BACnet instance calculator · Setra Power Meter (SPM) load device
Setra SPM BACnet Instance Calculator (CT 1-3)
Free browser tool · nothing is uploaded · 5 November 2026
Each Setra SPM load device prints only the CT 1 block and reserves the same block for CT 2 and CT 3, 30 instances further on.
CT n's objects are the CT 1 instance + 30 x (n - 1): CT 1 is AI 30-52, CT 2 AI 60-82, CT 3 AI 90-112. CT 2's real power is AI 62; its polarity correction is BV 2.
Setra calculator
The calculator needs JavaScript. The formula and a worked example are below.
Which unit does this instance belong to?
How the numbers are built
instance = CT 1 instance + 30 x (CT - 1); polarity = BV CT
| Part | Meaning | Range |
|---|---|---|
| CT | Current transformer number on the load | 1-3 |
| CT 1 instance | Printed CT 1 instance | 30-52 |
Load-level totals (voltage, power, energy) are fixed objects on each load device.
Worked example: CT 2
The first objects for CT 2 on the SPM load device, worked out with the formula above:
| Object | Name (as printed) | What it is |
|---|---|---|
| AI 60 | CT# 1 Amperage (A) | First CT block (AI 30-52) |
| AI 61 | CT# 1 Demand | |
| AI 62 | CT# 1 Real Power (kW) | |
| AI 63 | CT# 1 Apparent Power (kVA) | |
| AI 64 | CT# 1 Reactive Power (kvar) | |
| AI 65 | CT# 1 Harmonic Distortion (HD) | |
| BV 2 | CT# 1 Polarity Correction | Polarity correction for CT 1 (BV 2, BV 3 for CT 2, 3) |
Source
Formula and objects from Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H (manufacturer document ↗), re-typed in our points list. Object names are shown as printed.
Check it against the live device. The calculator applies the formula from the manufacturer’s documentation; the gateway in front of you may expose fewer objects or use other numbers after a firmware change. Easy BACnet scans a network for BACnet IP devices from an Android phone and reads every object on them — a quick way to confirm one unit before you map a whole building.
Questions
How do I work out a Setra instance number?
CT n's objects are the CT 1 instance + 30 x (n - 1): CT 1 is AI 30-52, CT 2 AI 60-82, CT 3 AI 90-112. CT 2's real power is AI 62; its polarity correction is BV 2.
Why does the meter show more than one BACnet device?
The SPM is a root device for the voltage inputs plus one load device per configured load. The CT blocks are inside each load device.
Is this Setra calculator official?
No. It applies the formula printed in Setra's own documentation to the points list in our library. Confirm the numbers against a scan of the live device before you map or write anything.
More instance calculators
- ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more)Boiler makers use FieldServer ProtoNode gateways to put Modbus boilers on BACnet.
device instance = Node_Offset + Node-ID - Carrier Open controllers (RTU Open, WSHP Open, UPC Open...)Carrier's Open controllers ship with a default device instance built from 16101 and the two-digit rotary switch (MAC) address.
device instance = 1610100 + rotary address - HeatNet V3 boiler control (Hydrotherm KN, RBI)Mestek's HeatNet V3 control prints its per-boiler objects once as Boiler##_ with a formula.
BV 1000s: base + 32(n-1); BV 2000s/3000s: base + 16(n-1); AI: base + (n-1) - Hamilton Engineering BDB-CDB (ProtoNode)The Hamilton BDB-CDB profile repeats a 9-object block for each BCB board.
instance = BCB1 instance + 9 x (BCB - 1) - Titus T3SQ Digital (MCU 2 gateway)The MCU 2 lays out each object type in blocks of 60, one instance per diffuser zone.
instance = block start + zone - 1 - Verdant VX4 thermostats (Online Connection Kit)Verdant VX4 rooms all get the same 15 objects at a base number plus the room number - but the room number is read as hexadecimal.
instance = base + hex-to-decimal(room number) - GPS Air GridSet BACnet gateway (Hub-4 Pro)The smartIAQ Hub-4 Pro gives each of its four ports the same block of objects at port x 1000.
instance = port x 1000 + offset