 "manufacturer": "Carrier",
 "manufacturer_slug": "carrier",
 "firmware": null,
 "access_inferred": false,
 "model": "AquaSnap 30RC 010-060",
 "model_slug": "aquasnap-30rc-010-060",
 "aliases": [
  "30RC",
  "AquaSnap 30RC",
  "30RC-101T",
  "Carrier Controller",
  "30RC BACnet IP"
 ],
 "equipment_type": "Air-cooled scroll chiller controller",
 "applies_to": "Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.",
 "summary": "The 30RC's Carrier Controller provides BACnet IP on Ethernet port J5 and BACnet MS/TP on RS-485 port J10, configured from the BACnet Standard Conf. menu. Command points come as separate read (_rd) and write (_wr) objects, with the writable copies at 10000+ instances. Alarm objects are numbered after Carrier's alarm codes (e.g. BV 110001).",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "default_device_instance": 1600001,
 "notes": [
  "Command points have a read object (e.g. BV 12 GENUNIT_CHIL_S_S_rd) and a separate write object (BV 10012 GENUNIT_CHIL_S_S_wr).",
  "Many ALM_ objects have a blank description in the table; the name identifies the alarm.",
  "The table also lists a database alias name and low/high limits, not reproduced here."
 ],
 "source": {
  "title": "AquaSnap 30RC 010-060 Air-Cooled Chillers - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix D, BACnet IP Points)",
  "doc_number": "30RC-101T",
  "revision_date": "2025-10",
  "url": "https://www.shareddocs.com/hvac/docs/1005/Public/04/30RC-101T.pdf"
 },
 "points": [
  {
   "type": "AV",
   "instance": 985,
   "name": "ALARMRST_alarm_1",
   "description": "Current Alarm 1 Index",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 980,
   "name": "ALARMRST_alarm_1c",
   "description": "Current Alarm 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 986,
   "name": "ALARMRST_alarm_2",
   "description": "Current Alarm 2 Index",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 981,
   "name": "ALARMRST_alarm_2c",
   "description": "Current Alarm 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 987,
   "name": "ALARMRST_alarm_3",
   "description": "Current Alarm 3 Index",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 982,
   "name": "ALARMRST_alarm_3c",
   "description": "Current Alarm 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 988,
   "name": "ALARMRST_alarm_4",
   "description": "Current Alarm 4 Index",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 983,
   "name": "ALARMRST_alarm_4c",
   "description": "Current Alarm 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 989,
   "name": "ALARMRST_alarm_5",
   "description": "Current Alarm 5 Index",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 984,
   "name": "ALARMRST_alarm_5c",
   "description": "Current Alarm 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 990,
   "name": "ALARMRST_ALM",
   "description": "Alarm State",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 157001,
   "name": "ALM_CIOB_A_LOW_VOLT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 157002,
   "name": "ALM_CIOB_B_LOW_VOLT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 104901,
   "name": "ALM_CIOB_CIR_A_COM_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 104902,
   "name": "ALM_CIOB_CIR_B_COM_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115006,
   "name": "ALM_COND_EWT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115007,
   "name": "ALM_COND_LWT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110073,
   "name": "ALM_COND_PUMP_F",
   "description": "Condenser Pump Default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110098,
   "name": "ALM_COND_SENSORS_SWAP_F",
   "description": "Temperature Sensors",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110015,
   "name": "ALM_CONDENSER_LOCK_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115001,
   "name": "ALM_COOL_EWT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115002,
   "name": "ALM_COOL_LWT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110032,
   "name": "ALM_COOL_PUMP1_F",
   "description": "Cooler Pump 1 Default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110033,
   "name": "ALM_COOL_PUMP2_F",
   "description": "Cooler Pump 2 Default",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110001,
   "name": "ALM_COOLER_FREEZE_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110014,
   "name": "ALM_COOLER_LOCK_F",
   "description": "Cooler Interlock Failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110016,
   "name": "ALM_CPA1_REVERSE_ROT_F",
   "description": "Pressure Increase not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110017,
   "name": "ALM_CPA2_REVERSE_ROT_F",
   "description": "Pressure Increase not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110018,
   "name": "ALM_CPA3_REVERSE_ROT_F",
   "description": "Pressure Increase not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110020,
   "name": "ALM_CPB1_REVERSE_ROT_F",
   "description": "Pressure Increase not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110021,
   "name": "ALM_CPB2_REVERSE_ROT_F",
   "description": "Pressure Increase not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115015,
   "name": "ALM_DGT_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115011,
   "name": "ALM_DLWT_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 112001,
   "name": "ALM_DP_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 112002,
   "name": "ALM_DP_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 157020,
   "name": "ALM_EXV_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 157021,
   "name": "ALM_EXV_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 104701,
   "name": "ALM_FAN_DRIVE_COM_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 117001,
   "name": "ALM_FAN_VFD_DRIVE_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 113005,
   "name": "ALM_FGAS_NEEDED",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110099,
   "name": "ALM_FLUIDE_FAIL",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110063,
   "name": "ALM_HP_SWITCH_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110064,
   "name": "ALM_HP_SWITCH_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 107001,
   "name": "ALM_ILL_FACT_CONF_F",
   "description": "Illegal configuration",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 108000,
   "name": "ALM_INI_FACT_CONF_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110030,
   "name": "ALM_LOSS_COM_MS_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110029,
   "name": "ALM_LOSS_COM_SM_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110011,
   "name": "ALM_LOW_SH_A_F",
   "description": "Circuit A Low Superheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110012,
   "name": "ALM_LOW_SH_B_F",
   "description": "Circuit B Low Superheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110005,
   "name": "ALM_LOW_SUCTION_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110006,
   "name": "ALM_LOW_SUCTION_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 109001,
   "name": "ALM_M_S_CONFIG_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110031,
   "name": "ALM_NETWORK_EMSTOP_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115010,
   "name": "ALM_OAT_F",
   "description": "OAT Thermistor Failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110037,
   "name": "ALM_REPEATED_HI_DGT_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110038,
   "name": "ALM_REPEATED_HI_DGT_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110040,
   "name": "ALM_REPEATED_LO_SST_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110041,
   "name": "ALM_REPEATED_LO_SST_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110210,
   "name": "ALM_RUN_OUT_MAP_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110211,
   "name": "ALM_RUN_OUT_MAP_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110097,
   "name": "ALM_SENSORS_SWAP_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 113001,
   "name": "ALM_SERVICE_MAINT_ALERT",
   "description": "Service Maintenance Alert",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 112004,
   "name": "ALM_SP_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 112005,
   "name": "ALM_SP_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115021,
   "name": "ALM_SPACETMP",
   "description": "Space Temperature Failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115012,
   "name": "ALM_SUCTION_T_A_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115013,
   "name": "ALM_SUCTION_T_B_F",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "BACnet_bacena",
   "description": "BACnet Enable Option",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "BACnet_bacunit",
   "description": "Metric Units?",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "BACnet_BMS_OCC",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 64,
   "name": "BACnet_COLOR",
   "description": "ALC color value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "BACnet_ident",
   "description": "Device Id Actually Used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "BACnet_network",
   "description": "Network",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "BACnet_PRIME_V",
   "description": "ALC prime value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5443,
   "name": "FACTORY_flui_typ",
   "description": "Cooler Fluid Type",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5770,
   "name": "FACTORY_hgbp_sel",
   "description": "Hot Gas Bypass Selection",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5013,
   "name": "FACTORY_unit_typ",
   "description": "UnitType (WaterCooled=3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5014,
   "name": "FACTORY_unitsize",
   "description": "Unit Capacity Model",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5766,
   "name": "FACTORY2_cap_a1",
   "description": "Compressor A1 Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5767,
   "name": "FACTORY2_cap_a2",
   "description": "Compressor A2 Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5768,
   "name": "FACTORY2_cap_a3",
   "description": "Compressor A3 Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5769,
   "name": "FACTORY2_cap_b1",
   "description": "Compressor B1 Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5078,
   "name": "GENCONF_ewt_opt",
   "description": "Entering Fluid Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5003,
   "name": "GENCONF_lim_sel",
   "description": "Demand Limit Type Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "GENUNIT_CAP_T",
   "description": "Percent Total Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1017,
   "name": "GENUNIT_CAPA_T",
   "description": "Circuit A Total Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2017,
   "name": "GENUNIT_CAPB_T",
   "description": "Circuit B Total Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "GENUNIT_CHIL_OCC_rd",
   "description": "Net.: Cmd Occupied",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10058,
   "name": "GENUNIT_CHIL_OCC_wr",
   "description": "Net.: Cmd Occupied",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "GENUNIT_CHIL_S_S_rd",
   "description": "Net.: Cmd Start/Stop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10012,
   "name": "GENUNIT_CHIL_S_S_wr",
   "description": "Net.: Cmd Start/Stop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "GENUNIT_CTRL_PNT_rd",
   "description": "Control Point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10006,
   "name": "GENUNIT_CTRL_PNT_wr",
   "description": "Control Point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "GENUNIT_CTRL_TYP",
   "description": "Local=0 Net.=1 Remote=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "GENUNIT_DEM_LIM_rd",
   "description": "Active Demand Limit Val",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10008,
   "name": "GENUNIT_DEM_LIM_wr",
   "description": "Active Demand Limit Val",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "GENUNIT_EMSTOP_rd",
   "description": "Emergency Stop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10013,
   "name": "GENUNIT_EMSTOP_wr",
   "description": "Emergency Stop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "GENUNIT_HC_SEL_rd",
   "description": "Heat/Cool Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10023,
   "name": "GENUNIT_HC_SEL_wr",
   "description": "Heat/Cool Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "GENUNIT_HEATCOOL",
   "description": "Heat/Cool status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "GENUNIT_min_left",
   "description": "Minutes Left for Start",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "GENUNIT_SP",
   "description": "Current Setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "GENUNIT_SP_OCC_rd",
   "description": "Setpoint Occupied?",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10059,
   "name": "GENUNIT_SP_OCC_wr",
   "description": "Setpoint Occupied?",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "GENUNIT_SP_SEL_rd",
   "description": "Setpoint Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10024,
   "name": "GENUNIT_SP_SEL_wr",
   "description": "Setpoint Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "GENUNIT_STATUS",
   "description": "Running Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5019,
   "name": "HCCONFIG_cr_sel",
   "description": "Cooling Reset Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5020,
   "name": "HCCONFIG_hr_sel",
   "description": "Heating Reset Select",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5772,
   "name": "HEADCTRL_condsp",
   "description": "Computed Cond Setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5773,
   "name": "HEADCTRL_fan",
   "description": "Fan Speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 966,
   "name": "HR_PARTIAL_DOWNTIME",
   "description": "Cumul Time Partial Alm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 967,
   "name": "HR_TOTAL_DOWNTIME",
   "description": "Cumul Time Tripout Alm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "INPUTS_CNFS",
   "description": "Condenser Water Flow SW",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5106,
   "name": "INPUTS_CSP_IN",
   "description": "4_20mA Cooling Setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5759,
   "name": "INPUTS_CWP1",
   "description": "Water Pump Interlock 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5760,
   "name": "INPUTS_CWP2",
   "description": "Water Pump Interlock 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5008,
   "name": "INPUTS_DSHTR_SW",
   "description": "Desuperheater Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "INPUTS_FLOW_SW",
   "description": "Flow Switch Interlock",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "INPUTS_HC_SW",
   "description": "Remote Heat/Cool Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5009,
   "name": "INPUTS_HP_SW_A",
   "description": "High Pressure Switch A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5011,
   "name": "INPUTS_HP_SW_B",
   "description": "High Pressure Switch B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "INPUTS_ICE_SW",
   "description": "Ice Done Storage Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5006,
   "name": "INPUTS_leak_v1",
   "description": "Leakage Detection 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5007,
   "name": "INPUTS_leak_v2",
   "description": "Leakage Detection 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5764,
   "name": "INPUTS_LIM_4_20",
   "description": "Capacity Limit Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "INPUTS_LIM_SW1",
   "description": "Limit Switch 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "INPUTS_LIM_SW2",
   "description": "Limit Switch 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "INPUTS_ONOFF_SW",
   "description": "Remote On/Off Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5761,
   "name": "INPUTS_REV_ROT",
   "description": "Phase Reversal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "INPUTS_SETP_SW",
   "description": "Second Setpoint Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5005,
   "name": "INPUTS_SP_RESET",
   "description": "Setpoint Reset Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1011,
   "name": "LOADFACT_SH_A",
   "description": "Suction Superheat A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2011,
   "name": "LOADFACT_SH_B",
   "description": "Suction Superheat B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5301,
   "name": "MODES_m_ice",
   "description": "Ice Mode In Effect",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5061,
   "name": "OPT_SEL_boil_en",
   "description": "Boiler Enable",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5012,
   "name": "OUTPUTS_ALARM",
   "description": "Alarm Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5711,
   "name": "OUTPUTS_BOILER",
   "description": "Boiler Output",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1032,
   "name": "OUTPUTS_CP_A1",
   "description": "Compressor A1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1033,
   "name": "OUTPUTS_CP_A2",
   "description": "Compressor A2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1034,
   "name": "OUTPUTS_CP_A3",
   "description": "Compressor A3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2032,
   "name": "OUTPUTS_CP_B1",
   "description": "Compressor B1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2033,
   "name": "OUTPUTS_CP_B2",
   "description": "Compressor B2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5754,
   "name": "OUTPUTS_DUS",
   "description": "Digital Unload Solenoid",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5765,
   "name": "OUTPUTS_EISOR",
   "description": "Evaporator Isolator Rly",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "OUTPUTS_EXCH_HTR",
   "description": "Exchanger Heater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5023,
   "name": "OUTPUTS_EXV_A",
   "description": "EXV Position Circuit A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5024,
   "name": "OUTPUTS_EXV_B",
   "description": "EXV Position Circuit B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5762,
   "name": "OUTPUTS_FANC_1",
   "description": "Fan Contactor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5763,
   "name": "OUTPUTS_FANC_2",
   "description": "Fan Contactor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5752,
   "name": "OUTPUTS_HEAD_ACT",
   "description": "Head Pressure Actuator A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5753,
   "name": "OUTPUTS_HGBP_V",
   "description": "Hot Gas ByPass Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5758,
   "name": "OUTPUTS_LLSV_A",
   "description": "Solenoid Valve A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5757,
   "name": "OUTPUTS_LLSV_B",
   "description": "Solenoid Valve B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5771,
   "name": "OUTPUTS_Mod_CPA1",
   "description": "Digital Modul. A1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "OUTPUTS_RUN",
   "description": "Running Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1015,
   "name": "OUTPUTS_VFAN",
   "description": "VariaFan Speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1000,
   "name": "PRESSURE_DP_A",
   "description": "Discharge Pressure A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2000,
   "name": "PRESSURE_DP_B",
   "description": "Discharge Pressure B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1001,
   "name": "PRESSURE_SP_A",
   "description": "Suction Pressure A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2001,
   "name": "PRESSURE_SP_B",
   "description": "Suction Pressure B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10053,
   "name": "PROTOCOL_PUMP_C",
   "description": "Condenser Pump",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5001,
   "name": "PUMPCONF_pump_del",
   "description": "Pump Auto Rotation Delay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5004,
   "name": "PUMPCONF_pump_loc",
   "description": "Flow Checked if Pump Off",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5002,
   "name": "PUMPCONF_pump_per",
   "description": "Pump Sticking Protection",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5003,
   "name": "PUMPCONF_pump_sby",
   "description": "Stop Pump During Standby",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "PUMPCONF_pump_seq",
   "description": "Cooler Pumps Sequence",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5756,
   "name": "PUMPSTAT_CPUMP",
   "description": "Condenser Pump Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "PUMPSTAT_PUMP_1_rd",
   "description": "Water Pump #1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10050,
   "name": "PUMPSTAT_PUMP_1_wr",
   "description": "Evaporator pump 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "PUMPSTAT_PUMP_2_rd",
   "description": "Water Pump #2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10051,
   "name": "PUMPSTAT_PUMP_2_wr",
   "description": "Evaporator pump 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5035,
   "name": "RESETCFG_cr_deg",
   "description": "Cooling Reset Deg. Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5030,
   "name": "RESETCFG_dt_cr_fu",
   "description": "Delta T Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5029,
   "name": "RESETCFG_dt_cr_no",
   "description": "Delta T No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5039,
   "name": "RESETCFG_dt_hr_fu",
   "description": "Delta T Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5038,
   "name": "RESETCFG_dt_hr_no",
   "description": "Delta T No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5044,
   "name": "RESETCFG_hr_deg",
   "description": "Heating Reset Deg. Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5032,
   "name": "RESETCFG_I_cr_fu",
   "description": "Current Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5031,
   "name": "RESETCFG_I_cr_no",
   "description": "Current No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5041,
   "name": "RESETCFG_I_hr_fu",
   "description": "Current Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5040,
   "name": "RESETCFG_I_hr_no",
   "description": "Current No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5028,
   "name": "RESETCFG_oat_crfu",
   "description": "OAT Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5027,
   "name": "RESETCFG_oat_crno",
   "description": "OAT No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5037,
   "name": "RESETCFG_oat_hrfu",
   "description": "OAT Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5036,
   "name": "RESETCFG_oat_hrno",
   "description": "OAT No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5034,
   "name": "RESETCFG_spacr_fu",
   "description": "Space T Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5033,
   "name": "RESETCFG_spacr_no",
   "description": "Space T No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5043,
   "name": "RESETCFG_spahr_fu",
   "description": "Space T Full Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5042,
   "name": "RESETCFG_spahr_no",
   "description": "Space T No Reset Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1960,
   "name": "RUNTIME_hr_cp_a1",
   "description": "Compressor A1 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1961,
   "name": "RUNTIME_hr_cp_a2",
   "description": "Compressor A2 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1962,
   "name": "RUNTIME_hr_cp_a3",
   "description": "Compressor A3 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2960,
   "name": "RUNTIME_hr_cp_b1",
   "description": "Compressor B1 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2961,
   "name": "RUNTIME_hr_cp_b2",
   "description": "Compressor B2 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 960,
   "name": "RUNTIME_hr_mach",
   "description": "Machine Operating Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 962,
   "name": "RUNTIME_hr_pump1",
   "description": "Water Pump #1 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 963,
   "name": "RUNTIME_hr_pump2",
   "description": "Water Pump #2 Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1964,
   "name": "RUNTIME_st_cp_a1",
   "description": "Compressor A1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1965,
   "name": "RUNTIME_st_cp_a2",
   "description": "Compressor A2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1966,
   "name": "RUNTIME_st_cp_a3",
   "description": "Compressor A3 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2964,
   "name": "RUNTIME_st_cp_b1",
   "description": "Compressor B1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2965,
   "name": "RUNTIME_st_cp_b2",
   "description": "Compressor B2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 961,
   "name": "RUNTIME_st_mach",
   "description": "Machine Starts Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5447,
   "name": "SERVICE1_freezesp",
   "description": "Brine Freeze Setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5016,
   "name": "SETPOINT_cauto_sp",
   "description": "Cool Changeover Setpt",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 900,
   "name": "SETPOINT_csp1",
   "description": "Cooling Setpoint 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 901,
   "name": "SETPOINT_csp2",
   "description": "Cooling Setpoint 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5017,
   "name": "SETPOINT_hauto_sp",
   "description": "Heat Changeover Setpt",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 903,
   "name": "SETPOINT_hsp1",
   "description": "Heating Setpoint 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 904,
   "name": "SETPOINT_hsp2",
   "description": "Heating Setpoint 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 905,
   "name": "SETPOINT_lim_sp1",
   "description": "Switch Limit Setpoint 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 906,
   "name": "SETPOINT_lim_sp2",
   "description": "Switch Limit Setpoint 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 907,
   "name": "SETPOINT_lim_sp3",
   "description": "Switch Limit Setpoint 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5064,
   "name": "SETPOINT_min_sct",
   "description": "Desuperheater Min Sct",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5015,
   "name": "SETPOINT_ramp_sp",
   "description": "Ramp Loading",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "TEMP_CEWT",
   "description": "Cond Entering Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "TEMP_CLWT",
   "description": "Cond Leaving Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1009,
   "name": "TEMP_DGT_A",
   "description": "Discharge Gas Temp A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2009,
   "name": "TEMP_DGT_B",
   "description": "Discharge Gas Temp B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "TEMP_DLWT",
   "description": "Dual Leaving Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "TEMP_EWT",
   "description": "Entering Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "TEMP_LWT",
   "description": "Leaving Water Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "TEMP_OAT",
   "description": "Outdoor Air Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1005,
   "name": "TEMP_SCT_A",
   "description": "Saturated Cond Tmp cir A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2005,
   "name": "TEMP_SCT_B",
   "description": "Saturated Cond Tmp cir B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5082,
   "name": "TEMP_SPACETMP",
   "description": "Space Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1006,
   "name": "TEMP_SST_A",
   "description": "Saturated Suction Temp A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2006,
   "name": "TEMP_SST_B",
   "description": "Saturated Suction Temp B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1007,
   "name": "TEMP_SUCT_A",
   "description": "Suction Temp Circuit A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2007,
   "name": "TEMP_SUCT_B",
   "description": "Suction Temp Circuit B",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "integration": {
  "summary": "Set bacena to BACnet IP or MS/TP in Main Menu > Configuration > BACnet, set device ID and network, then select the Network control method on the chiller. Command through the _wr objects (start/stop, occupancy, control point, demand limit, emergency stop) and read status, water temperatures, capacity and alarms.",
  "minimum_points": [
   {
    "ref": "BV 10012",
    "name": "GENUNIT_CHIL_S_S_wr",
    "why": "Network start/stop command"
   },
   {
    "ref": "BV 10058",
    "name": "GENUNIT_CHIL_OCC_wr",
    "why": "Network occupied command"
   },
   {
    "ref": "AV 10006",
    "name": "GENUNIT_CTRL_PNT_wr",
    "why": "Leaving water control point from the BMS"
   },
   {
    "ref": "AV 10008",
    "name": "GENUNIT_DEM_LIM_wr",
    "why": "Demand limit command"
   },
   {
    "ref": "AV 21",
    "name": "GENUNIT_CTRL_TYP",
    "why": "Control type: Local, Network or Remote"
   },
   {
    "ref": "AV 22",
    "name": "GENUNIT_STATUS",
    "why": "Running status"
   },
   {
    "ref": "AV 2",
    "name": "TEMP_LWT",
    "why": "Leaving water temperature"
   },
   {
    "ref": "AV 1",
    "name": "TEMP_EWT",
    "why": "Entering water temperature"
   },
   {
    "ref": "AV 9",
    "name": "GENUNIT_CAP_T",
    "why": "Percent total capacity"
   },
   {
    "ref": "AV 990",
    "name": "ALARMRST_ALM",
    "why": "Unit alarm state"
   }
  ],
  "enable": "Select the Network machine control method with the Start/Stop button; the unit then follows CCN, BACnet (if enabled) or Modbus commands and ignores the remote contacts. Start/stop and occupancy are written to the _wr objects.",
  "heartbeat": "The manual says that if communication with the network is lost while under network control, the chiller starts and runs under local control.",
  "remote_sensors": null,
  "setup": [
   "BACnet is disabled by default (bacena 0); set 1 for BACnet IP or 2 for BACnet MS/TP.",
   "Defaults shown: network number 1600, UDP port 47808, device ID 1600001 (manual or auto device ID option).",
   "MS/TP defaults: baud option 2 (38400), Max Master 10, Max Info Frames 5; MAC 1-127.",
   "J5 (ETH0) carries BACnet IP / Modbus TCP; J10 is RS-485 for BACnet MS/TP or secondary Modbus RTU."
  ],
  "gotchas": [
   "Write the _wr object, not the _rd one; the _rd copy only reports the current value.",
   "The BACnet menu has a 'BACnet Manage Occupancy' option (mng_occ) and the list has a writable BACnet_BMS_OCC (AV 66); check how they interact with CHIL_OCC before relying on either."
  ]
 },
 "page": "https://easybacnet.com/bacnet-points-lists/carrier/aquasnap-30rc-010-060",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}