Water-to-water heat pump controller · BACnet points list
Carrier W2W Open BACnet points list
Updated 4 November 2026
W2W Open is Carrier's i-Vu Open controller for water-to-water heat pumps. It heats or cools the load water to a chilled or hot water supply setpoint with up to 4 capacity stages, and DIP switches select BACnet MS/TP (the default), BACnet ARC156, Modbus or N2 (LonWorks by option card). The list has 76 objects: water setpoints and temperatures, compressor capacity and stages, pump status, enables, OA reset and demand-level settings, alarms and the 'system' points a BAS writes.
This page lists 76 BACnet objects for the Carrier W2W Open — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- W2W Open
- Equipment
- Water-to-water heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 76 (28 writable)
- Transport
- BACnet MS/TP, BACnet ARC156
- Firmware
- Not stated
- Default device instance
- 16101xx (xx = rotary switch address)
- Also known as
- Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01
Instance calculator. This list prints one unit; the other units follow a formula. Carrier Open controllers (RTU Open, WSHP Open, UPC Open...) instance calculator →
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier W2W Open
Set the controller for BACnet MS/TP with its DIP switches and rotary address. The unit is occupied by default and holds the load water at the chilled or hot water supply setpoint; the BAS commands occupancy through keypad_ovrde and writes the water setpoints. Outdoor air, T1 or water temperatures from the BMS go into the system_* points at priority 16.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1001 | keypad_ovrde | BAS occupancy command: occupied/unoccupied | Write |
| BV 9001 | shutdown | Network shutdown command | Write |
| AV 3024 | chws_setpoint | Chilled water supply setpoint | Write |
| AV 3023 | hws_setpoint | Hot water supply setpoint | Write |
| MV 2002 | run_status | Current system mode | Read |
| AV 1020 | lvg_load_wtr_temp | Leaving load water temperature | Read |
| AV 1019 | ent_load_wtr_temp | Entering load water temperature | Read |
| AV 5002 | total_comp_cap | Total compressor capacity, % | Read |
| BV 7013 | comp_alarm | Compressor status alarm | Read |
| BV 7048 | equip_alarm | General equipment alarm | Read |
Enable & remote start
The controller is occupied by default. A third-party BAS sets occupancy by writing BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied; the sequence says this takes precedence over the other occupancy sources, while the system-point table says occupancy control must be set to 3 (BAS On/Off). No heating or cooling runs while unoccupied. Cool Enable (BV:1011) and Heat Enable (BV:1012) must be Enable; Shutdown (BV:9001) stops the unit.
Heartbeat & communication loss
No general heartbeat. The guide gives refresh windows for the generic system points (OAT 5 min / 60 min, space RH 5 min / 10 min); a network value is only used while it is refreshed in time.
Sensors & values from the BMS
Write system_oat (AV:1901), system_rh (AV:1904), system_t1_temp (AV:1909) or the system water temperatures (AV:1910-1912) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so confirm a write by reading the control point (e.g. oa_temp, space_rh) at least 30 s later. System T1 is needed when Control Mode Selection uses T1 for heat/cool changeover.
Network setup
- MS/TP MAC address on rotary switches MSB (SW1) and LSB (SW2), 01-99; switch changes take effect after a power cycle.
- Device instance is generated as 16101xx (16 = Carrier vendor ID, xx = rotary address).
- SW3 DIP switches set protocol and baud (9600/19.2k/38.4k/76.8k, 76.8k default); 8N1 fixed. Network on port J19.
- Max Masters defaults to 127 and Max Info Frames to 10 (Equipment Touch). The controller counts as a full load on the MS/TP bus.
Watch out for
- System points must be written at priority 16; other priorities are ignored.
- Demand levels widen the water setpoints cumulatively (level 3 = level 1 + 2 + 3 adjustments); the demand level points themselves are read-only here.
- Only controllers set as MS/TP masters answer Who-Is.
- Multi-unit master/slave setups add linkage points (cw_link_status, mr_comm_fail) that only matter in those systems.
Carrier W2W Open BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 2020 | comp_stages | Active Compressor Stages | Read | ||
| AVmin | 3024 | chws_setpoint | Chilled Water Supply Setpoint (default 44) | °F | Write | |
| AV | 5001 | comp_cap | Compressor Capacity | % | Read | |
| AV | 9002 | oat_cl_lockout | Cooling Lockout Temperature (default 45) | °F | Write | |
| AV | 3005 | eff_cl_stpt | Effective Cool Setpoint | °F | Read | |
| AV | 3006 | eff_ht_stpt | Effective Heat Setpoint | °F | Read | |
| AVmin | 1019 | ent_load_wtr_temp | Entering Load Water Temp | °F | Read | |
| AV | 9003 | oat_ht_lockout | Heating Lockout Temperature (default 65) | °F | Write | |
| AVmin | 1020 | lvg_load_wtr_temp | Leaving Load Water Temp | °F | Read | |
| AV | 9037 | max_cw_reset | Maximum OA CHW Reset (default 10) | °F | Write | |
| AV | 1003 | oa_temp | Outdoor Air Temperature | °F | Read | |
| AV | 9007 | start_delay | Power Fail Restart Delay (default 5) | seconds | Write | |
| AV | 1011 | space_rh | Space Relative Humidity | %rh | Read | |
| AV | 1910 | system_elwt | System Entering Load Water Temp (default -999) | deg | Write | |
| AV | 1911 | system_ecwt | System Entering Source Water Temp (default -999) | deg | Write | |
| AV | 80001 | mstr_oa_temp | System OAT Master | °F | Read | |
| AV | 1901 | system_oat | System Outdoor Air Temperature (default -999) | °F | Write | |
| AV | 1909 | system_t1_temp | System T1 Temperature (default -999) | °F | Write | |
| AVmin | 5002 | total_comp_cap | Total System Cmpr Capacity | % | Read | |
| BV | 1011 | cl_enable | Cool Enable (default Active (1)) | Write | 0=Disable, 1=Enable | |
| BV | 1023 | clg_stpt_oa_rst_ena | Cooling Setpoint OA Reset (default Inactive (0)) | Write | 0=Disable, 1=Enable | |
| BV | 7041 | ent_lwt_fail | Entering Load Water Temp Sensor alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7040 | elwt_alarm | Entering Load Water Temperature alarm | Read | 0=Normal, 1=Alarm | |
| BV | 1012 | ht_enable | Heat Enable (default Active (1)) | Write | 0=Disable, 1=Enable | |
| BV | 1024 | htg_stpt_oa_rst_ena | Heating Setpoint OA Reset (default Inactive (0)) | Write | 0=Disable, 1=Enable | |
| BV | 7043 | llwt_alarm | Leaving Load Water Temperature alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7042 | lvg_cwt_fail | Leaving Source Water Temp Sensor alarm | Read | 0=Normal, 1=Alarm | |
| BV | 1019 | load_pump | Load Water Pump | Read | 0=Off, 1=On | |
| BV | 2008 | occ_status | Occupancy Status | Read | 0=Unoccupied, 1=Occupied | |
| BV | 7036 | oat_alarm | Outdoor Air Temperature alarm | Read | 0=Normal, 1=Alarm | |
| BV | 1020 | rh_clg_stpt_rst | RH Cooling Setpoint Reset (default Inactive (0)) | Write | 0=Normal, 1=Alarm | |
| BVmin | 9001 | shutdown | Shutdown (default Inactive (0)) | Write | 0=Normal, 1=Alarm | |
| BV | 1021 | pump_iso_vlv | Source Water Pump | Read | 0=Off/Close, 1=On/Open | |
| BV | 7027 | cwt_alarm | Source Water Temperature alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7018 | sprh_hi_alarm | Space Relative Humidity alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7022 | sprh_sensor_fail | Space Relative Humidity Sensor alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7032 | spt_sensor_fail | SPT Sensor alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7046 | t1_fail | System T1 Sensor alarm | Read | 0=Normal, 1=Alarm | |
| MVmin | 1001 | keypad_ovrde | BAS On / Off (default 2) | Write | 1=Inactive, 2=Occupied, 3=Unoccupied | |
| MVmin | 2002 | run_status | System Mode | Read | 1=Off, 2=Fan Only, 3=Economize, 4=Cooling, 5=Heating, 6=Cont Fan, 7=Test, 8=Start Delay, 9=Temer SAT, 10=Safety Shutdown, 11=Shutdown, 12=IAQ Override, 13=Dehumidify, 15=Pump Only | |
| AVmin | 3023 | hws_setpoint | Hot Water Supply Setpoint (default 120) | °F | Write | |
| AV | 1912 | system_llwt | System Leaving Load Water Temp (default -999) | deg | Write | |
| BV | 7044 | lvg_lwt_fail | Leaving Load Water Temp Sensor alarm | Read | 0=Normal, 1=Alarm | |
| AV | 1017 | cwl_temp | Leaving Source Water Temp | °F | Read | |
| BV | 7029 | oat_fail | Outdoor Air Temp Sensor alarm | Read | 0=Normal, 1=Alarm | |
| AV | 9038 | max_hw_reset | Maximum OA HW Reset (default 20) | °F | Write | |
| AV | 1904 | system_rh | System Space RH (default -999) | % | Write | |
| AV | 3016 | eff_stpt | Water Temperature Setpoint | °F | Read | |
| AV | 3011 | occ_dehum_stpt | Occ Relative Humidity Setpoint (default 60) | %rh | Write | |
| AV | 88001 | total_comp_stg | Total Req Sys Comp Stgs | Read | ||
| BV | 7055 | zs_config_fail | ZS Sensor Configuration alarm | Read | 0=Normal, 1=Alarm | |
| BVmin | 7013 | comp_alarm | Compressor Status alarm | Read | 0=Normal, 1=Alarm | |
| BV | 2702 | loop_pump | Loop Pump Status | Read | 0=Off, 1=On | |
| BV | 7049 | sw_flow_alarm | Source Water Flow alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7057 | load_flow_alarm | Load Water Flow alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7045 | sys_ecwt_fail | System Entering Source Water Temp Fail | Read | 0=Normal, 1=Alarm | |
| AV | 9006 | cool_demand_level | System Cooling Demand Level | Read | ||
| AV | 9036 | heat_demand_level | System Heating Demand Level | Read | ||
| AV | 3020 | h_dmd1_adj | Demand Level 1 Heat Adj (default 3) | °F | Write | |
| BV | 2701 | cw_link_status | Source Water Linkage | Read | 0=Inactive, 1=Active | |
| AV | 3017 | c_dmd1_adj | Demand Level 1 Cool Adj (default 3) | °F | Write | |
| AV | 3018 | c_dmd2_adj | Demand Level 2 Cool Adj (default 3) | °F | Write | |
| AV | 3019 | c_dmd3_adj | Demand Level 3 Cool Adj (default 4) | °F | Write | |
| BV | 7047 | mr_comm_fail | Communications with Master alarm | Read | 0=Normal, 1=Alarm | |
| AV | 3021 | h_dmd2_adj | Demand Level 2 Heat Adj (default 5) | °F | Write | |
| AV | 2701 | link_cwt | Water Loop Temp | °F | Read | |
| BV | 7031 | cond_water_linkage_fail | Source Water Linkage alarm | Read | 0=Normal, 1=Alarm | |
| AV | 3022 | h_dmd3_adj | Demand Level 3 Heat Adj (default 7) | °F | Write | |
| BV | 7056 | load_pmp_comm_fail | Load Water Flow Comm alarm | Read | 0=Normal, 1=Alarm | |
| AV | 2024 | loop_request | Loop Pump Request | Read | ||
| BV | 7058 | src_pmp_comm_fail | Source Water Flow Comm alarm | Read | 0=Normal, 1=Alarm | |
| BVmin | 7048 | equip_alarm | Equipment Alarm | Read | 0=Normal, 1=Alarm | |
| BV | 7024 | safety_alarm | Safety alarm | Read | 0=Normal, 1=Alarm | |
| MV | 2004 | fan_run | Fan / Speed | Read | 1=Off, 2=Low, 3=Med, 4=High, 5=On | |
| MV | 2009 | start_type | Optimal Start Type (default (2) Temp Compensated) | Write | 1=None, 2=Temp Compensated, 3=Learning Adaptive | |
| MV | 2003 | spt_status | Space Temp Source | Read | 1=Sensor Failure, 2=SPT Sensor, 3=RAT / T55, 4=Network, 5=Airside Linkage, 6=Locked Value, 7=T-Stat Linkage, 8=ZS Sensor |
No points match these filters.
Object ID lookup: Carrier W2W Open point IDs by name
AV2020comp_stagesAV3024chws_setpointAV5001comp_capAV9002oat_cl_lockoutAV3005eff_cl_stptAV3006eff_ht_stptAV1019ent_load_wtr_tempAV9003oat_ht_lockoutAV1020lvg_load_wtr_tempAV9037max_cw_resetAV1003oa_tempAV9007start_delayAV1011space_rhAV1910system_elwtAV1911system_ecwtAV80001mstr_oa_tempAV1901system_oatAV1909system_t1_tempAV5002total_comp_capBV1011cl_enableBV1023clg_stpt_oa_rst_enaBV7041ent_lwt_failBV7040elwt_alarmBV1012ht_enableBV1024htg_stpt_oa_rst_enaBV7043llwt_alarmBV7042lvg_cwt_failBV1019load_pumpBV2008occ_statusBV7036oat_alarmBV1020rh_clg_stpt_rstBV9001shutdownBV1021pump_iso_vlvBV7027cwt_alarmBV7018sprh_hi_alarmBV7022sprh_sensor_failBV7032spt_sensor_failBV7046t1_failMV1001keypad_ovrdeMV2002run_statusAV3023hws_setpointAV1912system_llwtBV7044lvg_lwt_failAV1017cwl_tempBV7029oat_failAV9038max_hw_resetAV1904system_rhAV3016eff_stptAV3011occ_dehum_stptAV88001total_comp_stgBV7055zs_config_failBV7013comp_alarmBV2702loop_pumpBV7049sw_flow_alarmBV7057load_flow_alarmBV7045sys_ecwt_failAV9006cool_demand_levelAV9036heat_demand_levelAV3020h_dmd1_adjBV2701cw_link_statusAV3017c_dmd1_adjAV3018c_dmd2_adjAV3019c_dmd3_adjBV7047mr_comm_failAV3021h_dmd2_adjAV2701link_cwtBV7031cond_water_linkage_failAV3022h_dmd3_adjBV7056load_pmp_comm_failAV2024loop_requestBV7058src_pmp_comm_failBV7048equip_alarmBV7024safety_alarmMV2004fan_runMV2009start_typeMV2003spt_status
Integration notes
- System points (system_oat, system_rh, system_t1_temp, system_elwt, system_llwt, system_ecwt) are network inputs; the guide says system points must be written at BACnet priority 16 and no more than once a minute, and -999 means no network value.
- The table prints System Mode (run_status, MSV:2002) twice. The first row has the water-to-water states (Safety Shutdown, Dehumidify, Pump Only) and is used here; the repeat on the last page has unit-ventilator style states (Fire Shutdown, Pre-Occ Purge) and was dropped.
- Shutdown (BV:9001) and RH Cooling Setpoint Reset (BV:1020) are printed with Normal/Alarm states; kept as printed.
- Units 'deg' on the system water temperature inputs are as printed.
- Each point also has a Modbus register in the same table (some later rows have none); only the BACnet side is captured here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the W2W Open and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier W2W Open
How many BACnet points does the Carrier W2W Open have?
This list has 76 BACnet objects: 37 analog values, 34 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier W2W Open BACnet points are writable?
28 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier W2W Open BACnet documentation?
The source is W2W Open Integration Guide (Appendix A: Network Points List for W2W Open) (11-808-538-01), revision 2021-06-15, published free by Carrier at https://www.shareddocs.com/hvac/docs/1000/Public/05/11-808-538-01.pdf.
What are the minimum BACnet points to integrate the Carrier W2W Open?
Start with MV 1001 keypad_ovrde (BAS occupancy command: occupied/unoccupied); BV 9001 shutdown (Network shutdown command); AV 3024 chws_setpoint (Chilled water supply setpoint); AV 3023 hws_setpoint (Hot water supply setpoint); MV 2002 run_status (Current system mode); AV 1020 lvg_load_wtr_temp (Leaving load water temperature); AV 1019 ent_load_wtr_temp (Entering load water temperature); AV 5002 total_comp_cap (Total compressor capacity, %); BV 7013 comp_alarm (Compressor status alarm); BV 7048 equip_alarm (General equipment alarm).
How do I enable BMS control of the Carrier W2W Open?
The controller is occupied by default. A third-party BAS sets occupancy by writing BAS On/Off keypad_ovrde (MSV:1001): 1=Inactive, 2=Occupied, 3=Unoccupied; the sequence says this takes precedence over the other occupancy sources, while the system-point table says occupancy control must be set to 3 (BAS On/Off). No heating or cooling runs while unoccupied. Cool Enable (BV:1011) and Heat Enable (BV:1012) must be Enable; Shutdown (BV:9001) stops the unit.
Does the Carrier W2W Open need a BACnet heartbeat or have a communication timeout?
No general heartbeat. The guide gives refresh windows for the generic system points (OAT 5 min / 60 min, space RH 5 min / 10 min); a network value is only used while it is refreshed in time.
Can the BMS supply sensor values to the Carrier W2W Open?
Write system_oat (AV:1901), system_rh (AV:1904), system_t1_temp (AV:1909) or the system water temperatures (AV:1910-1912) at BACnet priority 16, no more than once a minute. The controller clears a system point after processing it, so confirm a write by reading the control point (e.g. oa_temp, space_rh) at least 30 s later. System T1 is needed when Control Mode Selection uses T1 for heat/cool changeover.
How do I check these points on the real W2W Open?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: W2W Open Integration Guide (Appendix A: Network Points List for W2W Open) · 11-808-538-01 · rev. 2021-06-15. Object names, instances and units are reproduced as published; descriptions are our own.