- Home
- BACnet points lists
- Carrier
- AquaEdge 19XR (PIC 5, software version 3.0)
Water-cooled centrifugal chiller controller · BACnet points list
Carrier AquaEdge 19XR (PIC 5, software version 3.0) BACnet points list
Updated 12 November 2026
The PIC 5 controller on the 19XR talks BACnet IP over its Ethernet port once the optional BACnet dongle is fitted and BACnet is enabled in the BACnet Config menu. This software 3.0 manual prints a 455-object table of AVs and BVs named <CCN table>_<point>: status, temperatures, pressures, guide vane and VFD values, surge and hot gas bypass settings, alarms, service settings and paired _rd/_wr command objects.
This page lists 455 BACnet objects for the Carrier AquaEdge 19XR (PIC 5, software version 3.0) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaEdge 19XR (PIC 5, software version 3.0)
- Equipment
- Water-cooled centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 455 (14 writable)
- Transport
- BACnet IP
- Firmware
- 19XR PIC 5 software version 3.0
- Default device instance
- 1600001
- Also known as
- 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Fit the BACnet dongle, set BACnet Enable, network number and identifier in the BACnet Config menu, and put the chiller in NETWORK control mode. It then starts and stops from the CHIL_S_S and CHIL_OCC network points (BV 103 and BV 105); write control point and demand limit through the _wr objects and read control mode, chiller state, water temperatures and alarm state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 103 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 105 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| BV 104 | GENUNIT_EMSTOP_wr | Emergency stop command | Write |
| AV 349 | GENUNIT_CTRL_PNT_wr | Control point command | Write |
| AV 350 | GENUNIT_DEM_LIM_wr | Demand limit command, 10-100 % | Write |
| AV 15 | GENUNIT_ctl_mode | Control mode: Local, Network, Remote, Local Sched | Read |
| AV 23 | GENUNIT_ch_state | Chiller state number | Read |
| AV 26 | TEMP_LCW | Leaving chilled water temperature | Read |
| AV 25 | TEMP_ECW | Entering chilled water temperature | Read |
| AV 104 | ALARMRST_ALM_STAT | Alarm state: 0 normal, 1 alert, 2 alarm | Read |
Enable & remote start
In NETWORK control mode the chiller is started and stopped by the CHIL_S_S and CHIL_OCC points written over the network; EMSTOP can also shut it down. If the STOP OVERRIDE point in GENUNIT is enabled, the chiller cannot start.
Network setup
- BACnet IP only, through the PIC 5 Ethernet port; the blue BACnet dongle must be plugged into the PIC 5 board (check Inputs Status > BACnet Dongle = Yes).
- BACnet Config menu (Advanced User password): BACnet Enable, Metric Unit (default 1), Network (default 1) and Identifier (default 1600001; the leading 16 is Carrier's vendor ID).
- Change the network number and identifier when more than one Carrier chiller is on the network; changing them reboots the board after 1 minute.
- After changing the IP address in the SETUP menu, reboot or power-cycle the PIC 5 so the BACnet stack is rebuilt.
- A router between the chiller and the BMS stops discovery; the manual lists it as a cause of no response.
Watch out for
- Write the _wr objects; the matching _rd objects only report the value.
- Configuration parameters are read-only over BACnet; setpoints are read/write.
- Instance numbers differ from the software 3.3 table, so check the controller version before reusing a mapping.
Carrier AquaEdge 19XR (PIC 5, software version 3.0) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | GENCONF_min_off | Stop to Start Delay | min | Read | |
| AV | 2 | GENCONF_strt_dly | Start to Start Delay | min | Read | |
| AV | 3 | GENCONF_dem_sel | Demand Limit Type | Read | 0 = Base Demand, 1=4-20ma | |
| AV | 4 | GENCONF_rampslct | Pulldown Ramp Type | Read | 0 = Temp, 1 = Load | |
| AV | 5 | GENCONF_DEM_SLCT | Demand Limit Source | Read | Amps=0, KW=1 | |
| AV | 6 | USERCONF_use_pass | User Password | Read | ||
| AV | 7 | RESETCFG_res_sel | Temp Reset Type | Read | No=0, 4~20ma=1, Remote Temp=2, Water DT=3 | |
| AV | 8 | RESETCFG_der_20ma | Degrees Reset at 20mA | Write | ||
| AV | 9 | RESETCFG_deg_rset | Maximum Deg Temp Reset | Δ°F | Read | |
| AV | 10 | RESETCFG_remtm_fu | Remote Temp Full Reset | Δ°F | Read | |
| AV | 11 | RESETCFG_remtm_no | Remote Temp No Reset | °F | Read | |
| AV | 12 | RESETCFG_drwdt_fu | Deg Reset Water DT Full | °F | Read | |
| AV | 13 | RESETCFG_ctldt_fu | Controlled DT Full Reset | Δ°F | Read | |
| AV | 14 | RESETCFG_ctldt_no | Controlled DT No Reset | Δ°F | Read | |
| AVmin | 15 | GENUNIT_ctl_mode | Control Mode | Read | Local=0, Network=1, Remote=2, Local Sched=3 | |
| AV | 16 | GENUNIT_cm_stas1 | Compressor1 Run Status | Read | ||
| AV | 17 | GENUNIT_HC_SEL_rd | Cooling/Heating Select (read) | Read | ||
| AV | 18 | GENUNIT_CTRL_PNT_rd | Control Point (read) | Read | ||
| AV | 19 | GENUNIT_reset | Control Point Reset | Δ°F | Read | |
| AV | 20 | GENUNIT_setpoint | Actual Setpoint | °F | Read | |
| AV | 21 | GENUNIT_amps_p | Percent Load Current | % | Read | |
| AV | 22 | GENUNIT_DEM_LIM_rd | Active Demand Limit (read) | Read | ||
| AVmin | 23 | GENUNIT_ch_state | Chiller State Number | Read | ||
| AV | 24 | GENUNIT_ch_stat | Chiller Run Status | Read | OFF=0, Ready=1, ON=2 | |
| AVmin | 25 | TEMP_ECW | Entering Chilled Water | °F | Read | |
| AVmin | 26 | TEMP_LCW | Leaving Chilled Water | °F | Read | |
| AV | 27 | TEMP_ECDW | Entering Condenser Water | °F | Read | |
| AV | 28 | TEMP_LCDW | Leaving Condenser Water | °F | Read | |
| AV | 29 | TEMP_EVAP_SAT | Evap Sat Refrig Temp | °F | Read | |
| AV | 30 | TEMP_EVAP_T | Evap Refrig Liquid Temp | °F | Read | |
| AV | 31 | TEMP_evap_app | Evaporator Approach | Δ°F | Read | |
| AV | 32 | TEMP_cond_app | Condenser Approach | Δ°F | Read | |
| AV | 33 | TEMP_COND_SAT | Cond Sat Refrig Temp | Read | ||
| AV | 34 | TEMP_DGT | Comp Discharge Temp | °F | Read | |
| AV | 35 | TEMP_DSH | Discharge Superheat | Δ°F | Read | |
| AV | 36 | TEMP_MTRB_OIL | Comp Thrust Lvg Oil Temp | °F | Read | |
| AV | 37 | TEMP_MTRB | Comp Thrust Bearing Temp | °F | Read | |
| AV | 38 | TEMP_MTRB1 | LS Motor Bearing Temp | °F | Read | |
| AV | 39 | TEMP_MTRB2 | LS Comp Bearing Temp | °F | Read | |
| AV | 40 | TEMP_MTRB3 | HS Motor Bearing Temp | °F | Read | |
| AV | 41 | TEMP_MTRB4 | HS Comp Bearing Temp | °F | Read | |
| AV | 42 | TEMP_MTRW1 | Comp Motor Wind 1 Temp | °F | Read | |
| AV | 43 | TEMP_MTRW2 | Comp Motor Wind 2 Temp | °F | Read | |
| AV | 44 | TEMP_MTRW3 | Comp Motor Wind 3 Temp | °F | Read | |
| AV | 45 | TEMP_OILT_SMP | Oil Sump Temp | °F | Read | |
| AV | 46 | TEMP_OILT_DIS | Oil Supply Temp | °F | Read | |
| AV | 47 | TEMP_LIFT_A | Calc Actual Lift | Δ°F | Read | |
| AV | 48 | TEMP_LIFT_1 | VDO High Lift Load Line | Δ°F | Read | |
| AV | 49 | TEMP_LIFT_2 | VDO Low Lift Load Line | Δ°F | Read | |
| AV | 50 | TEMP_R_RESET | Remote Reset Sensor | °F | Read | |
| AV | 51 | PRESSURE_EVAP_P | Evaporator Pressure | psig | Read | |
| AV | 52 | PRESSURE_COND_P | Condenser Pressure | Δpsi | Read | |
| AV | 53 | PRESSURE_ECON_P | Economizer Pressure | psig | Read | |
| AV | 54 | PRESSURE_OILP_DIS | Oil Supply Pressure | psig | Read | |
| AV | 55 | PRESSURE_OILP_SMP | Oil Sump Pressure | psig | Read | |
| AV | 56 | PRESSURE_OIL_PD | Oil Pump Delta P | Δpsi | Read | |
| AV | 57 | PRESSURE_DIFF_P | Diffuser Pressure | Δpsi | Read | |
| AV | 58 | PRESSURE_HEAD_P | Head Pressure Reference | Δpsi | Read | |
| AV | 59 | PRESSURE_EVAP_EWP | Evap Entering Water Pres | Δpsi | Read | |
| AV | 60 | PRESSURE_EVAP_LWP | Evap Leaving Water Pres | Δpsi | Read | |
| AV | 61 | PRESSURE_COND_EWP | Cond Entering Water Pres | Δpsi | Read | |
| AV | 62 | PRESSURE_COND_LWP | Cond Leaving Water Pres | Δpsi | Read | |
| AV | 63 | INPUTS_DMP_ACT | Damper Valve Status | Read | Cl=0, Inter=1, Op=2, Fail=3 | |
| AV | 64 | INPUTS_HGBP_ACT | HGBP Valve Status | Read | Cl=0, Inter=1, Op=2, Fail=3 | |
| AV | 65 | INPUTS_GV1_OHMS | Guide Vane 1 Actual Ohms | ohm | Read | |
| AV | 66 | INPUTS_GV1_ACT | Actual Guide Vane 1 Pos | % | Read | |
| AV | 67 | INPUTS_VFD_ACT | Actual VFD Speed | % | Read | |
| AV | 68 | INPUTS_DIFF_ACT | Diffuser Actual Pos | % | Read | |
| AV | 69 | INPUTS_AUTO_DEM | Auto Demand Limit Input | mA | Read | |
| AV | 70 | INPUTS_AUTO_RES | Auto Water Temp Reset | mA | Read | |
| AV | 71 | INPUTS_REF_LEAK | Refrig Leak Sensor | mA | Read | |
| AV | 72 | INPUTS_EVAPFLIN | Evap Flow Input (mA) | mA | Read | |
| AV | 73 | INPUTS_CONDFLIN | Cond Flow Input (mA) | mA | Read | |
| AV | 74 | INPUTS_VFD_IN | VFD Speed Feedback | V | Read | |
| AV | 75 | INPUTS_GV1_MA | Guide Vane 1 Actual mA | mA | Read | |
| AV | 76 | INPUTS_VFDC_MA | VFD Current Actual mA | mA | Read | |
| AV | 77 | OUTPUTS_DIFF_OUT | Diffuser Output mA | mA | Read | |
| AV | 78 | OUTPUTS_HDPV_OUT | Head Pres Output mA | % | Read | |
| AV | 79 | OUTPUTS_CHST_OUT | Chiller Status Output mA | mA | Read | |
| AV | 80 | OUTPUTS_VFD_OUT | VFD Speed Output mA | mA | Read | |
| AV | 81 | OUTPUTS_hdpv_tgt | Head Pres Valve Tgt Pos | % | Read | |
| AV | 82 | OUTPUTS_GV1_OUT | Guide Vane1 Output mA | mA | Read | |
| AV | 83 | OUTPUTS_dmp_tgt | Damper Valve Tgt Pos | Read | 0=CL, 1=Hold, 2=Open | |
| AV | 84 | OUTPUTS_hgbp_tgt | HGBP Valve Tgt Pos | Read | 0=CL, 1=Hold, 2=Open | |
| AV | 85 | HYDRLIC_COND_EWP | Cond Entering Water Pres | psig | Read | |
| AV | 86 | HYDRLIC_COND_LWP | Cond Leaving Water Pres | psig | Read | |
| AV | 87 | HYDRLIC_cdw_pd | Condenser Water Delta P | psig | Read | |
| AV | 88 | HYDRLIC_cdw_pull | Cond Water Pulldown/Min | Δ°F | Read | |
| AV | 89 | HYDRLIC_EVAP_EWP | Evap Enter Water Pres | psig | Read | |
| AV | 90 | HYDRLIC_EVAP_LWP | Evap Leaving Water Pres | psig | Read | |
| AV | 91 | HYDRLIC_chw_pd | Chilled Water Delta P | psig | Read | |
| AV | 92 | HYDRLIC_chw_pull | Chill Water Pulldown/Min | Δ°F | Read | |
| AV | 93 | HYDRLIC_ctrlw_dt | Controlled Water DT | Δ°F | Read | |
| AV | 94 | HYDRLIC_cdw_fl_s | Cond water flow Status | Read | 0=Fail or Not Started, 1=Success, 2=Verifying | |
| AV | 95 | HYDRLIC_chw_fl_s | Evap water flow Status | Read | 0=Fail or Not Started, 1=Success, 2=Verifying | |
| AV | 96 | HYDRLIC_pdown_st | Pumpdown/Lockout State | Read | ||
| AV | 97 | RUNTIME_ST_CNT12 | Starts In 12 Hours | Read | ||
| AV | 98 | RUNTIME_C_STARTS | Total Compressor Starts | Read | ||
| AV | 99 | RUNTIME_COMP_HRS | Compressor Ontime | h | Read | |
| AV | 100 | RUNTIME_SRV_HRS | Service Ontime | h | Read | |
| AV | 101 | RUNTIME_spst_tim | Stop to Start Timer | min | Read | |
| AV | 102 | RUNTIME_stst_tim | Start to Start Timer | min | Read | |
| AV | 103 | RUNTIME_RCYSTCNT | Recy Startup In 4 Hours | Read | ||
| AVmin | 104 | ALARMRST_ALM_STAT | Alarm State | Read | 0=Normal, 1=Partial (Alert), 2=Shutdown (Alarm) | |
| AV | 105 | ALARMRST_alarm_1c | Current Alarm 1 | Read | ||
| AV | 106 | ALARMRST_alarm_2c | Current Alarm 2 | Read | ||
| AV | 107 | ALARMRST_alarm_3c | Current Alarm 3 | Read | ||
| AV | 108 | ALARMRST_alarm_4c | Current Alarm 4 | Read | ||
| AV | 109 | ALARMRST_alarm_5c | Current Alarm 5 | Read | ||
| AV | 110 | CAPACTRL_ctrl_wt | Controlled Water Temp | °F | Read | |
| AV | 111 | CAPACTRL_gv1_tgt | Target GV1 Pos | % | Read | |
| AV | 112 | CAPACTRL_vfd_tgt | Target VFD Speed | % | Read | |
| AV | 113 | MAISURGE_act_reg | Surge Region | Read | No=0, Low=1, High=2 | |
| AV | 114 | MAISURGE_dts_act | Active Delta Tsat | °F | Read | |
| AV | 115 | MAISURGE_dts_cal | Calc Ref Delta Tsat | °F | Read | |
| AV | 116 | MAISURGE_amps_dta | Amps Change Surge Prot | % | Read | |
| AV | 117 | MAISURGE_amch_max | Max Amps Change Value | % | Read | |
| AV | 118 | MAISURGE_sc | Surge Counts | Read | ||
| AV | 119 | MAISURGE_surg_act | Surge Prevention Active | Read | ||
| AV | 120 | MAISURGE_spc | Surge Protection Counts | Read | ||
| AV | 121 | MAISURGE_surg_pro | Surge Protection Active | Read | ||
| AV | 122 | MAISURGE_hgbp_chg | HGBP Change Flag | Read | Close=0, Hold=1, Open=2 | |
| AV | 123 | MAISURGE_dts_maxc | Cal Surge Delta Tsmax | Read | ||
| AV | 124 | MAISURGE_dts_minc | Cal Surge Delta Tsmin | Read | ||
| AV | 125 | POWER_LN_AMPS1 | Line Current Phase 1 | A | Read | |
| AV | 126 | POWER_LN_AMPS2 | Line Current Phase 2 | A | Read | |
| AV | 127 | POWER_LN_AMPS3 | Line Current Phase 3 | A | Read | |
| AV | 128 | POWER_AMPS_A | Actual Line Current | A | Read | |
| AV | 129 | POWER_AMPS_P | Percent Load Current | % | Read | |
| AV | 130 | POWER_GRFT_1 | Ground Fault Phase 1 | A | Read | |
| AV | 131 | POWER_GRFT_2 | Ground Fault Phase 2 | A | Read | |
| AV | 132 | POWER_GRFT_3 | Ground Fault Phase 3 | A | Read | |
| AV | 133 | POWER_LN_VOLT1 | Line Voltage Phase 1 | V | Read | |
| AV | 134 | POWER_LN_VOLT2 | Line Voltage Phase 2 | V | Read | |
| AV | 135 | POWER_LN_VOLT3 | Line Voltage Phase 3 | V | Read | |
| AV | 136 | POWER_VOLT_A | Actual Line Voltage | V | Read | |
| AV | 137 | POWER_VOLT_P | Percent Line Voltage | % | Read | |
| AV | 138 | POWER_KW | Motor Kilowatts | kW | Read | |
| AV | 139 | POWER_KW_P | Motor Percent Kilowatts | % | Read | |
| AV | 140 | POWER_KWH | Motor Kilowatts Hours | kW | Read | |
| AV | 141 | POWER_LN_FREQ | Line Frequency Faulting | Hz | Read | |
| AV | 142 | POWER_POW_FACT | Power Factor | Read | ||
| AV | 143 | POWER_MOT_FREQ | Motor Actual Frequency | Hz | Read | |
| AV | 144 | POWER_VFD_FACT | VFD Load Factor | Read | ||
| AV | 145 | POWER_VFD_LOAD | VFD Load Current | A | Read | |
| AV | 146 | MAIISMH_AMPS_H1 | Line Current Phase 1 | A | Read | |
| AV | 147 | MAIISMH_AMPS_H2 | Line Current Phase 2 | A | Read | |
| AV | 148 | MAIISMH_AMPS_H3 | Line Current Phase 3 | A | Read | |
| AV | 149 | MAIISMH_FREQ_H | Line Frequency Faulting | Hz | Read | |
| AV | 150 | MAIISMH_GRFT_H1 | Ground Fault Phase 3 | A | Read | |
| AV | 151 | MAIISMH_GRFT_H2 | Ground Fault Phase 2 | A | Read | |
| AV | 152 | MAIISMH_GRFT_H3 | Ground Fault Phase 1 | A | Read | |
| AV | 153 | MAIISMH_sum1ht_h | I2T Sum Heat Phase 1 | % | Read | |
| AV | 154 | MAIISMH_sum2ht_h | I2T Sum Heat Phase 2 | % | Read | |
| AV | 155 | MAIISMH_sum3ht_h | I2T Sum Heat Phase 3 | % | Read | |
| AV | 156 | MAIISMH_VOLT_H1 | Line Voltage Phase 1 | V | Read | |
| AV | 157 | MAIISMH_VOLT_H2 | Line Voltage Phase 2 | V | Read | |
| AV | 158 | MAIISMH_VOLT_H3 | Line Voltage Phase 3 | V | Read | |
| AV | 159 | MAIN_SRD_diff_tgt | Diffuser Target Pos | % | Read | |
| AV | 160 | MAIN_SRD_srd_a | Calculated SRD Position | % | Read | |
| AV | 161 | MAIN_SRD_srd_1 | Calc High Lift SRD Pos | % | Read | |
| AV | 162 | MAIN_SRD_srd_2 | Calc Low Lift SRD Pos | % | Read | |
| AV | 163 | MAIN_SRD_lift_a | Calc Actual Lift | Δ°F | Read | |
| AV | 164 | MAIN_SRD_lift_1 | VDO High Lift Load Line | Δ°F | Read | |
| AV | 165 | MAIN_SRD_lift_2 | VDO Low Lift Load Line | Δ°F | Read | |
| AV | 166 | MAIN_SRD_strt_tmr | VDO Logic Start Delay | min | Read | |
| AV | 167 | MAIN_SRD_stalltmr | SRD Stall Closure Time | min | Read | |
| AV | 168 | ISM_MCFG_com_tout | Communication Timeout | s | Read | |
| AV | 169 | ISM_MCFG_star_typ | Starter Type | Read | 0=Full Volt 1=Redu Volt, 2=Solid State 3=FS VFD | |
| AV | 170 | ISM_MCFG_rla | Motor Rated Load Amps | A | Read | |
| AV | 171 | ISM_MCFG_mot_lra | Motor Locked Rotor Trip | A | Read | |
| AV | 172 | ISM_MCFG_lrs_del | Locked Rotor Start Delay | cycles | Read | |
| AV | 173 | ISM_MCFG_str_lra | Starter LRA Rating | A | Read | |
| AV | 174 | ISM_MCFG_rlv | Motor Rated Line Voltage | V | Read | |
| AV | 175 | ISM_MCFG_cu_th | Current Umbal Threshold | % | Read | |
| AV | 176 | ISM_MCFG_vu_th | Voltage Umbal Threshold | % | Read | |
| AV | 177 | ISM_MCFG_ct_ratio | Motor Current CT Ratio:1 | Read | ||
| AV | 178 | ISM_MCFG_vt_rat | Volt Transformer Ratio:1 | Read | ||
| AV | 179 | ISM_MCFG_cu_per | Current Umbal Persist | s | Read | |
| AV | 181 | ISM_MCFG_linefreq | Frequency=60 Hz?(No=50) | Read | ||
| AV | 182 | ISM_MCFG_gf_amps | Ground Fault Current | A | Read | |
| AV | 183 | ISM_MCFG_gfp_pers | Ground Fault Persistence | cycles | Read | |
| AV | 184 | ISM_MCFG_gfs_del | Ground Fault Start Delay | cycles | Read | |
| AV | 185 | ISM_MCFG_gfct_rat | Ground Fault CT Ratio:1 | Read | ||
| AV | 186 | ISM_MCFG_ovvol_th | Overvoltage Threshold | % | Read | |
| AV | 187 | ISM_MCFG_udvol_th | Undervoltage Threshold | % | Read | |
| AV | 188 | ISM_MCFG_ovud_per | Over Under Volt Persist | s | Read | |
| AV | 189 | ISM_MCFG_uvs_del | Under Volt Start Delay | s | Read | |
| AV | 190 | MAISWRST_srd_shut | SRD Position @Shutdown | % | Read | |
| AV | 191 | MAISWRST_vfd_shut | VFD Speed @Shutdown | % | Read | |
| AV | 192 | MAISWRST_gv1_shut | GV1 Position @Shutdown | % | Read | |
| AV | 193 | MAISWRST_est_shut | Evap Sat Temp @Shutdown | °F | Read | |
| AV | 194 | MAISWRST_pd_dur | Power Recovery Duration | min | Read | |
| AV | 195 | MAIN_MS_mst_slv | Unit is Master or Slave | Read | 0=Disable, 1=Master, 2=Slave | |
| AV | 196 | MAIN_MS_lead_lag | Unit is Lead or Lag | Read | 0=Disable, 1=Lead, 2=Lag | |
| AV | 197 | MAIN_MS_ms_ctrl | Master Control Type | Read | 0=Local, 1=Network, 2=Remote, 3=Local Sched | |
| AV | 198 | MAIN_MS_sl_ctrl | Slave Control Type | Read | 0=Local, 1=Network, 2=Remote, 3=Local Sched | |
| AV | 199 | MAIN_MS_ll_fault | Lead Lag Chiller Fault | Read | 0=No, 1=Lead, 2=Lag, 3=Both | |
| AV | 200 | MAIN_MS_lagstat | Compressor1 Run Status | Read | ||
| AV | 201 | MAIN_MS_lagstart | LAG Start Time | min | Read | |
| AV | 202 | MAIN_MS_lagstop | LAG Stop Time | min | Read | |
| AV | 203 | MAIN_MS_preflt | Prestart Fault Time | min | Read | |
| AV | 204 | MAIN_MS_pulltime | Pulldown Time | min | Read | |
| AV | 205 | MAIN_MS_pull_dt | Pulldown: Delta T / Min | Δ°F | Read | |
| AV | 206 | MAIN_MS_ll_hr_d | Lead/Lag Hours Delta | h | Read | |
| AV | 207 | MAIN_MS_ctrpntov | Overrid Control Point | °F | Read | |
| AV | 208 | MAIN_MS_demlimov | Overrid Act Demand Limit | % | Read | |
| AV | 209 | FACTORY_chil_typ | Chiller Type | Read | NGC=0, Legacy=1 | |
| AV | 210 | FACTORY_unit_typ | Unit Type | Read | Cool Only=0, Heat Mach=1 | |
| AV | 211 | FACTORY_refg_typ | Refrigerant Type | Read | R134a=0, Low Pressure=1 | |
| AV | 212 | FACTORY_coun_cod | Country Code | Read | ||
| AV | 213 | FACTORY_comp_typ | Comp (Single=0,Dual=1) | Read | ||
| AV | 214 | FACTORY_cond_typ | Condenser Type | Read | Low Pres=0, High Pres=1 | |
| AV | 215 | FACTORY_chmedium | Chilled Medium | Read | ||
| AV | 216 | FACTORY_fac_pass | Factory Password | Read | ||
| AV | 217 | FACTORY_vfd_opt | VFD Option | Read | No =0, FS VFD=1, UM VFD=2 | |
| AV | 218 | FACTORY_startype | Starter Type | Read | Full=0, Reduced Voltage=1, Solid State=2, VFD=3 | |
| AV | 219 | FACTORY_rkw | Motor Rated Kilowatts | kW | Read | |
| AV | 220 | FACTORY_lv_enth | Low Entered Volt V1 IOB | V | Read | |
| AV | 221 | FACTORY_lv_exth | Low Exited Volt V2 IOB | V | Read | |
| AV | 222 | FACTORY_gv1_type | Guide Vane1 Type | Read | 0=Dig Po 1=Ana 2=Dig Ne | |
| AV | 223 | FACTORY_vfd_fdv | VFD Feedback Voltage Sel | Read | 0=0~5V 1=0~10V | |
| AV | 224 | CONF_VFD_vfd_gain | VFD Gain | Read | ||
| AV | 225 | CONF_VFD_vfd_max | VFD Maximum Speed | % | Read | |
| AV | 226 | CONF_VFD_vfd_min | VFD Minimum Speed | % | Read | |
| AV | 227 | CONF_VFD_vfd_str | VFD Start Speed | % | Read | |
| AV | 228 | CONF_VFD_vfd_slg | VFD Surge Line Gain | Read | ||
| AV | 229 | CONF_VFD_vfdculm | VFD Current Limit | A | Read | |
| AV | 230 | CONF_VFD_vfdc20ma | VFD Load Current 20mA | A | Read | |
| AV | 231 | CONF_VFD_comp_100 | Comp Frequency 100% | Hz | Read | |
| AV | 232 | SERVICE1_ser_pass | Service Password | Read | ||
| AV | 233 | SERVICE1_dw_int | Demand Watts Interval | min | Read | |
| AV | 234 | SERVICE1_ewtdgain | Derivatived EWT Gain | Read | ||
| AV | 235 | SERVICE1_ctrl_db | Controlled Fluid DB | Δ°F | Read | |
| AV | 236 | SERVICE1_gv1decdb | Proportional Dec Band | Read | ||
| AV | 237 | SERVICE1_gv1incdb | Proportional Inc Band | Read | ||
| AV | 238 | SERVICE1_dem_pdb | Demand Limit Prop Band | % | Read | |
| AV | 239 | SERVICE1_dem_20ma | Demand Limit At 20 mA | % | Read | |
| AV | 240 | SERVICE1_gv1_lim | GV1 Travel Limit | % | Read | |
| AV | 241 | SERVICE1_ldramprt | Amps or KW Ramp Per Min | % | Read | |
| AV | 242 | SERVICE1_tmramprt | Temp Ramp Rate F/Min | Δ°F | Read | |
| AV | 243 | SERVICE1_dmp_dly | Damper Valve Act Delay | min | Read | |
| AV | 244 | SERVICE1_rcysh_dt | Recycle Shutdown Delta T | Δ°F | Read | |
| AV | 245 | SERVICE1_rcyst_dt | Recycle Restart Delta T | Δ°F | Read | |
| AV | 246 | SERVICE1_dmp_cldb | Damper Valve Close DB | psig | Read | |
| AV | 247 | SERVICE1_dmp_opdb | Damper Valve Open DB | psig | Read | |
| AV | 248 | SERVICE1_oilpvr_t | Oil Press Verify Time | s | Read | |
| AV | 249 | SERVICE1_sf_st_th | Soft Stop Amps Threshold | % | Read | |
| AV | 250 | SERVICE1_wflow_t | Water Flow Verify Time | min | Read | |
| AV | 251 | SERVICE1_mbb_pfcl | MBB Power Calibration | Read | ||
| AV | 252 | SERVICE1_max_gv | Maximum GV Movement | % | Read | |
| AV | 253 | CFGSURGE_dts_max | Cal Surge Delta Tsmax | Δ°F | Read | |
| AV | 254 | CFGSURGE_dts_min | Cal Surge Delta Tsmin | Δ°F | Read | |
| AV | 255 | CFGSURGE_gv1_smax | Surge IGV1 Max Pos | Read | ||
| AV | 256 | CFGSURGE_gv1_smin | Surge IGV1 Min Pos | Read | ||
| AV | 257 | CFGSURGE_sgl_off | Surge Line Offset | Δ°F | Read | |
| AV | 258 | CFGSURGE_sghg_db | Surge Deadband | Δ°F | Read | |
| AV | 259 | CFGSURGE_sgl_hoff | Surge Line High Offset | Δ°F | Read | |
| AV | 260 | CFGSURGE_sgl_shpf | Surge Line Shape Factor | Read | ||
| AV | 261 | CFGSURGE_sgl_spdf | Surge Line Speed Factor | Read | ||
| AV | 262 | CFGSURGE_surge_a | Surge Delta Amps % | % | Read | |
| AV | 263 | CFGSURGE_gvstp_sg | GV1 Close Surge Prote | % | Read | |
| AV | 264 | CFGSURGE_vfdstpsg | VFD Speed Step Surge | % | Read | |
| AV | 265 | CFGSURGE_pr_max | Maximum Pressure Ratio | Read | ||
| AV | 266 | CFGSURGE_pr_min | Minimum Pressure Ratio | Read | ||
| AV | 267 | CFGSURGE_atom_pre | Atmospheric Pressure | psi | Read | |
| AV | 268 | CFGSURGE_surg_del | Surge Delay Time | s | Read | |
| AV | 269 | CFGSURGE_surge_t | Surge Time Period | min | Read | |
| AV | 270 | CFGLIMIT_cdfreeze | Condenser Freeze Point | °F | Read | |
| AV | 271 | CFGLIMIT_evap_al | Evap Approach Alert | °F | Read | |
| AV | 272 | CFGLIMIT_cond_al | Cond Approach Alert | °F | Read | |
| AV | 273 | CFGLIMIT_evap_cut | Evap Flow Delta P Cutout | psig | Read | |
| AV | 274 | CFGLIMIT_cond_cut | Cond Flow Delta P Cutout | psig | Read | |
| AV | 275 | CFGLIMIT_cond_val | Cond Hi Flow DP Limit | psig | Read | |
| AV | 276 | CFGLIMIT_cpov_lo | Cond Press Override Low | psig | Read | |
| AV | 277 | CFGLIMIT_cpov_hi | Cond Press Override High | psig | Read | |
| AV | 278 | CFGLIMIT_dgt_alrt | Comp Discharge Alert | °F | Read | |
| AV | 279 | CFGLIMIT_ert_ovdt | Evap Override Delta T | °F | Read | |
| AV | 280 | CFGLIMIT_ert_trip | Evap Refrig Trippoint | °F | Read | |
| AV | 281 | CFGLIMIT_mt_over | Comp Motor Temp Override | °F | Read | |
| AV | 282 | CFGLIMIT_tb_alert | Comp Bearing Temp Alert | °F | Read | |
| AV | 283 | CFGLIMIT_tb_trip | Comp Bearing Temp Trip | °F | Read | |
| AV | 284 | CFGLIMIT_cpcut_lo | Cond Press Cutout Low | psig | Read | |
| AV | 285 | CFGLIMIT_cpcut_hi | Cond Press Cutout High | psig | Read | |
| AV | 286 | CFGLIMIT_bri_min | Minimum Brine LWT | °F | Read | |
| AV | 287 | CFGLIMIT_tb_alt2 | LS Comp Bearing Alert | °F | Read | |
| AV | 288 | CFGLIMIT_tb_trip2 | LS Comp Bearing Trip | °F | Read | |
| AV | 289 | CFGLIMIT_lwtp_sp | LWT Protection Setpoint | °F | Read | |
| AV | 290 | CONF_SRD_off_sel | SRD IGV Offset Select | Read | ||
| AV | 291 | CONF_SRD_pro_sel | Low Lift Profile Select | Read | ||
| AV | 292 | CONF_SRD_diff_ma | Diffuser Full Span mA | mA | Read | |
| AV | 293 | CONF_SRD_gv11_25 | GV1 Pos Load @25% | % | Read | |
| AV | 294 | CONF_SRD_gv11_50 | GV1 Pos Load @50% | % | Read | |
| AV | 295 | CONF_SRD_gv11_75 | GV1 Pos Load @75% | % | Read | |
| AV | 296 | CONF_SRD_srd1_25 | SRD Pos Load @25% | % | Read | |
| AV | 297 | CONF_SRD_srd1_50 | SRD Pos Load @50% | % | Read | |
| AV | 298 | CONF_SRD_srd1_75 | SRD Pos Load @75% | % | Read | |
| AV | 299 | CONF_SRD_lf1_100 | High Lift Load @100% | Δ°F | Read | |
| AV | 300 | CONF_SRD_lf1_25 | High Lift Load @25% | Δ°F | Read | |
| AV | 301 | CONF_SRD_lf2_25 | Low Lift Load @25% | Δ°F | Read | |
| AV | 302 | CONF_SRD_peak_th | Peak Detection Threshold | V | Read | |
| AV | 303 | CONF_SRD_peak_ch3 | Peak Detection Channel | Read | ||
| AV | 304 | CONF_OPT_hgbp_sel | HGBP Selection | Read | Disable=0, Surge=1, Low Load=2, Comb=3 | |
| AV | 305 | CONF_OPT_gv1stpos | GV1 Closure at Startup | % | Read | |
| AV | 306 | CONF_OPT_hpop_gv1 | HGBP Open IGV1 Position | % | Read | |
| AV | 307 | CONF_OPT_hgcl_gv1 | HGBP Close IGV1 Position | % | Read | |
| AV | 308 | CONF_OPT_hgb_toff | HGBP Off DT for Low Load | Δ°F | Read | |
| AV | 309 | CONF_OPT_hgb_ton | HGBP On DT for Low Load | Δ°F | Read | |
| AV | 310 | CONF_OPT_hgbp_ldb | HGBP Low Load DB | Δ°F | Read | |
| AV | 311 | CONF_OPT_hdp_0 | Head Pres Delta P 0% | psig | Read | |
| AV | 312 | CONF_OPT_hdp_100 | Head Pres Delta P 100% | psig | Read | |
| AV | 313 | CONF_OPT_hdpv_min | Head Pressure Min Output | % | Read | |
| AV | 314 | CONF_OPT_gt_fact | Gas Torque Factor | °F | Read | |
| AV | 315 | CONF_OPT_gv_srd_f | Guide Vane/SRD Factor | Read | ||
| AV | 316 | CONF_OPT_pd_tcfg | Power Recovery Timeout | min | Read | |
| AV | 317 | CONF_OPT_ice_term | Ice Build Termin Source | Read | 0=Temp, 1=Contact, 2=Both | |
| AV | 318 | CONF_OPT_leak_ma | Refrig Leak Alarm mA | mA | Read | |
| AV | 319 | CONF_OPT_tfh_sp | Tower Fan High Setpoint | Read | ||
| AV | 320 | CONF_MS_slv_addr | Slave Address | Read | ||
| AV | 321 | CONF_MS_msl_sel | Master/Slave Select | Read | 0=Disable, 1=Master, 2=Slave | |
| AV | 322 | CONF_MS_ms_ctrl | Master Control Type | Read | 1=Local, 2=Network, 3=Rem, 4= LS | |
| AV | 323 | CONF_MS_ms_type | Chiller Connection Type | Read | 0=Parallel, 1=Series | |
| AV | 324 | CONF_MS_ms_pos | Master Chiller Position | Read | 0=Upstream, 1=Downstream | |
| AV | 325 | CONF_MS_lead_sel | Master Lead Lag Select | Read | 0=Lead, Lag Once Failed, 1=Lead/Lag Runtime Sel | |
| AV | 326 | CONF_MS_ms_per | Master per Capacity | % | Read | |
| AV | 327 | CONF_MS_lag_shut | LAG Shutdown Threshold | % | Read | |
| AV | 328 | CONF_MS_pref_tim | Prestart Fault Timer | min | Read | |
| AV | 329 | CONF_MS_un_th | Unload Threshold | % | Read | |
| AV | 330 | CONF_MS_ll_bal_d | Lead/Lag Balance Delta | h | Read | |
| AV | 331 | CONF_MS_lstr_tim | Lag Start Timer | min | Read | |
| AV | 332 | CONF_MS_lstp_tim | Lag Stop Timer | min | Read | |
| AV | 333 | CONF_MS_lead_pul | Lead Pulldown Time | min | Read | |
| AV | 334 | CONF_MS_lag_mini | Lag Minimum Running Time | min | Read | |
| AV | 335 | CONF_PRG_oilfl_th | Oil Filter Pres Diff | psig | Read | |
| AV | 336 | CONF_PRG_oilch_nt | Oil Change Duration | h | Read | |
| AV | 337 | CONF_PRG_refgc_th | Trans Calib Threshold | Read | ||
| AV | 338 | CONF_PRG_rch_cath | Low Charge Cond Approach | °F | Read | |
| AV | 339 | CONF_PRG_ep_dgap | Evap Design Approach | °F | Read | |
| AV | 340 | CONF_PRG_beart_th | Bearing Degradation | °F | Read | |
| AV | 341 | BACNET_network | Local=0,Network=1 | Read | ||
| AV | 342 | BACNET_ident | Identifier | Read | ||
| AV | 343 | SETPOINT_ecdw_sp | Heating ECDW Setpoint | °F | Write | |
| AV | 344 | SETPOINT_ecw_sp | Cooling ECW Setpoint | °F | Write | |
| AV | 345 | SETPOINT_ice_sp | Ice Build Setpoint | °F | Write | |
| AV | 346 | SETPOINT_lcdw_sp | Heating LCDW Setpoint | °F | Write | |
| AV | 347 | SETPOINT_lcw_sp | Cooling LCW Setpoint | °F | Write | |
| AV | 348 | SETPOINT_dem_base | Base Demand Limit | % | Write | |
| AVmin | 349 | GENUNIT_CTRL_PNT_wr | Control Point (write) | °F | Write | |
| AVmin | 350 | GENUNIT_DEM_LIM_wr | Active Demand Limit (write) | % | Write | |
| AV | 351 | GENUNIT_HC_SEL_wr | Cooling/Heating Select (write) | Write | ||
| BV | 1 | GENUNIT_statstop | Deter Start Stop Command | Read | ||
| BV | 2 | GENUNIT_CHIL_S_S_rd | Network:Cmd Start/Stop (read) | Read | ||
| BV | 3 | GENUNIT_CHIL_OCC_rd | Network:Cmd Occupied (read) | Read | ||
| BV | 4 | GENUNIT_EMSTOP_rd | Emergency Stop (read) | Read | ||
| BV | 5 | GENUNIT_loc_occ | Local Schedule Occupied | Read | NO/YES | |
| BV | 6 | GENUNIT_ice_occ | Ice Schedule Occupied | Read | NO/YES | |
| BV | 7 | GENUNIT_ms_stsp | MS Start Stop Command | Read | START/STOP | |
| BV | 8 | GENUNIT_REM_RST | Remote Reset Alarm | Read | ||
| BV | 9 | GENUNIT_STP_OVER | Stop Override | Read | ||
| BV | 10 | INPUTS_STAR_AUX | Compressor Start Contact | Read | OPEN/CLOSE | |
| BV | 11 | INPUTS_RUN_AUX | Compressor Run Contact | Read | OPEN/CLOSE | |
| BV | 12 | INPUTS_DMP_FC | Damper Valve Full Closed | Read | NO/YES | |
| BV | 13 | INPUTS_DMP_FO | Damper Valve Full Opened | Read | NO/YES | |
| BV | 14 | INPUTS_HGBP_FC | HGBP Valve Fully Closed | Read | NO/YES | |
| BV | 15 | INPUTS_HGBP_FO | HGBP Valve Fully Opened | Read | NO/YES | |
| BV | 16 | INPUTS_HP_SW | High Pressure Switch | Read | OPEN/CLOSE | |
| BV | 17 | INPUTS_REM_CON | Remote Contact | Read | OPEN/CLOSE | |
| BV | 18 | INPUTS_E_STOP | Emergency Stop Contact | Read | OPEN/CLOSE | |
| BV | 19 | INPUTS_ICE_CON | Ice Build Contact Closed | Read | OPEN/CLOSE | |
| BV | 20 | INPUTS_REM_LOCK | Chiller Lockout | Read | OPEN/CLOSE | |
| BV | 21 | INPUTS_SAFETY | Spare Safety Input | Read | OPEN/CLOSE | |
| BV | 22 | INPUTS_STARTFLT | Starter Fault Feedback | Read | OPEN/CLOSE | |
| BV | 23 | INPUTS_FS_LOCK | Fire Security Interlock | Read | OPEN/CLOSE | |
| BV | 24 | INPUTS_TRIPR | ISM Trip Relay Status | Read | OPEN/CLOSE | |
| BV | 25 | INPUTS_bacdongl | BACnet Dongle | Read | NO/YES | |
| BV | 26 | OUTPUTS_ALM | Alarm Relay | Read | OFF/ON | |
| BV | 27 | OUTPUTS_ALE | Alert Relay | Read | OFF/ON | |
| BV | 28 | OUTPUTS_COMP_SR | Compressor Start Relay | Read | OFF/ON | |
| BV | 29 | OUTPUTS_TRANS | Starter Trans Sw Status | Read | OFF/ON | |
| BV | 30 | OUTPUTS_DMP_CL | Damper Valve Close | Read | OFF/ON | |
| BV | 31 | OUTPUTS_DMP_OP | Damper Valve Open | Read | OFF/ON | |
| BV | 32 | OUTPUTS_GV1_DEC | Guide Vane 1 Decrease | Read | OFF/ON | |
| BV | 33 | OUTPUTS_GV1_INC | Guide Vane 1 Increase | Read | OFF/ON | |
| BV | 34 | OUTPUTS_HGBP_OFF | Hot Gas Bypass Close | Read | OFF/ON | |
| BV | 35 | OUTPUTS_HGBP_ON | Hot Gas Bypass Open | Read | OFF/ON | |
| BV | 36 | OUTPUTS_OIL_HEAT | Oil Heater Relay | Read | OFF/ON | |
| BV | 37 | OUTPUTS_OIL_PUMP | Oil Pump Relay | Read | OFF/ON | |
| BV | 38 | OUTPUTS_TFR_HIGH | Tower Fan Relay High | Read | OFF/ON | |
| BV | 39 | OUTPUTS_TFR_LOW | Tower Fan Relay Low | Read | OFF/ON | |
| BV | 40 | HYDRLIC_CDW_FLOW | Condenser Water Flow | Read | NO/YES | |
| BV | 41 | HYDRLIC_CHWP | Chilled Water Pump | Read | OFF/ON | |
| BV | 42 | HYDRLIC_CDWP | Condenser Water Pump | Read | OFF/ON | |
| BV | 43 | HYDRLIC_CHW_FLOW | Chilled Water Flow | Read | NO/YES | |
| BV | 44 | MODES_evapfrze | Evap Freeze Active | Read | NO/YES | |
| BV | 45 | MODES_condfrze | Cond Freeze Active | Read | NO/YES | |
| BV | 46 | ALARMRST_RST_ALM | Alarm Reset | Read | ||
| BV | 47 | CAPACTRL_cap_inh | Capacity Inhibit Flag | Read | NO/YES | |
| BV | 48 | CAPACTRL_cap_dec | Capacity Decrease Flag | Δ°F | Read | |
| BV | 49 | CAPACTRL_comp_run | Compressor is Running | Read | ||
| BV | 50 | OVERRIDE_cpov_fl | Cond Press Override Flag | Read | NO/YES | |
| BV | 51 | OVERRIDE_dshov_fl | Low DSH Override Flag | Read | NO/YES | |
| BV | 52 | OVERRIDE_lftov_fl | High Lift Override Flag | Read | NO/YES | |
| BV | 53 | OVERRIDE_sstov_fl | Low SST Override Flag | Read | NO/YES | |
| BV | 54 | OVERRIDE_mtov_fl | High Motor Temp Over | Read | NO/YES | |
| BV | 55 | OVERRIDE_tbov_fl | High Bearing Temp Over | Read | NO/YES | |
| BV | 56 | OVERRIDE_lstov_fl | Low Sour Temp Over Flag | Read | NO/YES | |
| BV | 57 | OVERRIDE_dgtov_fl | DGT Override Flag | Read | NO/YES | |
| BV | 58 | OVERRIDE_ampov_fl | High Motor Current Flag | Read | NO/YES | |
| BV | 59 | POWER_VFDC_HI | High VFD Current | Read | NO/YES | |
| BV | 60 | MAIISMH_phase_h1 | Phase 1 Faulted | Read | NO/YES | |
| BV | 61 | MAIISMH_phase_h2 | Phase 2 Faulted | Read | NO/YES | |
| BV | 62 | MAIISMH_phase_h3 | Phase 3 Faulted | Read | NO/YES | |
| BV | 63 | MAIN_SRD_diffault | Diffuser Fault | Read | NO/YES | |
| BV | 64 | MAIN_SRD_diff_alm | SRD Rotating Stall Alarm | Read | NO/YES | |
| BV | 65 | ISM_MCFG_ism_cflt | ISM Config Conflict | Read | NO/YES | |
| BV | 66 | ISM_MCFG_del_ismc | Delete ISM Config | Read | NO/YES | |
| BV | 67 | ISM_MCFG_scycd_en | Single Cycle Dropout | Read | DSABLE/ENABLE | |
| BV | 68 | ISM_MCFG_lfref_en | Line Frequency Faulting | Read | DSABLE/ENABLE | |
| BV | 69 | ISM_MCFG_gfp_en | Ground Fault Protection | Read | DSABLE/ENABLE | |
| BV | 70 | MAISWRST_power_dn | Power Down Active | Read | NO/YES | |
| BV | 71 | MAISWRST_auto_rst | Auto Restart Active | Read | NO/YES | |
| BV | 72 | MAISWRST_sw_rst | Swift Restart Active | Read | NO/YES | |
| BV | 73 | MAIN_MS_ms_act | Master/Slave Ctrl Active | Read | ||
| BV | 74 | MAIN_MS_ll_comm | Lead Lag Communication | Read | ||
| BV | 75 | MAIN_MS_lag_s_s | Network:Cmd Start/Stop | Read | ||
| BV | 76 | MAIN_MS_lag_rec | Recovery Start Request | Read | ||
| BV | 77 | MAIN_MS_ll_chang | Lead/Lag Changeover? | Read | ||
| BV | 78 | MAIN_MS_CAP_DECL | Capacity Decrease | Read | ||
| BV | 79 | MAIN_MS_CAP_INHL | Capacity Inhibit | Read | ||
| BV | 80 | MAIN_MS_MST_RUN | Master Chiller Running | Read | ||
| BV | 81 | MAIN_MS_EWT_OPT | EWT Control Option | Read | ||
| BV | 82 | MAIN_MS_DEM_SLCT | Demand Limit Source | Read | Amps=0, KW=1 | |
| BV | 83 | FACTORY_freq_60h | Power Freq 60Hz Select | Read | YES/NO | |
| BV | 84 | FACTORY_freecool | Free Cooling Option | Read | YES/NO | |
| BV | 85 | FACTORY_hyd_opt | Hydraulic System Option | Read | YES/NO | |
| BV | 86 | FACTORY_heatrecl | Heat Reclaim Option | Read | YES/NO | |
| BV | 87 | SERVICE1_ex_start | Enable Excessive Starts | Read | ||
| BV | 88 | CFGLIMIT_cond_alm | Cond Hi Flow Alarm | Read | DSABLE/ENABLE | |
| BV | 89 | CONF_SRD_diff_opt | Diffuser Option | Read | DSABLE/ENABLE | |
| BV | 90 | CONF_OPT_astart | Auto Restart Option | Read | DSABLE/ENABLE | |
| BV | 91 | CONF_OPT_commsens | Common Sensor Option | Read | DSABLE/ENABLE | |
| BV | 92 | CONF_OPT_wp_opt | Water Pressure Option | Read | DSABLE/ENABLE | |
| BV | 93 | CONF_OPT_hgbp_opt | HGBP Valve Is Configured | Read | DSABLE/ENABLE | |
| BV | 94 | CONF_OPT_ice_opt | Ice Build Option | Read | DSABLE/ENABLE | |
| BV | 95 | CONF_OPT_ice_recy | Ice Build Recycle | Read | DSABLE/ENABLE | |
| BV | 96 | CONF_OPT_leak_en | Refrigerant Leak Option | Read | DSABLE/ENABLE | |
| BV | 97 | CONF_OPT_hdpv_opt | Head Pres Valve Option | Read | DISABLE/ENABLE | |
| BV | 98 | CONF_MS_serct_fl | Series Counter Flow | Read | YES/NO | |
| BV | 99 | CONF_PRG_prog_en | Prog Function Enable | Read | YES/NO | |
| BV | 100 | BACNET_bacena | BACnet Enable | Read | ||
| BV | 101 | BACNET_bacunit | Metric Unit | Read | ||
| BV | 102 | SETPOINT_EWT_OPT | EWT Control Option | Write | DSABLE/ENABLE | |
| BVmin | 103 | GENUNIT_CHIL_S_S_wr | Network:Cmd Start/Stop (write) | Write | ||
| BVmin | 104 | GENUNIT_EMSTOP_wr | Emergency Stop (write) | Write | ||
| BVmin | 105 | GENUNIT_CHIL_OCC_wr | Network:Cmd Occupied (write) | Write |
No points match these filters.
Object ID lookup: Carrier AquaEdge 19XR (PIC 5, software version 3.0) point IDs by name
AV1GENCONF_min_offAV2GENCONF_strt_dlyAV3GENCONF_dem_selAV4GENCONF_rampslctAV5GENCONF_DEM_SLCTAV6USERCONF_use_passAV7RESETCFG_res_selAV8RESETCFG_der_20maAV9RESETCFG_deg_rsetAV10RESETCFG_remtm_fuAV11RESETCFG_remtm_noAV12RESETCFG_drwdt_fuAV13RESETCFG_ctldt_fuAV14RESETCFG_ctldt_noAV15GENUNIT_ctl_modeAV16GENUNIT_cm_stas1AV17GENUNIT_HC_SEL_rdAV18GENUNIT_CTRL_PNT_rdAV19GENUNIT_resetAV20GENUNIT_setpointAV21GENUNIT_amps_pAV22GENUNIT_DEM_LIM_rdAV23GENUNIT_ch_stateAV24GENUNIT_ch_statAV25TEMP_ECWAV26TEMP_LCWAV27TEMP_ECDWAV28TEMP_LCDWAV29TEMP_EVAP_SATAV30TEMP_EVAP_TAV31TEMP_evap_appAV32TEMP_cond_appAV33TEMP_COND_SATAV34TEMP_DGTAV35TEMP_DSHAV36TEMP_MTRB_OILAV37TEMP_MTRBAV38TEMP_MTRB1AV39TEMP_MTRB2AV40TEMP_MTRB3AV41TEMP_MTRB4AV42TEMP_MTRW1AV43TEMP_MTRW2AV44TEMP_MTRW3AV45TEMP_OILT_SMPAV46TEMP_OILT_DISAV47TEMP_LIFT_AAV48TEMP_LIFT_1AV49TEMP_LIFT_2AV50TEMP_R_RESETAV51PRESSURE_EVAP_PAV52PRESSURE_COND_PAV53PRESSURE_ECON_PAV54PRESSURE_OILP_DISAV55PRESSURE_OILP_SMPAV56PRESSURE_OIL_PDAV57PRESSURE_DIFF_PAV58PRESSURE_HEAD_PAV59PRESSURE_EVAP_EWPAV60PRESSURE_EVAP_LWPAV61PRESSURE_COND_EWPAV62PRESSURE_COND_LWPAV63INPUTS_DMP_ACTAV64INPUTS_HGBP_ACTAV65INPUTS_GV1_OHMSAV66INPUTS_GV1_ACTAV67INPUTS_VFD_ACTAV68INPUTS_DIFF_ACTAV69INPUTS_AUTO_DEMAV70INPUTS_AUTO_RESAV71INPUTS_REF_LEAKAV72INPUTS_EVAPFLINAV73INPUTS_CONDFLINAV74INPUTS_VFD_INAV75INPUTS_GV1_MAAV76INPUTS_VFDC_MAAV77OUTPUTS_DIFF_OUTAV78OUTPUTS_HDPV_OUTAV79OUTPUTS_CHST_OUTAV80OUTPUTS_VFD_OUTAV81OUTPUTS_hdpv_tgtAV82OUTPUTS_GV1_OUTAV83OUTPUTS_dmp_tgtAV84OUTPUTS_hgbp_tgtAV85HYDRLIC_COND_EWPAV86HYDRLIC_COND_LWPAV87HYDRLIC_cdw_pdAV88HYDRLIC_cdw_pullAV89HYDRLIC_EVAP_EWPAV90HYDRLIC_EVAP_LWPAV91HYDRLIC_chw_pdAV92HYDRLIC_chw_pullAV93HYDRLIC_ctrlw_dtAV94HYDRLIC_cdw_fl_sAV95HYDRLIC_chw_fl_sAV96HYDRLIC_pdown_stAV97RUNTIME_ST_CNT12AV98RUNTIME_C_STARTSAV99RUNTIME_COMP_HRSAV100RUNTIME_SRV_HRSAV101RUNTIME_spst_timAV102RUNTIME_stst_timAV103RUNTIME_RCYSTCNTAV104ALARMRST_ALM_STATAV105ALARMRST_alarm_1cAV106ALARMRST_alarm_2cAV107ALARMRST_alarm_3cAV108ALARMRST_alarm_4cAV109ALARMRST_alarm_5cAV110CAPACTRL_ctrl_wtAV111CAPACTRL_gv1_tgtAV112CAPACTRL_vfd_tgtAV113MAISURGE_act_regAV114MAISURGE_dts_actAV115MAISURGE_dts_calAV116MAISURGE_amps_dtaAV117MAISURGE_amch_maxAV118MAISURGE_scAV119MAISURGE_surg_actAV120MAISURGE_spcAV121MAISURGE_surg_proAV122MAISURGE_hgbp_chgAV123MAISURGE_dts_maxcAV124MAISURGE_dts_mincAV125POWER_LN_AMPS1AV126POWER_LN_AMPS2AV127POWER_LN_AMPS3AV128POWER_AMPS_AAV129POWER_AMPS_PAV130POWER_GRFT_1AV131POWER_GRFT_2AV132POWER_GRFT_3AV133POWER_LN_VOLT1AV134POWER_LN_VOLT2AV135POWER_LN_VOLT3AV136POWER_VOLT_AAV137POWER_VOLT_PAV138POWER_KWAV139POWER_KW_PAV140POWER_KWHAV141POWER_LN_FREQAV142POWER_POW_FACTAV143POWER_MOT_FREQAV144POWER_VFD_FACTAV145POWER_VFD_LOADAV146MAIISMH_AMPS_H1AV147MAIISMH_AMPS_H2AV148MAIISMH_AMPS_H3AV149MAIISMH_FREQ_HAV150MAIISMH_GRFT_H1AV151MAIISMH_GRFT_H2AV152MAIISMH_GRFT_H3AV153MAIISMH_sum1ht_hAV154MAIISMH_sum2ht_hAV155MAIISMH_sum3ht_hAV156MAIISMH_VOLT_H1AV157MAIISMH_VOLT_H2AV158MAIISMH_VOLT_H3AV159MAIN_SRD_diff_tgtAV160MAIN_SRD_srd_aAV161MAIN_SRD_srd_1AV162MAIN_SRD_srd_2AV163MAIN_SRD_lift_aAV164MAIN_SRD_lift_1AV165MAIN_SRD_lift_2AV166MAIN_SRD_strt_tmrAV167MAIN_SRD_stalltmrAV168ISM_MCFG_com_toutAV169ISM_MCFG_star_typAV170ISM_MCFG_rlaAV171ISM_MCFG_mot_lraAV172ISM_MCFG_lrs_delAV173ISM_MCFG_str_lraAV174ISM_MCFG_rlvAV175ISM_MCFG_cu_thAV176ISM_MCFG_vu_thAV177ISM_MCFG_ct_ratioAV178ISM_MCFG_vt_ratAV179ISM_MCFG_cu_perAV181ISM_MCFG_linefreqAV182ISM_MCFG_gf_ampsAV183ISM_MCFG_gfp_persAV184ISM_MCFG_gfs_delAV185ISM_MCFG_gfct_ratAV186ISM_MCFG_ovvol_thAV187ISM_MCFG_udvol_thAV188ISM_MCFG_ovud_perAV189ISM_MCFG_uvs_delAV190MAISWRST_srd_shutAV191MAISWRST_vfd_shutAV192MAISWRST_gv1_shutAV193MAISWRST_est_shutAV194MAISWRST_pd_durAV195MAIN_MS_mst_slvAV196MAIN_MS_lead_lagAV197MAIN_MS_ms_ctrlAV198MAIN_MS_sl_ctrlAV199MAIN_MS_ll_faultAV200MAIN_MS_lagstatAV201MAIN_MS_lagstartAV202MAIN_MS_lagstopAV203MAIN_MS_prefltAV204MAIN_MS_pulltimeAV205MAIN_MS_pull_dtAV206MAIN_MS_ll_hr_dAV207MAIN_MS_ctrpntovAV208MAIN_MS_demlimovAV209FACTORY_chil_typAV210FACTORY_unit_typAV211FACTORY_refg_typAV212FACTORY_coun_codAV213FACTORY_comp_typAV214FACTORY_cond_typAV215FACTORY_chmediumAV216FACTORY_fac_passAV217FACTORY_vfd_optAV218FACTORY_startypeAV219FACTORY_rkwAV220FACTORY_lv_enthAV221FACTORY_lv_exthAV222FACTORY_gv1_typeAV223FACTORY_vfd_fdvAV224CONF_VFD_vfd_gainAV225CONF_VFD_vfd_maxAV226CONF_VFD_vfd_minAV227CONF_VFD_vfd_strAV228CONF_VFD_vfd_slgAV229CONF_VFD_vfdculmAV230CONF_VFD_vfdc20maAV231CONF_VFD_comp_100AV232SERVICE1_ser_passAV233SERVICE1_dw_intAV234SERVICE1_ewtdgainAV235SERVICE1_ctrl_dbAV236SERVICE1_gv1decdbAV237SERVICE1_gv1incdbAV238SERVICE1_dem_pdbAV239SERVICE1_dem_20maAV240SERVICE1_gv1_limAV241SERVICE1_ldramprtAV242SERVICE1_tmramprtAV243SERVICE1_dmp_dlyAV244SERVICE1_rcysh_dtAV245SERVICE1_rcyst_dtAV246SERVICE1_dmp_cldbAV247SERVICE1_dmp_opdbAV248SERVICE1_oilpvr_tAV249SERVICE1_sf_st_thAV250SERVICE1_wflow_tAV251SERVICE1_mbb_pfclAV252SERVICE1_max_gvAV253CFGSURGE_dts_maxAV254CFGSURGE_dts_minAV255CFGSURGE_gv1_smaxAV256CFGSURGE_gv1_sminAV257CFGSURGE_sgl_offAV258CFGSURGE_sghg_dbAV259CFGSURGE_sgl_hoffAV260CFGSURGE_sgl_shpfAV261CFGSURGE_sgl_spdfAV262CFGSURGE_surge_aAV263CFGSURGE_gvstp_sgAV264CFGSURGE_vfdstpsgAV265CFGSURGE_pr_maxAV266CFGSURGE_pr_minAV267CFGSURGE_atom_preAV268CFGSURGE_surg_delAV269CFGSURGE_surge_tAV270CFGLIMIT_cdfreezeAV271CFGLIMIT_evap_alAV272CFGLIMIT_cond_alAV273CFGLIMIT_evap_cutAV274CFGLIMIT_cond_cutAV275CFGLIMIT_cond_valAV276CFGLIMIT_cpov_loAV277CFGLIMIT_cpov_hiAV278CFGLIMIT_dgt_alrtAV279CFGLIMIT_ert_ovdtAV280CFGLIMIT_ert_tripAV281CFGLIMIT_mt_overAV282CFGLIMIT_tb_alertAV283CFGLIMIT_tb_tripAV284CFGLIMIT_cpcut_loAV285CFGLIMIT_cpcut_hiAV286CFGLIMIT_bri_minAV287CFGLIMIT_tb_alt2AV288CFGLIMIT_tb_trip2AV289CFGLIMIT_lwtp_spAV290CONF_SRD_off_selAV291CONF_SRD_pro_selAV292CONF_SRD_diff_maAV293CONF_SRD_gv11_25AV294CONF_SRD_gv11_50AV295CONF_SRD_gv11_75AV296CONF_SRD_srd1_25AV297CONF_SRD_srd1_50AV298CONF_SRD_srd1_75AV299CONF_SRD_lf1_100AV300CONF_SRD_lf1_25AV301CONF_SRD_lf2_25AV302CONF_SRD_peak_thAV303CONF_SRD_peak_ch3AV304CONF_OPT_hgbp_selAV305CONF_OPT_gv1stposAV306CONF_OPT_hpop_gv1AV307CONF_OPT_hgcl_gv1AV308CONF_OPT_hgb_toffAV309CONF_OPT_hgb_tonAV310CONF_OPT_hgbp_ldbAV311CONF_OPT_hdp_0AV312CONF_OPT_hdp_100AV313CONF_OPT_hdpv_minAV314CONF_OPT_gt_factAV315CONF_OPT_gv_srd_fAV316CONF_OPT_pd_tcfgAV317CONF_OPT_ice_termAV318CONF_OPT_leak_maAV319CONF_OPT_tfh_spAV320CONF_MS_slv_addrAV321CONF_MS_msl_selAV322CONF_MS_ms_ctrlAV323CONF_MS_ms_typeAV324CONF_MS_ms_posAV325CONF_MS_lead_selAV326CONF_MS_ms_perAV327CONF_MS_lag_shutAV328CONF_MS_pref_timAV329CONF_MS_un_thAV330CONF_MS_ll_bal_dAV331CONF_MS_lstr_timAV332CONF_MS_lstp_timAV333CONF_MS_lead_pulAV334CONF_MS_lag_miniAV335CONF_PRG_oilfl_thAV336CONF_PRG_oilch_ntAV337CONF_PRG_refgc_thAV338CONF_PRG_rch_cathAV339CONF_PRG_ep_dgapAV340CONF_PRG_beart_thAV341BACNET_networkAV342BACNET_identAV343SETPOINT_ecdw_spAV344SETPOINT_ecw_spAV345SETPOINT_ice_spAV346SETPOINT_lcdw_spAV347SETPOINT_lcw_spAV348SETPOINT_dem_baseAV349GENUNIT_CTRL_PNT_wrAV350GENUNIT_DEM_LIM_wrAV351GENUNIT_HC_SEL_wrBV1GENUNIT_statstopBV2GENUNIT_CHIL_S_S_rdBV3GENUNIT_CHIL_OCC_rdBV4GENUNIT_EMSTOP_rdBV5GENUNIT_loc_occBV6GENUNIT_ice_occBV7GENUNIT_ms_stspBV8GENUNIT_REM_RSTBV9GENUNIT_STP_OVERBV10INPUTS_STAR_AUXBV11INPUTS_RUN_AUXBV12INPUTS_DMP_FCBV13INPUTS_DMP_FOBV14INPUTS_HGBP_FCBV15INPUTS_HGBP_FOBV16INPUTS_HP_SWBV17INPUTS_REM_CONBV18INPUTS_E_STOPBV19INPUTS_ICE_CONBV20INPUTS_REM_LOCKBV21INPUTS_SAFETYBV22INPUTS_STARTFLTBV23INPUTS_FS_LOCKBV24INPUTS_TRIPRBV25INPUTS_bacdonglBV26OUTPUTS_ALMBV27OUTPUTS_ALEBV28OUTPUTS_COMP_SRBV29OUTPUTS_TRANSBV30OUTPUTS_DMP_CLBV31OUTPUTS_DMP_OPBV32OUTPUTS_GV1_DECBV33OUTPUTS_GV1_INCBV34OUTPUTS_HGBP_OFFBV35OUTPUTS_HGBP_ONBV36OUTPUTS_OIL_HEATBV37OUTPUTS_OIL_PUMPBV38OUTPUTS_TFR_HIGHBV39OUTPUTS_TFR_LOWBV40HYDRLIC_CDW_FLOWBV41HYDRLIC_CHWPBV42HYDRLIC_CDWPBV43HYDRLIC_CHW_FLOWBV44MODES_evapfrzeBV45MODES_condfrzeBV46ALARMRST_RST_ALMBV47CAPACTRL_cap_inhBV48CAPACTRL_cap_decBV49CAPACTRL_comp_runBV50OVERRIDE_cpov_flBV51OVERRIDE_dshov_flBV52OVERRIDE_lftov_flBV53OVERRIDE_sstov_flBV54OVERRIDE_mtov_flBV55OVERRIDE_tbov_flBV56OVERRIDE_lstov_flBV57OVERRIDE_dgtov_flBV58OVERRIDE_ampov_flBV59POWER_VFDC_HIBV60MAIISMH_phase_h1BV61MAIISMH_phase_h2BV62MAIISMH_phase_h3BV63MAIN_SRD_diffaultBV64MAIN_SRD_diff_almBV65ISM_MCFG_ism_cfltBV66ISM_MCFG_del_ismcBV67ISM_MCFG_scycd_enBV68ISM_MCFG_lfref_enBV69ISM_MCFG_gfp_enBV70MAISWRST_power_dnBV71MAISWRST_auto_rstBV72MAISWRST_sw_rstBV73MAIN_MS_ms_actBV74MAIN_MS_ll_commBV75MAIN_MS_lag_s_sBV76MAIN_MS_lag_recBV77MAIN_MS_ll_changBV78MAIN_MS_CAP_DECLBV79MAIN_MS_CAP_INHLBV80MAIN_MS_MST_RUNBV81MAIN_MS_EWT_OPTBV82MAIN_MS_DEM_SLCTBV83FACTORY_freq_60hBV84FACTORY_freecoolBV85FACTORY_hyd_optBV86FACTORY_heatreclBV87SERVICE1_ex_startBV88CFGLIMIT_cond_almBV89CONF_SRD_diff_optBV90CONF_OPT_astartBV91CONF_OPT_commsensBV92CONF_OPT_wp_optBV93CONF_OPT_hgbp_optBV94CONF_OPT_ice_optBV95CONF_OPT_ice_recyBV96CONF_OPT_leak_enBV97CONF_OPT_hdpv_optBV98CONF_MS_serct_flBV99CONF_PRG_prog_enBV100BACNET_bacenaBV101BACNET_bacunitBV102SETPOINT_EWT_OPTBV103GENUNIT_CHIL_S_S_wrBV104GENUNIT_EMSTOP_wrBV105GENUNIT_CHIL_OCC_wr
Integration notes
- Instance numbers changed between PIC 5 software versions: the version 3.3 manual (19XR-CLT-3T, our 19xr-pic5 list) prints a shorter 159-object table, and the same instance can hold a different point (e.g. AV 114 here is MAISURGE_dts_act, in 3.3 it is the control point command). Match the list to the software on the chiller.
- Commands use paired objects: the _rd copy is read-only status and the _wr copy (RW) is what the BMS writes.
- AV 80 is printed twice (VFD Speed Output mA, OUTPUTS_VFD_OUT, and Voltage Umbal Persist, ISM_MCFG_vu_per); only the first is kept here. Two IDs print without a colon (AV231, AV285) and are kept as AV 231 and AV 285.
- Tower Fan High Setpoint (AV 319) has no read/write entry and is listed read-only.
- Units printed as ^F are shown as Δ°F and ^psig as Δpsi (differences). Coded AVs carry their state texts as printed.
- Compressor status codes (Table A): 1 Off, 2 Control Test, 3 Pumpdown, 4 Lockout, 5 Recycle, 6 Tripout, 7 Timeout, 8-9 Prestart, 10 Startup, 11 Autorst, 12 Ramping, 13 Running, 14 Override, 15 Demand Shutdown.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 19XR (PIC 5, software version 3.0) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaEdge 19XR (PIC 5, software version 3.0)
How many BACnet points does the Carrier AquaEdge 19XR (PIC 5, software version 3.0) have?
This list has 455 BACnet objects: 350 analog values, 105 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaEdge 19XR (PIC 5, software version 3.0) BACnet points are writable?
14 of the 455 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaEdge 19XR (PIC 5, software version 3.0) BACnet documentation?
The source is AquaEdge 19XR Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with PIC 5 Controls Version 3.0 - Controls Operation and Troubleshooting (Appendix D: BACnet Option, Table C BACnet Point Table) (19XR-CLT-2T), revision 12-15, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/00/19XR-CLT-2T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaEdge 19XR (PIC 5, software version 3.0)?
Start with BV 103 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 105 GENUNIT_CHIL_OCC_wr (Network occupied command); BV 104 GENUNIT_EMSTOP_wr (Emergency stop command); AV 349 GENUNIT_CTRL_PNT_wr (Control point command); AV 350 GENUNIT_DEM_LIM_wr (Demand limit command, 10-100 %); AV 15 GENUNIT_ctl_mode (Control mode: Local, Network, Remote, Local Sched); AV 23 GENUNIT_ch_state (Chiller state number); AV 26 TEMP_LCW (Leaving chilled water temperature); AV 25 TEMP_ECW (Entering chilled water temperature); AV 104 ALARMRST_ALM_STAT (Alarm state: 0 normal, 1 alert, 2 alarm).
How do I enable BMS control of the Carrier AquaEdge 19XR (PIC 5, software version 3.0)?
In NETWORK control mode the chiller is started and stopped by the CHIL_S_S and CHIL_OCC points written over the network; EMSTOP can also shut it down. If the STOP OVERRIDE point in GENUNIT is enabled, the chiller cannot start.
How do I check these points on the real AquaEdge 19XR (PIC 5, software version 3.0)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaEdge 19XR Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with PIC 5 Controls Version 3.0 - Controls Operation and Troubleshooting (Appendix D: BACnet Option, Table C BACnet Point Table) · 19XR-CLT-2T · rev. 12-15. Object names, instances and units are reproduced as published; descriptions are our own.