Air-cooled scroll chiller controller · BACnet points list
Carrier AquaSnap 30RC 010-060 BACnet points list
Updated 28 October 2026
The 30RC's Carrier Controller provides BACnet IP on Ethernet port J5 and BACnet MS/TP on RS-485 port J10, configured from the BACnet Standard Conf. menu. Command points come as separate read (_rd) and write (_wr) objects, with the writable copies at 10000+ instances. Alarm objects are numbered after Carrier's alarm codes (e.g. BV 110001).
This page lists 232 BACnet objects for the Carrier AquaSnap 30RC 010-060 — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaSnap 30RC 010-060
- Equipment
- Air-cooled scroll chiller controller
- Equipment type
- Chillers
- BACnet objects
- 232 (24 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP
BMS integration notes: Carrier AquaSnap 30RC 010-060
Set bacena to BACnet IP or MS/TP in Main Menu > Configuration > BACnet, set device ID and network, then select the Network control method on the chiller. Command through the _wr objects (start/stop, occupancy, control point, demand limit, emergency stop) and read status, water temperatures, capacity and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10012 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 10058 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| AV 10006 | GENUNIT_CTRL_PNT_wr | Leaving water control point from the BMS | Write |
| AV 10008 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| AV 21 | GENUNIT_CTRL_TYP | Control type: Local, Network or Remote | Read |
| AV 22 | GENUNIT_STATUS | Running status | Read |
| AV 2 | TEMP_LWT | Leaving water temperature | Read |
| AV 1 | TEMP_EWT | Entering water temperature | Read |
| AV 9 | GENUNIT_CAP_T | Percent total capacity | Read |
| AV 990 | ALARMRST_ALM | Unit alarm state | Read |
Enable & remote start
Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus commands and ignores the remote contacts. Start/stop and occupancy are written to the _wr objects.
Heartbeat & communication loss
The manual says that if communication with the network is lost while under network control, the chiller starts and runs under local control.
Network setup
- BACnet is disabled by default (bacena 0); set 1 for BACnet IP or 2 for BACnet MS/TP.
- Defaults shown: network number 1600, UDP port 47808, device ID 1600001 (manual or auto device ID option).
- MS/TP defaults: baud option 2 (38400), Max Master 10, Max Info Frames 5; MAC 1-127.
- J5 (ETH0) carries BACnet IP / Modbus TCP; J10 is RS-485 for BACnet MS/TP or secondary Modbus RTU.
Watch out for
- Write the _wr object, not the _rd one; the _rd copy only reports the current value.
- The BACnet menu has a 'BACnet Manage Occupancy' option (mng_occ) and the list has a writable BACnet_BMS_OCC (AV 66); check how they interact with CHIL_OCC before relying on either.
Carrier AquaSnap 30RC 010-060 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 985 | ALARMRST_alarm_1 | Current Alarm 1 Index | Read | ||
| AV | 980 | ALARMRST_alarm_1c | Current Alarm 1 | Read | ||
| AV | 986 | ALARMRST_alarm_2 | Current Alarm 2 Index | Read | ||
| AV | 981 | ALARMRST_alarm_2c | Current Alarm 2 | Read | ||
| AV | 987 | ALARMRST_alarm_3 | Current Alarm 3 Index | Read | ||
| AV | 982 | ALARMRST_alarm_3c | Current Alarm 3 | Read | ||
| AV | 988 | ALARMRST_alarm_4 | Current Alarm 4 Index | Read | ||
| AV | 983 | ALARMRST_alarm_4c | Current Alarm 4 | Read | ||
| AV | 989 | ALARMRST_alarm_5 | Current Alarm 5 Index | Read | ||
| AV | 984 | ALARMRST_alarm_5c | Current Alarm 5 | Read | ||
| AVmin | 990 | ALARMRST_ALM | Alarm State | Read | ||
| BV | 157001 | ALM_CIOB_A_LOW_VOLT_F | Read | |||
| BV | 157002 | ALM_CIOB_B_LOW_VOLT_F | Read | |||
| BV | 104901 | ALM_CIOB_CIR_A_COM_F | Read | |||
| BV | 104902 | ALM_CIOB_CIR_B_COM_F | Read | |||
| BV | 115006 | ALM_COND_EWT_F | Read | |||
| BV | 115007 | ALM_COND_LWT_F | Read | |||
| AV | 110073 | ALM_COND_PUMP_F | Condenser Pump Default | Read | ||
| BV | 110098 | ALM_COND_SENSORS_SWAP_F | Temperature Sensors | Read | ||
| BV | 110015 | ALM_CONDENSER_LOCK_F | Read | |||
| BV | 115001 | ALM_COOL_EWT_F | Read | |||
| BV | 115002 | ALM_COOL_LWT_F | Read | |||
| BV | 110032 | ALM_COOL_PUMP1_F | Cooler Pump 1 Default | Read | ||
| BV | 110033 | ALM_COOL_PUMP2_F | Cooler Pump 2 Default | Read | ||
| BV | 110001 | ALM_COOLER_FREEZE_F | Read | |||
| BV | 110014 | ALM_COOLER_LOCK_F | Cooler Interlock Failure | Read | ||
| BV | 110016 | ALM_CPA1_REVERSE_ROT_F | Pressure Increase not | Read | ||
| BV | 110017 | ALM_CPA2_REVERSE_ROT_F | Pressure Increase not | Read | ||
| BV | 110018 | ALM_CPA3_REVERSE_ROT_F | Pressure Increase not | Read | ||
| BV | 110020 | ALM_CPB1_REVERSE_ROT_F | Pressure Increase not | Read | ||
| BV | 110021 | ALM_CPB2_REVERSE_ROT_F | Pressure Increase not | Read | ||
| BV | 115015 | ALM_DGT_A_F | Read | |||
| BV | 115011 | ALM_DLWT_F | Read | |||
| BV | 112001 | ALM_DP_A_F | Read | |||
| BV | 112002 | ALM_DP_B_F | Read | |||
| BV | 157020 | ALM_EXV_A_F | Read | |||
| BV | 157021 | ALM_EXV_B_F | Read | |||
| BV | 104701 | ALM_FAN_DRIVE_COM_F | Read | |||
| BV | 117001 | ALM_FAN_VFD_DRIVE_F | Read | |||
| BV | 113005 | ALM_FGAS_NEEDED | Read | |||
| BV | 110099 | ALM_FLUIDE_FAIL | Read | |||
| BV | 110063 | ALM_HP_SWITCH_A_F | Read | |||
| BV | 110064 | ALM_HP_SWITCH_B_F | Read | |||
| BV | 107001 | ALM_ILL_FACT_CONF_F | Illegal configuration | Read | ||
| BV | 108000 | ALM_INI_FACT_CONF_F | Read | |||
| BV | 110030 | ALM_LOSS_COM_MS_F | Read | |||
| BV | 110029 | ALM_LOSS_COM_SM_F | Read | |||
| BV | 110011 | ALM_LOW_SH_A_F | Circuit A Low Superheat | Read | ||
| BV | 110012 | ALM_LOW_SH_B_F | Circuit B Low Superheat | Read | ||
| BV | 110005 | ALM_LOW_SUCTION_A_F | Read | |||
| BV | 110006 | ALM_LOW_SUCTION_B_F | Read | |||
| BV | 109001 | ALM_M_S_CONFIG_F | Read | |||
| BV | 110031 | ALM_NETWORK_EMSTOP_F | Read | |||
| BV | 115010 | ALM_OAT_F | OAT Thermistor Failure | Read | ||
| BV | 110037 | ALM_REPEATED_HI_DGT_A_F | Read | |||
| BV | 110038 | ALM_REPEATED_HI_DGT_B_F | Read | |||
| BV | 110040 | ALM_REPEATED_LO_SST_A_F | Read | |||
| BV | 110041 | ALM_REPEATED_LO_SST_B_F | Read | |||
| BV | 110210 | ALM_RUN_OUT_MAP_A_F | Read | |||
| BV | 110211 | ALM_RUN_OUT_MAP_B_F | Read | |||
| BV | 110097 | ALM_SENSORS_SWAP_F | Read | |||
| BV | 113001 | ALM_SERVICE_MAINT_ALERT | Service Maintenance Alert | Read | ||
| BV | 112004 | ALM_SP_A_F | Read | |||
| BV | 112005 | ALM_SP_B_F | Read | |||
| BV | 115021 | ALM_SPACETMP | Space Temperature Failure | Read | ||
| BV | 115012 | ALM_SUCTION_T_A_F | Read | |||
| BV | 115013 | ALM_SUCTION_T_B_F | Read | |||
| BV | 60 | BACnet_bacena | BACnet Enable Option | Read | ||
| BV | 61 | BACnet_bacunit | Metric Units? | Read | ||
| AV | 66 | BACnet_BMS_OCC | Write | |||
| MV | 64 | BACnet_COLOR | ALC color value | Read | ||
| AV | 63 | BACnet_ident | Device Id Actually Used | Read | ||
| AV | 62 | BACnet_network | Network | Read | ||
| AV | 65 | BACnet_PRIME_V | ALC prime value | Read | ||
| AV | 5443 | FACTORY_flui_typ | Cooler Fluid Type | Read | ||
| BV | 5770 | FACTORY_hgbp_sel | Hot Gas Bypass Selection | Read | ||
| AV | 5013 | FACTORY_unit_typ | UnitType (WaterCooled=3) | Read | ||
| AV | 5014 | FACTORY_unitsize | Unit Capacity Model | Read | ||
| AV | 5766 | FACTORY2_cap_a1 | Compressor A1 Capacity | Read | ||
| AV | 5767 | FACTORY2_cap_a2 | Compressor A2 Capacity | Read | ||
| AV | 5768 | FACTORY2_cap_a3 | Compressor A3 Capacity | Read | ||
| AV | 5769 | FACTORY2_cap_b1 | Compressor B1 Capacity | Read | ||
| BV | 5078 | GENCONF_ewt_opt | Entering Fluid Control | Read | ||
| AV | 5003 | GENCONF_lim_sel | Demand Limit Type Select | Read | ||
| AVmin | 9 | GENUNIT_CAP_T | Percent Total Capacity | Read | ||
| AV | 1017 | GENUNIT_CAPA_T | Circuit A Total Capacity | Read | ||
| AV | 2017 | GENUNIT_CAPB_T | Circuit B Total Capacity | Read | ||
| BV | 58 | GENUNIT_CHIL_OCC_rd | Net.: Cmd Occupied | Read | ||
| BVmin | 10058 | GENUNIT_CHIL_OCC_wr | Net.: Cmd Occupied | Write | ||
| BV | 12 | GENUNIT_CHIL_S_S_rd | Net.: Cmd Start/Stop | Read | ||
| BVmin | 10012 | GENUNIT_CHIL_S_S_wr | Net.: Cmd Start/Stop | Write | ||
| AV | 6 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AVmin | 10006 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 21 | GENUNIT_CTRL_TYP | Local=0 Net.=1 Remote=2 | Read | ||
| AV | 8 | GENUNIT_DEM_LIM_rd | Active Demand Limit Val | Read | ||
| AVmin | 10008 | GENUNIT_DEM_LIM_wr | Active Demand Limit Val | Write | ||
| BV | 13 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 10013 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| AV | 23 | GENUNIT_HC_SEL_rd | Heat/Cool Select | Read | ||
| AV | 10023 | GENUNIT_HC_SEL_wr | Heat/Cool Select | Write | ||
| AV | 77 | GENUNIT_HEATCOOL | Heat/Cool status | Read | ||
| AV | 11 | GENUNIT_min_left | Minutes Left for Start | Read | ||
| AV | 7 | GENUNIT_SP | Current Setpoint | Read | ||
| BV | 59 | GENUNIT_SP_OCC_rd | Setpoint Occupied? | Read | ||
| BV | 10059 | GENUNIT_SP_OCC_wr | Setpoint Occupied? | Write | ||
| AV | 24 | GENUNIT_SP_SEL_rd | Setpoint Select | Read | ||
| AV | 10024 | GENUNIT_SP_SEL_wr | Setpoint Select | Write | ||
| AVmin | 22 | GENUNIT_STATUS | Running Status | Read | ||
| AV | 5019 | HCCONFIG_cr_sel | Cooling Reset Select | Read | ||
| AV | 5020 | HCCONFIG_hr_sel | Heating Reset Select | Read | ||
| AV | 5772 | HEADCTRL_condsp | Computed Cond Setpoint | Read | ||
| AV | 5773 | HEADCTRL_fan | Fan Speed | Read | ||
| AV | 966 | HR_PARTIAL_DOWNTIME | Cumul Time Partial Alm | Read | ||
| AV | 967 | HR_TOTAL_DOWNTIME | Cumul Time Tripout Alm | Read | ||
| BV | 55 | INPUTS_CNFS | Condenser Water Flow SW | Read | ||
| AV | 5106 | INPUTS_CSP_IN | 4_20mA Cooling Setpoint | Read | ||
| AV | 5759 | INPUTS_CWP1 | Water Pump Interlock 1 | Read | ||
| AV | 5760 | INPUTS_CWP2 | Water Pump Interlock 2 | Read | ||
| AV | 5008 | INPUTS_DSHTR_SW | Desuperheater Switch | Read | ||
| BV | 52 | INPUTS_FLOW_SW | Flow Switch Interlock | Read | ||
| AV | 45 | INPUTS_HC_SW | Remote Heat/Cool Switch | Read | ||
| BV | 5009 | INPUTS_HP_SW_A | High Pressure Switch A | Read | ||
| BV | 5011 | INPUTS_HP_SW_B | High Pressure Switch B | Read | ||
| AV | 20 | INPUTS_ICE_SW | Ice Done Storage Switch | Read | ||
| AV | 5006 | INPUTS_leak_v1 | Leakage Detection 1 | Read | ||
| AV | 5007 | INPUTS_leak_v2 | Leakage Detection 2 | Read | ||
| AV | 5764 | INPUTS_LIM_4_20 | Capacity Limit Control | Read | ||
| BV | 18 | INPUTS_LIM_SW1 | Limit Switch 1 | Read | ||
| BV | 19 | INPUTS_LIM_SW2 | Limit Switch 2 | Read | ||
| BV | 16 | INPUTS_ONOFF_SW | Remote On/Off Switch | Read | ||
| AV | 5761 | INPUTS_REV_ROT | Phase Reversal | Read | ||
| BV | 48 | INPUTS_SETP_SW | Second Setpoint Switch | Read | ||
| AV | 5005 | INPUTS_SP_RESET | Setpoint Reset Signal | Read | ||
| AV | 1011 | LOADFACT_SH_A | Suction Superheat A | Read | ||
| AV | 2011 | LOADFACT_SH_B | Suction Superheat B | Read | ||
| BV | 5301 | MODES_m_ice | Ice Mode In Effect | Read | ||
| BV | 5061 | OPT_SEL_boil_en | Boiler Enable | Write | ||
| BV | 5012 | OUTPUTS_ALARM | Alarm Relay | Read | ||
| AV | 5711 | OUTPUTS_BOILER | Boiler Output | Read | ||
| BV | 1032 | OUTPUTS_CP_A1 | Compressor A1 | Read | ||
| BV | 1033 | OUTPUTS_CP_A2 | Compressor A2 | Read | ||
| BV | 1034 | OUTPUTS_CP_A3 | Compressor A3 | Read | ||
| BV | 2032 | OUTPUTS_CP_B1 | Compressor B1 | Read | ||
| BV | 2033 | OUTPUTS_CP_B2 | Compressor B2 | Read | ||
| AV | 5754 | OUTPUTS_DUS | Digital Unload Solenoid | Read | ||
| AV | 5765 | OUTPUTS_EISOR | Evaporator Isolator Rly | Read | ||
| BV | 57 | OUTPUTS_EXCH_HTR | Exchanger Heater | Read | ||
| AV | 5023 | OUTPUTS_EXV_A | EXV Position Circuit A | Read | ||
| AV | 5024 | OUTPUTS_EXV_B | EXV Position Circuit B | Read | ||
| AV | 5762 | OUTPUTS_FANC_1 | Fan Contactor 1 | Read | ||
| AV | 5763 | OUTPUTS_FANC_2 | Fan Contactor 2 | Read | ||
| AV | 5752 | OUTPUTS_HEAD_ACT | Head Pressure Actuator A | Read | ||
| AV | 5753 | OUTPUTS_HGBP_V | Hot Gas ByPass Valve | Read | ||
| AV | 5758 | OUTPUTS_LLSV_A | Solenoid Valve A | Read | ||
| AV | 5757 | OUTPUTS_LLSV_B | Solenoid Valve B | Read | ||
| AV | 5771 | OUTPUTS_Mod_CPA1 | Digital Modul. A1 | Read | ||
| BV | 15 | OUTPUTS_RUN | Running Relay | Read | ||
| AV | 1015 | OUTPUTS_VFAN | VariaFan Speed | Read | ||
| AV | 1000 | PRESSURE_DP_A | Discharge Pressure A | Read | ||
| AV | 2000 | PRESSURE_DP_B | Discharge Pressure B | Read | ||
| AV | 1001 | PRESSURE_SP_A | Suction Pressure A | Read | ||
| AV | 2001 | PRESSURE_SP_B | Suction Pressure B | Read | ||
| BV | 10053 | PROTOCOL_PUMP_C | Condenser Pump | Write | ||
| AV | 5001 | PUMPCONF_pump_del | Pump Auto Rotation Delay | Read | ||
| BV | 5004 | PUMPCONF_pump_loc | Flow Checked if Pump Off | Read | ||
| BV | 5002 | PUMPCONF_pump_per | Pump Sticking Protection | Read | ||
| BV | 5003 | PUMPCONF_pump_sby | Stop Pump During Standby | Read | ||
| AV | 73 | PUMPCONF_pump_seq | Cooler Pumps Sequence | Read | ||
| BV | 5756 | PUMPSTAT_CPUMP | Condenser Pump Relay | Read | ||
| BV | 50 | PUMPSTAT_PUMP_1_rd | Water Pump #1 | Read | ||
| BV | 10050 | PUMPSTAT_PUMP_1_wr | Evaporator pump 1 | Write | ||
| BV | 51 | PUMPSTAT_PUMP_2_rd | Water Pump #2 | Read | ||
| BV | 10051 | PUMPSTAT_PUMP_2_wr | Evaporator pump 2 | Write | ||
| AV | 5035 | RESETCFG_cr_deg | Cooling Reset Deg. Value | Read | ||
| AV | 5030 | RESETCFG_dt_cr_fu | Delta T Full Reset Value | Read | ||
| AV | 5029 | RESETCFG_dt_cr_no | Delta T No Reset Value | Read | ||
| AV | 5039 | RESETCFG_dt_hr_fu | Delta T Full Reset Value | Read | ||
| AV | 5038 | RESETCFG_dt_hr_no | Delta T No Reset Value | Read | ||
| AV | 5044 | RESETCFG_hr_deg | Heating Reset Deg. Value | Read | ||
| AV | 5032 | RESETCFG_I_cr_fu | Current Full Reset Value | Read | ||
| AV | 5031 | RESETCFG_I_cr_no | Current No Reset Value | Read | ||
| AV | 5041 | RESETCFG_I_hr_fu | Current Full Reset Value | Read | ||
| AV | 5040 | RESETCFG_I_hr_no | Current No Reset Value | Read | ||
| AV | 5028 | RESETCFG_oat_crfu | OAT Full Reset Value | Read | ||
| AV | 5027 | RESETCFG_oat_crno | OAT No Reset Value | Read | ||
| AV | 5037 | RESETCFG_oat_hrfu | OAT Full Reset Value | Read | ||
| AV | 5036 | RESETCFG_oat_hrno | OAT No Reset Value | Read | ||
| AV | 5034 | RESETCFG_spacr_fu | Space T Full Reset Value | Read | ||
| AV | 5033 | RESETCFG_spacr_no | Space T No Reset Value | Read | ||
| AV | 5043 | RESETCFG_spahr_fu | Space T Full Reset Value | Read | ||
| AV | 5042 | RESETCFG_spahr_no | Space T No Reset Value | Read | ||
| AV | 1960 | RUNTIME_hr_cp_a1 | Compressor A1 Hours | Read | ||
| AV | 1961 | RUNTIME_hr_cp_a2 | Compressor A2 Hours | Read | ||
| AV | 1962 | RUNTIME_hr_cp_a3 | Compressor A3 Hours | Read | ||
| AV | 2960 | RUNTIME_hr_cp_b1 | Compressor B1 Hours | Read | ||
| AV | 2961 | RUNTIME_hr_cp_b2 | Compressor B2 Hours | Read | ||
| AV | 960 | RUNTIME_hr_mach | Machine Operating Hours | Read | ||
| AV | 962 | RUNTIME_hr_pump1 | Water Pump #1 Hours | Read | ||
| AV | 963 | RUNTIME_hr_pump2 | Water Pump #2 Hours | Read | ||
| AV | 1964 | RUNTIME_st_cp_a1 | Compressor A1 Starts | Read | ||
| AV | 1965 | RUNTIME_st_cp_a2 | Compressor A2 Starts | Read | ||
| AV | 1966 | RUNTIME_st_cp_a3 | Compressor A3 Starts | Read | ||
| AV | 2964 | RUNTIME_st_cp_b1 | Compressor B1 Starts | Read | ||
| AV | 2965 | RUNTIME_st_cp_b2 | Compressor B2 Starts | Read | ||
| AV | 961 | RUNTIME_st_mach | Machine Starts Number | Read | ||
| AV | 5447 | SERVICE1_freezesp | Brine Freeze Setpoint | Read | ||
| AV | 5016 | SETPOINT_cauto_sp | Cool Changeover Setpt | Write | ||
| AV | 900 | SETPOINT_csp1 | Cooling Setpoint 1 | Write | ||
| AV | 901 | SETPOINT_csp2 | Cooling Setpoint 2 | Write | ||
| AV | 5017 | SETPOINT_hauto_sp | Heat Changeover Setpt | Write | ||
| AV | 903 | SETPOINT_hsp1 | Heating Setpoint 1 | Write | ||
| AV | 904 | SETPOINT_hsp2 | Heating Setpoint 2 | Write | ||
| AV | 905 | SETPOINT_lim_sp1 | Switch Limit Setpoint 1 | Write | ||
| AV | 906 | SETPOINT_lim_sp2 | Switch Limit Setpoint 2 | Write | ||
| AV | 907 | SETPOINT_lim_sp3 | Switch Limit Setpoint 3 | Write | ||
| AV | 5064 | SETPOINT_min_sct | Desuperheater Min Sct | Write | ||
| AV | 5015 | SETPOINT_ramp_sp | Ramp Loading | Write | ||
| AV | 25 | TEMP_CEWT | Cond Entering Water Temp | Read | ||
| AV | 26 | TEMP_CLWT | Cond Leaving Water Temp | Read | ||
| AV | 1009 | TEMP_DGT_A | Discharge Gas Temp A | Read | ||
| AV | 2009 | TEMP_DGT_B | Discharge Gas Temp B | Read | ||
| AV | 5 | TEMP_DLWT | Dual Leaving Water Temp | Read | ||
| AVmin | 1 | TEMP_EWT | Entering Water Temp | Read | ||
| AVmin | 2 | TEMP_LWT | Leaving Water Temp | Read | ||
| AV | 3 | TEMP_OAT | Outdoor Air Temperature | Read | ||
| AV | 1005 | TEMP_SCT_A | Saturated Cond Tmp cir A | Read | ||
| AV | 2005 | TEMP_SCT_B | Saturated Cond Tmp cir B | Read | ||
| AV | 5082 | TEMP_SPACETMP | Space Temperature | Read | ||
| AV | 1006 | TEMP_SST_A | Saturated Suction Temp A | Read | ||
| AV | 2006 | TEMP_SST_B | Saturated Suction Temp B | Read | ||
| AV | 1007 | TEMP_SUCT_A | Suction Temp Circuit A | Read | ||
| AV | 2007 | TEMP_SUCT_B | Suction Temp Circuit B | Read |
No points match these filters.
Integration notes
- Command points have a read object (e.g. BV 12 GENUNIT_CHIL_S_S_rd) and a separate write object (BV 10012 GENUNIT_CHIL_S_S_wr).
- Many ALM_ objects have a blank description in the table; the name identifies the alarm.
- The table also lists a database alias name and low/high limits, not reproduced here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RC 010-060 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaSnap 30RC 010-060
How many BACnet points does the Carrier AquaSnap 30RC 010-060 have?
This list has 232 BACnet objects: 137 analog values, 94 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaSnap 30RC 010-060 BACnet points are writable?
24 of the 232 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaSnap 30RC 010-060 BACnet documentation?
The source is AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points) (30RC-101T), revision 2025-10, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/04/30RC-101T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaSnap 30RC 010-060?
Start with BV 10012 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 10058 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 10006 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 10008 GENUNIT_DEM_LIM_wr (Demand limit command); AV 21 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 22 GENUNIT_STATUS (Running status); AV 2 TEMP_LWT (Leaving water temperature); AV 1 TEMP_EWT (Entering water temperature); AV 9 GENUNIT_CAP_T (Percent total capacity); AV 990 ALARMRST_ALM (Unit alarm state).
How do I enable BMS control of the Carrier AquaSnap 30RC 010-060?
Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus commands and ignores the remote contacts. Start/stop and occupancy are written to the _wr objects.
Does the Carrier AquaSnap 30RC 010-060 need a BACnet heartbeat or have a communication timeout?
The manual says that if communication with the network is lost while under network control, the chiller starts and runs under local control.
How do I check these points on the real AquaSnap 30RC 010-060?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points) · 30RC-101T · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.