 "manufacturer": "Carrier",
 "manufacturer_slug": "carrier",
 "model": "AquaSnap 30RB 060-390 (UPC Open BACnet option)",
 "model_slug": "aquasnap-30rb-upc-open",
 "aliases": [
  "30RB",
  "AquaSnap 30RB",
  "30RB-8T",
  "30RB Greenspeed",
  "UPC Open",
  "ComfortLink"
 ],
 "equipment_type": "Air-cooled scroll chiller controller (BACnet option)",
 "applies_to": "Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.",
 "summary": "On the 30RB, BACnet MS/TP comes from a UPC Open controller added to the ComfortLink chiller. It publishes about 300 AV and BV objects (names ending in _1) covering start/stop, emergency stop, control point, demand limit, heat/cool select, setpoints, temperatures, pressures, compressor and fan status for up to three circuits, run hours and alarm state.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "Network number 16101 followed by the MAC address (MAC 20 gives 1610120)",
 "access_inferred": false,
 "notes": [
  "BACnet comes from the optional UPC Open controller, mounted in a separate enclosure below the main control box; object names end in _1.",
  "The Network Points List gives a point description, CCN name, read/write, units, default and range for each object; descriptions here are the printed point descriptions.",
  "AV 137 Run Status codes: 0 Off, 1 Running, 2 Stopping, 3 Delay, 4 Tripout, 5 Ready, 6 Override, 7 Defrost, 8 Run Test, 9 Test. AV 2 Alarm State: 0 Normal, 1 Partial, 2 Shutdown.",
  "The printed table gives Cooling Setpoint 2 (AV 103) the unit \"min\" and the Cooling Ice Setpoint (AV 99) a delta unit; both are absolute setpoints and are shown here in °F. Some other printed units and defaults look shifted by a row and are kept as printed."
 ],
 "source": {
  "title": "AquaSnap 30RB060-390 Air-Cooled Chillers and 30RB080-390 with Greenspeed Intelligence - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix F, BACnet Communication Option, Network Points List)",
  "doc_number": "30RB-8T Rev. B",
  "revision_date": "12-23",
  "url": "https://www.shareddocs.com/hvac/docs/1005/Public/05/30RB-8T.pdf"
 },
 "integration": {
  "summary": "Address the UPC Open (rotary switches), set the MS/TP baud and protocol DIP switches, and configure the chiller for CCN control. The BMS then starts and stops the chiller with BV 1500 (CCN Chiller Start/Stop) and can write control point, demand limit and heat/cool select; read run status, leaving water temperature, capacity and alarm state.",
  "minimum_points": [
   {
    "ref": "BV 1500",
    "name": "chil_s_s_1",
    "why": "Network start/stop (Enable/Disable)"
   },
   {
    "ref": "BV 68",
    "name": "emstop_1",
    "why": "Emergency stop command"
   },
   {
    "ref": "AV 110",
    "name": "hc_sel_1",
    "why": "Heat/cool select: 0 Cool, 1 Heat, 2 Auto"
   },
   {
    "ref": "AV 96",
    "name": "ctrl_pnt_1",
    "why": "Control point (leaving water setpoint)"
   },
   {
    "ref": "AV 1",
    "name": "dem_lim_1",
    "why": "Demand limit, 0-100 %"
   },
   {
    "ref": "AV 137",
    "name": "status_1",
    "why": "Run status code"
   },
   {
    "ref": "AV 151",
    "name": "lwt_1",
    "why": "Leaving water temperature"
   },
   {
    "ref": "AV 1700",
    "name": "cap_t_1",
    "why": "Percent total capacity"
   },
   {
    "ref": "AV 2",
    "name": "alm_1",
    "why": "Alarm state: 0 Normal, 1 Partial, 2 Shutdown"
   }
  ],
  "enable": "Set the Operating Control Type to 2 (CCN Control). An external CCN device then forces CHIL_S_S (BV 1500) between start and stop. The Status Unit Control Type reads 2 (CCN) when the Enable/Off/Remote Contact switch is On and 0 (Local Off) when it is Off.",
  "heartbeat": null,
  "remote_sensors": null,
  "gotchas": [
   "The Enable/Off/Remote Contact switch must be On for network start/stop to take effect.",
   "Many objects only apply with options such as heat reclaim, free cooling or a third circuit."
  ],
  "setup": [
   "The BACnet option adds a UPC Open controller; it speaks BACnet MS/TP at 9600, 19.2k, 38.4k or 76.8k (Carrier default 76.8k), set on BAS port DIP switches DS1-DS2.",
   "For MS/TP set DS3 to enable, DS4 to E1-485 and the protocol switches DS5-DS8 to MSTP; the EIA-485 jumpers must be set to EIA-485 and 2W.",
   "MAC address from the two rotary switches (tens and ones); the controller reads switches and DIP settings only at power-up.",
   "Device instance is auto-generated as the network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120; change it with i-Vu Tools or a BACview.",
   "Fit a BT485 terminator on the first and last controller of the MS/TP segment."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 1,
   "name": "dem_lim_1",
   "description": "Active Demand Limit Val",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "alm_1",
   "description": "Alarm State",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "capt_010_1",
   "description": "Chiller Capacity Signal",
   "units": "volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "cpa1_cur_1",
   "description": "Cir A Crank Heater Current Cp1",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "cpa2_cur_1",
   "description": "Cir A Crank Heater Current Cp2",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "cpa3_cur_1",
   "description": "Cir A Crank Heater Current Cp3",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "cpa4_cur_1",
   "description": "Cir A Crank Heater Current Cp4",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "exv_a_1",
   "description": "Cir A EXV Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "fan_st_a_1",
   "description": "Cir A Fan Staging Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "hd_pos_a_1",
   "description": "Cir A Head Press Actuator Pos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "cpa1_tmp_1",
   "description": "Cir A Motor Thermistor Comp 1",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "cpa2_tmp_1",
   "description": "Cir A Motor Thermistor Comp 2",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "cpa3_tmp_1",
   "description": "Cir A Motor Thermistor Comp 3",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "cpa4_tmp_1",
   "description": "Cir A Motor Thermistor Comp 4",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "capa_t_1",
   "description": "Cir A Percent Total Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "suct_t_a_1",
   "description": "Cir A Suction Gas Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "sh_a_1",
   "description": "Cir A Suction Superheat Temp",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "cpb1_cur_1",
   "description": "Cir B Crank Heater Current Cp1",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "cpb2_cur_1",
   "description": "Cir B Crank Heater Current Cp2",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "cpb3_cur_1",
   "description": "Cir B Crank Heater Current Cp3",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "cpb4_cur_1",
   "description": "Cir B Crank Heater Current Cp4",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "exv_b_1",
   "description": "Cir B EXV Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "fan_st_b_1",
   "description": "Cir B Fan Staging Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "hd_pos_b_1",
   "description": "Cir B Head Press Actuator Pos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "cpb1_tmp_1",
   "description": "Cir B Motor Thermistor Comp 1",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "cpb2_tmp_1",
   "description": "Cir B Motor Thermistor Comp 2",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "cpb3_tmp_1",
   "description": "Cir B Motor Thermistor Comp 3",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "cpb4_tmp_1",
   "description": "Cir B Motor Thermistor Comp 4",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "capb_t_1",
   "description": "Cir B Percent Total Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "sct_b_1",
   "description": "Cir B Saturated Condensing Tmp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "sst_b_1",
   "description": "Cir B Saturated Suction Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "suct_t_b_1",
   "description": "Cir B Suction Gas Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "sp_b_1",
   "description": "Cir B Suction Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "sh_b_1",
   "description": "Cir B Suction Superheat Temp",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "cpc1_cur_1",
   "description": "Cir C Crank Heater Current Cp1",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "cpc2_cur_1",
   "description": "Cir C Crank Heater Current Cp2",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "cpc3_cur_1",
   "description": "Cir C Crank Heater Current Cp3",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "cpc4_cur_1",
   "description": "Cir C Crank Heater Current Cp4",
   "units": "amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "exv_c_1",
   "description": "Cir C EXV Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "fan_st_c_1",
   "description": "Cir C Fan Staging Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "hd_pos_c_1",
   "description": "Cir C Head Press Actuator Pos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "cpc1_tmp_1",
   "description": "Cir C Motor Thermistor Comp 1",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "cpc2_tmp_1",
   "description": "Cir C Motor Thermistor Comp 2",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "cpc3_tmp_1",
   "description": "Cir C Motor Thermistor Comp 3",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "cpc4_tmp_1",
   "description": "Cir C Motor Thermistor Comp 4",
   "units": "ohms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "capc_t_1",
   "description": "Cir C Percent Total Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "sct_c_1",
   "description": "Cir C Saturated Condensing Tmp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "sst_c_1",
   "description": "Cir C Saturated Suction Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "suct_t_c_1",
   "description": "Cir C Suction Gas Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "sp_c_1",
   "description": "Cir C Suction Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "sh_c_1",
   "description": "Cir C Suction Superheat Temp",
   "units": "°F (delta)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "hr_fana1_1",
   "description": "Circuit A Fan #1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "hr_fana2_1",
   "description": "Circuit A Fan #2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "hr_fana3_1",
   "description": "Circuit A Fan #3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "hr_fana4_1",
   "description": "Circuit A Fan #4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "hr_fana5_1",
   "description": "Circuit A Fan #5 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "hr_fana6_1",
   "description": "Circuit A Fan #6 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "hr_fanb1_1",
   "description": "Circuit B Fan #1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "hr_fanb2_1",
   "description": "Circuit B Fan #2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "hr_fanb3_1",
   "description": "Circuit B Fan #3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "hr_fanb4_1",
   "description": "Circuit B Fan #4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "hr_fanb5_1",
   "description": "Circuit B Fan #5 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "hr_fanb6_1",
   "description": "Circuit B Fan #6 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "hr_fanc1_1",
   "description": "Circuit C Fan #1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "hr_fanc2_1",
   "description": "Circuit C Fan #2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "hr_fanc3_1",
   "description": "Circuit C Fan #3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "hr_fanc4_1",
   "description": "Circuit C Fan #4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "hr_fanc5_1",
   "description": "Circuit C Fan #5 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "hr_fanc6_1",
   "description": "Circuit C Fan #6 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "lead_cir_1",
   "description": "Circuit Loading Sequence",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "hr_cp_a1_1",
   "description": "Compressor A1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "st_cp_a1_1",
   "description": "Compressor A1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "hr_cp_a2_1",
   "description": "Compressor A2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "st_cp_a2_1",
   "description": "Compressor A2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "hr_cp_a3_1",
   "description": "Compressor A3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "st_cp_a3_1",
   "description": "Compressor A3 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "hr_cp_a4_1",
   "description": "Compressor A4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "st_cp_a4_1",
   "description": "Compressor A4 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "hr_cp_b1_1",
   "description": "Compressor B1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "st_cp_b1_1",
   "description": "Compressor B1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "hr_cp_b2_1",
   "description": "Compressor B2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "st_cp_b2_1",
   "description": "Compressor B2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "hr_cp_b3_1",
   "description": "Compressor B3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "st_cp_b3_1",
   "description": "Compressor B3 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "hr_cp_b4_1",
   "description": "Compressor B4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "st_cp_b4_1",
   "description": "Compressor B4 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "hr_cp_c1_1",
   "description": "Compressor C1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "st_cp_c1_1",
   "description": "Compressor C1 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "hr_cp_c2_1",
   "description": "Compressor C2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "st_cp_c2_1",
   "description": "Compressor C2 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "hr_cp_c3_1",
   "description": "Compressor C3 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "st_cp_c3_1",
   "description": "Compressor C3 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "hr_cp_c4_1",
   "description": "Compressor C4 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "st_cp_c4_1",
   "description": "Compressor C4 Starts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "ctrl_wt_1",
   "description": "Controlled Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "ctrl_pnt_1",
   "description": "Control Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "flui_typ_1",
   "description": "Cooler Fluid Type",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "pump_seq_1",
   "description": "Cooler Pumps Sequence",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "ice_sp_1",
   "description": "Cooling Ice Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "cramp_sp_1",
   "description": "Cooling Ramp Loading",
   "units": "°F (delta)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "cr_deg_1",
   "description": "Cooling Reset Deg. Value",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "csp1_1",
   "description": "Cooling Setpoint 1",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "csp2_1",
   "description": "Cooling Setpoint 2",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "v_cr_fu_1",
   "description": "Current Full Reset Value",
   "units": "ma",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "v_cr_no_1",
   "description": "Current No Reset Value",
   "units": "ma",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "dt_cr_fu_1",
   "description": "Delta T Full Reset Value",
   "units": "°F (delta)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "dt_cr_no_1",
   "description": "Delta T No Reset Value",
   "units": "°F (delta)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "lim_sel_1",
   "description": "Demand Limit Type Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "oat_1",
   "description": "External Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "hc_sel_1",
   "description": "Heat/Cool Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "heatcool_1",
   "description": "Heat/Cool Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "hr_hpump_1",
   "description": "Heat Reclaim Pump Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "lag_lim_1",
   "description": "Lag Capacity Limit Value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "lim_anal_1",
   "description": "Limit 4-20mA Signal",
   "units": "ma",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "hr_mach_1",
   "description": "Machine Operating Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "st_mach_1",
   "description": "Machine Starts Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "lim_ze_1",
   "description": "mA For 0% Demand Limit",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "lim_mx_1",
   "description": "mA For 100% Demand Limit",
   "units": "mA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "ms_sel_1",
   "description": "Master/Slave Select",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "min_left_1",
   "description": "Minutes Left for Start",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "oatcr_fu_1",
   "description": "OAT Full Reset Value",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "oatcr_no_1",
   "description": "OAT No Reset Value",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "spacetmp_1",
   "description": "Optional Space Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "pump_del_1",
   "description": "Pump Auto Rotation Delay",
   "units": "hours",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "pd_p_a_1",
   "description": "Pumpdown Pressure Cir A",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "pd_p_b_1",
   "description": "Pumpdown Pressure Cir B",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "hr_sat_a_1",
   "description": "Pumpdown Saturated Tmp A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "hr_sat_b_1",
   "description": "Pumpdown Saturated Tmp B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "hr_deadb_1",
   "description": "Reclaim Deadband",
   "units": "°F (delta)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "hr_ewt_1",
   "description": "Reclaim Entering Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "hr_lwt_1",
   "description": "Reclaim Leaving Fluid",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "rsp_1",
   "description": "Reclaim Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "hrstat_a_1",
   "description": "Reclaim Status Circuit A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "hrstat_b_1",
   "description": "Reclaim Status Circuit B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "hr_v_pos_1",
   "description": "Reclaim Valve Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "sp_reset_1",
   "description": "Reset/Setpoint 4-20mA In",
   "units": "ma",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "status_1",
   "description": "Run Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "spacr_fu_1",
   "description": "Space T Full Reset Value",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "spacr_no_1",
   "description": "Space T No Reset Value",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "st_cp_av_1",
   "description": "Starts/hr From Last 24 h",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "st_cp_mx_1",
   "description": "Starts Max During 1 Hour",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "hr_subta_1",
   "description": "Sub Condenser Temp Cir A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "hr_subtb_1",
   "description": "Sub Condenser Temp Cir B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "hr_subca_1",
   "description": "Subcooling Temperature A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "hr_subcb_1",
   "description": "Subcooling Temperature B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "lim_sp1_1",
   "description": "Switch Limit Setpoint 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "lim_sp2_1",
   "description": "Switch Limit Setpoint 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "lim_sp3_1",
   "description": "Switch Limit Setpoint 3",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "off_on_d_1",
   "description": "Unit Off to On Delay",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "ewt_1",
   "description": "Water Exchanger Entering Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "lwt_1",
   "description": "Water Exchanger Leaving Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "hr_cpum1_1",
   "description": "Water Pump #1 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "hr_cpum2_1",
   "description": "Water Pump #2 Hours",
   "units": "hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1600,
   "name": "sp_a_1",
   "description": "Cir A Suction Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1601,
   "name": "dp_a_1",
   "description": "Cir A Discharge Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1602,
   "name": "sct_a_1",
   "description": "Cir A Saturated Condensing Tmp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1603,
   "name": "sst_a_1",
   "description": "Cir A Saturated Suction Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1605,
   "name": "dp_b_1",
   "description": "Cir B Discharge Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1609,
   "name": "dp_c_1",
   "description": "Cir C Discharge Pressure",
   "units": "psi",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1612,
   "name": "chwstemp_1",
   "description": "CHWS Temperature - Prime Variable",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1700,
   "name": "cap_t_1",
   "description": "Percent Total Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2901,
   "name": "user_analog_1_1",
   "description": "User Defined Analog 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2902,
   "name": "user_analog_2_1",
   "description": "User Defined Analog 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2903,
   "name": "user_analog_3_1",
   "description": "User Defined Analog 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2904,
   "name": "user_analog_4_1",
   "description": "User Defined Analog 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2905,
   "name": "user_analog_5_1",
   "description": "User Defined Analog 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3500,
   "name": "chws_sp_1",
   "description": "Current Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9006,
   "name": "cool_demand_level_1",
   "description": "System Cooling Demand Level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80001,
   "name": "mstr_oa_temp_1",
   "description": "System OAT Master",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "schedule_1",
   "description": "Local Schedule",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "dem_lmt_act_1",
   "description": "System Demand Limiting",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "hr_ea_a_1",
   "description": "Air Cond Entering Valv A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "hr_ea_b_1",
   "description": "Air Cond Entering Valv B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "hr_la_a_1",
   "description": "Air Cond Leaving Valve A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "hr_la_b_1",
   "description": "Air Cond Leaving Valve B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "alarmout_1",
   "description": "Alarm Relay Status",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "alert_1",
   "description": "Alert Relay Status",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "mode_12_1",
   "description": "Auto Changeover Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "mode_17_1",
   "description": "Boiler Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "boiler_1",
   "description": "Boiler Command",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "cp_a1_ht_1",
   "description": "Cir A Compressor 1 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "cp_a1_1",
   "description": "Cir A Compressor 1 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "cp_a2_ht_1",
   "description": "Cir A Compressor 2 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "cp_a2_1",
   "description": "Cir A Compressor 2 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "cp_a3_ht_1",
   "description": "Cir A Compressor 3 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "cp_a3_1",
   "description": "Cir A Compressor 3 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "cp_a4_ht_1",
   "description": "Cir A Compressor 4 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "cp_a4_1",
   "description": "Cir A Compressor 4 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "fan_a1_1",
   "description": "Cir A Fan Output DO # 1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "fan_a2_1",
   "description": "Cir A Fan Output DO # 2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "fan_a3_1",
   "description": "Cir A Fan Output DO # 3",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "fan_a4_1",
   "description": "Cir A Fan Output DO # 4",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "fan_a5_1",
   "description": "Cir A Fan Output DO # 5",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "fan_a6_1",
   "description": "Cir A Fan Output DO # 6",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "hgbp_v_a_1",
   "description": "Cir A Hot Gas Bypass Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "cp_b1_ht_1",
   "description": "Cir B Compressor 1 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "cp_b1_1",
   "description": "Cir B Compressor 1 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "cp_b2_ht_1",
   "description": "Cir B Compressor 2 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "cp_b2_1",
   "description": "Cir B Compressor 2 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "cp_b3_ht_1",
   "description": "Cir B Compressor 3 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "cp_b3_1",
   "description": "Cir B Compressor 3 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "cp_b4_ht_1",
   "description": "Cir B Compressor 4 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "cp_b4_1",
   "description": "Cir B Compressor 4 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "fan_b1_1",
   "description": "Cir B Fan Output DO # 1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "fan_b2_1",
   "description": "Cir B Fan Output DO # 2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "fan_b3_1",
   "description": "Cir B Fan Output DO # 3",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "fan_b4_1",
   "description": "Cir B Fan Output DO # 4",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "fan_b5_1",
   "description": "Cir B Fan Output DO # 5",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "fan_b6_1",
   "description": "Cir B Fan Output DO # 6",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "hgbp_v_b_1",
   "description": "Cir B Hot Gas Bypass Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "cp_c1_ht_1",
   "description": "Cir C Compressor 1 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "cp_c1_1",
   "description": "Cir C Compressor 1 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "cp_c2_ht_1",
   "description": "Cir C Compressor 2 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "cp_c2_1",
   "description": "Cir C Compressor 2 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "cp_c3_ht_1",
   "description": "Cir C Compressor 3 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "cp_c3_1",
   "description": "Cir C Compressor 3 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "cp_c4_ht_1",
   "description": "Cir C Compressor 4 Heater Out",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "cp_c4_1",
   "description": "Cir C Compressor 4 Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "fan_c1_1",
   "description": "Cir C Fan Output DO # 1",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "fan_c2_1",
   "description": "Cir C Fan Output DO # 2",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "fan_c3_1",
   "description": "Cir C Fan Output DO # 3",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "fan_c4_1",
   "description": "Cir C Fan Output DO # 4",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "fan_c5_1",
   "description": "Cir C Fan Output DO # 5",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "fan_c6_1",
   "description": "Cir C Fan Output DO # 6",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "hgbp_v_c_1",
   "description": "Cir C Hot Gas Bypass Output",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "mode_06_1",
   "description": "Cooler Heater Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "coolheat_1",
   "description": "Cooler Heater Command",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "mode_07_1",
   "description": "Cooler Pumps Rotation",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "critical_1",
   "description": "Critical Alarm Status",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "mode_19_1",
   "description": "Defrost Active On Cir A",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "mode_20_1",
   "description": "Defrost Active On Cir B",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "mode_04_1",
   "description": "Demand Limit Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "elec_box_1",
   "description": "Electrical Box Safety",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "ehs_step_1",
   "description": "Electrical Heat Stage",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "mode_15_1",
   "description": "Electric Heat Active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "emstop_1",
   "description": "Emergency Stop",
   "units": "",
   "access": "W",
   "states": "Enable/Disable"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "pump_loc_1",
   "description": "Flow Checked if Pump Off",
   "units": "",
   "access": "W",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "mode_13_1",
   "description": "Free Cooling Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "fc_dsble_1",
   "description": "Free Cooling Disable?",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "fc_sw_1",
   "description": "Free Cooling Disable Sw.",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "mode_16_1",
   "description": "Heating Low EWT Lockout",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "recl_sel_1",
   "description": "Heat Reclaim Select",
   "units": "",
   "access": "W",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "mode_24_1",
   "description": "High DGT Circuit A",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "mode_25_1",
   "description": "High DGT Circuit B",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "mode_26_1",
   "description": "High DGT Circuit C",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "mode_27_1",
   "description": "High Pres Override Cir A",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "mode_28_1",
   "description": "High Pres Override Cir B",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "mode_29_1",
   "description": "High Pres Override Cir C",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "ice_sw_1",
   "description": "Ice Done Storage Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "mode_18_1",
   "description": "Ice Mode in Effect",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "lock_1_1",
   "description": "Interlock Status",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "lim_sw1_1",
   "description": "Limit Switch 1 Status",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "lim_sw2_1",
   "description": "Limit Switch 2 Status",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "mode_21_1",
   "description": "Low Suction Circuit A",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "mode_22_1",
   "description": "Low Suction Circuit B",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "mode_23_1",
   "description": "Low Suction Circuit C",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "mode_09_1",
   "description": "Night Low Noise Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "occ_ovsw_1",
   "description": "Occupied Override Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "onoff_sw_1",
   "description": "On/Off - Remote Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "all_pass_1",
   "description": "Pass For All User Config",
   "units": "",
   "access": "W",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "mode_08_1",
   "description": "Pump Periodic Start",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "pump_def_1",
   "description": "Pump Run Status",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "pump_per_1",
   "description": "Pump Sticking Protection",
   "units": "",
   "access": "W",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "mode_05_1",
   "description": "Ramp Loading Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "ramp_sel_1",
   "description": "Ramp Loading Select",
   "units": "",
   "access": "W",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "ready_1",
   "description": "Ready or Running Status",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "mode_14_1",
   "description": "Reclaim Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "condflow_1",
   "description": "Reclaim Condenser Flow",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "cond_htr_1",
   "description": "Reclaim Condenser Heater",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "condpump_1",
   "description": "Reclaim Condenser Pump",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "cond_pmp_1",
   "description": "Reclaim Condenser Pump",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "hc_sw_1",
   "description": "Remote Heat/Cool Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "rem_lock_1",
   "description": "Remote Interlock Status",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "recl_sw_1",
   "description": "Remote Reclaim Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "setp_sw_1",
   "description": "Remote Setpoint Switch",
   "units": "",
   "access": "R",
   "states": "Open/Close"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "mode_03_1",
   "description": "Reset in Effect",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "rot_pump_1",
   "description": "Rotate Pumps Now?",
   "units": "",
   "access": "W",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "running_1",
   "description": "Running Status",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "mode_02_1",
   "description": "Second Setpoint in Use",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 112,
   "name": "sp_occ_1",
   "description": "Setpoint Occupied?",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 113,
   "name": "shutdown_1",
   "description": "Shutdown Indicator State",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 114,
   "name": "seq_typ_1",
   "description": "Staged Loading Sequence",
   "units": "",
   "access": "W",
   "states": "No/Yes"
  },
  {
   "type": "BV",
   "instance": 115,
   "name": "mode_01_1",
   "description": "Startup Delay in Effect",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "mode_30_1",
   "description": "Superheat Override Cir A",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "mode_31_1",
   "description": "Superheat Override Cir B",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "mode_32_1",
   "description": "Superheat Override Cir C",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "mode_10_1",
   "description": "System Manager Active",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "hr_ew_a_1",
   "description": "Water Cond Enter Valve A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 121,
   "name": "hr_ew_b_1",
   "description": "Water Cond Enter Valve B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 122,
   "name": "hr_lw_a_1",
   "description": "Water Cond Leaving Val A",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 123,
   "name": "hr_lw_b_1",
   "description": "Water Cond Leaving Val B",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 124,
   "name": "cpump_1_1",
   "description": "Water Pump #1 Command",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 125,
   "name": "cpump_2_1",
   "description": "Water Pump #2 Command",
   "units": "",
   "access": "R",
   "states": "On/Off"
  },
  {
   "type": "BV",
   "instance": 146,
   "name": "element_alarm_1",
   "description": "Equipment Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1500,
   "name": "chil_s_s_1",
   "description": "CCN Chiller Start/Stop",
   "units": "",
   "access": "W",
   "states": "Enable/Disable"
  },
  {
   "type": "BV",
   "instance": 1501,
   "name": "chil_occ_1",
   "description": "Chiller Occupied?",
   "units": "",
   "access": "R",
   "states": "Yes/No"
  },
  {
   "type": "BV",
   "instance": 2911,
   "name": "user_binary_1_1",
   "description": "User Defined Binary 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2912,
   "name": "user_binary_2_1",
   "description": "User Defined Binary 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2913,
   "name": "user_binary_3_1",
   "description": "User Defined Binary 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2914,
   "name": "user_binary_4_1",
   "description": "User Defined Binary 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2915,
   "name": "user_binary_5_1",
   "description": "User Defined Binary 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2999,
   "name": "element_stat_1",
   "description": "Element Comm Status",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/carrier/aquasnap-30rb-upc-open",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}