VVT bypass damper / duct static pressure controller (terminal zoning) · BACnet points list

Carrier VVT Bypass II BACnet points list

Updated 4 November 2026

Short answer

The VVT Bypass II holds supply duct static pressure in a Carrier VVT system by modulating its own bypass damper actuator, an external actuator or the air source fan VFD through a 0-10 Vdc output. It talks BACnet MS/TP or BACnet ARC156 and is normally linked to the VVT Master and air source. Its BACnet points are mostly read-only status: static pressure, the controlling setpoint, damper or VFD output, supply air temperature and two alarms.

This page lists 19 BACnet objects for the Carrier VVT Bypass II — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
VVT Bypass II
Equipment
VVT bypass damper / duct static pressure controller (terminal zoning)
Equipment type
VAV boxes & fan coils
BACnet objects
19 (6 writable)
Transport
BACnet MS/TP, BACnet ARC156
Firmware
Not stated
Also known as
OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01
Source document
VVT Bypass II Controller Installation and Start-up Guide (Appendix B: BACnet points list) · 11-808-601-01 · rev. 2026-01-28
Download CSV 19 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier VVT Bypass II

Integration in brief

This is a monitoring device for a BMS: the static pressure loop runs inside the controller and through Carrier linkage. Read duct static pressure, the setpoint in use and the damper or VFD output, and alarm on supply air temperature and linkage failure.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1016static_pressMeasured supply duct static pressure, in H2ORead
AV 1015sys_press_stptStatic pressure setpoint currently in useRead
AV 1013dpr_posBypass damper position, %Read
AV 1014vfd_outputFan VFD output when VFD control is set, %Read
AV 1008sa_tempSupply air temperatureRead
BV 1013lat_controlRaising pressure to protect against SAT limitsRead
BV 7004sat_alarmSupply air temperature outside the SAT limitsRead
BV 7030air_linkage_failLinkage to the air source lostRead

Network setup

Watch out for

Carrier VVT Bypass II BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

19 of 19 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier VVT Bypass II BACnet Points List
DescriptionStates
AVmin1008sa_tempSupply Air Temperature°FRead
AVmin1013dpr_posDamper Position%Read
AVmin1014vfd_outputVFD output%Read
AVmin1015sys_press_stptControlling Pressure Setpointin H2ORead
AVmin1016static_pressStatic Pressure - Prime Variablein H2ORead
AV2608link_satAir Source Supply Air Temp°FRead
AV3016press_hysteresisPressure Control Deadband (default 0.05)in H2OWrite
AV5002lat_airflow_incLAT Airflow Increase%Read
AV5003max_press_stptMaximum Duct Pressure Setpointin H2ORead
AV9007start_delayPower Fail Restart Delay (default 60)secWrite
AV83003sat_cl_minMinimum Cooling SAT (default 45)°FWrite
AV83004sat_ht_maxMaximum Heating SAT (default 120)°FWrite
BVmin1013lat_controlLAT ControlRead0=Off; 1=Active
BV2601a_link_statusAirside Linkage StatusRead0=Not Active; 1=Active
BVmin7004sat_alarmSupply Air Temperature AlarmRead0=Normal; 1=Alarm
BVmin7030air_linkage_failAirside Linkage AlarmRead0=Normal; 1=Alarm
BV99002ctrl_typeControl Device Type (default Inactive (0))Write0=Actuator; 1=VFD
BV99003auto_adjustAutomatic Deadband Adjustment (default Active (1))Write0=Disable; 1=Enable
MV2005link_ahu_modeAir Source ModeRead1=Off; 2=Warmup; 3=Heat; 4=Cool; 5=Freecool; 6=Pressure; 7=Evac; 8=Vent
Object ID lookup: Carrier VVT Bypass II point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VVT Bypass II and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier VVT Bypass II

How many BACnet points does the Carrier VVT Bypass II have?

This list has 19 BACnet objects: 12 analog values, 6 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier VVT Bypass II BACnet points are writable?

6 of the 19 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier VVT Bypass II BACnet documentation?

The source is VVT Bypass II Controller Installation and Start-up Guide (Appendix B: BACnet points list) (11-808-601-01), revision 2026-01-28, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/02/11-808-601-01.pdf.

What are the minimum BACnet points to integrate the Carrier VVT Bypass II?

Start with AV 1016 static_press (Measured supply duct static pressure, in H2O); AV 1015 sys_press_stpt (Static pressure setpoint currently in use); AV 1013 dpr_pos (Bypass damper position, %); AV 1014 vfd_output (Fan VFD output when VFD control is set, %); AV 1008 sa_temp (Supply air temperature); BV 1013 lat_control (Raising pressure to protect against SAT limits); BV 7004 sat_alarm (Supply air temperature outside the SAT limits); BV 7030 air_linkage_fail (Linkage to the air source lost).

How do I check these points on the real VVT Bypass II?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: VVT Bypass II Controller Installation and Start-up Guide (Appendix B: BACnet points list) · 11-808-601-01 · rev. 2026-01-28. Object names, instances and units are reproduced as published; descriptions are our own.