Multi-load power meter · BACnet points list

Setra Power Meter (SPM) - load device BACnet points list

Updated 4 November 2026

Short answer

Each load on a Setra Power Meter appears as its own BACnet load device, with objects reserved for up to three CTs. The load device reports voltages, frequency, total real, reactive and apparent power, current, power factor, demand and energy totals, plus a block of per-CT readings. Energy totals are also offered as Large Analog Values.

This page lists 68 BACnet objects for the Setra Power Meter (SPM) - load device — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Setra’s own free documentation, linked below.

Manufacturer
Setra
Model
Setra Power Meter (SPM) - load device
Equipment
Multi-load power meter
Equipment type
Thermostats, sensors & meters
BACnet objects
68 (0 writable)
Transport
—
Firmware
Not stated
Also known as
SPM, Setra SPM, Setra Power Meter, SPM load
Source document
Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H

Instance calculator. This list prints one unit; the other units follow a formula. Setra Setra Power Meter (SPM) load device instance calculator →

Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.

BMS integration notes: Setra Power Meter (SPM) - load device

Integration in brief

Read total real power, current, power factor, demand and the kWh total from each load device; add the per-CT block if phase detail is needed. The meter is monitoring only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 8Total Real Power (kW)Total real power, kWRead
AI 9Total Amperage (A)Total current, ARead
AI 11Total Apparent Power Factor (aPF)Total apparent power factorRead
AI 17Total Power DemandTotal power demand, kWRead
LAV 1Total Kilowatt Hours (kWh)Total energy, kWh (double precision)Read

Network setup

Watch out for

Setra Power Meter (SPM) - load device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

68 of 68 shown
Type
AnalogBinary
Show
Setra Power Meter (SPM) - load device BACnet Points List
DescriptionStates
AI1Line 1 Measured Line-Neutral Voltage (L1-N)VRead
AI2Line 2 Measured Line-Neutral Voltage (L2-N)VRead
AI3Line 3 Measured Line-Neutral Voltage (L3-N)VRead
AI4Line 1 - Line 2 Measured Voltage (L1-L2)VRead
AI5Line 2 - Line 3 Measured Voltage (L2-L3)VRead
AI6Line 3 - Line 1 Measured Voltage (L3-L2)VRead
AI7FrequencyHzRead
AImin8Total Real Power (kW)kWRead
AImin9Total Amperage (A)ARead
AI10Total Reactive Power (kvar)kvarRead
AImin11Total Apparent Power Factor (aPF)PFRead
AI12Total Displacement Power Factor (dPF)PFRead
AI13Total Apparent Power (kVA)kVARead
AI14Total Harmonic Distortion (THD)%Read
AI15Total Peak Demand (PD)kWRead
AI163-phase Current Unbalance%Read
AImin17Total Power DemandkWRead
AI30CT# 1 Amperage (A)First CT block (AI 30-52)ARead
AI31CT# 1 DemandkWRead
AI32CT# 1 Real Power (kW)kWRead
AI33CT# 1 Apparent Power (kVA)kVARead
AI34CT# 1 Reactive Power (kvar)kvarRead
AI35CT# 1 Harmonic Distortion (HD)%Read
AI36CT# 1 Apparent Power Factor (aPF)PFRead
AI37CT# 1 Displacement Power Factor (dPF)PFRead
AI38CT# 1 Kilowatt Hours (kWh)kWhRead
AI39CT# 1 Kilovolt Ampere Reactive Hours (kvarh)kvarhRead
AI40CT# 1 Kilovolt Ampere Hours (kVAh)kVAhRead
AI41CT# 1 Export Kilowatt Hours (kWh-)kWhRead
AI42CT# 1 Import Kilowatt Hours (kWh+)kWhRead
AI43CT# 1 Export Kilovolt Ampere Hours (kVAh-)kvarhRead
AI44CT# 1 Import Kilovolt Ampere Hours (kVAh+)kvarhRead
AI45Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)kvarhRead
AI46Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)kvarhRead
AI47Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)kvarhRead
AI48Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)kvarhRead
AI49CT# 1 Peak DemandkWRead
AI50CT# 1Phase AngleUnits can be set to radians or degrees-phaseRead
AI51CT# 1 Reactive Energy Received (kvarh-)Import, Q1+Q2kvarhRead
AI52CT#1 Reactive Energy Delivered (kvarh-)Export, Q3+Q4°Read
AI140Total Kilowatt Hours (kWh)kWhRead
AI141Total Kilovolt Ampere Hours (kVAh)kvarhRead
AI142Total Kilovolt Ampere Reactive Hours (kVARh)kVAhRead
AI143Total Export Kilowatt Hours (kWh-)kWhRead
AI144Total Import Kilowatt Hours (kWh+)kWhRead
AI145Total Export Kilovolt Ampere Hours (kVAh-)kvarhRead
AI146Total Import Kilovolt Ampere Hours (kVAh+)kvarhRead
AI147Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)kvarhRead
AI148Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)kvarhRead
AI149Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)kvarhRead
AI150Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)kvarhRead
AI151Total Reactive Energy Delivered (kvarh+)Import, Q1+Q2kvarhRead
AI152Total Reactive Energy Received (kvarh-)Export, Q3+Q4kvarhRead
BV1CT# 1 Polarity CorrectionPolarity correction for CT 1 (BV 2, BV 3 for CT 2, 3)Read
NC1Event Notification ClassRead
LAVmin1Total Kilowatt Hours (kWh)Large analog (double) energy totalkWhRead
LAV2Total Kilovolt Ampere Hours (kVAh)Large analog (double) energy totalkvarhRead
LAV3Total Kilovolt Ampere Reactive Hours (kVARh)Large analog (double) energy totalkVAhRead
LAV4Total Export Kilowatt Hours (kWh-)Large analog (double) energy totalkWhRead
LAV5Total Import Kilowatt Hours (kWh+)Large analog (double) energy totalkWhRead
LAV6Total Export Kilovolt Ampere Hours (kVAh-)Large analog (double) energy totalkvarhRead
LAV7Total Import Kilovolt Ampere Hours (kVAh+)Large analog (double) energy totalkvarhRead
LAV8Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)Large analog (double) energy totalkvarhRead
LAV9Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)Large analog (double) energy totalkvarhRead
LAV10Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)Large analog (double) energy totalkvarhRead
LAV11Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)Large analog (double) energy totalkvarhRead
LAV12Total Reactive Energy Delivered (kvarh+)Import, Q1+Q2kvarhRead
LAV13Total Reactive Energy Received (kvarh-)Export, Q3+Q4kvarhRead
Object ID lookup: Setra Power Meter (SPM) load device point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Setra Power Meter (SPM) - load device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Setra Power Meter (SPM) - load device

How many BACnet points does the Setra Power Meter (SPM) - load device have?

This list has 68 BACnet objects: 53 analog inputs, 1 binary value, 1 notification class, 13 large analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Setra Power Meter (SPM) - load device BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Setra Power Meter (SPM) - load device BACnet documentation?

The source is Setra Power Meter Master BACnet Object List (SS-SPM-BAC-OBJ), revision Rev H, published free by Setra at https://www.setra.com/hubfs/SS-SPM-BAC-OBJ,%20print_A.pdf.

What are the minimum BACnet points to integrate the Setra Power Meter (SPM) - load device?

Start with AI 8 Total Real Power (kW) (Total real power, kW); AI 9 Total Amperage (A) (Total current, A); AI 11 Total Apparent Power Factor (aPF) (Total apparent power factor); AI 17 Total Power Demand (Total power demand, kW); LAV 1 Total Kilowatt Hours (kWh) (Total energy, kWh (double precision)).

How do I check these points on the real Setra Power Meter (SPM) - load device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Setra BACnet points lists

Source: Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H. Object names, instances and units are reproduced as published; descriptions are our own.