Rooftop unit controller (VAV) · BACnet points list

Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet points list

Updated 4 November 2026

Short answer

The VAV-RTU Open is the factory controller on the 48/50LC B VAV rooftops. It runs as a BACnet MS/TP master, either as the air source for a Carrier VAV zoning system (Airside Linkage) or standalone under a third-party BMS. The points list has about 190 objects: sensor inputs, setpoints, supply-air and static-pressure control, service tests, runtimes and alarms.

This page lists 191 BACnet objects for the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) — 87 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Equipment
Rooftop unit controller (VAV)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
191 (87 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T
Source document
48/50LCB07-26 with VAV-RTU Open Controller, Controls, Start-Up, Operation and Troubleshooting (Appendix D: BACnet Points List) · 48-50LCB-7-26-04T · rev. 2022-05
Download CSV 191 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)

Integration in brief

Set SW3 to BACnet MS/TP and the baud rate, set the address on SW1/SW2 and cycle power. For standalone use under a third-party BMS, command occupancy with BAS On / Off (MV 1001), write the occupied setpoints and the supply-air and static-pressure setpoints, and read the system mode, fan state, supply air temperature and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1001keypad_ovrdeBAS occupancy: 1=Inactive, 2=Occupied, 3=UnoccupiedWrite
AV 3001occ_cl_stptOccupied cooling setpointWrite
AV 3002occ_ht_stptOccupied heating setpointWrite
AV 3029sat_cl_stptSupply air setpoint for cooling (default 53 °F)Write
AV 3030sa_static_stptDuct static pressure setpointWrite
MV 2002run_statusCurrent system modeRead
BV 2001sfanSupply fan relay on/offRead
AV 1008sa_tempSupply air temperatureRead
AV 2028static_pressDuct static pressureRead
BV 7024safety_alarmSafety chain alarmRead

Enable & remote start

BAS On / Off (keypad_ovrde, MV 1001) is the network occupancy input for third-party systems: 1 = Inactive (default), 2 = Occupied (occupied heating and cooling setpoints apply), 3 = Unoccupied (unoccupied setpoints apply). A BACnet schedule from i-Vu or the remote occupancy input can also set occupancy. Shutdown (BV 9001) is a writable shutdown point.

Sensors & values from the BMS

The System points take network values: System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901), System Outdoor AQ (AV 1908) and System Return Air Temperature (AV 1920). The table prints -999 as their default value. The guide gives no refresh time.

Network setup

Watch out for

Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

191 of 191 shown
Type
Multi-state
Access
Show
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet Points List
DescriptionStates
AI1001ai_1Static Pressure SensormARead
AI1002ai_2input_2mARead
AI1006ai_6SAT Sensor°FRead
AI1007ai_7OAT sensor°FRead
AI1010ai_10Space Temp Sensor°FRead
AI1011ai_11RAT Sensor°FRead
BI1003di_3input_3Read
BI1004di_4input_4Read
BI1005di_5input_5Read
BI1008di_8input_8Read
BI1009di_9input_9Read
AV1003oa_tempOutdoor Air Temperature°FRead
AVmin1008sa_tempSupply Air Temperature - Prime Variable°FRead
AV1009iaqIndoor Air Quality CO2 (ppm)ppmRead
AV1010ra_tempReturn Air Temperature°FRead
AV1011space_rhSpace Relative Humidity%rhRead
AV1012oaqOutdoor Air Quality CO2 (ppm)ppmRead
AV1032spt_tempSpace Temperature°FRead
AV1901system_oatSystem Outdoor Air Temperature (default -999)°FWrite
AV1902system_sptSystem Space Temperature (default -999)°FWrite
AV1903system_iaqSystem Space AQ (default -999)ppmWrite
AV1904system_rhSystem Space RH (default -999)%rhWrite
AV1908system_oaqSystem Outdoor AQ (default -999)ppmWrite
AV1920system_ratSystem Return Air Temperature (default -999)°FWrite
AV2003heat_runActive Heat StagesRead
AV2014sfan_rntmSupply Fan RuntimehrRead
AV2015filter_rntmFilter RuntimehrRead
AV2016ovrde_timeOverride Time RemainingminRead
AV2017comp1_rntmCompressor 1 RuntimehrRead
AV2018comp2_rntmCompressor 2 RuntimehrRead
AV2019filter_service_hrsFilter Service Alarm Timer (default 600)hrWrite
AV2020et_comp_runActive Cooling StagesRead
AV2022econ_outputEconomizer Output%OpenRead
AV2027vfd_outputSupply Fan VFD%Read
AVmin2028static_pressStatic Pressurein H2ORead
AV2029heat1_rntmHeat 1 RuntimehrRead
AV2030heat2_rntmHeat 2 RuntimehrRead
AV2031saspSupply Air Setpoint°FRead
AV2034htg_cntl_ptHeating Control Setpoint°FRead
AV2035ctrl_tempControlling Temperature°FRead
AV2608link_satAir Source Supply Air Temp°FRead
AV2609link_ahu_oatAir Source Outdoor Air Temp°FRead
AV2610link_spAir Source Static Pressurein H2ORead
AVmin3001occ_cl_stptSetpoint - occupied cooling°FWrite
AVmin3002occ_ht_stptSetpoint - occupied heating°FWrite
AV3003unocc_cl_stptSetpoint - unoccupied cooling°FWrite
AV3004unocc_ht_stptSetpoint - unoccupied heating°FWrite
AV3005eff_cl_stptEffective Cool Setpoint°FRead
AV3006eff_ht_stptEffective Heat Setpoint°FRead
AV3010pexh_stptPower Exhaust Setpoint (default 50)%OpenWrite
AV3011occ_dehum_stptOcc Relative Humidity Setpoint (default 60)%rhWrite
AV3013iaq_stpt_maxDCV Max Ctrl Setpoint (default 1100)ppmWrite
AV3026max_vfd_spdMax VFD Output (default 100)%Write
AV3027min_vfd_spdMin VFD Output (default 25)%Write
AVmin3029sat_cl_stptSupply Air Setpoint (default 53)°FWrite
AVmin3030sa_static_stptStatic Pressure Setpoint (default 0.5)in H2OWrite
AV3031sa_static_stpt_valueCurrent Static Pressure Setpointin H2ORead
AV3032tempering_stptSA Tempering Setpoint (default 55)°FWrite
AV9002oat_cl_lockoutCooling Lockout Temperature (default 45)°FWrite
AV9003oat_ht_lockoutHeating Lockout Temperature (default 65)°FWrite
AV9005econ_minVent Dmpr Pos / DCV Min Pos (default 20)%OpenWrite
AV9006cool_demand_levelSystem Cooling Demand LevelRead
AV9007start_delayPower Fail Restart Delay (default 5)secondsWrite
AV9008oat_ec_lockoutEconomizer High OAT Lockout Temp (default 75)°FWrite
AV9011iaq_dpr_maxDCV Max Vent Damper Pos (default 50)%OpenWrite
AV9024fan_delay_offFan Off Delay (default 90)secondsWrite
AV9030econ_min_2Low Fan Econ Min Pos (default 33)%OpenWrite
AV9036heat_demand_levelSystem Heating Demand LevelRead
AV9040sat_cl_stpt_reset_maxReset Maximum Limit (default 10)°^FWrite
AV9041sat_cl_stpt_resetReset Ratio (default 3)Write
AV80001mstr_oa_tempSystem OAT Master°FRead
AV81001econ_testEconomizer Test (default 0)%OpenWrite
AV81002vfd_spd_testVFD Speed Test (default 0)%Write
AV83003sat_cl_minMinimum Cooling SAT (default 45)°FWrite
AV83004sat_ht_maxMaximum Heating SAT (default 120)°FWrite
AV83005sfan_service_hrsSupply Fan Service Alarm Timer (default 0)hrWrite
AV83006comp1_service_hrsCompressor 1 Service Alarm Timer (default 0)hrWrite
AV83007comp2_service_hrsCompressor 2 Service Alarm Timer (default 0)hrWrite
AV83008heat1_service_hrsHeat 1 Service Alarm Timer (default 0)hrWrite
AV83009heat2_service_hrsHeat 2 Service Alarm Timer (default 0)hrWrite
AV90000ppoPassword Protected Output Variable (default 0)Write
AV91001ao1_fac_testFactory Test Analog 1 Control (default 0)%Write
AV91002ao2_fac_testFactory Test Analog 2 Control (default 0)%Write
BV1002enthalpy_statusEnthalpy StatusRead
BV1003sfan_statusSupply Fan StatusRead
BV1004filter_statusFilter StatusRead
BV1005firedown_statusFire Shutdown StatusRead
BV1006humstat_statusHumidistat Input StatusRead
BV1007occ_contact_statusOccupancy ContactRead
BV1008comp_statusCompressor Safety StatusRead
BV1009safety_statusSafety Chain FeedbackRead
BV1010door_contact_statusDoor Contact StatusRead
BV1022igcovr_statusIGC OverrideRead
BV1025rh_enableSA Reset Humidity Override (default Inactive (0))Write
BV1027dcv_enableDCV Control (default Inactive (0))Write
BV1901oaeEnthalpy (BACnet) (default Active (1))Write
BV1908hsl_resetReset High Static Trip (default Inactive (0))Write
BVmin2001sfanSupply Fan Relay StateRead
BV2002heat_2Heat Stage 2 Relay StateRead
BV2003heat_1Heat Stage 1 Relay StateRead
BV2004comp_2Compressor 2 Relay StateRead
BV2005comp_1Compressor 1 Relay StateRead
BV2007comp_3Compressor 3 Relay StateRead
BV2008occ_statusOccupancy StatusRead
BV2010pexhPower Exhaust Relay StateRead
BV2011shutdown_statusSystem is shut downRead
BV2012ht_interlockHeat Interlock Relay StateRead
BV2031occ_heatOccupied Heating (default Inactive (0))Write
BV7001spt_failSpace Temp SensorRead
BV7003loc_oat_sensor_failLocal OAT SensorRead
BV7004sat_alarmSupply Air TemperatureRead
BV7005iaq_alarmIndoor Air QualityRead
BV7006oaq_failOutdoor Air Quality SensorRead
BV7007fire_alarmFire / Smoke ShutdownRead
BV7008sfan_fail_alarmSupply Fan FailureRead
BV7009sfan_hand_alarmSupply Fan in HandRead
BV7010sfan_rntm_alarmSupply Fan RuntimeRead
BV7013comp_alarmCompressor StatusRead
BV7014comp1_rntm_alarmCompressor 1 RuntimeRead
BV7015comp2_rntm_alarmCompressor 2 RuntimeRead
BV7017filter_alarmFilterRead
BV7018sprh_hi_alarmSpace Relative HumidityRead
BV7020loc_sat_sensor_failSupply Air Temp SensorRead
BV7022sprh_sensor_failSpace Relative Humidity SensorRead
BVmin7024safety_alarmSafety ChainRead
BV7025di_cfg_alarmSwitch ConfigurationRead
BV7026ai_cfg_alarmAnalog Input ConfigurationRead
BV7029oat_failOutdoor Air Temp SensorRead
BV7030air_linkage_failAirside LinkageRead
BV7035rat_alarmReturn Air TemperatureRead
BV7039iaq_sensor_failIndoor Air Quality SensorRead
BV7050igc_alarmGas ValveRead
BV7052rat_failReturn Air Temp SensorRead
BV7054econ_oprEconomizer OperationRead
BV7055zs_config_failZS Sensor ConfigurationRead
BV7060sp_alarmHPCO ShutdownRead
BV7061sp_failStatic Pressure SensorRead
BV7062heat1_rntm_alarmHeat 1 RuntimeRead
BV7063heat2_rntm_alarmHeat 2 RuntimeRead
BV7067ctrl_temp_failCtrl Temp Sensor FailureRead
BV7510sfan_rntm_clrReset Supply Fan Runtime Alarm (default Inactive (0))Write
BV7514comp1_rntm_clrReset Comp 1 Runtime Alarm (default Inactive (0))Write
BV7515comp2_rntm_clrReset Comp 2 Runtime Alarm (default Inactive (0))Write
BV7517filter_rntm_clrReset Filter Alarm (default Inactive (0))Write
BV7518heat1_rntm_clrReset Heat 1 Runtime Alarm (default Inactive (0))Write
BV7519heat2_rntm_clrReset Heat 2 Runtime Alarm (default Inactive (0))Write
BV9001shutdownShutdown (default Inactive (0))Write
BV9002occ_exhContinuous Occupied Exhaust (default Inactive (0))Write
BV9003calc_limit_resetReset Calculated Max Heat Limit (default Inactive (0))Write
BV9004sa_reset_enSupply Air Temp Reset (default Inactive (0))Write
BV80001ntfc_enaUnocc Free Cool (default Inactive (0))Write
BV81000test_enableService Test (default Inactive (0))Write
BV81002heat2_testHeat 2Test (default Inactive (0))Write
BV81003heat1_testHeat 1Test (default Inactive (0))Write
BV81004comp2_testCompressor 2 Test (default Inactive (0))Write
BV81005comp1_testCompressor 1 Test (default Inactive (0))Write
BV81006hir_testHeat Interlock Relay Test (default Inactive (0))Write
BV81008pexh_testPower Exhaust Test (default Inactive (0))Write
BV83016sa_tempering_enSA Tempering (default Inactive (0))Write
BV91001relay1_fac_testFactory Test Relay 1 Control (default Inactive (0))Write
BV91002relay2_fac_testFactory Test Relay 2 Control (default Inactive (0))Write
BV91003relay3_fac_testFactory Test Relay 3 Control (default Inactive (0))Write
BV91004relay4_fac_testFactory Test Relay 4 Control (default Inactive (0))Write
BV91005relay5_fac_testFactory Test Relay 5 Control (default Inactive (0))Write
BV91006relay6_fac_testFactory Test Relay 6 Control (default Inactive (0))Write
BV91007relay7_fac_testFactory Test Relay 7 Control (default Inactive (0))Write
BV91008relay8_fac_testFactory Test Relay 8 Control (default Inactive (0))Write
BV99001econ_existEconomizer Exists (required) (default Active (1))Write
BV99002heat_typeHeat Type (default Active (1))Write
MVmin1001keypad_ovrdeBAS On / Off (default 1)Write1=Inactive; 2=Occupied; 3=Unoccupied
MV1002occ_sourceOccupancy SourceRead
MV2001mode_statusEquipment StatusRead1=Disabled; 2=Test; 3=Run
MVmin2002run_statusSystem ModeRead1=Off; 2=Fan Only; 3=Economizer Cooling; 4=Cooling; 5=Heating; 6=Dehumidification; 7=Test; 8=Shutdow; 9=Unocc Free Cooling; 10=Fire Shutdown; 11=IAQ Override; 12=Pre-Occ Purge; 13=IGC Override
MV2005link_ahu_modeAir Source ModeRead1=Off; 2=Warmup; 3=Heating; 4=Cooling; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent
MV2011econ_fdd_resultEconomizerRead1=Normal; 2=Failed to Fully Open; 3=Failed to Open; 4=Failed to Close; 5=Stuck Open
MV2013ctrl_temp_srcCtrl Temp SourceRead1=Sensor Failure; 2=Space; 3=Return Air; 4=Linkage Zone; 5=Locked Value
MV2014spt_sourceSpace Temp SourceRead
MV2015rat_srcRAT SourceRead
MV2016sat_reset_sourceSAT Reset SourceRead
MV7068sp_proof_almSP ProofRead
MV9033sp_reset_dmd_lvlSP Reset Demand Level (default 1)Write
MV81002ai2_functionInput 2 Function (default 1)Write
MV81003di3_functionInput 3 Function (default 1)Write
MV81005di5_functionInput 5 Function (default 2)Write
MV81008di8_functionInput 8 Function (default 2)Write
MV81009di9_functionInput 9 Function (default 1)Write
MV81013di3_typeInput 3 Switch Configuration (default 1)Write
MV81015di5_typeInput 5 Switch Configuration (default 1)Write
MV81018di8_typeInput 8 Switch Configuration (default 1)Write
MV81019di9_typeInput 9 Switch Configuration (default 1)Write
MV91004heat_stagesNumber Of Heat Stages (default 2)Write
Object ID lookup: Carrier 48/50LC B 07-26 VAV Rooftop point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)

How many BACnet points does the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) have?

This list has 191 BACnet objects: 6 analog inputs, 72 analog values, 5 binary inputs, 86 binary values, 22 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet points are writable?

87 of the 191 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open) BACnet documentation?

The source is 48/50LCB07-26 with VAV-RTU Open Controller, Controls, Start-Up, Operation and Troubleshooting (Appendix D: BACnet Points List) (48-50LCB-7-26-04T), revision 2022-05, published free by Carrier at https://brandportal.carrier.com/asset/1d59de26-3b17-4555-8d1e-6f6126a95717/48-50LCB-7-26-04T.pdf.

What are the minimum BACnet points to integrate the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?

Start with MV 1001 keypad_ovrde (BAS occupancy: 1=Inactive, 2=Occupied, 3=Unoccupied); AV 3001 occ_cl_stpt (Occupied cooling setpoint); AV 3002 occ_ht_stpt (Occupied heating setpoint); AV 3029 sat_cl_stpt (Supply air setpoint for cooling (default 53 °F)); AV 3030 sa_static_stpt (Duct static pressure setpoint); MV 2002 run_status (Current system mode); BV 2001 sfan (Supply fan relay on/off); AV 1008 sa_temp (Supply air temperature); AV 2028 static_press (Duct static pressure); BV 7024 safety_alarm (Safety chain alarm).

How do I enable BMS control of the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?

BAS On / Off (keypad_ovrde, MV 1001) is the network occupancy input for third-party systems: 1 = Inactive (default), 2 = Occupied (occupied heating and cooling setpoints apply), 3 = Unoccupied (unoccupied setpoints apply). A BACnet schedule from i-Vu or the remote occupancy input can also set occupancy. Shutdown (BV 9001) is a writable shutdown point.

Can the BMS supply sensor values to the Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?

The System points take network values: System Space Temperature (AV 1902), System Space RH (AV 1904), System Space AQ (AV 1903), System Outdoor Air Temperature (AV 1901), System Outdoor AQ (AV 1908) and System Return Air Temperature (AV 1920). The table prints -999 as their default value. The guide gives no refresh time.

How do I check these points on the real 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: 48/50LCB07-26 with VAV-RTU Open Controller, Controls, Start-Up, Operation and Troubleshooting (Appendix D: BACnet Points List) · 48-50LCB-7-26-04T · rev. 2022-05. Object names, instances and units are reproduced as published; descriptions are our own.