 "manufacturer": "Carrier",
 "manufacturer_slug": "carrier",
 "model": "30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)",
 "model_slug": "30hx-upc-open",
 "aliases": [
  "30HX",
  "30HXA",
  "30HXC",
  "30HX-2T",
  "UPC Open",
  "ComfortLink",
  "screw chiller"
 ],
 "equipment_type": "Water-cooled screw chiller controller (BACnet option)",
 "applies_to": "Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.",
 "summary": "On the 30HX, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. Its list has about 250 AVs, BVs and three multistate values covering start/stop, control point, demand limit, setpoints, cooler and condenser water temperatures, refrigerant pressures, compressor currents and run hours, and alarm state.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "Network number 16101 followed by the MAC address (MAC 20 gives 1610120)",
 "access_inferred": false,
 "notes": [
  "BACnet comes from the optional UPC Open controller, mounted in the main control box; object names end in _1.",
  "The Network Points List gives a point description, CCN name, read/write, units, default and range for each object; descriptions here are the printed point descriptions.",
  "The table lists multistate values as MSV (mapped as MV here). AV 19 / MV 2 (Alarm State) and AV 58 / MV 5 (Control Mode) share one table row each.",
  "AV 58 Control Mode codes: 0 Service Test, 1 Off-Local, 2 Off-CCN, 3 Off-Clock, 4 Off-Emergency, 5 On-Local, 6 On-CCN, 7 On-Clock.",
  "Emergency Stop (BV 33) is printed as read-only in this table.",
  "Some printed units are clear misprints and are corrected here: Cooling Setpoint 1 (AV 64) has no unit printed (set to °F), Lead/Lag Sequence Select (AV 103) shows °F (removed), circuit starts (AV 33, AV 35) show hr (removed), and \"Minimum\" is shown as min. Other printed defaults and ranges that look shifted by a row are not carried over."
 ],
 "source": {
  "title": "30HXA,HXC076-271 Condenserless and Water-Cooled Chillers with ComfortLink Controls 50/60 Hz, Series 9 - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix H, BACnet Communication Option, Network Points List)",
  "doc_number": "30HX-2T",
  "revision_date": "8-24",
  "url": "https://www.shareddocs.com/hvac/docs/1005/Public/08/30HX-2T.pdf"
 },
 "integration": {
  "summary": "Address the UPC Open, set the MS/TP DIP switches, and set the control method (OPT2 > CTRL) to CCN. The BMS then starts and stops the chiller with BV 3 (CHIL_S_S) and can write control point and demand limit; read control mode, leaving fluid temperature, capacity and alarm state.",
  "minimum_points": [
   {
    "ref": "BV 3",
    "name": "chil_s_s_1",
    "why": "Network start/stop"
   },
   {
    "ref": "AV 59",
    "name": "ctrl_pnt_1",
    "why": "Control point (leaving fluid setpoint)"
   },
   {
    "ref": "AV 16",
    "name": "dem_lim_1",
    "why": "Demand limit, 0-100 %"
   },
   {
    "ref": "MV 5",
    "name": "stat_msv_1",
    "why": "Control mode"
   },
   {
    "ref": "AV 62",
    "name": "cool_lwt_1",
    "why": "Cooler leaving fluid temperature"
   },
   {
    "ref": "AV 61",
    "name": "cool_ewt_1",
    "why": "Cooler entering fluid temperature"
   },
   {
    "ref": "AV 120",
    "name": "cap_t_1",
    "why": "Percent total capacity"
   },
   {
    "ref": "MV 2",
    "name": "alm_msv_1",
    "why": "Alarm state: 1 Normal, 2 Alert, 3 Alarm"
   }
  ],
  "enable": "Set the control method (OPT2 > CTRL) to CCN = CCN Control; CHIL_S_S (BV 3) then starts and stops the chiller from the network.",
  "heartbeat": null,
  "remote_sensors": null,
  "gotchas": [
   "Alarm state and control mode exist both as AVs (AV 19, AV 58) and as multistate values (MV 2, MV 5); the alarm codes start at 0 on the AV and at 1 on the MV.",
   "Emergency Stop (BV 33) is listed read-only in the BACnet table, so it is not a BMS command here."
  ],
  "setup": [
   "The BACnet option adds a UPC Open controller; it speaks BACnet MS/TP at 9600, 19.2k, 38.4k or 76.8k (Carrier default 76.8k), set on BAS port DIP switches DS1-DS2.",
   "For MS/TP set DS3 to enable, DS4 to E1-485 and the protocol switches DS5-DS8 to MSTP; the EIA-485 jumpers must be set to EIA-485 and 2W.",
   "MAC address from the two rotary switches (tens and ones); the controller reads switches and DIP settings only at power-up.",
   "Device instance is auto-generated as the network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120; change it with i-Vu Tools or a BACview.",
   "Fit a BT485 terminator on the first and last controller of the MS/TP segment."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 1,
   "name": "dmv_lvl_1_perct_1",
   "description": "Demand Level 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "dmv_lvl_2_perct_1",
   "description": "Demand Level 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "dmv_lvl_3_perct_1",
   "description": "Demand Level 3",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "csp_in_1",
   "description": "4-20 ma Cooling Setpoint",
   "units": "mA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "lmt_ma_1",
   "description": "4-20 ma Demand Signal",
   "units": "mA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "hsp_in_1",
   "description": "4-20 ma Heating Setpoint",
   "units": "mA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "rst_ma_1",
   "description": "4-20 ma Reset Signal",
   "units": "mA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "tmtr_a1_1",
   "description": "A1 Motor Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "fltp_a1_1",
   "description": "A1 Oil Filter Diff.Press",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "op_a1_1",
   "description": "A1 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "dop_a1_1",
   "description": "A1 Oil Pressure Diff.",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "tmtr_a2_1",
   "description": "A2 Motor Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "fltp_a2_1",
   "description": "A2 Oil Filter Diff.Press",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "op_a2_1",
   "description": "A2 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "dop_a2_1",
   "description": "A2 Oil Pressure Diff.",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "dem_lim_1",
   "description": "Active Demand Limit",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "sp_1",
   "description": "Active Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "alrmcnfg_1",
   "description": "Alarm Relay Usage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "alm_1",
   "description": "Alarm State",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "aprch_sp_1",
   "description": "Approach Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "tmtr_b1_1",
   "description": "B1 Motor Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "fltp_b1_1",
   "description": "B1 Oil Filter Diff.Press",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "op_b1_1",
   "description": "B1 Oil Pressure",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "dop_b1_1",
   "description": "B1 Oil Pressure Diff.",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "tmtr_b2_1",
   "description": "B2 Motor Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "fltp_b2_1",
   "description": "B2 Oil Filter Diff.Press",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "op_b2_1",
   "description": "B2 Oil Pressure",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "dop_b2_1",
   "description": "B2 Oil Pressure Diff.",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "mop_spa_1",
   "description": "Calculated MOP Circuit A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "mop_spb_1",
   "description": "Calculated MOP Circuit B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "dl_stat_1",
   "description": "CCN Loadshed Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "hr_cira_1",
   "description": "Circuit A Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "cy_cira_1",
   "description": "Circuit A Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "hr_cirb_1",
   "description": "Circuit B Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "cy_cirb_1",
   "description": "Circuit B Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "a_curr_1",
   "description": "Circuit Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "b_curr_1",
   "description": "Circuit Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "a1_mta_1",
   "description": "Comp A1 % Must Trip Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "a1_curr_1",
   "description": "Comp A1 Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "a2_mta_1",
   "description": "Comp A2 % Must Trip Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "a2_curr_1",
   "description": "Comp A2 Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "b1_mta_1",
   "description": "Comp B1 % Must Trip Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "b1_curr_1",
   "description": "Comp B1 Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "b2_mta_1",
   "description": "Comp B2 % Must Trip Amps",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "b2_curr_1",
   "description": "Comp B2 Running Current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "hr_a1_1",
   "description": "Compressor A1 Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "cy_a1_1",
   "description": "Compressor A1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "hr_a2_1",
   "description": "Compressor A2 Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "cy_a2_1",
   "description": "Compressor A2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "hr_b1_1",
   "description": "Compressor B1 Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "cy_b1_1",
   "description": "Compressor B1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "hr_b2_1",
   "description": "Compressor B2 Run Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "cy_b2_1",
   "description": "Compressor B2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "comp_seq_1",
   "description": "Compressor Sequence",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "cond_ewt_1",
   "description": "Condenser Entering Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "cond_lwt_1",
   "description": "Condenser Leaving Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "cnpc_1",
   "description": "Condenser Pump Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "stat_1",
   "description": "Control Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "ctrl_pnt_1",
   "description": "Control Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "coolewts_1",
   "description": "Cool Entering Fluid-Slave",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "cool_ewt_1",
   "description": "Cooler Entering Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "cool_lwt_1",
   "description": "Cooler Leaving Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "cramp_1",
   "description": "Cooling Ramp Loading",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "csp1_1",
   "description": "Cooling Setpoint 1",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "csp2_1",
   "description": "Cooling Setpoint 2",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "coollwts_1",
   "description": "Cool Leaving Fluid-Slave",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "cur_trip_1",
   "description": "Current Unbalance SetPnt",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "z_gain_1",
   "description": "Deadband Multiplier",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "dmt20ma_1",
   "description": "Demand Limit at 20 mA",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "distmp_a_1",
   "description": "Discharge Gas Temp (circuit A)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "distmp_b_1",
   "description": "Discharge Gas Temp (circuit B)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "distmpa1_1",
   "description": "Discharge Gas Temp - A1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "distmpa2_1",
   "description": "Discharge Gas Temp - A2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "distmpb1_1",
   "description": "Discharge Gas Temp - B1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "distmpb2_1",
   "description": "Discharge Gas Temp - B2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "dp_a_1",
   "description": "Discharge Pressure (circuit A)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "dp_b_1",
   "description": "Discharge Pressure (circuit B)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "sh_a_1",
   "description": "Discharge Superheat Temp (circuit A)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "sh_b_1",
   "description": "Discharge Superheat Temp (circuit B)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "size_dpx_1",
   "description": "Dual Chiller Size",
   "units": "tons",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "sizeadpx_1",
   "description": "Dual Chiller Tons Avail",
   "units": "tons",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "dclgcapl_1",
   "description": "Dual Chill Lag CapLimit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "dcldcapl_1",
   "description": "Dual Chill Lead Cap Limit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "capa_dpx_1",
   "description": "Dual Chill Pct Avail Cap",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "capt_dpx_1",
   "description": "Dual Chill Pct Total Cap",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "ecnp_a_1",
   "description": "Economizer Pressure (circuit A)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "ecnp_b_1",
   "description": "Economizer Pressure (circuit B)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "ewt_1",
   "description": "Entering Fluid Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "exv_a_1",
   "description": "EXV % Open (circuit A)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "exv_b_1",
   "description": "EXV % Open (circuit B)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "head_typ_1",
   "description": "Head Press. Control Type",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "hsp_a_1",
   "description": "Head Pressure Setpoint A",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "hsp_b_1",
   "description": "Head Pressure Setpoint B",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "hramp_1",
   "description": "Heating Ramp Loading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "hsp1_1",
   "description": "Heating Setpoint 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "hsp2_1",
   "description": "Heating Setpoint 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "csp3_1",
   "description": "Ice Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "lag_cp_1",
   "description": "Lag Chiller Ctrl Point",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "ll_delay_1",
   "description": "Lag Start Delay",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "ll_bal_d_1",
   "description": "Lead/Lag Balance Delta",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "ll_bal_1",
   "description": "Lead/Lag Balance Select",
   "units": "hrs",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "dual_lwt_1",
   "description": "Lead/Lag Leaving Fluid",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "lead_type_1",
   "description": "Lead/Lag Sequence Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "lead_cp_1",
   "description": "Lead Chiller Ctrl Point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "lwt_1",
   "description": "Leaving Fluid Temp - Prime Variable",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "smz_1",
   "description": "Load/Unload Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "smzslave_1",
   "description": "Load/Unload Factor-Slave",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "seq_type_1",
   "description": "Loading Sequence Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "shed_del_1",
   "description": "Loadshed Demand Delta",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "shed_num_1",
   "description": "Loadshed Group Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "hr_mach_1",
   "description": "Machine Operating Hours",
   "units": "hr",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "cy_mach_1",
   "description": "Machine Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "shed_tim_1",
   "description": "Maximum Loadshed Time",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "delay_1",
   "description": "Minutes Off Time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "fp_sp_1",
   "description": "Oil Filter Delta P Setpt",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "oat_1",
   "description": "Outside Air Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "cap_a_1",
   "description": "Percent Avail.Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "capa_a_1",
   "description": "Percent Available Cap. (circuit A)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "capb_a_1",
   "description": "Percent Available Cap. (circuit A)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "cap_t_1",
   "description": "Percent Total Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "capa_t_1",
   "description": "Percent Total Capacity (circuit A)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "capb_t_1",
   "description": "Percent Total Capacity (circuit B)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "hrem_deg_1",
   "description": "Remote - Degrees Reset",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "hrem_ful_1",
   "description": "Remote - Full Reset Temp",
   "units": "dF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "hrem_no_1",
   "description": "Remote - No Reset Temp",
   "units": "dF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "hrtn_deg_1",
   "description": "Return - Degrees Reset",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "hrtn_ful_1",
   "description": "Return - Full Reset Temp",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "hrtn_no_1",
   "description": "Return - No Reset Temp",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "tmp_scta_1",
   "description": "Saturated Condensing Tmp (circuit A)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "tmp_sctb_1",
   "description": "Saturated Condensing Tmp (circuit B)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "tmp_ssta_1",
   "description": "Saturated Suction Temp (circuit A)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "tmp_sstb_1",
   "description": "Saturated Suction Temp (circuit B)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "slv_addr_1",
   "description": "Slave Address",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "spt_1",
   "description": "Space Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "sp_a_1",
   "description": "Suction Pressure (circuit A)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "sp_b_1",
   "description": "Suction Pressure (circuit B)",
   "units": "PSI",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "vhptype_1",
   "description": "Var Head Pressure Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "vhpa_1",
   "description": "Variable Head Press Pct. (circuit A)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "vhpb_1",
   "description": "Variable Head Press Pct. (circuit B)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2901,
   "name": "user_analog_1_1",
   "description": "User Defined Analog 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2902,
   "name": "user_analog_2_1",
   "description": "User Defined Analog 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2903,
   "name": "user_analog_3_1",
   "description": "User Defined Analog 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2904,
   "name": "user_analog_4_1",
   "description": "User Defined Analog 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2905,
   "name": "user_analog_5_1",
   "description": "User Defined Analog 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9006,
   "name": "cool_demand_level_1",
   "description": "System Cooling Demand Level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "schedule_1",
   "description": "Local Schedule",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "dem_lmt_act_1",
   "description": "System Demand Limiting",
   "units": "",
   "access": "R",
   "states": "Inactive/Active"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "chil_s_s_1",
   "description": "CCN Chiller",
   "units": "",
   "access": "W",
   "states": "Start/Stop"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "mode_27_1",
   "description": "Circuit A - Pumping out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "mode_28_1",
   "description": "Circuit B - Pumping out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "mode_25_1",
   "description": "Ckt A Off Ref Flow Delay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "mode_26_1",
   "description": "Ckt B Off Ref Flow Delay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "cls_ctrl_1",
   "description": "Close Control Select",
   "units": "",
   "access": "R",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "k_a1_fbk_1",
   "description": "Compressor A1 Feedback",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "k_a1_rly_1",
   "description": "Compressor A1 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "k_a2_fbk_1",
   "description": "Compressor A2 Feedback",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "k_a2_rly_1",
   "description": "Compressor A2 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "k_b1_fbk_1",
   "description": "Compressor B1 Feedback",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "k_b1_rly_1",
   "description": "Compressor B1 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "k_b2_fbk_1",
   "description": "Compressor B2 Feedback",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "k_b2_rly_1",
   "description": "Compressor B2 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "condflow_1",
   "description": "Condenser Flow Switch",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "cd_temp_1",
   "description": "Condenser Fluid Sensors",
   "units": "",
   "access": "R",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "cnd_lock_1",
   "description": "Condenser Pump Interlock",
   "units": "",
   "access": "R",
   "states": "Off/On"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "cond_pmp_1",
   "description": "Condenser Pump Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "coolflow_1",
   "description": "Cooler Flow Switch",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "mode_16_1",
   "description": "Cooler Freeze Protection",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "cool_htr_1",
   "description": "Cooler Heater",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "cpc_1",
   "description": "Cooler Pump Control",
   "units": "",
   "access": "R",
   "states": "Off/On"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "cool_pmp_1",
   "description": "Cooler Pump Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "mode_1_1",
   "description": "CSM Controlling Chiller",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "mode_15_1",
   "description": "Demand Limit In Effect",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "dmd_sw1_1",
   "description": "Demand Limit Switch 1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "dmd_sw2_1",
   "description": "Demand Limit Switch 2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "dc_link_1",
   "description": "Dual Chiller Link Good ?",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "mode_13_1",
   "description": "Dual Setpoint",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "dual_in_1",
   "description": "Dual Setpoint Switch",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "emstop_1",
   "description": "Emergency Stop",
   "units": "",
   "access": "R",
   "states": "Enable/Emstop"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "emm_brd_1",
   "description": "EMM Module installed",
   "units": "",
   "access": "R",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "noflowen_1",
   "description": "Enable No Flow Detection",
   "units": "",
   "access": "R",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "fan_1_1",
   "description": "Fan 1 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "fan_2_1",
   "description": "Fan 2 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "fan_3_1",
   "description": "Fan 3 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "fan_4_1",
   "description": "Fan 4 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "heatcool_1",
   "description": "Heat Cool Select",
   "units": "",
   "access": "R",
   "states": "Heat/Cool"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "mode_23_1",
   "description": "High Motor Current Cir.A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "mode_24_1",
   "description": "High Motor Current Cir.B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "mode_21_1",
   "description": "High SCT Circuit A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "mode_22_1",
   "description": "High SCT Circuit B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "mode_18_1",
   "description": "Hi Tmp Cool/Lo Tmp Heat",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "ice_1",
   "description": "Ice Done",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "ice_cnfg_1",
   "description": "Ice Mode Enable",
   "units": "",
   "access": "R",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "lag_off_1",
   "description": "Lag Commanded Off?",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "lag_smzc_1",
   "description": "Lag- SMZ Clear Commanded",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "ll_ena_1",
   "description": "Lead/Lag Chiller Enable",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "leadsmzc_1",
   "description": "Lead SMZ Clear Commanded",
   "units": "",
   "access": "R",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "llsv_1",
   "description": "Liq. Line Solenoid Valve",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "loadr_a1_1",
   "description": "Loader A1 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "loadr_a2_1",
   "description": "Loader A2 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "loadr_b1_1",
   "description": "Loader B1 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "loadr_b2_1",
   "description": "Loader B2 Relay",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "mode_17_1",
   "description": "Lo Tmp Cool/Hi Tmp Heat",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "mode_7_1",
   "description": "Low Cooler Suction Temp A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "mode_8_1",
   "description": "Low Cooler Suction Temp B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "mode_11_1",
   "description": "Low Dischrge Superheat A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "mode_12_1",
   "description": "Low Dischrge Superheat B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "mode_4_1",
   "description": "Low Source Protection",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "mode_19_1",
   "description": "Making ICE",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "mode_3_1",
   "description": "Master/Slave Control",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "ms_sel_1",
   "description": "Master/Slave Select",
   "units": "",
   "access": "R",
   "states": "Slave/Master"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "mlv_flg_1",
   "description": "Minimum Load Valve Select",
   "units": "",
   "access": "R",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "mlva_1",
   "description": "Minimum Load Valve (circuit A)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "mlvb_1",
   "description": "Minimum Load Valve (circuit B)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "mode_10_1",
   "description": "Minimum OFF Time Active",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "mtrcl_a1_1",
   "description": "Motor Coolng A1 Solenoid",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "mtrcl_a2_1",
   "description": "Motor Coolng A2 Solenoid",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "mtrcl_b1_1",
   "description": "Motor Coolng B1 Solenoid",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "mtrcl_b2_1",
   "description": "Motor Coolng B2 Solenoid",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "occ_1",
   "description": "Occupied",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "oila_htr_1",
   "description": "Oil Heater (circuit A)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "oilb_htr_1",
   "description": "Oil Heater (circuit B)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "oila_sw_1",
   "description": "Oil Level Switch (circuit A)",
   "units": "",
   "access": "R",
   "states": "Close/Open"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "oilb_sw_1",
   "description": "Oil Level Switch (circuit B)",
   "units": "",
   "access": "R",
   "states": "Close/Open"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "oilpmp_a_1",
   "description": "Oil Pump (circuit A)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "oilpmp_b_1",
   "description": "Oil Pump (circuit B)",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "oilsl_a1_1",
   "description": "Oil Solenoid A1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "oilsl_a2_1",
   "description": "Oil Solenoid A2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "oilsl_b1_1",
   "description": "Oil Solenoid B1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "oilsl_b2_1",
   "description": "Oil Solenoid B2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "mode_1",
   "description": "Override Modes in Effect",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "parallel_1",
   "description": "Parallel Configuration",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "press_ty_1",
   "description": "Pressure Transducers",
   "units": "",
   "access": "R",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "mode_5_1",
   "description": "Ramp Load Limited",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "ramp_ebl_1",
   "description": "Ramp Load Select",
   "units": "",
   "access": "W",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "mode_9_1",
   "description": "Slow Change Override",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "mode_20_1",
   "description": "Storing ICE",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "mode_14_1",
   "description": "Temperature Reset",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "mode_6_1",
   "description": "Timed Override In Effect",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "mode_29_1",
   "description": "Unit Off: No Water Flow",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "wintmsg_1",
   "description": "Winterize Alert Config",
   "units": "",
   "access": "R",
   "states": "Disable/Enable"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "mode_2_1",
   "description": "WSM Controlling Chiller",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "comm_lost_alm_1",
   "description": "Element Communications Alarm",
   "units": "",
   "access": "R",
   "states": "Comm Normal/Comm Lost"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "element_alarm_1",
   "description": "Equipment Alarm",
   "units": "",
   "access": "R",
   "states": "Normal/Alarm"
  },
  {
   "type": "BV",
   "instance": 2911,
   "name": "user_binary_1_1",
   "description": "User Defined Binary 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2912,
   "name": "user_binary_2_1",
   "description": "User Defined Binary 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2913,
   "name": "user_binary_3_1",
   "description": "User Defined Binary 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2914,
   "name": "user_binary_4_1",
   "description": "User Defined Binary 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2915,
   "name": "user_binary_5_1",
   "description": "User Defined Binary 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2999,
   "name": "element_stat_1",
   "description": "Element Comm Status",
   "units": "",
   "access": "R",
   "states": "No Comm/Normal"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "alm_msv_1",
   "description": "Alarm State",
   "units": "",
   "access": "R",
   "states": "1 = Normal, 2 = Alert, 3 = Alarm"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "stat_msv_1",
   "description": "Control Mode",
   "units": "",
   "access": "R",
   "states": "0 = Service Test, 1 = Off-Local, 2 = Off-CCN, 3 = Off-Clock, 4 = Off-Emergency, 5 = On-Local, 6 = On-CCN, 7 = On-Clock"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "fluidtyp_msv_1",
   "description": "Cooler Fluid",
   "units": "",
   "access": "R",
   "states": "1 = Water, 2 = Medium Brine, 3 = Low Brine"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/carrier/30hx-upc-open",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}