- 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Rooftop unit controller (VAV) · BACnet points list
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet points list
Updated 4 November 2026
The VAV-RTU Open is the factory controller on the 48/50LC B VAV rooftops. It runs as a BACnet MS/TP master, either as the air source for a Carrier VAV zoning system (Airside Linkage) or standalone under a third-party BMS. The points list has about 190 objects: sensor inputs, setpoints, supply-air and static-pressure control, service tests, runtimes and alarms.
This page lists 191 BACnet objects for the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) — 87 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
- Equipment
- Rooftop unit controller (VAV)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 191 (87 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Set SW3 to BACnet MS/TP and the baud rate, set the address on SW1/SW2 and cycle power. For standalone use under a third-party BMS, command occupancy with BAS On / Off (MV 1001), write the occupied setpoints and the supply-air and static-pressure setpoints, and read the system mode, fan state, supply air temperature and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1001 | keypad_ovrde | BAS occupancy: 1=Inactive, 2=Occupied, 3=Unoccupied | Write |
| AV 3001 | occ_cl_stpt | Occupied cooling setpoint | Write |
| AV 3002 | occ_ht_stpt | Occupied heating setpoint | Write |
| AV 3029 | sat_cl_stpt | Supply air setpoint for cooling (default 53 °F) | Write |
| AV 3030 | sa_static_stpt | Duct static pressure setpoint | Write |
| MV 2002 | run_status | Current system mode | Read |
| BV 2001 | sfan | Supply fan relay on/off | Read |
| AV 1008 | sa_temp | Supply air temperature | Read |
| AV 2028 | static_press | Duct static pressure | Read |
| BV 7024 | safety_alarm | Safety chain alarm | Read |
Enable & remote start
BAS On / Off (keypad_ovrde, MV 1001) is the network occupancy input for third-party systems: 1 = Inactive (default), 2 = Occupied (occupied heating and cooling setpoints apply), 3 = Unoccupied (unoccupied setpoints apply). A BACnet schedule from i-Vu or the remote occupancy input can also set occupancy. Shutdown (BV 9001) is a writable shutdown point.
Sensors & values from the BMS
The System points take network values: System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901), System Outdoor AQ (AV 1908) and System Return Air Temperature (AV 1920). The table prints -999 as their default value. The guide gives no refresh time.
Network setup
- SW3 DIP switches set the protocol (BACnet MS/TP master) and baud rate (9600, 19200, 38400 or 76800); SW1 and SW2 set the MS/TP address (01-99). Cycle power after changing them.
- In a Carrier VAV system the zone controllers and the VAV-RTU Open are linked through a VAV Master zone controller, which must have the highest address on the MS/TP network.
- A Field Assistant laptop connects at the J12 local access port; the System Touch wall display connects to the MS/TP network.
Watch out for
- Economizer Exists (BV 99001) is set at the factory and is not field configurable.
- Several alarm BVs share a display name with the analog value they belong to (e.g. 'Compressor 1 Runtime' is both AV 2017 and BV 7014); go by the object name.
- The Service Test and Factory Test points (BV 81000-81008, BV 91001-91008, AV 91001-91002) drive outputs directly; leave them alone in normal operation.
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1001 | ai_1 | Static Pressure Sensor | mA | Read | |
| AI | 1002 | ai_2 | input_2 | mA | Read | |
| AI | 1006 | ai_6 | SAT Sensor | °F | Read | |
| AI | 1007 | ai_7 | OAT sensor | °F | Read | |
| AI | 1010 | ai_10 | Space Temp Sensor | °F | Read | |
| AI | 1011 | ai_11 | RAT Sensor | °F | Read | |
| BI | 1003 | di_3 | input_3 | Read | ||
| BI | 1004 | di_4 | input_4 | Read | ||
| BI | 1005 | di_5 | input_5 | Read | ||
| BI | 1008 | di_8 | input_8 | Read | ||
| BI | 1009 | di_9 | input_9 | Read | ||
| AV | 1003 | oa_temp | Outdoor Air Temperature | °F | Read | |
| AVmin | 1008 | sa_temp | Supply Air Temperature - Prime Variable | °F | Read | |
| AV | 1009 | iaq | Indoor Air Quality CO2 (ppm) | ppm | Read | |
| AV | 1010 | ra_temp | Return Air Temperature | °F | Read | |
| AV | 1011 | space_rh | Space Relative Humidity | %rh | Read | |
| AV | 1012 | oaq | Outdoor Air Quality CO2 (ppm) | ppm | Read | |
| AV | 1032 | spt_temp | Space Temperature | °F | Read | |
| AV | 1901 | system_oat | System Outdoor Air Temperature (default -999) | °F | Write | |
| AV | 1902 | system_spt | System Space Temperature (default -999) | °F | Write | |
| AV | 1903 | system_iaq | System Space AQ (default -999) | ppm | Write | |
| AV | 1904 | system_rh | System Space RH (default -999) | %rh | Write | |
| AV | 1908 | system_oaq | System Outdoor AQ (default -999) | ppm | Write | |
| AV | 1920 | system_rat | System Return Air Temperature (default -999) | °F | Write | |
| AV | 2003 | heat_run | Active Heat Stages | Read | ||
| AV | 2014 | sfan_rntm | Supply Fan Runtime | hr | Read | |
| AV | 2015 | filter_rntm | Filter Runtime | hr | Read | |
| AV | 2016 | ovrde_time | Override Time Remaining | min | Read | |
| AV | 2017 | comp1_rntm | Compressor 1 Runtime | hr | Read | |
| AV | 2018 | comp2_rntm | Compressor 2 Runtime | hr | Read | |
| AV | 2019 | filter_service_hrs | Filter Service Alarm Timer (default 600) | hr | Write | |
| AV | 2020 | et_comp_run | Active Cooling Stages | Read | ||
| AV | 2022 | econ_output | Economizer Output | %Open | Read | |
| AV | 2027 | vfd_output | Supply Fan VFD | % | Read | |
| AVmin | 2028 | static_press | Static Pressure | in H2O | Read | |
| AV | 2029 | heat1_rntm | Heat 1 Runtime | hr | Read | |
| AV | 2030 | heat2_rntm | Heat 2 Runtime | hr | Read | |
| AV | 2031 | sasp | Supply Air Setpoint | °F | Read | |
| AV | 2034 | htg_cntl_pt | Heating Control Setpoint | °F | Read | |
| AV | 2035 | ctrl_temp | Controlling Temperature | °F | Read | |
| AV | 2608 | link_sat | Air Source Supply Air Temp | °F | Read | |
| AV | 2609 | link_ahu_oat | Air Source Outdoor Air Temp | °F | Read | |
| AV | 2610 | link_sp | Air Source Static Pressure | in H2O | Read | |
| AVmin | 3001 | occ_cl_stpt | Setpoint - occupied cooling | °F | Write | |
| AVmin | 3002 | occ_ht_stpt | Setpoint - occupied heating | °F | Write | |
| AV | 3003 | unocc_cl_stpt | Setpoint - unoccupied cooling | °F | Write | |
| AV | 3004 | unocc_ht_stpt | Setpoint - unoccupied heating | °F | Write | |
| AV | 3005 | eff_cl_stpt | Effective Cool Setpoint | °F | Read | |
| AV | 3006 | eff_ht_stpt | Effective Heat Setpoint | °F | Read | |
| AV | 3010 | pexh_stpt | Power Exhaust Setpoint (default 50) | %Open | Write | |
| AV | 3011 | occ_dehum_stpt | Occ Relative Humidity Setpoint (default 60) | %rh | Write | |
| AV | 3013 | iaq_stpt_max | DCV Max Ctrl Setpoint (default 1100) | ppm | Write | |
| AV | 3026 | max_vfd_spd | Max VFD Output (default 100) | % | Write | |
| AV | 3027 | min_vfd_spd | Min VFD Output (default 25) | % | Write | |
| AVmin | 3029 | sat_cl_stpt | Supply Air Setpoint (default 53) | °F | Write | |
| AVmin | 3030 | sa_static_stpt | Static Pressure Setpoint (default 0.5) | in H2O | Write | |
| AV | 3031 | sa_static_stpt_value | Current Static Pressure Setpoint | in H2O | Read | |
| AV | 3032 | tempering_stpt | SA Tempering Setpoint (default 55) | °F | Write | |
| AV | 9002 | oat_cl_lockout | Cooling Lockout Temperature (default 45) | °F | Write | |
| AV | 9003 | oat_ht_lockout | Heating Lockout Temperature (default 65) | °F | Write | |
| AV | 9005 | econ_min | Vent Dmpr Pos / DCV Min Pos (default 20) | %Open | Write | |
| AV | 9006 | cool_demand_level | System Cooling Demand Level | Read | ||
| AV | 9007 | start_delay | Power Fail Restart Delay (default 5) | seconds | Write | |
| AV | 9008 | oat_ec_lockout | Economizer High OAT Lockout Temp (default 75) | °F | Write | |
| AV | 9011 | iaq_dpr_max | DCV Max Vent Damper Pos (default 50) | %Open | Write | |
| AV | 9024 | fan_delay_off | Fan Off Delay (default 90) | seconds | Write | |
| AV | 9030 | econ_min_2 | Low Fan Econ Min Pos (default 33) | %Open | Write | |
| AV | 9036 | heat_demand_level | System Heating Demand Level | Read | ||
| AV | 9040 | sat_cl_stpt_reset_max | Reset Maximum Limit (default 10) | °^F | Write | |
| AV | 9041 | sat_cl_stpt_reset | Reset Ratio (default 3) | Write | ||
| AV | 80001 | mstr_oa_temp | System OAT Master | °F | Read | |
| AV | 81001 | econ_test | Economizer Test (default 0) | %Open | Write | |
| AV | 81002 | vfd_spd_test | VFD Speed Test (default 0) | % | Write | |
| AV | 83003 | sat_cl_min | Minimum Cooling SAT (default 45) | °F | Write | |
| AV | 83004 | sat_ht_max | Maximum Heating SAT (default 120) | °F | Write | |
| AV | 83005 | sfan_service_hrs | Supply Fan Service Alarm Timer (default 0) | hr | Write | |
| AV | 83006 | comp1_service_hrs | Compressor 1 Service Alarm Timer (default 0) | hr | Write | |
| AV | 83007 | comp2_service_hrs | Compressor 2 Service Alarm Timer (default 0) | hr | Write | |
| AV | 83008 | heat1_service_hrs | Heat 1 Service Alarm Timer (default 0) | hr | Write | |
| AV | 83009 | heat2_service_hrs | Heat 2 Service Alarm Timer (default 0) | hr | Write | |
| AV | 90000 | ppo | Password Protected Output Variable (default 0) | Write | ||
| AV | 91001 | ao1_fac_test | Factory Test Analog 1 Control (default 0) | % | Write | |
| AV | 91002 | ao2_fac_test | Factory Test Analog 2 Control (default 0) | % | Write | |
| BV | 1002 | enthalpy_status | Enthalpy Status | Read | ||
| BV | 1003 | sfan_status | Supply Fan Status | Read | ||
| BV | 1004 | filter_status | Filter Status | Read | ||
| BV | 1005 | firedown_status | Fire Shutdown Status | Read | ||
| BV | 1006 | humstat_status | Humidistat Input Status | Read | ||
| BV | 1007 | occ_contact_status | Occupancy Contact | Read | ||
| BV | 1008 | comp_status | Compressor Safety Status | Read | ||
| BV | 1009 | safety_status | Safety Chain Feedback | Read | ||
| BV | 1010 | door_contact_status | Door Contact Status | Read | ||
| BV | 1022 | igcovr_status | IGC Override | Read | ||
| BV | 1025 | rh_enable | SA Reset Humidity Override (default Inactive (0)) | Write | ||
| BV | 1027 | dcv_enable | DCV Control (default Inactive (0)) | Write | ||
| BV | 1901 | oae | Enthalpy (BACnet) (default Active (1)) | Write | ||
| BV | 1908 | hsl_reset | Reset High Static Trip (default Inactive (0)) | Write | ||
| BVmin | 2001 | sfan | Supply Fan Relay State | Read | ||
| BV | 2002 | heat_2 | Heat Stage 2 Relay State | Read | ||
| BV | 2003 | heat_1 | Heat Stage 1 Relay State | Read | ||
| BV | 2004 | comp_2 | Compressor 2 Relay State | Read | ||
| BV | 2005 | comp_1 | Compressor 1 Relay State | Read | ||
| BV | 2007 | comp_3 | Compressor 3 Relay State | Read | ||
| BV | 2008 | occ_status | Occupancy Status | Read | ||
| BV | 2010 | pexh | Power Exhaust Relay State | Read | ||
| BV | 2011 | shutdown_status | System is shut down | Read | ||
| BV | 2012 | ht_interlock | Heat Interlock Relay State | Read | ||
| BV | 2031 | occ_heat | Occupied Heating (default Inactive (0)) | Write | ||
| BV | 7001 | spt_fail | Space Temp Sensor | Read | ||
| BV | 7003 | loc_oat_sensor_fail | Local OAT Sensor | Read | ||
| BV | 7004 | sat_alarm | Supply Air Temperature | Read | ||
| BV | 7005 | iaq_alarm | Indoor Air Quality | Read | ||
| BV | 7006 | oaq_fail | Outdoor Air Quality Sensor | Read | ||
| BV | 7007 | fire_alarm | Fire / Smoke Shutdown | Read | ||
| BV | 7008 | sfan_fail_alarm | Supply Fan Failure | Read | ||
| BV | 7009 | sfan_hand_alarm | Supply Fan in Hand | Read | ||
| BV | 7010 | sfan_rntm_alarm | Supply Fan Runtime | Read | ||
| BV | 7013 | comp_alarm | Compressor Status | Read | ||
| BV | 7014 | comp1_rntm_alarm | Compressor 1 Runtime | Read | ||
| BV | 7015 | comp2_rntm_alarm | Compressor 2 Runtime | Read | ||
| BV | 7017 | filter_alarm | Filter | Read | ||
| BV | 7018 | sprh_hi_alarm | Space Relative Humidity | Read | ||
| BV | 7020 | loc_sat_sensor_fail | Supply Air Temp Sensor | Read | ||
| BV | 7022 | sprh_sensor_fail | Space Relative Humidity Sensor | Read | ||
| BVmin | 7024 | safety_alarm | Safety Chain | Read | ||
| BV | 7025 | di_cfg_alarm | Switch Configuration | Read | ||
| BV | 7026 | ai_cfg_alarm | Analog Input Configuration | Read | ||
| BV | 7029 | oat_fail | Outdoor Air Temp Sensor | Read | ||
| BV | 7030 | air_linkage_fail | Airside Linkage | Read | ||
| BV | 7035 | rat_alarm | Return Air Temperature | Read | ||
| BV | 7039 | iaq_sensor_fail | Indoor Air Quality Sensor | Read | ||
| BV | 7050 | igc_alarm | Gas Valve | Read | ||
| BV | 7052 | rat_fail | Return Air Temp Sensor | Read | ||
| BV | 7054 | econ_opr | Economizer Operation | Read | ||
| BV | 7055 | zs_config_fail | ZS Sensor Configuration | Read | ||
| BV | 7060 | sp_alarm | HPCO Shutdown | Read | ||
| BV | 7061 | sp_fail | Static Pressure Sensor | Read | ||
| BV | 7062 | heat1_rntm_alarm | Heat 1 Runtime | Read | ||
| BV | 7063 | heat2_rntm_alarm | Heat 2 Runtime | Read | ||
| BV | 7067 | ctrl_temp_fail | Ctrl Temp Sensor Failure | Read | ||
| BV | 7510 | sfan_rntm_clr | Reset Supply Fan Runtime Alarm (default Inactive (0)) | Write | ||
| BV | 7514 | comp1_rntm_clr | Reset Comp 1 Runtime Alarm (default Inactive (0)) | Write | ||
| BV | 7515 | comp2_rntm_clr | Reset Comp 2 Runtime Alarm (default Inactive (0)) | Write | ||
| BV | 7517 | filter_rntm_clr | Reset Filter Alarm (default Inactive (0)) | Write | ||
| BV | 7518 | heat1_rntm_clr | Reset Heat 1 Runtime Alarm (default Inactive (0)) | Write | ||
| BV | 7519 | heat2_rntm_clr | Reset Heat 2 Runtime Alarm (default Inactive (0)) | Write | ||
| BV | 9001 | shutdown | Shutdown (default Inactive (0)) | Write | ||
| BV | 9002 | occ_exh | Continuous Occupied Exhaust (default Inactive (0)) | Write | ||
| BV | 9003 | calc_limit_reset | Reset Calculated Max Heat Limit (default Inactive (0)) | Write | ||
| BV | 9004 | sa_reset_en | Supply Air Temp Reset (default Inactive (0)) | Write | ||
| BV | 80001 | ntfc_ena | Unocc Free Cool (default Inactive (0)) | Write | ||
| BV | 81000 | test_enable | Service Test (default Inactive (0)) | Write | ||
| BV | 81002 | heat2_test | Heat 2Test (default Inactive (0)) | Write | ||
| BV | 81003 | heat1_test | Heat 1Test (default Inactive (0)) | Write | ||
| BV | 81004 | comp2_test | Compressor 2 Test (default Inactive (0)) | Write | ||
| BV | 81005 | comp1_test | Compressor 1 Test (default Inactive (0)) | Write | ||
| BV | 81006 | hir_test | Heat Interlock Relay Test (default Inactive (0)) | Write | ||
| BV | 81008 | pexh_test | Power Exhaust Test (default Inactive (0)) | Write | ||
| BV | 83016 | sa_tempering_en | SA Tempering (default Inactive (0)) | Write | ||
| BV | 91001 | relay1_fac_test | Factory Test Relay 1 Control (default Inactive (0)) | Write | ||
| BV | 91002 | relay2_fac_test | Factory Test Relay 2 Control (default Inactive (0)) | Write | ||
| BV | 91003 | relay3_fac_test | Factory Test Relay 3 Control (default Inactive (0)) | Write | ||
| BV | 91004 | relay4_fac_test | Factory Test Relay 4 Control (default Inactive (0)) | Write | ||
| BV | 91005 | relay5_fac_test | Factory Test Relay 5 Control (default Inactive (0)) | Write | ||
| BV | 91006 | relay6_fac_test | Factory Test Relay 6 Control (default Inactive (0)) | Write | ||
| BV | 91007 | relay7_fac_test | Factory Test Relay 7 Control (default Inactive (0)) | Write | ||
| BV | 91008 | relay8_fac_test | Factory Test Relay 8 Control (default Inactive (0)) | Write | ||
| BV | 99001 | econ_exist | Economizer Exists (required) (default Active (1)) | Write | ||
| BV | 99002 | heat_type | Heat Type (default Active (1)) | Write | ||
| MVmin | 1001 | keypad_ovrde | BAS On / Off (default 1) | Write | 1=Inactive; 2=Occupied; 3=Unoccupied | |
| MV | 1002 | occ_source | Occupancy Source | Read | ||
| MV | 2001 | mode_status | Equipment Status | Read | 1=Disabled; 2=Test; 3=Run | |
| MVmin | 2002 | run_status | System Mode | Read | 1=Off; 2=Fan Only; 3=Economizer Cooling; 4=Cooling; 5=Heating; 6=Dehumidification; 7=Test; 8=Shutdow; 9=Unocc Free Cooling; 10=Fire Shutdown; 11=IAQ Override; 12=Pre-Occ Purge; 13=IGC Override | |
| MV | 2005 | link_ahu_mode | Air Source Mode | Read | 1=Off; 2=Warmup; 3=Heating; 4=Cooling; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent | |
| MV | 2011 | econ_fdd_result | Economizer | Read | 1=Normal; 2=Failed to Fully Open; 3=Failed to Open; 4=Failed to Close; 5=Stuck Open | |
| MV | 2013 | ctrl_temp_src | Ctrl Temp Source | Read | 1=Sensor Failure; 2=Space; 3=Return Air; 4=Linkage Zone; 5=Locked Value | |
| MV | 2014 | spt_source | Space Temp Source | Read | ||
| MV | 2015 | rat_src | RAT Source | Read | ||
| MV | 2016 | sat_reset_source | SAT Reset Source | Read | ||
| MV | 7068 | sp_proof_alm | SP Proof | Read | ||
| MV | 9033 | sp_reset_dmd_lvl | SP Reset Demand Level (default 1) | Write | ||
| MV | 81002 | ai2_function | Input 2 Function (default 1) | Write | ||
| MV | 81003 | di3_function | Input 3 Function (default 1) | Write | ||
| MV | 81005 | di5_function | Input 5 Function (default 2) | Write | ||
| MV | 81008 | di8_function | Input 8 Function (default 2) | Write | ||
| MV | 81009 | di9_function | Input 9 Function (default 1) | Write | ||
| MV | 81013 | di3_type | Input 3 Switch Configuration (default 1) | Write | ||
| MV | 81015 | di5_type | Input 5 Switch Configuration (default 1) | Write | ||
| MV | 81018 | di8_type | Input 8 Switch Configuration (default 1) | Write | ||
| MV | 81019 | di9_type | Input 9 Switch Configuration (default 1) | Write | ||
| MV | 91004 | heat_stages | Number Of Heat Stages (default 2) | Write |
No points match these filters.
Object ID lookup: Carrier 48/50LC B 07-26 VAV Rooftop point IDs by name
AI1001ai_1AI1002ai_2AI1006ai_6AI1007ai_7AI1010ai_10AI1011ai_11BI1003di_3BI1004di_4BI1005di_5BI1008di_8BI1009di_9AV1003oa_tempAV1008sa_tempAV1009iaqAV1010ra_tempAV1011space_rhAV1012oaqAV1032spt_tempAV1901system_oatAV1902system_sptAV1903system_iaqAV1904system_rhAV1908system_oaqAV1920system_ratAV2003heat_runAV2014sfan_rntmAV2015filter_rntmAV2016ovrde_timeAV2017comp1_rntmAV2018comp2_rntmAV2019filter_service_hrsAV2020et_comp_runAV2022econ_outputAV2027vfd_outputAV2028static_pressAV2029heat1_rntmAV2030heat2_rntmAV2031saspAV2034htg_cntl_ptAV2035ctrl_tempAV2608link_satAV2609link_ahu_oatAV2610link_spAV3001occ_cl_stptAV3002occ_ht_stptAV3003unocc_cl_stptAV3004unocc_ht_stptAV3005eff_cl_stptAV3006eff_ht_stptAV3010pexh_stptAV3011occ_dehum_stptAV3013iaq_stpt_maxAV3026max_vfd_spdAV3027min_vfd_spdAV3029sat_cl_stptAV3030sa_static_stptAV3031sa_static_stpt_valueAV3032tempering_stptAV9002oat_cl_lockoutAV9003oat_ht_lockoutAV9005econ_minAV9006cool_demand_levelAV9007start_delayAV9008oat_ec_lockoutAV9011iaq_dpr_maxAV9024fan_delay_offAV9030econ_min_2AV9036heat_demand_levelAV9040sat_cl_stpt_reset_maxAV9041sat_cl_stpt_resetAV80001mstr_oa_tempAV81001econ_testAV81002vfd_spd_testAV83003sat_cl_minAV83004sat_ht_maxAV83005sfan_service_hrsAV83006comp1_service_hrsAV83007comp2_service_hrsAV83008heat1_service_hrsAV83009heat2_service_hrsAV90000ppoAV91001ao1_fac_testAV91002ao2_fac_testBV1002enthalpy_statusBV1003sfan_statusBV1004filter_statusBV1005firedown_statusBV1006humstat_statusBV1007occ_contact_statusBV1008comp_statusBV1009safety_statusBV1010door_contact_statusBV1022igcovr_statusBV1025rh_enableBV1027dcv_enableBV1901oaeBV1908hsl_resetBV2001sfanBV2002heat_2BV2003heat_1BV2004comp_2BV2005comp_1BV2007comp_3BV2008occ_statusBV2010pexhBV2011shutdown_statusBV2012ht_interlockBV2031occ_heatBV7001spt_failBV7003loc_oat_sensor_failBV7004sat_alarmBV7005iaq_alarmBV7006oaq_failBV7007fire_alarmBV7008sfan_fail_alarmBV7009sfan_hand_alarmBV7010sfan_rntm_alarmBV7013comp_alarmBV7014comp1_rntm_alarmBV7015comp2_rntm_alarmBV7017filter_alarmBV7018sprh_hi_alarmBV7020loc_sat_sensor_failBV7022sprh_sensor_failBV7024safety_alarmBV7025di_cfg_alarmBV7026ai_cfg_alarmBV7029oat_failBV7030air_linkage_failBV7035rat_alarmBV7039iaq_sensor_failBV7050igc_alarmBV7052rat_failBV7054econ_oprBV7055zs_config_failBV7060sp_alarmBV7061sp_failBV7062heat1_rntm_alarmBV7063heat2_rntm_alarmBV7067ctrl_temp_failBV7510sfan_rntm_clrBV7514comp1_rntm_clrBV7515comp2_rntm_clrBV7517filter_rntm_clrBV7518heat1_rntm_clrBV7519heat2_rntm_clrBV9001shutdownBV9002occ_exhBV9003calc_limit_resetBV9004sa_reset_enBV80001ntfc_enaBV81000test_enableBV81002heat2_testBV81003heat1_testBV81004comp2_testBV81005comp1_testBV81006hir_testBV81008pexh_testBV83016sa_tempering_enBV91001relay1_fac_testBV91002relay2_fac_testBV91003relay3_fac_testBV91004relay4_fac_testBV91005relay5_fac_testBV91006relay6_fac_testBV91007relay7_fac_testBV91008relay8_fac_testBV99001econ_existBV99002heat_typeMV1001keypad_ovrdeMV1002occ_sourceMV2001mode_statusMV2002run_statusMV2005link_ahu_modeMV2011econ_fdd_resultMV2013ctrl_temp_srcMV2014spt_sourceMV2015rat_srcMV2016sat_reset_sourceMV7068sp_proof_almMV9033sp_reset_dmd_lvlMV81002ai2_functionMV81003di3_functionMV81005di5_functionMV81008di8_functionMV81009di9_functionMV81013di3_typeMV81015di5_typeMV81018di8_typeMV81019di9_typeMV91004heat_stages
Integration notes
- Taken from Appendix D, Table C 'VAV-RTU Open Protocol Maps' (pp. 49-52). MSV objects are listed as MV.
- Point display names are as printed; four setpoints are all named 'Setpoint' in the table, so the description says which one (from the BACnet object name).
- Default values printed in the table are added to the descriptions. Multistate state texts are taken from the units column where printed.
- The System Mode states are printed with '8=Shutdow'; kept as printed.
- A different controller from the SystemVu control used on the 48/50LC 04-26 units and from the RTU Open controller, which have their own lists.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
How many BACnet points does the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) have?
This list has 191 BACnet objects: 6 analog inputs, 72 analog values, 5 binary inputs, 86 binary values, 22 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet points are writable?
87 of the 191 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet documentation?
The source is 48/50LCB07-26 with VAV-RTU Open Controller, Controls, Start-Up, Operation and Troubleshooting (Appendix D: BACnet Points List) (48-50LCB-7-26-04T), revision 2022-05, published free by Carrier at https://brandportal.carrier.com/asset/1d59de26-3b17-4555-8d1e-6f6126a95717/48-50LCB-7-26-04T.pdf.
What are the minimum BACnet points to integrate the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?
Start with MV 1001 keypad_ovrde (BAS occupancy: 1=Inactive, 2=Occupied, 3=Unoccupied); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); AV 3029 sat_cl_stpt (Supply air setpoint for cooling (default 53 °F)); AV 3030 sa_static_stpt (Duct static pressure setpoint); MV 2002 run_status (Current system mode); BV 2001 sfan (Supply fan relay on/off); AV 1008 sa_temp (Supply air temperature); AV 2028 static_press (Duct static pressure); BV 7024 safety_alarm (Safety chain alarm).
How do I enable BMS control of the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?
BAS On / Off (keypad_ovrde, MV 1001) is the network occupancy input for third-party systems: 1 = Inactive (default), 2 = Occupied (occupied heating and cooling setpoints apply), 3 = Unoccupied (unoccupied setpoints apply). A BACnet schedule from i-Vu or the remote occupancy input can also set occupancy. Shutdown (BV 9001) is a writable shutdown point.
Can the BMS supply sensor values to the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?
The System points take network values: System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901), System Outdoor AQ (AV 1908) and System Return Air Temperature (AV 1920). The table prints -999 as their default value. The guide gives no refresh time.
How do I check these points on the real 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: 48/50LCB07-26 with VAV-RTU Open Controller, Controls, Start-Up, Operation and Troubleshooting (Appendix D: BACnet Points List) · 48-50LCB-7-26-04T · rev. 2022-05. Object names, instances and units are reproduced as published; descriptions are our own.