Air-cooled scroll chiller controller · BACnet points list

Carrier AquaSnap 30RC 010-060 BACnet points list

Updated 28 October 2026

Short answer

The 30RC's Carrier Controller provides BACnet IP on Ethernet port J5 and BACnet MS/TP on RS-485 port J10, configured from the BACnet Standard Conf. menu. Command points come as separate read (_rd) and write (_wr) objects, with the writable copies at 10000+ instances. Alarm objects are numbered after Carrier's alarm codes (e.g. BV 110001).

This page lists 232 BACnet objects for the Carrier AquaSnap 30RC 010-060 — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
AquaSnap 30RC 010-060
Equipment
Air-cooled scroll chiller controller
Equipment type
Chillers
BACnet objects
232 (24 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1600001
Also known as
30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP
Source document
AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points) · 30RC-101T · rev. 2025-10
Download CSV 232 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Carrier AquaSnap 30RC 010-060

Integration in brief

Set bacena to BACnet IP or MS/TP in Main Menu > Configuration > BACnet, set device ID and network, then select the Network control method on the chiller. Command through the _wr objects (start/stop, occupancy, control point, demand limit, emergency stop) and read status, water temperatures, capacity and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10012GENUNIT_CHIL_S_S_wrNetwork start/stop commandWrite
BV 10058GENUNIT_CHIL_OCC_wrNetwork occupied commandWrite
AV 10006GENUNIT_CTRL_PNT_wrLeaving water control point from the BMSWrite
AV 10008GENUNIT_DEM_LIM_wrDemand limit commandWrite
AV 21GENUNIT_CTRL_TYPControl type: Local, Network or RemoteRead
AV 22GENUNIT_STATUSRunning statusRead
AV 2TEMP_LWTLeaving water temperatureRead
AV 1TEMP_EWTEntering water temperatureRead
AV 9GENUNIT_CAP_TPercent total capacityRead
AV 990ALARMRST_ALMUnit alarm stateRead

Enable & remote start

Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus commands and ignores the remote contacts. Start/stop and occupancy are written to the _wr objects.

Heartbeat & communication loss

The manual says that if communication with the network is lost while under network control, the chiller starts and runs under local control.

Network setup

Watch out for

Carrier AquaSnap 30RC 010-060 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

232 of 232 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier AquaSnap 30RC 010-060 BACnet Points List
DescriptionStates
AV985ALARMRST_alarm_1Current Alarm 1 IndexRead
AV980ALARMRST_alarm_1cCurrent Alarm 1Read
AV986ALARMRST_alarm_2Current Alarm 2 IndexRead
AV981ALARMRST_alarm_2cCurrent Alarm 2Read
AV987ALARMRST_alarm_3Current Alarm 3 IndexRead
AV982ALARMRST_alarm_3cCurrent Alarm 3Read
AV988ALARMRST_alarm_4Current Alarm 4 IndexRead
AV983ALARMRST_alarm_4cCurrent Alarm 4Read
AV989ALARMRST_alarm_5Current Alarm 5 IndexRead
AV984ALARMRST_alarm_5cCurrent Alarm 5Read
AVmin990ALARMRST_ALMAlarm StateRead
BV157001ALM_CIOB_A_LOW_VOLT_FRead
BV157002ALM_CIOB_B_LOW_VOLT_FRead
BV104901ALM_CIOB_CIR_A_COM_FRead
BV104902ALM_CIOB_CIR_B_COM_FRead
BV115006ALM_COND_EWT_FRead
BV115007ALM_COND_LWT_FRead
AV110073ALM_COND_PUMP_FCondenser Pump DefaultRead
BV110098ALM_COND_SENSORS_SWAP_FTemperature SensorsRead
BV110015ALM_CONDENSER_LOCK_FRead
BV115001ALM_COOL_EWT_FRead
BV115002ALM_COOL_LWT_FRead
BV110032ALM_COOL_PUMP1_FCooler Pump 1 DefaultRead
BV110033ALM_COOL_PUMP2_FCooler Pump 2 DefaultRead
BV110001ALM_COOLER_FREEZE_FRead
BV110014ALM_COOLER_LOCK_FCooler Interlock FailureRead
BV110016ALM_CPA1_REVERSE_ROT_FPressure Increase notRead
BV110017ALM_CPA2_REVERSE_ROT_FPressure Increase notRead
BV110018ALM_CPA3_REVERSE_ROT_FPressure Increase notRead
BV110020ALM_CPB1_REVERSE_ROT_FPressure Increase notRead
BV110021ALM_CPB2_REVERSE_ROT_FPressure Increase notRead
BV115015ALM_DGT_A_FRead
BV115011ALM_DLWT_FRead
BV112001ALM_DP_A_FRead
BV112002ALM_DP_B_FRead
BV157020ALM_EXV_A_FRead
BV157021ALM_EXV_B_FRead
BV104701ALM_FAN_DRIVE_COM_FRead
BV117001ALM_FAN_VFD_DRIVE_FRead
BV113005ALM_FGAS_NEEDEDRead
BV110099ALM_FLUIDE_FAILRead
BV110063ALM_HP_SWITCH_A_FRead
BV110064ALM_HP_SWITCH_B_FRead
BV107001ALM_ILL_FACT_CONF_FIllegal configurationRead
BV108000ALM_INI_FACT_CONF_FRead
BV110030ALM_LOSS_COM_MS_FRead
BV110029ALM_LOSS_COM_SM_FRead
BV110011ALM_LOW_SH_A_FCircuit A Low SuperheatRead
BV110012ALM_LOW_SH_B_FCircuit B Low SuperheatRead
BV110005ALM_LOW_SUCTION_A_FRead
BV110006ALM_LOW_SUCTION_B_FRead
BV109001ALM_M_S_CONFIG_FRead
BV110031ALM_NETWORK_EMSTOP_FRead
BV115010ALM_OAT_FOAT Thermistor FailureRead
BV110037ALM_REPEATED_HI_DGT_A_FRead
BV110038ALM_REPEATED_HI_DGT_B_FRead
BV110040ALM_REPEATED_LO_SST_A_FRead
BV110041ALM_REPEATED_LO_SST_B_FRead
BV110210ALM_RUN_OUT_MAP_A_FRead
BV110211ALM_RUN_OUT_MAP_B_FRead
BV110097ALM_SENSORS_SWAP_FRead
BV113001ALM_SERVICE_MAINT_ALERTService Maintenance AlertRead
BV112004ALM_SP_A_FRead
BV112005ALM_SP_B_FRead
BV115021ALM_SPACETMPSpace Temperature FailureRead
BV115012ALM_SUCTION_T_A_FRead
BV115013ALM_SUCTION_T_B_FRead
BV60BACnet_bacenaBACnet Enable OptionRead
BV61BACnet_bacunitMetric Units?Read
AV66BACnet_BMS_OCCWrite
MV64BACnet_COLORALC color valueRead
AV63BACnet_identDevice Id Actually UsedRead
AV62BACnet_networkNetworkRead
AV65BACnet_PRIME_VALC prime valueRead
AV5443FACTORY_flui_typCooler Fluid TypeRead
BV5770FACTORY_hgbp_selHot Gas Bypass SelectionRead
AV5013FACTORY_unit_typUnitType (WaterCooled=3)Read
AV5014FACTORY_unitsizeUnit Capacity ModelRead
AV5766FACTORY2_cap_a1Compressor A1 CapacityRead
AV5767FACTORY2_cap_a2Compressor A2 CapacityRead
AV5768FACTORY2_cap_a3Compressor A3 CapacityRead
AV5769FACTORY2_cap_b1Compressor B1 CapacityRead
BV5078GENCONF_ewt_optEntering Fluid ControlRead
AV5003GENCONF_lim_selDemand Limit Type SelectRead
AVmin9GENUNIT_CAP_TPercent Total CapacityRead
AV1017GENUNIT_CAPA_TCircuit A Total CapacityRead
AV2017GENUNIT_CAPB_TCircuit B Total CapacityRead
BV58GENUNIT_CHIL_OCC_rdNet.: Cmd OccupiedRead
BVmin10058GENUNIT_CHIL_OCC_wrNet.: Cmd OccupiedWrite
BV12GENUNIT_CHIL_S_S_rdNet.: Cmd Start/StopRead
BVmin10012GENUNIT_CHIL_S_S_wrNet.: Cmd Start/StopWrite
AV6GENUNIT_CTRL_PNT_rdControl PointRead
AVmin10006GENUNIT_CTRL_PNT_wrControl PointWrite
AVmin21GENUNIT_CTRL_TYPLocal=0 Net.=1 Remote=2Read
AV8GENUNIT_DEM_LIM_rdActive Demand Limit ValRead
AVmin10008GENUNIT_DEM_LIM_wrActive Demand Limit ValWrite
BV13GENUNIT_EMSTOP_rdEmergency StopRead
BV10013GENUNIT_EMSTOP_wrEmergency StopWrite
AV23GENUNIT_HC_SEL_rdHeat/Cool SelectRead
AV10023GENUNIT_HC_SEL_wrHeat/Cool SelectWrite
AV77GENUNIT_HEATCOOLHeat/Cool statusRead
AV11GENUNIT_min_leftMinutes Left for StartRead
AV7GENUNIT_SPCurrent SetpointRead
BV59GENUNIT_SP_OCC_rdSetpoint Occupied?Read
BV10059GENUNIT_SP_OCC_wrSetpoint Occupied?Write
AV24GENUNIT_SP_SEL_rdSetpoint SelectRead
AV10024GENUNIT_SP_SEL_wrSetpoint SelectWrite
AVmin22GENUNIT_STATUSRunning StatusRead
AV5019HCCONFIG_cr_selCooling Reset SelectRead
AV5020HCCONFIG_hr_selHeating Reset SelectRead
AV5772HEADCTRL_condspComputed Cond SetpointRead
AV5773HEADCTRL_fanFan SpeedRead
AV966HR_PARTIAL_DOWNTIMECumul Time Partial AlmRead
AV967HR_TOTAL_DOWNTIMECumul Time Tripout AlmRead
BV55INPUTS_CNFSCondenser Water Flow SWRead
AV5106INPUTS_CSP_IN4_20mA Cooling SetpointRead
AV5759INPUTS_CWP1Water Pump Interlock 1Read
AV5760INPUTS_CWP2Water Pump Interlock 2Read
AV5008INPUTS_DSHTR_SWDesuperheater SwitchRead
BV52INPUTS_FLOW_SWFlow Switch InterlockRead
AV45INPUTS_HC_SWRemote Heat/Cool SwitchRead
BV5009INPUTS_HP_SW_AHigh Pressure Switch ARead
BV5011INPUTS_HP_SW_BHigh Pressure Switch BRead
AV20INPUTS_ICE_SWIce Done Storage SwitchRead
AV5006INPUTS_leak_v1Leakage Detection 1Read
AV5007INPUTS_leak_v2Leakage Detection 2Read
AV5764INPUTS_LIM_4_20Capacity Limit ControlRead
BV18INPUTS_LIM_SW1Limit Switch 1Read
BV19INPUTS_LIM_SW2Limit Switch 2Read
BV16INPUTS_ONOFF_SWRemote On/Off SwitchRead
AV5761INPUTS_REV_ROTPhase ReversalRead
BV48INPUTS_SETP_SWSecond Setpoint SwitchRead
AV5005INPUTS_SP_RESETSetpoint Reset SignalRead
AV1011LOADFACT_SH_ASuction Superheat ARead
AV2011LOADFACT_SH_BSuction Superheat BRead
BV5301MODES_m_iceIce Mode In EffectRead
BV5061OPT_SEL_boil_enBoiler EnableWrite
BV5012OUTPUTS_ALARMAlarm RelayRead
AV5711OUTPUTS_BOILERBoiler OutputRead
BV1032OUTPUTS_CP_A1Compressor A1Read
BV1033OUTPUTS_CP_A2Compressor A2Read
BV1034OUTPUTS_CP_A3Compressor A3Read
BV2032OUTPUTS_CP_B1Compressor B1Read
BV2033OUTPUTS_CP_B2Compressor B2Read
AV5754OUTPUTS_DUSDigital Unload SolenoidRead
AV5765OUTPUTS_EISOREvaporator Isolator RlyRead
BV57OUTPUTS_EXCH_HTRExchanger HeaterRead
AV5023OUTPUTS_EXV_AEXV Position Circuit ARead
AV5024OUTPUTS_EXV_BEXV Position Circuit BRead
AV5762OUTPUTS_FANC_1Fan Contactor 1Read
AV5763OUTPUTS_FANC_2Fan Contactor 2Read
AV5752OUTPUTS_HEAD_ACTHead Pressure Actuator ARead
AV5753OUTPUTS_HGBP_VHot Gas ByPass ValveRead
AV5758OUTPUTS_LLSV_ASolenoid Valve ARead
AV5757OUTPUTS_LLSV_BSolenoid Valve BRead
AV5771OUTPUTS_Mod_CPA1Digital Modul. A1Read
BV15OUTPUTS_RUNRunning RelayRead
AV1015OUTPUTS_VFANVariaFan SpeedRead
AV1000PRESSURE_DP_ADischarge Pressure ARead
AV2000PRESSURE_DP_BDischarge Pressure BRead
AV1001PRESSURE_SP_ASuction Pressure ARead
AV2001PRESSURE_SP_BSuction Pressure BRead
BV10053PROTOCOL_PUMP_CCondenser PumpWrite
AV5001PUMPCONF_pump_delPump Auto Rotation DelayRead
BV5004PUMPCONF_pump_locFlow Checked if Pump OffRead
BV5002PUMPCONF_pump_perPump Sticking ProtectionRead
BV5003PUMPCONF_pump_sbyStop Pump During StandbyRead
AV73PUMPCONF_pump_seqCooler Pumps SequenceRead
BV5756PUMPSTAT_CPUMPCondenser Pump RelayRead
BV50PUMPSTAT_PUMP_1_rdWater Pump #1Read
BV10050PUMPSTAT_PUMP_1_wrEvaporator pump 1Write
BV51PUMPSTAT_PUMP_2_rdWater Pump #2Read
BV10051PUMPSTAT_PUMP_2_wrEvaporator pump 2Write
AV5035RESETCFG_cr_degCooling Reset Deg. ValueRead
AV5030RESETCFG_dt_cr_fuDelta T Full Reset ValueRead
AV5029RESETCFG_dt_cr_noDelta T No Reset ValueRead
AV5039RESETCFG_dt_hr_fuDelta T Full Reset ValueRead
AV5038RESETCFG_dt_hr_noDelta T No Reset ValueRead
AV5044RESETCFG_hr_degHeating Reset Deg. ValueRead
AV5032RESETCFG_I_cr_fuCurrent Full Reset ValueRead
AV5031RESETCFG_I_cr_noCurrent No Reset ValueRead
AV5041RESETCFG_I_hr_fuCurrent Full Reset ValueRead
AV5040RESETCFG_I_hr_noCurrent No Reset ValueRead
AV5028RESETCFG_oat_crfuOAT Full Reset ValueRead
AV5027RESETCFG_oat_crnoOAT No Reset ValueRead
AV5037RESETCFG_oat_hrfuOAT Full Reset ValueRead
AV5036RESETCFG_oat_hrnoOAT No Reset ValueRead
AV5034RESETCFG_spacr_fuSpace T Full Reset ValueRead
AV5033RESETCFG_spacr_noSpace T No Reset ValueRead
AV5043RESETCFG_spahr_fuSpace T Full Reset ValueRead
AV5042RESETCFG_spahr_noSpace T No Reset ValueRead
AV1960RUNTIME_hr_cp_a1Compressor A1 HoursRead
AV1961RUNTIME_hr_cp_a2Compressor A2 HoursRead
AV1962RUNTIME_hr_cp_a3Compressor A3 HoursRead
AV2960RUNTIME_hr_cp_b1Compressor B1 HoursRead
AV2961RUNTIME_hr_cp_b2Compressor B2 HoursRead
AV960RUNTIME_hr_machMachine Operating HoursRead
AV962RUNTIME_hr_pump1Water Pump #1 HoursRead
AV963RUNTIME_hr_pump2Water Pump #2 HoursRead
AV1964RUNTIME_st_cp_a1Compressor A1 StartsRead
AV1965RUNTIME_st_cp_a2Compressor A2 StartsRead
AV1966RUNTIME_st_cp_a3Compressor A3 StartsRead
AV2964RUNTIME_st_cp_b1Compressor B1 StartsRead
AV2965RUNTIME_st_cp_b2Compressor B2 StartsRead
AV961RUNTIME_st_machMachine Starts NumberRead
AV5447SERVICE1_freezespBrine Freeze SetpointRead
AV5016SETPOINT_cauto_spCool Changeover SetptWrite
AV900SETPOINT_csp1Cooling Setpoint 1Write
AV901SETPOINT_csp2Cooling Setpoint 2Write
AV5017SETPOINT_hauto_spHeat Changeover SetptWrite
AV903SETPOINT_hsp1Heating Setpoint 1Write
AV904SETPOINT_hsp2Heating Setpoint 2Write
AV905SETPOINT_lim_sp1Switch Limit Setpoint 1Write
AV906SETPOINT_lim_sp2Switch Limit Setpoint 2Write
AV907SETPOINT_lim_sp3Switch Limit Setpoint 3Write
AV5064SETPOINT_min_sctDesuperheater Min SctWrite
AV5015SETPOINT_ramp_spRamp LoadingWrite
AV25TEMP_CEWTCond Entering Water TempRead
AV26TEMP_CLWTCond Leaving Water TempRead
AV1009TEMP_DGT_ADischarge Gas Temp ARead
AV2009TEMP_DGT_BDischarge Gas Temp BRead
AV5TEMP_DLWTDual Leaving Water TempRead
AVmin1TEMP_EWTEntering Water TempRead
AVmin2TEMP_LWTLeaving Water TempRead
AV3TEMP_OATOutdoor Air TemperatureRead
AV1005TEMP_SCT_ASaturated Cond Tmp cir ARead
AV2005TEMP_SCT_BSaturated Cond Tmp cir BRead
AV5082TEMP_SPACETMPSpace TemperatureRead
AV1006TEMP_SST_ASaturated Suction Temp ARead
AV2006TEMP_SST_BSaturated Suction Temp BRead
AV1007TEMP_SUCT_ASuction Temp Circuit ARead
AV2007TEMP_SUCT_BSuction Temp Circuit BRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30RC 010-060 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier AquaSnap 30RC 010-060

How many BACnet points does the Carrier AquaSnap 30RC 010-060 have?

This list has 232 BACnet objects: 137 analog values, 94 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier AquaSnap 30RC 010-060 BACnet points are writable?

24 of the 232 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier AquaSnap 30RC 010-060 BACnet documentation?

The source is AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points) (30RC-101T), revision 2025-10, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/04/30RC-101T.pdf.

What are the minimum BACnet points to integrate the Carrier AquaSnap 30RC 010-060?

Start with BV 10012 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 10058 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 10006 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 10008 GENUNIT_DEM_LIM_wr (Demand limit command); AV 21 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 22 GENUNIT_STATUS (Running status); AV 2 TEMP_LWT (Leaving water temperature); AV 1 TEMP_EWT (Entering water temperature); AV 9 GENUNIT_CAP_T (Percent total capacity); AV 990 ALARMRST_ALM (Unit alarm state).

How do I enable BMS control of the Carrier AquaSnap 30RC 010-060?

Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus commands and ignores the remote contacts. Start/stop and occupancy are written to the _wr objects.

Does the Carrier AquaSnap 30RC 010-060 need a BACnet heartbeat or have a communication timeout?

The manual says that if communication with the network is lost while under network control, the chiller starts and runs under local control.

How do I check these points on the real AquaSnap 30RC 010-060?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points) · 30RC-101T · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.