- WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Packaged rooftop unit controller (BACnet option) · BACnet points list
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) BACnet points list
Updated 12 November 2026
This is the ComfortLink 6.x generation of the WeatherExpert 48/50N. BACnet MS/TP comes from a UPC Open controller in its own enclosure below the main control box, which reads the ComfortLink board over CCN. The list has 351 objects (AVs, BVs and one multistate value): occupancy, supply air and static pressure setpoints, air temperatures, pressures and flows, up to four compressors per circuit, heat, economizer, Motormaster and VFD values, Humidi-MiZer, airside linkage values, thermostat inputs, alarm flags and spare user values.
This page lists 351 BACnet objects for the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) — 129 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
- Equipment
- Packaged rooftop unit controller (BACnet option)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 351 (129 writable)
- Transport
- BACnet MS/TP
- Firmware
- ComfortLink 6.x
- Default device instance
- Network number 16101 followed by the MAC address (MAC 20 gives 1610120)
- Also known as
- 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
The BMS talks BACnet MS/TP to the UPC Open, which reads and writes the ComfortLink control over CCN. Clear Local Machine Disable, set the CCN schedule number for the occupancy source you want, then write occupancy and (for VAV) the supply air and duct static setpoints; read HVAC mode, temperatures, fan speed and alarm state. Values the BMS feeds in are forces that clear if not refreshed.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2008 | occ_status_1 | Occupied? (0 = no, 1 = yes); writable | Write |
| AV 3007 | sa_temp_stpt_1 | Supply air setpoint (VAV units) | Write |
| AV 3050 | sa_static_stpt_1 | Duct static pressure setpoint (VAV units) | Write |
| AV 1022 | hvac_mode_1 | HVAC mode as a number | Read |
| AV 2050 | sf_vfd_output_1 | Supply fan VFD speed, % | Read |
| AV 43 | ctrltemp_1 | Control temperature (RAT, SPT or zone) | Read |
| AV 10 | sat_1 | Supply air temperature leaving the fan | Read |
| BV 9 | alm_1 | Unit alarm state | Read |
| BV 105 | comm_lost_alm_1 | UPC lost CCN communication with the unit | Read |
Enable & remote start
The unit ships with Local Machine Disable (Service Test > STOP, BV 59 unitstop_1) set to Yes; set it to No before the unit runs. Occupancy follows the ComfortLink CCN schedule number (SCH.N): 0 = always occupied, 1 = local schedule, 65-99 = a CCN schedule. The points list makes Occupied? (BV 2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site.
Heartbeat & communication loss
The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.
Sensors & values from the BMS
Space Temperature (AV 137), Return Air Temperature (AV 135), Outside Air Temperature (AV 1003), Outside Air RH (AV 119), IAQ (AV 1009) and OAQ (AV 113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).
Network setup
- Set the MAC address on the UPC Open's Tens and Ones rotary switches; the controller reads switches, DIP switches and jumpers only at power-up.
- Device instance = network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120.
- BAS port: DS3 enable, DS4 E1-485, DS5-DS8 set to MSTP; baud on DS1-DS2 (9600, 19.2k, 38.4k or 76.8k, Carrier default 76.8k); 8N1 fixed. EIA-485 jumpers to EIA-485 and 2W.
- Fit a BT485 terminator on the first and last controller of the MS/TP segment.
- The UPC Open and the ComfortLink board must use the same CCN element and bus numbers (factory 1 and 0).
Watch out for
- Points depend on unit options (heat type, economizer, Humidi-MiZer, VFDs, airflow monitoring, controls expansion boards); objects for options not fitted carry no useful data.
- Thermostat inputs (Y1, Y2, W1, W2, G) and switch inputs are writable BVs (CCN forces).
- The user-defined analog and binary values are spare objects with no unit function.
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | override_time_remaining_1 | Zone Temp/Override Time Remaining | Read | ||
| AV | 2 | stpt_adj_range_1 | Setpoint Adjustment Range | Write | ||
| AV | 3 | castexv1_1 | Cir A EXV1 Suction Temp. | °F | Read | |
| AV | 4 | sh_a1_1 | Cir A EXV1 Superheat Tmp | Δ°F | Read | |
| AV | 5 | castexv2_1 | Cir A EXV2 Suction Temp. | °F | Read | |
| AV | 6 | sh_a2_1 | Cir A EXV2 Superheat Tmp | Δ°F | Read | |
| AV | 7 | lp_a_1 | Cir A Liquid Pressure | psig | Read | |
| AV | 8 | lt_a_1 | Cir A Liquid Temperature | °F | Read | |
| AV | 9 | dem_lim_1 | Active Demand Limit | % | Write | |
| AVmin | 10 | sat_1 | Air Temp Lvg Supply Fan | °F | Read | |
| AV | 11 | cct_1 | Air Temp Lvg Evap Coil | °F | Read | |
| AV | 12 | cbstexv1_1 | Cir B EXV1 Suction Temp. | °F | Read | |
| AV | 13 | sh_b1_1 | Cir B EXV1 Superheat Tmp | Δ°F | Read | |
| AV | 14 | bldgpmax_1 | BP VFD Maximum Speed | % | Write | |
| AV | 15 | sasptemp_1 | Temper Supply Air Setpt | °F | Write | |
| AV | 16 | byp_exv_1 | Bypass EXV Position | % | Read | |
| AV | 17 | bpso_1 | BP Setpoint Offset | in H2O | Write | |
| AV | 18 | cmpa1cap_1 | Compressor A1 Capacity | % | Read | |
| AV | 19 | hr_a3_1 | Compressor A3 Run Hours | hr | Read | |
| AV | 20 | cy_a3_1 | Compressor A3 Starts | Read | ||
| AV | 21 | cmpa3str_1 | Compressor A3 Strikes | Read | ||
| AV | 22 | smz_1 | Capacity Load Factor | Read | ||
| AV | 23 | z_gain_1 | Capacity Threshold Adj | Write | ||
| AV | 24 | hr_a1_1 | Compressor A1 Run Hours | hr | Read | |
| AV | 25 | cy_a1_1 | Compressor A1 Starts | Read | ||
| AV | 26 | cmpa1str_1 | Compressor A1 Strikes | Read | ||
| AV | 27 | hr_b3_1 | Compressor B3 Run Hours | hr | Read | |
| AV | 28 | hr_a2_1 | Compressor A2 Run Hours | hr | Read | |
| AV | 29 | cy_a2_1 | Compressor A2 Starts | Read | ||
| AV | 30 | cmpa2str_1 | Compressor A2 Strikes | Read | ||
| AV | 31 | cy_b3_1 | Compressor B3 Starts | Read | ||
| AV | 32 | hr_b1_1 | Compressor B1 Run Hours | hr | Read | |
| AV | 33 | cy_b1_1 | Compressor B1 Starts | Read | ||
| AV | 34 | cmpb1str_1 | Compressor B1 Strikes | Read | ||
| AV | 35 | cmpb3str_1 | Compressor B3 Strikes | Read | ||
| AV | 36 | hr_b2_1 | Compressor B2 Run Hours | hr | Read | |
| AV | 37 | cy_b2_1 | Compressor B2 Starts | Read | ||
| AV | 38 | cmpb2str_1 | Compressor B2 Strikes | Read | ||
| AV | 39 | cond_exv_1 | Condenser EXV Position | % | Read | |
| AV | 40 | oatlcomp_1 | Compressor Lockout Temp | °F | Write | |
| AV | 41 | ecn2cpos_1 | Econ2 Ret Cmd Position | % | Write | |
| AV | 42 | ecmincfm_1 | Econo Current Min. CFM | CFM | Read | |
| AVmin | 43 | ctrltemp_1 | Ctl.Temp RAT,SPT or ZONE | °F | Read | |
| AV | 44 | htsg_cap_1 | Current Running Capacity (Heat) | % | Read | |
| AV | 45 | ecminpos_1 | Econo Current Min. Pos. | % | Read | |
| AV | 46 | oacfmmax_1 | Economizer Min.Flow | CFM | Write | |
| AV | 47 | deltacfm_1 | Fan Track Control D.CFM | CFM | Read | |
| AV | 48 | dcfm_ram_1 | Fan Track Internal RAM | CFM | Write | |
| AV | 49 | dhcoolsp_1 | Dehumidify Cool Setpoint | °F | Write | |
| AV | 50 | dhrelhsp_1 | Dehumidify RH Setpoint | % | Write | |
| AV | 51 | dcfm_max_1 | Fan Track Max Clamp | CFM | Write | |
| AV | 52 | dcfm_adj_1 | Fan Track Max Correction | CFM | Write | |
| AV | 53 | dlswsp1_1 | Demand Limit Sw.1 Setpt. | % | Write | |
| AV | 54 | dlswsp2_1 | Demand Limit Sw.2 Setpt. | % | Write | |
| AV | 55 | htclcpos_1 | Ht.Coil Command Position | % | Read | |
| AV | 56 | daq_1 | Diff.Air Quality in PPM | Read | ||
| AV | 57 | hmzrcapc_1 | HumidiMizer Capacity | % | Read | |
| AV | 58 | oacfmmin_1 | IAQ Demand Vent Min.Flow | CFM | Write | |
| AV | 59 | dmdlcoff_1 | Dmd Level(-) Low Cool OFF | Δ°F | Write | |
| AV | 60 | dmdlhoff_1 | Dmd Level(-) Low Heat OFF | Δ°F | Write | |
| AV | 61 | dmdhcon_1 | Dmd Level(+) Hi Cool ON | Δ°F | Write | |
| AV | 62 | dmdhhon_1 | Dmd Level(+) Hi Heat ON | Δ°F | Write | |
| AV | 63 | dmdlcon_1 | Dmd Level Low Cool ON | Δ°F | Write | |
| AV | 64 | dmdlhon_1 | Dmd Level Low Heat ON | Δ°F | Write | |
| AV | 65 | htmg_cap_1 | Modulating Gas Capacity | % | Read | |
| AV | 66 | oacfm_1 | Outside Air CFM | CFM | Read | |
| AV | 67 | econocmd_1 | Econ1Out Act. Cmd Pos | % | Write | |
| AV | 68 | econpnt_1 | Economizer Control Point | °F | Read | |
| AV | 69 | racfm_1 | Return Air CFM | CFM | Read | |
| AV | 70 | economax_1 | Economizer Max.Position | % | Write | |
| AV | 71 | spe_1 | Space Enthalpy | Read | ||
| AV | 72 | sprh_1 | Space Relative Humidity | % | Write | |
| AV | 73 | sph_1 | SP High Alert Limit | Write | ||
| AV | 74 | spl_1 | SP Low Alert Limit | Write | ||
| AV | 75 | htsgcalc_1 | Staged Gas Capacity Calc | % | Read | |
| AV | 76 | edt_1 | Evaporator Discharge Tmp | °F | Read | |
| AV | 77 | fan_mode_1 | Fan Mode | Write | ||
| AV | 78 | sacfm_1 | Supply Air CFM | CFM | Read | |
| AV | 79 | vfd1amps_1 | VFD1 Actual Motor Amps | A | Read | |
| AV | 80 | vfd1freq_1 | VFD1 Actual Motor Freq | Read | ||
| AV | 81 | vfd1pwr_1 | VFD1 Actual Motor Power | kW | Read | |
| AV | 82 | vfd1rpm_1 | VFD1 Actual Motor RPM | Read | ||
| AV | 83 | hcsp_gap_1 | Heat-Cool Setpoint Gap | Δ°F | Write | |
| AV | 84 | vfd1kwh_1 | VFD1 Cumulative kWh | Read | ||
| AV | 85 | saspheat_1 | Heating Supply Air Setpt | °F | Write | |
| AV | 86 | vfd1runt_1 | VFD1 Cumulative Run Time | hr | Read | |
| AV | 87 | vfd1vdc_1 | VFD1 DC Bus Voltage | V | Read | |
| AV | 88 | vfd1lfc_1 | VFD1 Last Fault Code | Read | ||
| AV | 89 | vfd1vout_1 | VFD1 Output Voltage | V | Read | |
| AV | 90 | vfd1stat_1 | VFD1 Status Word 1 | Read | ||
| AV | 91 | vfd1temp_1 | VFD1 Transistor Temp (C) | Read | ||
| AV | 92 | vfd2amps_1 | VFD2 Actual Motor Amps | A | Read | |
| AV | 93 | vfd2freq_1 | VFD2 Actual Motor Freq | Read | ||
| AV | 94 | vfd2pwr_1 | VFD2 Actual Motor Power | Read | ||
| AV | 95 | vfd2rpm_1 | VFD2 Actual Motor RPM | Read | ||
| AV | 96 | vfd2kwh_1 | VFD2 Cumulative kWh | Read | ||
| AV | 97 | vfd2runt_1 | VFD2 Cumulative Run Time | hr | Read | |
| AV | 98 | iaqptime_1 | IAQ Purge Duration | min | Write | |
| AV | 99 | vfd2vdc_1 | VFD2 DC Bus Voltage | V | Read | |
| AV | 100 | vfd2lfc_1 | VFD2 Last Fault Code | Read | ||
| AV | 101 | iaqpntlo_1 | IAQ Purge OAT Lockout | °F | Write | |
| AV | 102 | vfd2vout_1 | VFD2 Output Voltage | V | Read | |
| AV | 103 | vfd2stat_1 | VFD2 Status Word 1 | Read | ||
| AV | 104 | vfd2temp_1 | VFD2 Transistor Temp (C) | Read | ||
| AV | 105 | bldgpmin_1 | VFD/Act. Min. Speed/Pos. | % | Write | |
| AV | 106 | cbstexv2_1 | Cir B EXV2 Suction Temp. | °F | Read | |
| AV | 107 | sh_b2_1 | Cir B EXV2 Superheat Tmp | Δ°F | Read | |
| AV | 108 | lp_b_1 | Cir B Liquid Pressure | psig | Read | |
| AV | 109 | lt_b_1 | Cir B Liquid Temperature | Read | ||
| AV | 110 | xv1aposp_1 | Circuit A EXV 1 Position | % | Read | |
| AV | 111 | xv2aposp_1 | Circuit A EXV 2 Position | % | Read | |
| AV | 112 | oaqlock_1 | OAQ Lockout Value | Write | ||
| AV | 113 | oaq_1 | OAQ - PPM Outdoor CO2 | Write | ||
| AV | 114 | occl_end_1 | Occupied Cool Mode End | °F | Read | |
| AV | 115 | occlstrt_1 | Occupied Cool Mode Start | °F | Read | |
| AV | 116 | ocht_end_1 | Occupied Heat Mode End | °F | Read | |
| AV | 117 | ochtstrt_1 | Occupied Heat Mode Start | °F | Read | |
| AV | 118 | oa_humr_1 | Outside Air Humidity Ratio | Read | ||
| AV | 119 | oarh_1 | Outside Air Relative Humidity | % | Write | |
| AV | 120 | otl_1 | Override Time Limit | hr | Write | |
| AV | 121 | xv1bposp_1 | Circuit B EXV 1 Position | % | Read | |
| AV | 122 | xv2bposp_1 | Circuit B EXV 2 Position | % | Read | |
| AV | 123 | hr_a4_1 | Compressor A4 Run Hours | hr | Read | |
| AV | 124 | cy_a4_1 | Compressor A4 Starts | Read | ||
| AV | 125 | cmpa4str_1 | Compressor A4 Strikes | Read | ||
| AV | 126 | hr_b4_1 | Compressor B4 Run Hours | hr | Read | |
| AV | 127 | cy_b4_1 | Compressor B4 Starts | Read | ||
| AV | 128 | cmpb4str_1 | Compressor B4 Strikes | Read | ||
| AV | 129 | ecn3cpos_1 | Econ3 Ret Cmd Position | % | Write | |
| AV | 130 | econ2_pos_1 | Econ 2 Out Act.Curr.Pos. | % | Read | |
| AV | 131 | limt_1 | Reset Limit | Δ°F | Write | |
| AV | 132 | rtio_1 | Reset Ratio | Write | ||
| AV | 133 | rae_1 | Return Air Enthalpy | Read | ||
| AV | 134 | rarh_1 | Return Air Relative Humidity | % | Write | |
| AV | 135 | rat_1 | Return Air Temperature | °F | Write | |
| AV | 136 | econ3_pos_1 | Econ 3 Out Act.Curr.Pos. | % | Read | |
| AV | 137 | spt_1 | Space Temperature | °F | Write | |
| AV | 138 | spto_1 | Space Temperature Offset | Δ°F | Write | |
| AV | 139 | spto_rng_1 | Space Temp Offset Range | Δ°F | Write | |
| AV | 140 | eacfm_1 | Exhaust Air CFM | CFM | Read | |
| AV | 141 | mf_dp_1 | Main Filter Delta Press | Read | ||
| AV | 142 | mf_stat_1 | Main Filter Status | % | Read | |
| AV | 143 | sprlimit_1 | SP Reset Limit | Write | ||
| AV | 144 | sprratio_1 | SP Reset Ratio | Write | ||
| AV | 145 | marh_1 | Mixed Air Relative Humidity | % | Write | |
| AV | 146 | mm_a_vfd_output_1 | MtrMaster A Commanded % | % | Read | |
| AV | 147 | mm_b_vfd_output_1 | MtrMaster B Commanded % | % | Read | |
| AV | 148 | pf_dp_1 | Post Filter Delta Press | Read | ||
| AV | 149 | pf_stat_1 | Post Filter Status | % | Read | |
| AV | 150 | lat1sgas_1 | Staged Gas LAT 1 | °F | Read | |
| AV | 151 | lat2sgas_1 | Staged Gas LAT 2 | °F | Read | |
| AV | 152 | lat3sgas_1 | Staged Gas LAT 3 | °F | Read | |
| AV | 153 | lat_sgas_1 | Staged Gas LAT Sum | °F | Read | |
| AV | 154 | limswtmp_1 | Staged Gas Limit Sw Temp | °F | Read | |
| AV | 155 | schedule_override_time_remaining_1 | Local Schedule/Override Time Remaining | Read | ||
| AV | 156 | sprstcfg_1 | Stat. Pres. Reset Config | Write | ||
| AV | 157 | spreset_1 | Static Pressure Reset | Write | ||
| AV | 158 | sasprset_1 | Supply Air Setpnt. Reset | Δ°F | Write | |
| AV | 159 | tcstcool_1 | Temp Comp Start Cool Factor | min | Write | |
| AV | 160 | tcstheat_1 | Temp Comp Start Heat Factor | min | Write | |
| AV | 161 | tempcool_1 | Tempering in Cool SASP | Δ°F | Write | |
| AV | 162 | temppurg_1 | Tempering Purge SASP | Δ°F | Write | |
| AV | 163 | tempvocc_1 | Tempering Vent Occ SASP | Δ°F | Write | |
| AV | 164 | tempvunc_1 | Temper Vent Unocc | Δ°F | Write | |
| AV | 166 | uefcntlo_1 | Un.Ec.Free Cool OAT Lock | °F | Write | |
| AV | 168 | uccl_end_1 | Unoccupied Cool Mode End | °F | Read | |
| AV | 169 | ucclstrt_1 | Unoccupied Cool Mode Start | °F | Read | |
| AV | 170 | ucht_end_1 | Unoccupied Heat Mode End | °F | Read | |
| AV | 171 | uchtstrt_1 | Unoccupied Heat Mode Start | °F | Read | |
| AV | 172 | uefc_cfg_1 | Unoc Econ Free Cool Cfg | Write | ||
| AV | 173 | uefctime_1 | Unoc Econ Free Cool Time | min | Write | |
| AV | 180 | vavocoff_1 | VAV Occ. Cool Off Delta | Δ°F | Write | |
| AV | 181 | vavocon_1 | VAV Occ. Cool On Delta | Δ°F | Write | |
| AV | 183 | dhvraoff_1 | Vent Reheat RAT Offset | Δ°F | Write | |
| AV | 184 | dhvht_sp_1 | Vent Reheat Setpoint | °F | Write | |
| AV | 186 | bldgpfso_1 | VFD/Act. Fire Speed/Pos. | % | Write | |
| AV | 187 | statpfso_1 | VFD-IGV Fire Speed Override | % | Write | |
| AV | 188 | statpmax_1 | VFD Maximum Speed | % | Write | |
| AV | 189 | statpmin_1 | VFD Minimum Speed | % | Write | |
| AV | 1003 | oat_1 | Outside Air Temperature | °F | Write | |
| AV | 1009 | iaq_1 | IAQ - PPM Indoor CO2 | Write | ||
| AV | 1016 | bldg_static_press_1 | Static Pressure | in H2O | Read | |
| AVmin | 1022 | hvac_mode_1 | HVAC Mode Numerical Form | Read | ||
| AV | 1023 | cool_capacity_1 | Current Running Capacity | % | Read | |
| AV | 1024 | cool_ctrl_point_1 | Cooling Control Point | °F | Read | |
| AV | 1025 | heat_ctrl_point_1 | Heating Control Point | Read | ||
| AV | 1027 | lvg_air_temeprature_1 | Leaving Air Temperature | °F | Read | |
| AV | 1028 | econ1_pos_1 | Econ 1 Out Act.Curr.Pos. | % | Read | |
| AV | 1030 | re_temp_1 | Controlling Return Air Temp | °F | Write | |
| AV | 1070 | bldg_static_press_1 | Building Pressure | in H2O | Read | |
| AV | 1500 | ma_temp_1 | Mixed Air Temperature | °F | Read | |
| AV | 1600 | suction_press_a_1 | Cir A Suction Pressure | psig | Read | |
| AV | 1601 | discharge_press_a_1 | Cir A Discharge Pressure | psig | Read | |
| AV | 1602 | sat_cond_temp_a_1 | Cir A Sat. Condensing Temperature | °F | Read | |
| AV | 1603 | sat_suction_temp_a_1 | Cir A Sat. Suction Temperature | °F | Read | |
| AV | 1604 | suction_press_b_1 | Cir B Suction Pressure | psig | Read | |
| AV | 1605 | discharge_press_b_1 | Cir B Discharge Pressure (DP_B) | psig | Read | |
| AV | 1606 | sat_cond_temp_b_1 | Cir B Sat. Condensing Temperature | °F | Read | |
| AV | 1607 | sat_suction_temp_b_1 | Cir B Sat. Suction Temperature | °F | Read | |
| AV | 2003 | heat_run_1 | Requested Heat Stage | Read | ||
| AV | 2007 | space_temp_1 | Controlling Space Temp | °F | Write | |
| AVmin | 2050 | sf_vfd_output_1 | Supply Fan VFD Speed | % | Read | |
| AV | 2075 | ef_vfd_output_1 | Exhaust Fan VFD Speed | % | Read | |
| AV | 2604 | link_ucsp_1 | Unoccupied Cooling Setpoint | Write | ||
| AV | 2605 | link_uhsp_1 | Unoccupied Heating Setpoint | Write | ||
| AV | 2607 | link_iaq_1 | Indoor Air CO2 | Read | ||
| AV | 2608 | link_sat_1 | Air Source Supply Air Temp | Read | ||
| AV | 2609 | link_ahu_oat_1 | Air Source Outdoor Air Temp | Read | ||
| AV | 2610 | link_ahu_static_1 | Air Source Static Pressure | Read | ||
| AV | 2611 | link_max_dmpr_1 | Linkage Max Damper Position | Write | ||
| AV | 2901 | user_analog_1_1 | User Defined Analog 1 | Write | ||
| AV | 2902 | user_analog_2_1 | User Defined Analog 2 | Write | ||
| AV | 2903 | user_analog_3_1 | User Defined Analog 3 | Write | ||
| AV | 2904 | user_analog_4_1 | User Defined Analog 4 | Write | ||
| AV | 2905 | user_analog_5_1 | User Defined Analog 5 | Write | ||
| AV | 3001 | occ_cl_stpt_1 | Cooling Occupied Setpoint | °F | Write | |
| AV | 3002 | occ_ht_stpt_1 | Heating Occupied Setpoint | °F | Write | |
| AV | 3003 | unocc_cl_stpt_1 | Cooling Unoccupied Setpoint | °F | Write | |
| AV | 3004 | unocc_ht_stpt_1 | Heating Unoccupied Setpoint | °F | Write | |
| AVmin | 3007 | sa_temp_stpt_1 | Supply Air Setpoint | °F | Write | |
| AVmin | 3050 | sa_static_stpt_1 | Static Pressure Setpoint | in H2O | Write | |
| AV | 3070 | bldg_press_stpt_1 | Building Pressure Setp. | in H2O | Write | |
| AV | 4005 | econ_min_1 | Economizer Min.Position | % | Write | |
| AV | 9006 | cool_demand_level_1 | System Cooling Demand Level | Read | ||
| AV | 9008 | econ_oat_lockout_1 | High OAT Lockout Temp | °F | Write | |
| AV | 9036 | heat_demand_level_1 | System Heating Demand Level | Read | ||
| AV | 80001 | mstr_oa_temp_1 | System OAT Master | °F | Read | |
| BV | 1 | oat_mstr_1 | Broadcast External Temp? | Read | ||
| BV | 2 | m684_1 | Dmd Level Map Select | Write | ||
| BV | 3 | circahps_1 | Circ A High Press.Switch | Read | ||
| BV | 4 | pb_enable_1 | Push Button Override | Write | ||
| BV | 5 | schedule_1 | Local Schedule | Read | ||
| BV | 6 | stpt_adj_enable_1 | Setpoint Adjustment Enable | Write | ||
| BV | 7 | dem_lmt_act_1 | System Demand Limiting | Read | ||
| BV | 8 | spt_sen_valid | SPT Sensor | Read | ||
| BVmin | 9 | alm_1 | Alarm State | Read | ||
| BV | 10 | capmode_1 | Capacity Clamp Mode | Read | ||
| BV | 11 | igcfan_1 | Fan request from IGC | Read | ||
| BV | 12 | circbhps_1 | Circ B High Press.Switch | Read | ||
| BV | 13 | cmpa3_1 | Compressor A3 Relay | Read | ||
| BV | 14 | cmpb3_1 | Compressor B3 Relay | Read | ||
| BV | 15 | condfan1_1 | Condenser Fan Output 1 | Read | ||
| BV | 16 | cmpa1_1 | Compressor A1 Relay | Read | ||
| BV | 17 | cmpa2_1 | Compressor A2 Relay | Read | ||
| BV | 18 | cmpb1_1 | Compressor B1 Relay | Read | ||
| BV | 19 | cmpb2_1 | Compressor B2 Relay | Read | ||
| BV | 20 | cool_off_1 | Cool Mode Not In Effect? | Read | ||
| BV | 21 | condfan2_1 | Condenser Fan Output 2 | Read | ||
| BV | 22 | sfonstat_1 | Supply Fan not on 30s ? | Read | ||
| BV | 23 | condfan3_1 | Condenser Fan Output 3 | Read | ||
| BV | 24 | condfan4_1 | Condenser Fan Output 4 | Read | ||
| BV | 25 | dbc_stat_1 | DBC - OAT Lockout? | Read | ||
| BV | 26 | modeadcv_1 | DCV Resetting Min Pos | Read | ||
| BV | 27 | ddbcstat_1 | DDBC- OAT > RAT Lockout? | Read | ||
| BV | 28 | dec_stat_1 | DEC - Diff.Enth.Lockout? | Read | ||
| BV | 29 | dhdisabl_1 | Dehumid. Disabled Econ.? | Read | ||
| BV | 30 | dhdiscin_1 | Dehumidify Input | Write | ||
| BV | 31 | modedmlt_1 | Demand Limit In Effect | Read | ||
| BV | 32 | dew_stat_1 | DEW - OA Dewpt.Lockout? | Read | ||
| BV | 33 | aps_1 | Air Pressure Switch | Read | ||
| BV | 34 | econunav_1 | Econ Act. Unavailable? | Read | ||
| BV | 35 | dhecdisa_1 | Econ disable in DH mode? | Write | ||
| BV | 36 | ecactive_1 | Economizer Active? | Read | ||
| BV | 37 | modeoccp_1 | Currently Occupied | Read | ||
| BV | 38 | econforc_1 | Economizer Forced ? | Read | ||
| BV | 39 | mode_occ_1 | Currently Occupied ? | Read | ||
| BV | 40 | enth_1 | Enth. Switch Read High ? | Write | ||
| BV | 41 | frz_1 | Freeze Status Switch | Write | ||
| BV | 42 | econheld_1 | Econ Recovery Hold Off? | Read | ||
| BV | 44 | edt_stat_1 | EDT Sensor Bad ? | Read | ||
| BV | 45 | emstop_1 | Emergency Stop | Write | ||
| BV | 46 | humidrly_1 | Humidifier Relay | Read | ||
| BV | 47 | hum3wval_1 | HumidiMizer 3-way Valve | Read | ||
| BV | 48 | pps_1 | Plenum Press.Safety Sw. | Write | ||
| BV | 49 | condfan5_1 | Condenser Fan Output 5 | Read | ||
| BV | 50 | sfs_shut_1 | Fan Fail Shuts Down Unit | Write | ||
| BV | 51 | econ1unav_1 | Econ1 Act. Unavailable? | Read | ||
| BV | 52 | hs1_1 | Heat Relay 1 | Read | ||
| BV | 53 | hs2_1 | Heat Relay 2 | Read | ||
| BV | 54 | spt_over_1 | SPT Override Enabled ? | Write | ||
| BV | 55 | limtmode_1 | Hi Limit Switch Tmp Mode | Read | ||
| BV | 56 | modeiqpg_1 | IAQ Pre-Occ Purge Active | Read | ||
| BV | 57 | econ2unav_1 | Econ2 Act. Unavailable? | Read | ||
| BV | 58 | latcmode_1 | LAT Cutoff Mode | Read | ||
| BV | 59 | unitstop_1 | Local Machine Disable | Write | ||
| BV | 60 | econ3unav_1 | Econ3 Act. Unavailable? | Read | ||
| BV | 61 | low_temp_1 | Low Temp Cap Override | Read | ||
| BV | 62 | htrclrly_1 | Heat Reclaim Relay | Read | ||
| BV | 63 | modelock_1 | Mech Cooling Locked Out | Read | ||
| BV | 64 | hs7_1 | Heat Relay 7 | Read | ||
| BV | 65 | hs8_1 | Heat Relay 8 | Read | ||
| BV | 66 | hs9_1 | Heat Relay 9 | Read | ||
| BV | 67 | oaecstat_1 | OAEC- OA Enth Lockout? | Read | ||
| BV | 68 | oaqlockd_1 | OAQ Lockout In Effect ? | Read | ||
| BV | 69 | oat_stat_1 | OAT Sensor Bad ? | Read | ||
| BV | 70 | htoccena_1 | Occupied Heating Enabled | Write | ||
| BV | 71 | hs10_1 | Heat Relay 10 | Read | ||
| BV | 72 | pflts_status_1 | Post Filter Status Input | Write | ||
| BV | 73 | pebyin_1 | Power Exhaust Bypass Input | Read | ||
| BV | 74 | pebyrly_1 | Power Exhaust Bypass Relay | Read | ||
| BV | 75 | pulldown_1 | Pull Down Cap Override | Read | ||
| BV | 76 | hs3_1 | Relay 3 W1 Gas Valve 2 | Read | ||
| BV | 77 | hs4_1 | Relay 4 W2 Gas Valve 2 | Read | ||
| BV | 78 | hs5_1 | Relay 5 W1 Gas Valve 3 | Read | ||
| BV | 79 | hs6_1 | Relay 6 W2 Gas Valve 3 | Read | ||
| BV | 80 | pwrfault_1 | Power Fault Input | Read | ||
| BV | 81 | rmtin_1 | Remote Input State | Write | ||
| BV | 82 | sfbyin_1 | Supply Fan Bypass Input | Read | ||
| BV | 83 | sfbyrly_1 | Supply Fan Bypass Relay | Read | ||
| BV | 86 | slo_chng_1 | Slow Change Cap Override | Read | ||
| BV | 87 | softstop_1 | Soft Stop Request | Write | ||
| BV | 88 | a700_1 | Air Temp Lvg Supply Fan Thermistor Failure | Read | ||
| BV | 93 | modesars_1 | Supply Air Reset | Read | ||
| BV | 95 | sfs_1 | Supply Fan Status Switch | Write | ||
| BV | 96 | modetcst_1 | Temp Compensated Start | Read | ||
| BV | 97 | modetovr_1 | Timed Override In Effect | Read | ||
| BV | 98 | overlast_1 | Timed-Override in Effect | Read | ||
| BVmin | 105 | comm_lost_alm_1 | Element Communications Alarm | Read | ||
| BV | 114 | a404_1 | Fire Shut Down Emergency Mode | Read | ||
| BV | 116 | t211_1 | Static Pressure Transducer Failure | Read | ||
| BV | 117 | a152_1 | Unit Down Due to Failure | Read | ||
| BV | 127 | element_alarm_1 | Equipment Alarm | Read | ||
| BV | 1005 | firedown_status_1 | Fire Shutdown Input | Write | ||
| BV | 1006 | dmd_sw1_1 | Demand Limit Switch 1 | Write | ||
| BV | 1007 | dmd_sw2_1 | Demand Limit Switch 2 | Write | ||
| BV | 1017 | y1_input_1 | Thermostat Y1 Input | Write | ||
| BV | 1018 | y2_input_1 | Thermostat Y2 Input | Write | ||
| BV | 1019 | w1_input_1 | Thermostat W1 Input | Write | ||
| BV | 1020 | w2_input_1 | Thermostat W2 Input | Write | ||
| BV | 1021 | g_input_1 | Thermostat G Input | Write | ||
| BV | 1026 | heat_interlock_relay_1 | Heat Interlock Relay | Write | ||
| BV | 1050 | iaq_status_1 | IAQ - Discrete Input | Write | ||
| BV | 1052 | filter_status_1 | Filter Status Input | Write | ||
| BV | 1060 | smk_evac_1 | Evacuation Input | Write | ||
| BV | 1061 | smk_press_1 | Pressurization Input | Write | ||
| BV | 1062 | smk_purg_1 | Smoke Purge Input | Write | ||
| BV | 2004 | sfan_forc_1 | Supply Fan Request | Write | ||
| BVmin | 2008 | occ_status_1 | Occupied? | Write | ||
| BV | 2014 | aux_relay_1 | Remote Alarm/Aux Relay | Write | ||
| BV | 2601 | a_link_status_1 | Airside Linkage | Read | ||
| BV | 2602 | a_link_occ_status | Occupancy Status | Read | ||
| BV | 2603 | a_link_opt_start_1 | Linkage Optimal Start | Read | ||
| BV | 2604 | a_link_config_error_1 | Linkage Config Error/Data Invalid | Read | ||
| BV | 2911 | user_binary_1_1 | User Defined Binary 1 | Write | ||
| BV | 2912 | user_binary_2_1 | User Defined Binary 2 | Write | ||
| BV | 2913 | user_binary_3_1 | User Defined Binary 3 | Write | ||
| BV | 2914 | user_binary_4_1 | User Defined Binary 4 | Write | ||
| BV | 2915 | user_binary_5_1 | User Defined Binary 5 | Write | ||
| BV | 2999 | element_stat_1 | Element Comm Status | Read | ||
| BV | 7030 | air_linkage_fail_1 | Airside Linkage Alarm | Read | ||
| MV | 2005 | link_ahu_mode_1 | Air Source Mode | Read |
No points match these filters.
Object ID lookup: Carrier WeatherExpert 48/50N2-N9 Rooftop point IDs by name
AV1override_time_remaining_1AV2stpt_adj_range_1AV3castexv1_1AV4sh_a1_1AV5castexv2_1AV6sh_a2_1AV7lp_a_1AV8lt_a_1AV9dem_lim_1AV10sat_1AV11cct_1AV12cbstexv1_1AV13sh_b1_1AV14bldgpmax_1AV15sasptemp_1AV16byp_exv_1AV17bpso_1AV18cmpa1cap_1AV19hr_a3_1AV20cy_a3_1AV21cmpa3str_1AV22smz_1AV23z_gain_1AV24hr_a1_1AV25cy_a1_1AV26cmpa1str_1AV27hr_b3_1AV28hr_a2_1AV29cy_a2_1AV30cmpa2str_1AV31cy_b3_1AV32hr_b1_1AV33cy_b1_1AV34cmpb1str_1AV35cmpb3str_1AV36hr_b2_1AV37cy_b2_1AV38cmpb2str_1AV39cond_exv_1AV40oatlcomp_1AV41ecn2cpos_1AV42ecmincfm_1AV43ctrltemp_1AV44htsg_cap_1AV45ecminpos_1AV46oacfmmax_1AV47deltacfm_1AV48dcfm_ram_1AV49dhcoolsp_1AV50dhrelhsp_1AV51dcfm_max_1AV52dcfm_adj_1AV53dlswsp1_1AV54dlswsp2_1AV55htclcpos_1AV56daq_1AV57hmzrcapc_1AV58oacfmmin_1AV59dmdlcoff_1AV60dmdlhoff_1AV61dmdhcon_1AV62dmdhhon_1AV63dmdlcon_1AV64dmdlhon_1AV65htmg_cap_1AV66oacfm_1AV67econocmd_1AV68econpnt_1AV69racfm_1AV70economax_1AV71spe_1AV72sprh_1AV73sph_1AV74spl_1AV75htsgcalc_1AV76edt_1AV77fan_mode_1AV78sacfm_1AV79vfd1amps_1AV80vfd1freq_1AV81vfd1pwr_1AV82vfd1rpm_1AV83hcsp_gap_1AV84vfd1kwh_1AV85saspheat_1AV86vfd1runt_1AV87vfd1vdc_1AV88vfd1lfc_1AV89vfd1vout_1AV90vfd1stat_1AV91vfd1temp_1AV92vfd2amps_1AV93vfd2freq_1AV94vfd2pwr_1AV95vfd2rpm_1AV96vfd2kwh_1AV97vfd2runt_1AV98iaqptime_1AV99vfd2vdc_1AV100vfd2lfc_1AV101iaqpntlo_1AV102vfd2vout_1AV103vfd2stat_1AV104vfd2temp_1AV105bldgpmin_1AV106cbstexv2_1AV107sh_b2_1AV108lp_b_1AV109lt_b_1AV110xv1aposp_1AV111xv2aposp_1AV112oaqlock_1AV113oaq_1AV114occl_end_1AV115occlstrt_1AV116ocht_end_1AV117ochtstrt_1AV118oa_humr_1AV119oarh_1AV120otl_1AV121xv1bposp_1AV122xv2bposp_1AV123hr_a4_1AV124cy_a4_1AV125cmpa4str_1AV126hr_b4_1AV127cy_b4_1AV128cmpb4str_1AV129ecn3cpos_1AV130econ2_pos_1AV131limt_1AV132rtio_1AV133rae_1AV134rarh_1AV135rat_1AV136econ3_pos_1AV137spt_1AV138spto_1AV139spto_rng_1AV140eacfm_1AV141mf_dp_1AV142mf_stat_1AV143sprlimit_1AV144sprratio_1AV145marh_1AV146mm_a_vfd_output_1AV147mm_b_vfd_output_1AV148pf_dp_1AV149pf_stat_1AV150lat1sgas_1AV151lat2sgas_1AV152lat3sgas_1AV153lat_sgas_1AV154limswtmp_1AV155schedule_override_time_remaining_1AV156sprstcfg_1AV157spreset_1AV158sasprset_1AV159tcstcool_1AV160tcstheat_1AV161tempcool_1AV162temppurg_1AV163tempvocc_1AV164tempvunc_1AV166uefcntlo_1AV168uccl_end_1AV169ucclstrt_1AV170ucht_end_1AV171uchtstrt_1AV172uefc_cfg_1AV173uefctime_1AV180vavocoff_1AV181vavocon_1AV183dhvraoff_1AV184dhvht_sp_1AV186bldgpfso_1AV187statpfso_1AV188statpmax_1AV189statpmin_1AV1003oat_1AV1009iaq_1AV1016bldg_static_press_1AV1022hvac_mode_1AV1023cool_capacity_1AV1024cool_ctrl_point_1AV1025heat_ctrl_point_1AV1027lvg_air_temeprature_1AV1028econ1_pos_1AV1030re_temp_1AV1070bldg_static_press_1AV1500ma_temp_1AV1600suction_press_a_1AV1601discharge_press_a_1AV1602sat_cond_temp_a_1AV1603sat_suction_temp_a_1AV1604suction_press_b_1AV1605discharge_press_b_1AV1606sat_cond_temp_b_1AV1607sat_suction_temp_b_1AV2003heat_run_1AV2007space_temp_1AV2050sf_vfd_output_1AV2075ef_vfd_output_1AV2604link_ucsp_1AV2605link_uhsp_1AV2607link_iaq_1AV2608link_sat_1AV2609link_ahu_oat_1AV2610link_ahu_static_1AV2611link_max_dmpr_1AV2901user_analog_1_1AV2902user_analog_2_1AV2903user_analog_3_1AV2904user_analog_4_1AV2905user_analog_5_1AV3001occ_cl_stpt_1AV3002occ_ht_stpt_1AV3003unocc_cl_stpt_1AV3004unocc_ht_stpt_1AV3007sa_temp_stpt_1AV3050sa_static_stpt_1AV3070bldg_press_stpt_1AV4005econ_min_1AV9006cool_demand_level_1AV9008econ_oat_lockout_1AV9036heat_demand_level_1AV80001mstr_oa_temp_1BV1oat_mstr_1BV2m684_1BV3circahps_1BV4pb_enable_1BV5schedule_1BV6stpt_adj_enable_1BV7dem_lmt_act_1BV8spt_sen_validBV9alm_1BV10capmode_1BV11igcfan_1BV12circbhps_1BV13cmpa3_1BV14cmpb3_1BV15condfan1_1BV16cmpa1_1BV17cmpa2_1BV18cmpb1_1BV19cmpb2_1BV20cool_off_1BV21condfan2_1BV22sfonstat_1BV23condfan3_1BV24condfan4_1BV25dbc_stat_1BV26modeadcv_1BV27ddbcstat_1BV28dec_stat_1BV29dhdisabl_1BV30dhdiscin_1BV31modedmlt_1BV32dew_stat_1BV33aps_1BV34econunav_1BV35dhecdisa_1BV36ecactive_1BV37modeoccp_1BV38econforc_1BV39mode_occ_1BV40enth_1BV41frz_1BV42econheld_1BV44edt_stat_1BV45emstop_1BV46humidrly_1BV47hum3wval_1BV48pps_1BV49condfan5_1BV50sfs_shut_1BV51econ1unav_1BV52hs1_1BV53hs2_1BV54spt_over_1BV55limtmode_1BV56modeiqpg_1BV57econ2unav_1BV58latcmode_1BV59unitstop_1BV60econ3unav_1BV61low_temp_1BV62htrclrly_1BV63modelock_1BV64hs7_1BV65hs8_1BV66hs9_1BV67oaecstat_1BV68oaqlockd_1BV69oat_stat_1BV70htoccena_1BV71hs10_1BV72pflts_status_1BV73pebyin_1BV74pebyrly_1BV75pulldown_1BV76hs3_1BV77hs4_1BV78hs5_1BV79hs6_1BV80pwrfault_1BV81rmtin_1BV82sfbyin_1BV83sfbyrly_1BV86slo_chng_1BV87softstop_1BV88a700_1BV93modesars_1BV95sfs_1BV96modetcst_1BV97modetovr_1BV98overlast_1BV105comm_lost_alm_1BV114a404_1BV116t211_1BV117a152_1BV127element_alarm_1BV1005firedown_status_1BV1006dmd_sw1_1BV1007dmd_sw2_1BV1017y1_input_1BV1018y2_input_1BV1019w1_input_1BV1020w2_input_1BV1021g_input_1BV1026heat_interlock_relay_1BV1050iaq_status_1BV1052filter_status_1BV1060smk_evac_1BV1061smk_press_1BV1062smk_purg_1BV2004sfan_forc_1BV2008occ_status_1BV2014aux_relay_1BV2601a_link_status_1BV2602a_link_occ_statusBV2603a_link_opt_start_1BV2604a_link_config_error_1BV2911user_binary_1_1BV2912user_binary_2_1BV2913user_binary_3_1BV2914user_binary_4_1BV2915user_binary_5_1BV2999element_stat_1BV7030air_linkage_fail_1MV2005link_ahu_mode_1
Integration notes
- Form 48/50N-6T (4-18) for ComfortLink 6.x units. All 164 objects of the ComfortLink 11.x list (48-50N-8T) are also here; this older list adds 187 more, mostly individual alarm flags, linkage values and service data.
- Object names end in _1. Descriptions are the printed point descriptions, with the CCN point name added where two rows share a description.
- Econ3 Act. Unavailable? is printed as BV60 (no colon) and kept as BV 60. The Linkage Collector row (link_collector_1) prints no object ID and is left out. Cir B Discharge Pressure (AV 1605) is printed twice and kept once.
- Air Source Mode is printed as MSV:2005 (mapped as MV 2005).
- Units printed as dF are shown as °F; °^F as Δ°F (temperature differences). Ranges and defaults are left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
How many BACnet points does the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) have?
This list has 351 BACnet objects: 227 analog values, 123 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) BACnet points are writable?
129 of the 351 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) BACnet documentation?
The source is WeatherExpert 48/50N2,N3,N4,N5,N6,N7,N8,N9 Packaged Rooftop Cooling Units with Gas Heat, Optional Electric Heat, or Hydronic Heat and ComfortLink Controls Version 6.x - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix F: BACnet Communication Option, Network Points List) (48/50N-6T), revision 4-18, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0C/48_50N-6T.pdf.
What are the minimum BACnet points to integrate the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)?
Start with BV 2008 occ_status_1 (Occupied? (0 = no, 1 = yes); writable); AV 3007 sa_temp_stpt_1 (Supply air setpoint (VAV units)); AV 3050 sa_static_stpt_1 (Duct static pressure setpoint (VAV units)); AV 1022 hvac_mode_1 (HVAC mode as a number); AV 2050 sf_vfd_output_1 (Supply fan VFD speed, %); AV 43 ctrltemp_1 (Control temperature (RAT, SPT or zone)); AV 10 sat_1 (Supply air temperature leaving the fan); BV 9 alm_1 (Unit alarm state); BV 105 comm_lost_alm_1 (UPC lost CCN communication with the unit).
How do I enable BMS control of the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)?
The unit ships with Local Machine Disable (Service Test > STOP, BV 59 unitstop_1) set to Yes; set it to No before the unit runs. Occupancy follows the ComfortLink CCN schedule number (SCH.N): 0 = always occupied, 1 = local schedule, 65-99 = a CCN schedule. The points list makes Occupied? (BV 2008) writable, but the manual does not describe how a write interacts with SCH.N; test it on site.
Does the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option) need a BACnet heartbeat or have a communication timeout?
The manual says forces at CCN priority 7 clear unless rewritten in time: outside air temperature, outside RH, outside air quality and static pressure reset after 30 minutes, return air and space temperature after 3 minutes.
Can the BMS supply sensor values to the Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)?
Space Temperature (AV 137), Return Air Temperature (AV 135), Outside Air Temperature (AV 1003), Outside Air RH (AV 119), IAQ (AV 1009) and OAQ (AV 113) are writable. Refresh them within the force timeouts (3 min for space and return temperature, 30 min for outdoor values).
How do I check these points on the real WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: WeatherExpert 48/50N2,N3,N4,N5,N6,N7,N8,N9 Packaged Rooftop Cooling Units with Gas Heat, Optional Electric Heat, or Hydronic Heat and ComfortLink Controls Version 6.x - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix F: BACnet Communication Option, Network Points List) · 48/50N-6T · rev. 4-18. Object names, instances and units are reproduced as published; descriptions are our own.