Dedicated outdoor air unit (DOAS) controller · BACnet points list
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) BACnet points list
Updated 4 November 2026
62H dedicated outdoor air units with Revision K controls use an Automated Logic LS-1628u controller that speaks BACnet MS/TP on its RS-485 ports and BACnet IP on its Gig-E port. The Table C mapping lists 251 AVs, BVs and two MSVs: occupancy and BAS heartbeat points, supply air, zone and dehumidification setpoints, sensor readings, digital compressor output, compressor, fan, wheel and damper status, PID override points and many individual alarms.
This page lists 251 BACnet objects for the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) — 85 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 62H Dedicated Outdoor Air Unit (Rev. K controls)
- Equipment
- Dedicated outdoor air unit (DOAS) controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 251 (85 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Revision K controls
- Default device instance
- 1602
- Also known as
- 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
The 62H uses an Automated Logic LS-1628u controller (third-party to i-Vu). Set Occupancy Control Options to BAS, then command occupancy with BAS Manual Occ Control and toggle Field BAS Comm. Status faster than the BAS lost delay. Write the supply air setpoints the unit discharges to, read operating mode, occupancy, SAT and the alarm status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 101 | occ_en | BAS occupied/unoccupied command | Write |
| MV 101 | occ_ctrl_opts | Must be BAS for BAS occupancy control | Write |
| AV 313 | clg_sat_sp_o | Occupied cooling supply air setpoint | Write |
| AV 354 | htg_sat_sp_o | Occupied heating supply air setpoint | Write |
| BV 110 | bas_comm_status | Heartbeat: toggle before the BAS lost delay ends | Write |
| BV 900 | alarm_reset | Alarm reset | Write |
| AV 112 | op_mode | Operating mode code (Appendix B) | Read |
| BV 105 | occ_status | Occupied/unoccupied status | Read |
| AV 235 | sat_stat | Supply air temperature | Read |
| BV 851 | alarm_status | Unit alarm status | Read |
Enable & remote start
Occupancy Control (Occupancy Control Options, MSV 101) chooses BAS control, local schedule, 24/7 or CO2. With BAS control, BAS Manual Occ Control (BV 101) puts the unit in occupied or unoccupied mode. Enable Unit Operation (Tech Set Up) must be on. Emergency Shutdown in Tech Set Up disables the unit; Emerg. Shutdown Enable (BV 821) is writable over BACnet.
Heartbeat & communication loss
Field BAS Comm. Status (BV 110) must change state before the BAS Comm. Lost Delay (AV 103, default 60 s) runs out, or BAS Communication Lost (BV 107) and the BAS LOST alarm (BV 899) are set. Enable BAS Monitor Schedule (BV 106) lets the unit fall back to its local schedule on a loss. The manual does not describe the OAT/OARH loss action beyond its status point (BV 1102).
Sensors & values from the BMS
The BAS can write zone temperature (ZAT From BAS, AV 208), zone RH (AV 211), CO2 (AV 213), outdoor temperature (AV 1104) and outdoor RH (AV 1106). BAS outdoor values are monitored when Enable BAS Mon OAT/OARH (BV 1100) is on; Local OAT/OARH Sensor Enabled (BV 1115) selects the unit's own sensors.
Network setup
- BACnet device instance defaults to 1602; with Auto Generate Device ID = Yes, the rotary switch address is added to 1602. Set it on the Equipment Touch (BAS Set Up > Communication).
- MS/TP on Port S1 (Port S1 rotary switch = 1) or Port S2; MAC 0-127 on the three rotary switches; baud default 76.8k or autobaud.
- BACnet IP or BACnet Ethernet on the Gig-E port; IP by DHCP, custom static, or default 192.168.168.x from the rotary switches.
- Set the port's End of Net? switch to Yes at either end of an MS/TP segment.
- Service port web pages at http://169.254.1.1 (laptop 169.254.1.2-7, mask 255.255.255.248).
Watch out for
- BAS Manual Occ Control only works when Occupancy Control is set to BAS control.
- The PID Output Override and Override Lock points (SF, EF, OADA, heat, HGRH) fix outputs for CAV setups; don't write them for normal control.
- Operating mode and condition are integer AVs; see the Appendix B code lists in the notes.
- To use the unit with Carrier i-Vu Open it needs an i-Vu Link and i-Vu Open Plus.
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 900 | alarm_reset | Alarm Reset | Write | ||
| BVmin | 851 | alarm_status | Alarm Status | Read | ||
| BV | 539 | comp_dis | Allow Compressor Disable | Write | ||
| BV | 202 | zat_sp_adj_en | Allow Zone Set Point Adjust (default plus or minus 5°F) | Write | ||
| BV | 580 | ahtg_en | Aux. Htg. Enable | Read | ||
| BV | 1102 | bas_com_lost_on | BAS Com Lost OAT/ OARH Status | Read | ||
| AV | 103 | bas_comm_lost_delay | BAS Comm. Lost Delay (default 60 seconds) | Write | ||
| BV | 107 | bas_comm_lost | BAS Communication Lost | Read | ||
| BV | 899 | bas_comm_lost_alarm | BAS LOST | Read | ||
| BVmin | 101 | occ_en | BAS Manual Occ Control | Write | ||
| BV | 863 | c1_alarm | C1 ALARM | Read | ||
| BV | 243 | c1_cmd | C1 Command | Read | ||
| BV | 555 | c1_freeze_stat | C1 Freeze Status | Read | ||
| BV | 873 | c1_hand_alarm | C1 HAND | Read | ||
| BV | 864 | c1_stop_alarm | C1 STOP | Read | ||
| BV | 847 | c1c2_stop_disables_unit | C1/C2 Stop Disables Unit | Write | ||
| AV | 6402 | dig1_pct_c2_sp | C1DIG Percentage Before C2 SP (default 95%) | Write | ||
| BV | 877 | c2_alarm | C2 ALARM | Read | ||
| BV | 244 | c2_cmd | C2 Command | Read | ||
| BV | 556 | c2_freeze_stat | C2 Freeze Status | Read | ||
| BV | 887 | c2_hand_alarm | C2 HAND | Read | ||
| BV | 878 | c2_stop_alarm | C2 STOP | Read | ||
| BV | 893 | cfi_alarm | CFI ALARM | Read | ||
| BV | 232 | cfi_stat | CFI Status | Read | ||
| AV | 307 | clg1_en_sp | Clg #1 Enable SP (default varies) | Write | ||
| AV | 327 | clg2_en_sp | Clg #2 Enable SP (default varies) | Write | ||
| AV | 375 | clg_mod_sp_o | Clg Modulation SP Occ (default 55°F) | Write | ||
| AVmin | 313 | clg_sat_sp_o | Clg SAT SP Occ (default varies) | Write | ||
| AV | 314 | clg_sat_sp_u | Clg SAT SP Unocc (default varies) | Write | ||
| AV | 217 | co2_db | CO2 Dead Band (default 200 ppm) | Write | ||
| BV | 854 | co2_failure | CO2 FAIL | Read | ||
| AV | 213 | co2_bas | CO2 From BAS | Write | ||
| BV | 203 | co2_occ_stat | CO2 Occupancy Status | Read | ||
| AV | 215 | co2_sp1 | CO2 Set Point #1 (default 300ppm) | Write | ||
| AV | 216 | co2_sp2 | CO2 Set Point #2 (default 1200ppm) | Write | ||
| AV | 214 | co2_stat | CO2 Status | Read | ||
| BV | 224 | cc1_cs_stat | Comp #1 CS Status | Read | ||
| BV | 227 | cc2_cs_stat | Comp #2 CS Status | Read | ||
| AV | 541 | comp_dis_sp | Compressor Disable SP (default 32°F) | Write | ||
| BV | 540 | comp_dis_oat | Compressor Disabled by OAT | Read | ||
| BV | 233 | cos_stat | Condensate Overflow Switch | Read | ||
| BV | 551 | clg1_en | Cooling #1 Enable | Read | ||
| BV | 552 | clg2_en | Cooling #2 Enable | Read | ||
| BV | 894 | cos_alarm | COS ALARM | Read | ||
| BV | 640 | cwv_action | CWV Action (default N.O.) | Write | ||
| AV | 288 | cwv_pct | CWV Percentage | Read | ||
| BV | 565 | dh1_en | Dehumid. #1 Enable | Read | ||
| BV | 566 | dh2_en | Dehumid. #2 Enable | Read | ||
| AV | 346 | dh_mod_sp | DH Mod. SP | Write | ||
| AV | 344 | dh_llim | DH Mode Low Limit (default 60°F) | Write | ||
| AV | 341 | dh_sat_sp_o | DH SAT SP Occ (default 70°F) | Write | ||
| AV | 342 | dh_sat_sp_u | DH SAT SP Unocc (default 75°) | Write | ||
| AV | 337 | dh_sp_o | DH SP Occ (default 55) | Write | ||
| AV | 338 | dh_sp_u | DH SP Unocc (default 65) | Write | ||
| AV | 345 | dh1_stat | DH1 Sensor Status | Read | ||
| AV | 349 | dh2_sens_stat | DH2 Sensor Status | Read | ||
| AV | 647 | dig1_min | DIG1 Minimum Output (default 20%) | Write | ||
| AV | 6401 | dig_c1_pct | Digital Compressor #1 Percent | Read | ||
| AV | 6501 | dig_c2_pct | Digital Compressor #2 Percent | Read | ||
| BV | 256 | dr1_stat | DR1 Status | Read | ||
| BV | 257 | dr2_stat | DR2 Status | Read | ||
| AV | 245 | dx_lat2_stat | DX LAT #2 Status | Read | ||
| AV | 243 | dx_lat_stat | DX LAT Status | Read | ||
| BV | 843 | dx_lat_failure | DXLAT FAIL | Read | ||
| BV | 844 | dx_lat2_failure | DXLAT2 FAIL | Read | ||
| BV | 831 | ecat_failure | ECAT FAIL | Read | ||
| AV | 219 | ecat_stat | ECAT Status | Read | ||
| BV | 962 | econ_not_fdd | ECON NOT | Read | ||
| AV | 600 | econ_mat_sp | Econ. MAT SP (default 65°F) | Write | ||
| AV | 549 | econ_oae_sp | Econ. OAE SP (default 22btu/lb) | Write | ||
| AV | 550 | econ_oat_usp | Econ. OAT Upper SP (default 59°F) | Write | ||
| BV | 832 | ecrh_failure | ECRH FAIL | Read | ||
| AV | 221 | ecrh_stat | ECRH Status | Read | ||
| BV | 952 | ecw_alarm | ECW ALARM | Read | ||
| BV | 247 | ecw_cmd | ECW Command | Read | ||
| BV | 222 | ecw_cs_stat | ECW CS Status | Read | ||
| BV | 514 | ecw_def_on | ECW Defrost ON | Read | ||
| BV | 513 | ecw_en | ECW Enable (default 25°F) | Read | ||
| BV | 953 | ecw_hand_alarm | ECW HAND | Read | ||
| AV | 284 | ecwvfd_freq | ECW VFD Frequency | Read | ||
| BV | 860 | ef_alarm | EF ALARM | Read | ||
| AV | 305 | ef_ams_sp | EF AMS SP (default 2000cfm) | Write | ||
| AV | 302 | ef_dpt_sp | EF DPT SP (default 1 in. of H2O) | Write | ||
| BV | 861 | ef_hand_alarm | EF HAND | Read | ||
| AV | 287 | efmod_pct | EF Modulation | Read | ||
| AV | 259 | ef_oa_ams_stat | EF OA AMS Status | Read | ||
| AV | 639 | ef_pid_ovrd | EF PID Output Override | Write | ||
| BV | 631 | ef_pid_ovrd_lock | EF PID Output Override Lock | Write | ||
| BV | 221 | ef_aps_stat | EF-APS or CS Status | Read | ||
| BV | 895 | em_shtdn_alarm | EM SHTDN | Read | ||
| BV | 579 | ehtg_en | Em. Htg. Enable | Read | ||
| BV | 821 | emsd_en | Emerg. Shutdown Enable | Write | ||
| BV | 822 | emsd_status | Emergency Shutdown Status | Read | ||
| BV | 234 | emrsd_stat | EMR/EMSD Status | Read | ||
| BV | 1100 | en_bas_mon_oa | Enable BAS Mon OAT/ OARH | Write | ||
| BV | 106 | en_bas_mon | Enable BAS Monitor Schedule | Write | ||
| BV | 960 | fdd_alarm_en | Enable FDD Alarms | Write | ||
| AV | 262 | eca_dewpoint | Entering Coil Air Dew Point | Read | ||
| AV | 263 | ec_enthalpy | Entering coil Air Enthalpy | Read | ||
| BV | 964 | excess_oa_fdd | EXCESS OA | Read | ||
| BVmin | 110 | bas_comm_status | Field BAS Comm. Status | Write | ||
| BV | 871 | fp1_alarm | FP1 ALARM | Read | ||
| BV | 872 | fp1_stop_alarm | FP1 STOP | Read | ||
| BV | 885 | fp2_alarm | FP2 ALARM | Read | ||
| BV | 886 | fp2_stop_alarm | FP2 STOP | Read | ||
| AV | 323 | fp_lsp | Freeze Protection LSP (default 38°F) | Write | ||
| AV | 322 | fp_msp | Freeze Protection MSP (default 45°F) | Write | ||
| AV | 321 | fp_usp | Freeze Protection USP (default 55°F) | Write | ||
| BV | 231 | frz_stat | FRZ Status | Read | ||
| BV | 830 | fzt_alarm | FZT ALARM | Read | ||
| AV | 677 | htg_mod_min | Heat Mod. Minimum Output (default 0%) | Write | ||
| AV | 286 | htg_mod | Heat Modulation | Read | ||
| AV | 678 | htg_pid_ovrd | Heat PID Output Override | Write | ||
| BV | 671 | htg_pid_ovrd_lock | Heat PID Output Override Lock | Write | ||
| BV | 571 | hp1_en | Heat Pump #1 Enable | Read | ||
| BV | 572 | hp2_en | Heat Pump #2 Enable | Read | ||
| BV | 563 | htg_rh_en | Heating Supports Reheat | Write | ||
| AV | 668 | hgrh_mod_min | HGRH Mod. Minimum Output (default 0%) | Write | ||
| AV | 285 | hgrh_mod | HGRH Modulation | Read | ||
| AV | 669 | hgrh_pid_ovrd | HGRH PID Output Override | Write | ||
| BV | 661 | hgrh_pid_ovrd_lock | HGRH PID Output Override Lock | Write | ||
| BV | 826 | high_co2_alarm | HIGH CO2 | Read | ||
| AV | 804 | high_sfdpt_sp | High Supply DPT SP (default 5 in. of H2O) | Write | ||
| BV | 226 | hps1_stat | HPS #1 Status | Read | ||
| BV | 229 | hps2_stat | HPS #2 Status | Read | ||
| BV | 867 | hps1_alarm | HPS1 ALARM | Read | ||
| BV | 868 | hps1_stop_alarm | HPS1 STOP | Read | ||
| BV | 881 | hps2_alarm | HPS2 ALARM | Read | ||
| BV | 882 | hps2_stop_alarm | HPS2 STOP | Read | ||
| BV | 892 | hsat_alarm | HSAT ALARM | Read | ||
| BV | 858 | hsdp_alarm | HSDP ALARM | Read | ||
| BV | 859 | hsdp_stop_alarm | HSDP STOP | Read | ||
| BV | 891 | heat_failure | HT FAIL | Read | ||
| AV | 351 | htg_en_sp | Htg Enable SP (default 55°F) | Write | ||
| AV | 360 | htg_hlim | Htg Mode High Limit Set Point (default 60°F) | Write | ||
| AVmin | 354 | htg_sat_sp_o | Htg SAT SP Occ (default 70°F or 90°F Recirc) | Write | ||
| AV | 355 | htg_sat_sp_u | Htg SAT SP Unocc (default 90°F) | Write | ||
| AV | 253 | zn_ef_dpt11_stat | IN0/11_ZN/EFdpt Status | Read | ||
| BV | 1115 | local_oa_sens_en | Local OAT/OARH Sensor Enabled | Write | ||
| BV | 225 | lps1_stat | LPS #1 Status | Read | ||
| BV | 228 | lps2_stat | LPS #2 Status | Read | ||
| BV | 869 | lps1_alarm | LPS1 ALARM | Read | ||
| BV | 870 | lps1_stop_alarm | LPS1 STOP | Read | ||
| BV | 883 | lps2_alarm | LPS2 ALARM | Read | ||
| BV | 884 | lps2_stop_alarm | LPS2 STOP | Read | ||
| BV | 898 | low_sat_alarm | LSAT ALARM | Read | ||
| BV | 828 | marh_failure | MARH FAIL | Read | ||
| AV | 224 | marh_stat | MA-RH Status | Read | ||
| BV | 827 | mat_failure | MAT FAIL | Read | ||
| AV | 223 | mat_stat | MAT Status | Read | ||
| AV | 264 | ma_dewpoint | Mixed Air Dew Point | Read | ||
| AV | 265 | ma_enthalpy | Mixed Air Enthalpy | Read | ||
| BV | 219 | nsb_on | Night Setback Mode ON | Read | ||
| BV | 961 | not_econ_fdd | NOT ECON | Read | ||
| AV | 306 | oa_ams_sp | OA AMS SP (default 800 cfm) | Write | ||
| BV | 242 | oada_en | OA Damper Enable | Read | ||
| BV | 950 | oada_alarm | OADA ALARM | Read | ||
| BV | 951 | oada_hand_alarm | OADA HAND | Read | ||
| AV | 607 | oada_min_pos_cmd | OADA Minimum Position | Write | ||
| AV | 609 | oada_pid_ovrd | OADA PID Output Override | Write | ||
| BV | 601 | oada_pid_ovrd_lock | OADA PID Output Override Lock | Write | ||
| AV | 204 | oada_pos | OADA Position | Read | ||
| BV | 220 | oada_stat | OADA Status | Read | ||
| BV | 836 | oarh_failure | OARH FAIL | Read | ||
| AV | 1106 | bas_oarh | OARH from BAS | Write | ||
| AV | 229 | oarh_stat | OA-RH Status | Read | ||
| BV | 835 | oat_failure | OAT FAIL | Read | ||
| AV | 1104 | bas_oat | OAT from BAS | Write | ||
| AV | 227 | oat_stat | OAT Status | Read | ||
| MVmin | 101 | occ_ctrl_opts | Occupancy Control Options: local, BAS, 24/7 or CO2 | Write | ||
| BVmin | 105 | occ_status | Occupancy Status | Read | ||
| AV | 319 | clg_llim | Occupied Cooling Mode Low Limit (default 55°F) | Write | ||
| BV | 1120 | od_cmd | OD Command | Read | ||
| AV | 111 | op_cond | Operating Condition (code, see notes) | Read | ||
| AVmin | 112 | op_mode | Operating Mode (code, see notes) | Read | ||
| BV | 902 | opt_start_on | Optimal Start On | Read | ||
| AV | 266 | oa_dewpoint | Outside Air Dew Point | Read | ||
| AV | 267 | oa_enthalpy | Outside Air Enthalpy | Read | ||
| BV | 963 | rada_not_mod_fdd | RADA NOT | Read | ||
| AV | 601 | rada_pos | RADA Position | Read | ||
| AV | 283 | rada_stat | RADA Status | Read | ||
| BV | 834 | rarh_failure | RARH FAIL | Read | ||
| AV | 226 | rarh_stat | RA-RH Status | Read | ||
| BV | 833 | rat_failure | RAT FAIL | Read | ||
| AV | 225 | rat_stat | RAT Status | Read | ||
| BV | 503 | rada_cmd | Return Air Damper Status | Read | ||
| AV | 268 | ra_dewpoint | Return Air Dew Point | Read | ||
| AV | 269 | ra_enthalpy | Return Air Enthalpy | Read | ||
| BV | 564 | rh_cmd | RH CMD | Read | ||
| BV | 561 | rh_clg_mode | RH in Cooling | Write | ||
| BV | 550 | rv_cmd | RV CMD | Read | ||
| BV | 840 | sarh_failure | SARH FAIL | Read | ||
| AV | 237 | sarh_stat | SARH Status | Read | ||
| BV | 839 | sat_failure | SAT FAIL | Read | ||
| AV | 361 | sat_heat_fail_sp | SAT Heat Fail SP (default 50°F) | Write | ||
| AV | 362 | sat_high_limit_sp | SAT High Limit SP (default 120°F) | Write | ||
| AV | 808 | sat_low_limit_sp | SAT Low Limit SP (default 40°F) | Write | ||
| AV | 326 | sat_max_reset | SAT Maximum Reset (default 15) | Write | ||
| AV | 325 | sat_ratio | SAT Ratio (default 3) | Write | ||
| AVmin | 235 | sat_stat | SAT Status | Read | ||
| BV | 1110 | sc_zat_disa | SC ZAT DISA | Write | ||
| BV | 896 | sd_alarm | SD ALARM | Read | ||
| BV | 235 | sd_stat | SD Status | Read | ||
| BV | 855 | sf_alarm | SF ALARM | Read | ||
| AV | 304 | sf_ams_sp | SF AMS SP (default 3900 cfm) | Write | ||
| AV | 261 | sf_ams_stat | SF AMS Status | Read | ||
| BV | 241 | sf_cmd | SF Command | Read | ||
| AV | 301 | sf_dpt_sp | SF DPT SP (default 1 in. of H2O) | Write | ||
| AV | 255 | sf_dpt_stat | SF DPT Status (default 5 in. of H2O) | Read | ||
| BV | 856 | sf_hand_alarm | SF HAND | Read | ||
| AV | 630 | sf_clg_min_out | SF Mod. CLG Min. Output (default 50%) | Write | ||
| AV | 629 | sf_hp_min_out | SF Mod. HP Min. Output (default 85%) | Write | ||
| AV | 282 | sfmod_pct | SF Modulation | Read | ||
| MV | 931 | sf_oper | SF Operation | Write | 1=Continuous/Demand, 2=Con/Con, 3=Dem/Dem | |
| AV | 628 | sf_pid_ovrd | SF PID Output Override (default 90%) | Write | ||
| BV | 621 | sf_pid_ovrd_lock | SF PID Output Override Lock | Write | ||
| BV | 223 | sf_aps_stat | SF-APS or CS Status | Read | ||
| AV | 627 | sf_min_out | SFMinimum Output | Read | ||
| AV | 250 | slt_stat | SLT #1 Status | Read | ||
| AV | 251 | slt2_stat | SLT #2 Status | Read | ||
| BV | 845 | slt_failure | SLT FAIL | Read | ||
| BV | 846 | slt2_failure | SLT2 FAIL | Read | ||
| BV | 248 | sc_cmd | Sub-Cooling Command | Read | ||
| AV | 270 | sa_dewpoint | Supply Air Dew Point | Read | ||
| AV | 271 | sa_enthalpy | Supply Air Enthalpy | Read | ||
| BV | 819 | unit_stop | Unit Stop | Read | ||
| AV | 320 | clg_llim_u | Unoccupied Cooling Mode Low Limit | Write | ||
| BV | 240 | w1_cmd | W1 Command | Read | ||
| BV | 578 | w1_en | W1 Enable | Read | ||
| BV | 239 | w2_cmd | W2 Command | Read | ||
| BV | 837 | wexat_failure | WExAT FAIL | Read | ||
| AV | 238 | wexat_stat | WExAT Status | Read | ||
| BV | 838 | wexrh_failure | WExRH FAIL | Read | ||
| AV | 239 | wexrh_stat | WExRH Status | Read | ||
| BV | 829 | wfs_alarm | WFS ALARM | Read | ||
| BV | 230 | wfs_stat | WFS Status | Read | ||
| BV | 852 | zat_failure | ZAT FAIL | Read | ||
| AV | 208 | zat_bas | ZAT From BAS | Write | ||
| AV | 324 | zat_ratio | ZAT Ratio (default 1) | Write | ||
| AV | 209 | zat_stat | ZAT Status | Read | ||
| BV | 301 | rs_sat_en | ZAT/SAT Set Point Reset Enable | Write | ||
| AV | 303 | zn_dpt_sp | ZN DPT SP (default 0.020 in. of H2O) | Write | ||
| AV | 274 | za_dewpoint | Zone Air Dew Point | Read | ||
| AV | 275 | za_enthalpy | Zone Air Enthalpy | Read | ||
| AV | 200 | clg_zat_sp_o | Zone set point, occupied cooling (default 74°F) | Write | ||
| AV | 201 | htg_zat_sp_o | Zone set point, occupied heating (default 68°F) | Write | ||
| AV | 202 | clg_zat_sp_u | Zone set point, unoccupied cooling (default 80°F) | Write | ||
| AV | 203 | htg_zat_sp_u | Zone set point, unoccupied heating (default 60) | Write | ||
| BV | 853 | zrh_failure | ZRH FAIL | Read | ||
| AV | 211 | zrh_bas | Z-RH From BAS | Write | ||
| AV | 212 | zrh_stat | Z-RH Status | Read |
No points match these filters.
Object ID lookup: Carrier 62H Dedicated Outdoor Air Unit point IDs by name
BV900alarm_resetBV851alarm_statusBV539comp_disBV202zat_sp_adj_enBV580ahtg_enBV1102bas_com_lost_onAV103bas_comm_lost_delayBV107bas_comm_lostBV899bas_comm_lost_alarmBV101occ_enBV863c1_alarmBV243c1_cmdBV555c1_freeze_statBV873c1_hand_alarmBV864c1_stop_alarmBV847c1c2_stop_disables_unitAV6402dig1_pct_c2_spBV877c2_alarmBV244c2_cmdBV556c2_freeze_statBV887c2_hand_alarmBV878c2_stop_alarmBV893cfi_alarmBV232cfi_statAV307clg1_en_spAV327clg2_en_spAV375clg_mod_sp_oAV313clg_sat_sp_oAV314clg_sat_sp_uAV217co2_dbBV854co2_failureAV213co2_basBV203co2_occ_statAV215co2_sp1AV216co2_sp2AV214co2_statBV224cc1_cs_statBV227cc2_cs_statAV541comp_dis_spBV540comp_dis_oatBV233cos_statBV551clg1_enBV552clg2_enBV894cos_alarmBV640cwv_actionAV288cwv_pctBV565dh1_enBV566dh2_enAV346dh_mod_spAV344dh_llimAV341dh_sat_sp_oAV342dh_sat_sp_uAV337dh_sp_oAV338dh_sp_uAV345dh1_statAV349dh2_sens_statAV647dig1_minAV6401dig_c1_pctAV6501dig_c2_pctBV256dr1_statBV257dr2_statAV245dx_lat2_statAV243dx_lat_statBV843dx_lat_failureBV844dx_lat2_failureBV831ecat_failureAV219ecat_statBV962econ_not_fddAV600econ_mat_spAV549econ_oae_spAV550econ_oat_uspBV832ecrh_failureAV221ecrh_statBV952ecw_alarmBV247ecw_cmdBV222ecw_cs_statBV514ecw_def_onBV513ecw_enBV953ecw_hand_alarmAV284ecwvfd_freqBV860ef_alarmAV305ef_ams_spAV302ef_dpt_spBV861ef_hand_alarmAV287efmod_pctAV259ef_oa_ams_statAV639ef_pid_ovrdBV631ef_pid_ovrd_lockBV221ef_aps_statBV895em_shtdn_alarmBV579ehtg_enBV821emsd_enBV822emsd_statusBV234emrsd_statBV1100en_bas_mon_oaBV106en_bas_monBV960fdd_alarm_enAV262eca_dewpointAV263ec_enthalpyBV964excess_oa_fddBV110bas_comm_statusBV871fp1_alarmBV872fp1_stop_alarmBV885fp2_alarmBV886fp2_stop_alarmAV323fp_lspAV322fp_mspAV321fp_uspBV231frz_statBV830fzt_alarmAV677htg_mod_minAV286htg_modAV678htg_pid_ovrdBV671htg_pid_ovrd_lockBV571hp1_enBV572hp2_enBV563htg_rh_enAV668hgrh_mod_minAV285hgrh_modAV669hgrh_pid_ovrdBV661hgrh_pid_ovrd_lockBV826high_co2_alarmAV804high_sfdpt_spBV226hps1_statBV229hps2_statBV867hps1_alarmBV868hps1_stop_alarmBV881hps2_alarmBV882hps2_stop_alarmBV892hsat_alarmBV858hsdp_alarmBV859hsdp_stop_alarmBV891heat_failureAV351htg_en_spAV360htg_hlimAV354htg_sat_sp_oAV355htg_sat_sp_uAV253zn_ef_dpt11_statBV1115local_oa_sens_enBV225lps1_statBV228lps2_statBV869lps1_alarmBV870lps1_stop_alarmBV883lps2_alarmBV884lps2_stop_alarmBV898low_sat_alarmBV828marh_failureAV224marh_statBV827mat_failureAV223mat_statAV264ma_dewpointAV265ma_enthalpyBV219nsb_onBV961not_econ_fddAV306oa_ams_spBV242oada_enBV950oada_alarmBV951oada_hand_alarmAV607oada_min_pos_cmdAV609oada_pid_ovrdBV601oada_pid_ovrd_lockAV204oada_posBV220oada_statBV836oarh_failureAV1106bas_oarhAV229oarh_statBV835oat_failureAV1104bas_oatAV227oat_statMV101occ_ctrl_optsBV105occ_statusAV319clg_llimBV1120od_cmdAV111op_condAV112op_modeBV902opt_start_onAV266oa_dewpointAV267oa_enthalpyBV963rada_not_mod_fddAV601rada_posAV283rada_statBV834rarh_failureAV226rarh_statBV833rat_failureAV225rat_statBV503rada_cmdAV268ra_dewpointAV269ra_enthalpyBV564rh_cmdBV561rh_clg_modeBV550rv_cmdBV840sarh_failureAV237sarh_statBV839sat_failureAV361sat_heat_fail_spAV362sat_high_limit_spAV808sat_low_limit_spAV326sat_max_resetAV325sat_ratioAV235sat_statBV1110sc_zat_disaBV896sd_alarmBV235sd_statBV855sf_alarmAV304sf_ams_spAV261sf_ams_statBV241sf_cmdAV301sf_dpt_spAV255sf_dpt_statBV856sf_hand_alarmAV630sf_clg_min_outAV629sf_hp_min_outAV282sfmod_pctMV931sf_operAV628sf_pid_ovrdBV621sf_pid_ovrd_lockBV223sf_aps_statAV627sf_min_outAV250slt_statAV251slt2_statBV845slt_failureBV846slt2_failureBV248sc_cmdAV270sa_dewpointAV271sa_enthalpyBV819unit_stopAV320clg_llim_uBV240w1_cmdBV578w1_enBV239w2_cmdBV837wexat_failureAV238wexat_statBV838wexrh_failureAV239wexrh_statBV829wfs_alarmBV230wfs_statBV852zat_failureAV208zat_basAV324zat_ratioAV209zat_statBV301rs_sat_enAV303zn_dpt_spAV274za_dewpointAV275za_enthalpyAV200clg_zat_sp_oAV201htg_zat_sp_oAV202clg_zat_sp_uAV203htg_zat_sp_uBV853zrh_failureAV211zrh_basAV212zrh_stat
Integration notes
- The mapping table has no units column, so units are left blank; defaults quoted in the table's descriptions are added to the descriptions here.
- Appendix B Table D (operating modes): 0 SCHEDULE, 1 OA DAMPER, 2 FAN ONLY, 3 ECONOMIZER, 4 COOLING, 5 CLG and REHEAT, 6 DEHUMID, 7 HEATING, 8 HEAT PUMP, 9 AUX HEAT, 10 EMER HEAT, 11 DEFROST ON, 12 PURGE #1, 13 PURGE#2, 14 FDD ALARM, 15 SF FAIL, 16 SF HAND, 17 EF FAIL, 18 EF HAND, 19 C1 ALARM, 20 C1 STOP, 21 HPS1 ALARM, 22 APS2 STOP, 23 LPS1 ALARM, 24 LPS1 STOP, 25 FP1 ALARM, 26 FP1 STOP, 27 C1 HAND, 28 C2 ALARM, 29 C2 STOP, 30 HPS2 ALARM, 31 HPS2 STOP, 32 LPS2 ALARM, 33 LPS2 STOP, 34 FP2 ALARM, 35 FP2 STOP, 36 C2 HAND, 37 HEAT FAIL, 38 HIGH SAT, 39 WFS ALARM, 40 FZT ALARM, 41 RUN TIME, 42 SP OVERLAP, 43 SENSOR FAIL, 44 CLGD FLTR, 45 COS ALARM, 46 HIGH CO2, 47 HIGH SFDPT, 48 SD STOP, 49 SAT FAIL, 50 LOW SAT, 51 DISABLED, 52 ENERGY MGT, 53 EMERSHTDN.
- Appendix B Table E (operating conditions): 0 UNOCCUPIED, 1 NIGHT STBK, 2 OPT START, 3 OCCUPIED, 4 TESTING, 5 ALARM, 6 SHUTDOWN.
- The table sends Operating Condition (AV 111) to Table D and Operating Mode (AV 112) to Table E, but Table D is titled Operating Modes and Table E Operating Conditions; the names suggest AV 112 uses Table D and AV 111 Table E. Check on the unit.
- Many objects only apply with the matching option (energy wheel, exhaust fan, hot gas reheat, heat pump, chilled water valve, airflow stations, CO2).
- Same table as the 62X/62W Rev. K manuals plus three digital compressor points: DIG1 Minimum Output (AV 647), Digital Compressor #1 Percent (AV 6401) and #2 Percent (AV 6501).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 62H Dedicated Outdoor Air Unit (Rev. K controls) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
How many BACnet points does the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) have?
This list has 251 BACnet objects: 113 analog values, 136 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) BACnet points are writable?
85 of the 251 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) BACnet documentation?
The source is 62H 03-55 Tons Revision K Controls Dedicated Outdoor Air Unit - Controls, Operation, Start-Up, and Troubleshooting (Appendix A, Table C: Mapping Points - Carrier 62H Rev. K - 100% Outdoor Air) (62H-2T), revision 4-26, published free by Carrier at https://brandportal.carrier.com/asset/07ef7df6-5ec8-4570-a4dd-84659551da6c/62H-2T.pdf.
What are the minimum BACnet points to integrate the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)?
Start with BV 101 occ_en (BAS occupied/unoccupied command); MV 101 occ_ctrl_opts (Must be BAS for BAS occupancy control); AV 313 clg_sat_sp_o (Occupied cooling supply air setpoint); AV 354 htg_sat_sp_o (Occupied heating supply air setpoint); BV 110 bas_comm_status (Heartbeat: toggle before the BAS lost delay ends); BV 900 alarm_reset (Alarm reset); AV 112 op_mode (Operating mode code (Appendix B)); BV 105 occ_status (Occupied/unoccupied status); AV 235 sat_stat (Supply air temperature); BV 851 alarm_status (Unit alarm status).
How do I enable BMS control of the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)?
Occupancy Control (Occupancy Control Options, MSV 101) chooses BAS control, local schedule, 24/7 or CO2. With BAS control, BAS Manual Occ Control (BV 101) puts the unit in occupied or unoccupied mode. Enable Unit Operation (Tech Set Up) must be on. Emergency Shutdown in Tech Set Up disables the unit; Emerg. Shutdown Enable (BV 821) is writable over BACnet.
Does the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls) need a BACnet heartbeat or have a communication timeout?
Field BAS Comm. Status (BV 110) must change state before the BAS Comm. Lost Delay (AV 103, default 60 s) runs out, or BAS Communication Lost (BV 107) and the BAS LOST alarm (BV 899) are set. Enable BAS Monitor Schedule (BV 106) lets the unit fall back to its local schedule on a loss. The manual does not describe the OAT/OARH loss action beyond its status point (BV 1102).
Can the BMS supply sensor values to the Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)?
The BAS can write zone temperature (ZAT From BAS, AV 208), zone RH (AV 211), CO2 (AV 213), outdoor temperature (AV 1104) and outdoor RH (AV 1106). BAS outdoor values are monitored when Enable BAS Mon OAT/OARH (BV 1100) is on; Local OAT/OARH Sensor Enabled (BV 1115) selects the unit's own sensors.
How do I check these points on the real 62H Dedicated Outdoor Air Unit (Rev. K controls)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: 62H 03-55 Tons Revision K Controls Dedicated Outdoor Air Unit - Controls, Operation, Start-Up, and Troubleshooting (Appendix A, Table C: Mapping Points - Carrier 62H Rev. K - 100% Outdoor Air) · 62H-2T · rev. 4-26. Object names, instances and units are reproduced as published; descriptions are our own.