BACnet instance calculator · Open controllers (RTU Open, WSHP Open, UPC Open...)
Carrier Open Controller BACnet Device Instance Calculator
Free browser tool · nothing is uploaded · 5 November 2026
Carrier's Open controllers ship with a default device instance built from 16101 and the two-digit rotary switch (MAC) address. Enter the address to get it.
Default device instance = 16101 followed by the 2-digit rotary address, i.e. 1610100 + address. Address 23 gives 1610123; address 5 gives 1610105. The object instances inside are the same on every controller of that type.
Carrier calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit is this device?
How the numbers are built
device instance = 1610100 + rotary address
| Part | Meaning | Range |
|---|---|---|
| 16101 | Fixed prefix in Carrier's default (16 is Carrier's BACnet vendor ID) | 16101 |
| address | Rotary switch (MS/TP MAC) address, two digits | 00-99 |
The address is set on the controller's two rotary switches (tens and ones). This is the factory default; if the device instance was changed in the controller's setup, read it from a scan.
Worked example: rotary address 23
The first objects for rotary address 23 on the RTU Open v5, worked out with the formula above (RTU Open v5):
| Unit type | Device instance | For |
|---|---|---|
| Controller device | 1610123 | Rotary switch address 23 |
Source
- Carrier RTU Open v5 BACnet points list (200 objects)
- Carrier WSHP Open v3 BACnet points list (83 objects)
- Carrier Fan Coil Open BACnet points list (80 objects)
- Carrier Unit Ventilator Open BACnet points list (71 objects)
- Carrier W2W Open BACnet points list (76 objects)
- Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option) BACnet points list (156 objects)
- Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option) BACnet points list (168 objects)
- Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option) BACnet points list (252 objects)
- Carrier AquaForce 30XA 080-501 (UPC Open BACnet option) BACnet points list (268 objects)
- Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option) BACnet points list (161 objects)
- Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option) BACnet points list (302 objects)
Formula and objects from RTU Open v5 Integration Guide (Appendix A: Network Points List) · 11-808-697-01 · rev. 2019-11-19 (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Carrier instance number?
Default device instance = 16101 followed by the 2-digit rotary address, i.e. 1610100 + address. Address 23 gives 1610123; address 5 gives 1610105. The object instances inside are the same on every controller of that type.
Why is my Carrier controller's device instance 16101xx?
Carrier's default joins 16101 and the two-digit rotary address, so address 20 shows up as device 1610120. Change the rotary address and the default device instance changes with it.
Is this Carrier calculator official?
No. It applies the formula printed in Carrier's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more)Boiler makers use FieldServer ProtoNode gateways to put Modbus boilers on BACnet.
device instance = Node_Offset + Node-ID - HeatNet V3 boiler control (Hydrotherm KN, RBI)Mestek's HeatNet V3 control prints its per-boiler objects once as Boiler##_ with a formula.
BV 1000s: base + 32(n-1); BV 2000s/3000s: base + 16(n-1); AI: base + (n-1) - Hamilton Engineering BDB-CDB (ProtoNode)The Hamilton BDB-CDB profile repeats a 9-object block for each BCB board.
instance = BCB1 instance + 9 x (BCB - 1) - Titus T3SQ Digital (MCU 2 gateway)The MCU 2 lays out each object type in blocks of 60, one instance per diffuser zone.
instance = block start + zone - 1 - Verdant VX4 thermostats (Online Connection Kit)Verdant VX4 rooms all get the same 15 objects at a base number plus the room number - but the room number is read as hexadecimal.
instance = base + hex-to-decimal(room number) - GPS Air GridSet BACnet gateway (Hub-4 Pro)The smartIAQ Hub-4 Pro gives each of its four ports the same block of objects at port x 1000.
instance = port x 1000 + offset - Setra Setra Power Meter (SPM) load deviceEach Setra SPM load device prints only the CT 1 block and reserves the same block for CT 2 and CT 3, 30 instances further on.
instance = CT 1 instance + 30 x (CT - 1); polarity = BV CT