp_1Cooling Ramp Loading°FWrite
AV64csp1_1Cooling Setpoint 1°FWrite
AV65csp2_1Cooling Setpoint 2°FWrite
AV66coollwts_1Cool Leaving Fluid-Slave°FRead
AV67cur_trip_1Current Unbalance SetPnt%Read
AV68z_gain_1Deadband MultiplierRead
AV69dmt20ma_1Demand Limit at 20 mA%Read
AV70distmp_a_1Discharge Gas Temp (circuit A)°FRead
AV71distmp_b_1Discharge Gas Temp (circuit B)°FRead
AV72distmpa1_1Discharge Gas Temp - A1°FRead
AV73distmpa2_1Discharge Gas Temp - A2°FRead
AV74distmpb1_1Discharge Gas Temp - B1°FRead
AV75distmpb2_1Discharge Gas Temp - B2°FRead
AV76dp_a_1Discharge Pressure (circuit A)PSIRead
AV77dp_b_1Discharge Pressure (circuit B)PSIRead
AV78sh_a_1Discharge Superheat Temp (circuit A)°FRead
AV79sh_b_1Discharge Superheat Temp (circuit B)°FRead
AV80size_dpx_1Dual Chiller SizetonsRead
AV81sizeadpx_1Dual Chiller Tons AvailtonsRead
AV82dclgcapl_1Dual Chill Lag CapLimit%Read
AV83dcldcapl_1Dual Chill Lead Cap Limit%Read
AV84capa_dpx_1Dual Chill Pct Avail Cap%Read
AV85capt_dpx_1Dual Chill Pct Total Cap%Read
AV86ecnp_a_1Economizer Pressure (circuit A)PSIRead
AV87ecnp_b_1Economizer Pressure (circuit B)PSIRead
AV88ewt_1Entering Fluid Temp°FRead
AV89exv_a_1EXV % Open (circuit A)%Read
AV90exv_b_1EXV % Open (circuit B)%Read
AV91head_typ_1Head Press. Control TypeRead
AV92hsp_a_1Head Pressure Setpoint A°FWrite
AV93hsp_b_1Head Pressure Setpoint B°FWrite
AV94hramp_1Heating Ramp LoadingRead
AV95hsp1_1Heating Setpoint 1°FRead
AV96hsp2_1Heating Setpoint 2°FRead
AV97csp3_1Ice Setpoint°FWrite
AV98lag_cp_1Lag Chiller Ctrl Point°FRead
AV99ll_delay_1Lag Start DelayminRead
AV100ll_bal_d_1Lead/Lag Balance Delta°FRead
AV101ll_bal_1Lead/Lag Balance SelecthrsRead
AV102dual_lwt_1Lead/Lag Leaving FluidRead
AV103lead_type_1Lead/Lag Sequence SelectWrite
AV104lead_cp_1Lead Chiller Ctrl PointRead
AV105lwt_1Leaving Fluid Temp - Prime Variable°FRead
AV106smz_1Load/Unload FactorRead
AV107smzslave_1Load/Unload Factor-SlaveRead
AV108seq_type_1Loading Sequence SelectWrite
AV109shed_del_1Loadshed Demand Delta%Read
AV110shed_num_1Loadshed Group NumberRead
AV111hr_mach_1Machine Operating HourshrRead
AV112cy_mach_1Machine StartsRead
AV113shed_tim_1Maximum Loadshed TimeminRead
AV114delay_1Minutes Off TimeminWrite
AV115fp_sp_1Oil Filter Delta P SetptPSIRead
AV116oat_1Outside Air Temperature°FWrite
AV117cap_a_1Percent Avail.Capacity%Read
AV118capa_a_1Percent Available Cap. (circuit A)%Read
AV119capb_a_1Percent Available Cap. (circuit A)%Read
AVmin120cap_t_1Percent Total Capacity%Read
AV121capa_t_1Percent Total Capacity (circuit A)%Read
AV122capb_t_1Percent Total Capacity (circuit B)%Read
AV123hrem_deg_1Remote - Degrees Reset°F (delta)Read
AV124hrem_ful_1Remote - Full Reset TempdFRead
AV125hrem_no_1Remote - No Reset TempdFRead
AV126hrtn_deg_1Return - Degrees Reset°F (delta)Read
AV127hrtn_ful_1Return - Full Reset Temp°F (delta)Read
AV128hrtn_no_1Return - No Reset Temp°F (delta)Read
AV129tmp_scta_1Saturated Condensing Tmp (circuit A)°FRead
AV130tmp_sctb_1Saturated Condensing Tmp (circuit B)°FRead
AV131tmp_ssta_1Saturated Suction Temp (circuit A)°FRead
AV132tmp_sstb_1Saturated Suction Temp (circuit B)°FRead
AV133slv_addr_1Slave AddressRead
AV134spt_1Space Temperature°FWrite
AV135sp_a_1Suction Pressure (circuit A)PSIRead
AV136sp_b_1Suction Pressure (circuit B)PSIRead
AV137vhptype_1Var Head Pressure SelectRead
AV138vhpa_1Variable Head Press Pct. (circuit A)%Read
AV139vhpb_1Variable Head Press Pct. (circuit B)%Read
AV2901user_analog_1_1User Defined Analog 1Read
AV2902user_analog_2_1User Defined Analog 2Read
AV2903user_analog_3_1User Defined Analog 3Read
AV2904user_analog_4_1User Defined Analog 4Read
AV2905user_analog_5_1User Defined Analog 5Read
AV9006cool_demand_level_1System Cooling Demand LevelRead
BV1schedule_1Local ScheduleReadOn/Off
BV2dem_lmt_act_1System Demand LimitingReadInactive/Active
BVmin3chil_s_s_1CCN ChillerWriteStart/Stop
BV4mode_27_1Circuit A - Pumping outReadOn/Off
BV5mode_28_1Circuit B - Pumping outReadOn/Off
BV6mode_25_1Ckt A Off Ref Flow DelayReadOn/Off
BV7mode_26_1Ckt B Off Ref Flow DelayReadOn/Off
BV8cls_ctrl_1Close Control SelectReadDisable/Enable
BV9k_a1_fbk_1Compressor A1 FeedbackReadOn/Off
BV10k_a1_rly_1Compressor A1 RelayReadOn/Off
BV11k_a2_fbk_1Compressor A2 FeedbackReadOn/Off
BV12k_a2_rly_1Compressor A2 RelayReadOn/Off
BV13k_b1_fbk_1Compressor B1 FeedbackReadOn/Off
BV14k_b1_rly_1Compressor B1 RelayReadOn/Off
BV15k_b2_fbk_1Compressor B2 FeedbackReadOn/Off
BV16k_b2_rly_1Compressor B2 RelayReadOn/Off
BV17condflow_1Condenser Flow SwitchReadOn/Off
BV18cd_temp_1Condenser Fluid SensorsReadNo/Yes
BV19cnd_lock_1Condenser Pump InterlockReadOff/On
BV20cond_pmp_1Condenser Pump RelayReadOn/Off
BV21coolflow_1Cooler Flow SwitchReadOn/Off
BV22mode_16_1Cooler Freeze ProtectionReadOn/Off
BV23cool_htr_1Cooler HeaterReadOn/Off
BV24cpc_1Cooler Pump ControlReadOff/On
BV25cool_pmp_1Cooler Pump RelayReadOn/Off
BV26mode_1_1CSM Controlling ChillerReadOn/Off
BV27mode_15_1Demand Limit In EffectReadOn/Off
BV28dmd_sw1_1Demand Limit Switch 1ReadOn/Off
BV29dmd_sw2_1Demand Limit Switch 2ReadOn/Off
BV30dc_link_1Dual Chiller Link Good ?ReadYes/No
BV31mode_13_1Dual SetpointReadOn/Off
BV32dual_in_1Dual Setpoint SwitchReadOn/Off
BV33emstop_1Emergency StopReadEnable/Emstop
BV34emm_brd_1EMM Module installedReadNo/Yes
BV35noflowen_1Enable No Flow DetectionReadDisable/Enable
BV36fan_1_1Fan 1 RelayReadOn/Off
BV37fan_2_1Fan 2 RelayReadOn/Off
BV38fan_3_1Fan 3 RelayReadOn/Off
BV39fan_4_1Fan 4 RelayReadOn/Off
BV40heatcool_1Heat Cool SelectReadHeat/Cool
BV41mode_23_1High Motor Current Cir.AReadOn/Off
BV42mode_24_1High Motor Current Cir.BReadOn/Off
BV43mode_21_1High SCT Circuit AReadOn/Off
BV44mode_22_1High SCT Circuit BReadOn/Off
BV45mode_18_1Hi Tmp Cool/Lo Tmp HeatReadOn/Off
BV46ice_1Ice DoneReadYes/No
BV47ice_cnfg_1Ice Mode EnableReadDisable/Enable
BV48lag_off_1Lag Commanded Off?ReadYes/No
BV49lag_smzc_1Lag- SMZ Clear CommandedReadYes/No
BV50ll_ena_1Lead/Lag Chiller EnableReadYes/No
BV51leadsmzc_1Lead SMZ Clear CommandedReadDisable/Enable
BV52llsv_1Liq. Line Solenoid ValveReadOpen/Close
BV53loadr_a1_1Loader A1 RelayReadOn/Off
BV54loadr_a2_1Loader A2 RelayReadOn/Off
BV55loadr_b1_1Loader B1 RelayReadOn/Off
BV56loadr_b2_1Loader B2 RelayReadOn/Off
BV57mode_17_1Lo Tmp Cool/Hi Tmp HeatReadOn/Off
BV58mode_7_1Low Cooler Suction Temp AReadOn/Off
BV59mode_8_1Low Cooler Suction Temp BReadOn/Off
BV60mode_11_1Low Dischrge Superheat AReadOn/Off
BV61mode_12_1Low Dischrge Superheat BReadOn/Off
BV62mode_4_1Low Source ProtectionReadOn/Off
BV63mode_19_1Making ICEReadOn/Off
BV64mode_3_1Master/Slave ControlReadOn/Off
BV65ms_sel_1Master/Slave SelectReadSlave/Master
BV66mlv_flg_1Minimum Load Valve SelectReadNo/Yes
BV67mlva_1Minimum Load Valve (circuit A)ReadOn/Off
BV68mlvb_1Minimum Load Valve (circuit B)ReadOn/Off
BV69mode_10_1Minimum OFF Time ActiveReadOn/Off
BV70mtrcl_a1_1Motor Coolng A1 SolenoidReadOn/Off
BV71mtrcl_a2_1Motor Coolng A2 SolenoidReadOn/Off
BV72mtrcl_b1_1Motor Coolng B1 SolenoidReadOn/Off
BV73mtrcl_b2_1Motor Coolng B2 SolenoidReadOn/Off
BV74occ_1OccupiedReadYes/No
BV75oila_htr_1Oil Heater (circuit A)ReadOn/Off
BV76oilb_htr_1Oil Heater (circuit B)ReadOn/Off
BV77oila_sw_1Oil Level Switch (circuit A)ReadClose/Open
BV78oilb_sw_1Oil Level Switch (circuit B)ReadClose/Open
BV79oilpmp_a_1Oil Pump (circuit A)ReadOn/Off
BV80oilpmp_b_1Oil Pump (circuit B)ReadOn/Off
BV81oilsl_a1_1Oil Solenoid A1ReadOn/Off
BV82oilsl_a2_1Oil Solenoid A2ReadOn/Off
BV83oilsl_b1_1Oil Solenoid B1ReadOn/Off
BV84oilsl_b2_1Oil Solenoid B2ReadOn/Off
BV85mode_1Override Modes in EffectReadYes/No
BV86parallel_1Parallel ConfigurationReadYes/No
BV87press_ty_1Pressure TransducersReadNo/Yes
BV88mode_5_1Ramp Load LimitedReadOn/Off
BV89ramp_ebl_1Ramp Load SelectWriteDisable/Enable
BV90mode_9_1Slow Change OverrideReadOn/Off
BV91mode_20_1Storing ICEReadOn/Off
BV92mode_14_1Temperature ResetReadOn/Off
BV93mode_6_1Timed Override In EffectReadOn/Off
BV94mode_29_1Unit Off: No Water FlowReadOn/Off
BV95wintmsg_1Winterize Alert ConfigReadDisable/Enable
BV96mode_2_1WSM Controlling ChillerReadOn/Off
BV97comm_lost_alm_1Element Communications AlarmReadComm Normal/Comm Lost
BV118element_alarm_1Equipment AlarmReadNormal/Alarm
BV2911user_binary_1_1User Defined Binary 1Read
BV2912user_binary_2_1User Defined Binary 2Read
BV2913user_binary_3_1User Defined Binary 3Read
BV2914user_binary_4_1User Defined Binary 4Read
BV2915user_binary_5_1User Defined Binary 5Read
BV2999element_stat_1Element Comm StatusReadNo Comm/Normal
MVmin2alm_msv_1Alarm StateRead1 = Normal, 2 = Alert, 3 = Alarm
MVmin5stat_msv_1Control ModeRead0 = Service Test, 1 = Off-Local, 2 = Off-CCN, 3 = Off-Clock, 4 = Off-Emergency, 5 = On-Local, 6 = On-CCN, 7 = On-Clock
MV6fluidtyp_msv_1Cooler FluidRead1 = Water, 2 = Medium Brine, 3 = Low Brine

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)

How many BACnet points does the Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) have?

This list has 252 BACnet objects: 145 analog values, 104 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet points are writable?

16 of the 252 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet documentation?

The source is 30HXA,HXC076-271 Condenserless and Water-Cooled Chillers with ComfortLink Controls 50/60 Hz, Series 9 - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix H, BACnet Communication Option, Network Points List) (30HX-2T), revision 8-24, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/08/30HX-2T.pdf.

What are the minimum BACnet points to integrate the Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)?

Start with BV 3 chil_s_s_1 (Network start/stop); AV 59 ctrl_pnt_1 (Control point (leaving fluid setpoint)); AV 16 dem_lim_1 (Demand limit, 0-100 %); MV 5 stat_msv_1 (Control mode); AV 62 cool_lwt_1 (Cooler leaving fluid temperature); AV 61 cool_ewt_1 (Cooler entering fluid temperature); AV 120 cap_t_1 (Percent total capacity); MV 2 alm_msv_1 (Alarm state: 1 Normal, 2 Alert, 3 Alarm).

How do I enable BMS control of the Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)?

Set the control method (OPT2 > CTRL) to CCN = CCN Control; CHIL_S_S (BV 3) then starts and stops the chiller from the network.

How do I check these points on the real 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: 30HXA,HXC076-271 Condenserless and Water-Cooled Chillers with ComfortLink Controls 50/60 Hz, Series 9 - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix H, BACnet Communication Option, Network Points List) · 30HX-2T · rev. 8-24. Object names, instances and units are reproduced as published; descriptions are our own.