- Setra Power Meter (SPM) - load device
Multi-load power meter · BACnet points list
Setra Power Meter (SPM) - load device BACnet points list
Updated 4 November 2026
Each load on a Setra Power Meter appears as its own BACnet load device, with objects reserved for up to three CTs. The load device reports voltages, frequency, total real, reactive and apparent power, current, power factor, demand and energy totals, plus a block of per-CT readings. Energy totals are also offered as Large Analog Values.
This page lists 68 BACnet objects for the Setra Power Meter (SPM) - load device — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Setra’s own free documentation, linked below.
- Manufacturer
- Setra
- Model
- Setra Power Meter (SPM) - load device
- Equipment
- Multi-load power meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 68 (0 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- SPM, Setra SPM, Setra Power Meter, SPM load
Instance calculator. This list prints one unit; the other units follow a formula. Setra Setra Power Meter (SPM) load device instance calculator →
Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.
BMS integration notes: Setra Power Meter (SPM) - load device
Read total real power, current, power factor, demand and the kWh total from each load device; add the per-CT block if phase detail is needed. The meter is monitoring only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 8 | Total Real Power (kW) | Total real power, kW | Read |
| AI 9 | Total Amperage (A) | Total current, A | Read |
| AI 11 | Total Apparent Power Factor (aPF) | Total apparent power factor | Read |
| AI 17 | Total Power Demand | Total power demand, kW | Read |
| LAV 1 | Total Kilowatt Hours (kWh) | Total energy, kWh (double precision) | Read |
Network setup
- Each load device has its own object list; the CT 2 and CT 3 blocks use the reserved instances AI 60-82 and AI 90-112.
Watch out for
- Use the Large Analog Value totals where the BMS supports them; they keep resolution on big kWh counts.
Setra Power Meter (SPM) - load device BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Line 1 Measured Line-Neutral Voltage (L1-N) | V | Read | ||
| AI | 2 | Line 2 Measured Line-Neutral Voltage (L2-N) | V | Read | ||
| AI | 3 | Line 3 Measured Line-Neutral Voltage (L3-N) | V | Read | ||
| AI | 4 | Line 1 - Line 2 Measured Voltage (L1-L2) | V | Read | ||
| AI | 5 | Line 2 - Line 3 Measured Voltage (L2-L3) | V | Read | ||
| AI | 6 | Line 3 - Line 1 Measured Voltage (L3-L2) | V | Read | ||
| AI | 7 | Frequency | Hz | Read | ||
| AImin | 8 | Total Real Power (kW) | kW | Read | ||
| AImin | 9 | Total Amperage (A) | A | Read | ||
| AI | 10 | Total Reactive Power (kvar) | kvar | Read | ||
| AImin | 11 | Total Apparent Power Factor (aPF) | PF | Read | ||
| AI | 12 | Total Displacement Power Factor (dPF) | PF | Read | ||
| AI | 13 | Total Apparent Power (kVA) | kVA | Read | ||
| AI | 14 | Total Harmonic Distortion (THD) | % | Read | ||
| AI | 15 | Total Peak Demand (PD) | kW | Read | ||
| AI | 16 | 3-phase Current Unbalance | % | Read | ||
| AImin | 17 | Total Power Demand | kW | Read | ||
| AI | 30 | CT# 1 Amperage (A) | First CT block (AI 30-52) | A | Read | |
| AI | 31 | CT# 1 Demand | kW | Read | ||
| AI | 32 | CT# 1 Real Power (kW) | kW | Read | ||
| AI | 33 | CT# 1 Apparent Power (kVA) | kVA | Read | ||
| AI | 34 | CT# 1 Reactive Power (kvar) | kvar | Read | ||
| AI | 35 | CT# 1 Harmonic Distortion (HD) | % | Read | ||
| AI | 36 | CT# 1 Apparent Power Factor (aPF) | PF | Read | ||
| AI | 37 | CT# 1 Displacement Power Factor (dPF) | PF | Read | ||
| AI | 38 | CT# 1 Kilowatt Hours (kWh) | kWh | Read | ||
| AI | 39 | CT# 1 Kilovolt Ampere Reactive Hours (kvarh) | kvarh | Read | ||
| AI | 40 | CT# 1 Kilovolt Ampere Hours (kVAh) | kVAh | Read | ||
| AI | 41 | CT# 1 Export Kilowatt Hours (kWh-) | kWh | Read | ||
| AI | 42 | CT# 1 Import Kilowatt Hours (kWh+) | kWh | Read | ||
| AI | 43 | CT# 1 Export Kilovolt Ampere Hours (kVAh-) | kvarh | Read | ||
| AI | 44 | CT# 1 Import Kilovolt Ampere Hours (kVAh+) | kvarh | Read | ||
| AI | 45 | Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3) | kvarh | Read | ||
| AI | 46 | Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4) | kvarh | Read | ||
| AI | 47 | Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2) | kvarh | Read | ||
| AI | 48 | Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1) | kvarh | Read | ||
| AI | 49 | CT# 1 Peak Demand | kW | Read | ||
| AI | 50 | CT# 1Phase Angle | Units can be set to radians or degrees-phase | Read | ||
| AI | 51 | CT# 1 Reactive Energy Received (kvarh-) | Import, Q1+Q2 | kvarh | Read | |
| AI | 52 | CT#1 Reactive Energy Delivered (kvarh-) | Export, Q3+Q4 | ° | Read | |
| AI | 140 | Total Kilowatt Hours (kWh) | kWh | Read | ||
| AI | 141 | Total Kilovolt Ampere Hours (kVAh) | kvarh | Read | ||
| AI | 142 | Total Kilovolt Ampere Reactive Hours (kVARh) | kVAh | Read | ||
| AI | 143 | Total Export Kilowatt Hours (kWh-) | kWh | Read | ||
| AI | 144 | Total Import Kilowatt Hours (kWh+) | kWh | Read | ||
| AI | 145 | Total Export Kilovolt Ampere Hours (kVAh-) | kvarh | Read | ||
| AI | 146 | Total Import Kilovolt Ampere Hours (kVAh+) | kvarh | Read | ||
| AI | 147 | Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3) | kvarh | Read | ||
| AI | 148 | Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4) | kvarh | Read | ||
| AI | 149 | Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2) | kvarh | Read | ||
| AI | 150 | Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1) | kvarh | Read | ||
| AI | 151 | Total Reactive Energy Delivered (kvarh+) | Import, Q1+Q2 | kvarh | Read | |
| AI | 152 | Total Reactive Energy Received (kvarh-) | Export, Q3+Q4 | kvarh | Read | |
| BV | 1 | CT# 1 Polarity Correction | Polarity correction for CT 1 (BV 2, BV 3 for CT 2, 3) | Read | ||
| NC | 1 | Event Notification Class | Read | |||
| LAVmin | 1 | Total Kilowatt Hours (kWh) | Large analog (double) energy total | kWh | Read | |
| LAV | 2 | Total Kilovolt Ampere Hours (kVAh) | Large analog (double) energy total | kvarh | Read | |
| LAV | 3 | Total Kilovolt Ampere Reactive Hours (kVARh) | Large analog (double) energy total | kVAh | Read | |
| LAV | 4 | Total Export Kilowatt Hours (kWh-) | Large analog (double) energy total | kWh | Read | |
| LAV | 5 | Total Import Kilowatt Hours (kWh+) | Large analog (double) energy total | kWh | Read | |
| LAV | 6 | Total Export Kilovolt Ampere Hours (kVAh-) | Large analog (double) energy total | kvarh | Read | |
| LAV | 7 | Total Import Kilovolt Ampere Hours (kVAh+) | Large analog (double) energy total | kvarh | Read | |
| LAV | 8 | Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3) | Large analog (double) energy total | kvarh | Read | |
| LAV | 9 | Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4) | Large analog (double) energy total | kvarh | Read | |
| LAV | 10 | Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2) | Large analog (double) energy total | kvarh | Read | |
| LAV | 11 | Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1) | Large analog (double) energy total | kvarh | Read | |
| LAV | 12 | Total Reactive Energy Delivered (kvarh+) | Import, Q1+Q2 | kvarh | Read | |
| LAV | 13 | Total Reactive Energy Received (kvarh-) | Export, Q3+Q4 | kvarh | Read |
No points match these filters.
Object ID lookup: Setra Power Meter (SPM) load device point IDs by name
AI1Line 1 Measured Line-Neutral Voltage (L1-N)AI2Line 2 Measured Line-Neutral Voltage (L2-N)AI3Line 3 Measured Line-Neutral Voltage (L3-N)AI4Line 1 - Line 2 Measured Voltage (L1-L2)AI5Line 2 - Line 3 Measured Voltage (L2-L3)AI6Line 3 - Line 1 Measured Voltage (L3-L2)AI7FrequencyAI8Total Real Power (kW)AI9Total Amperage (A)AI10Total Reactive Power (kvar)AI11Total Apparent Power Factor (aPF)AI12Total Displacement Power Factor (dPF)AI13Total Apparent Power (kVA)AI14Total Harmonic Distortion (THD)AI15Total Peak Demand (PD)AI163-phase Current UnbalanceAI17Total Power DemandAI30CT# 1 Amperage (A)AI31CT# 1 DemandAI32CT# 1 Real Power (kW)AI33CT# 1 Apparent Power (kVA)AI34CT# 1 Reactive Power (kvar)AI35CT# 1 Harmonic Distortion (HD)AI36CT# 1 Apparent Power Factor (aPF)AI37CT# 1 Displacement Power Factor (dPF)AI38CT# 1 Kilowatt Hours (kWh)AI39CT# 1 Kilovolt Ampere Reactive Hours (kvarh)AI40CT# 1 Kilovolt Ampere Hours (kVAh)AI41CT# 1 Export Kilowatt Hours (kWh-)AI42CT# 1 Import Kilowatt Hours (kWh+)AI43CT# 1 Export Kilovolt Ampere Hours (kVAh-)AI44CT# 1 Import Kilovolt Ampere Hours (kVAh+)AI45Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)AI46Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)AI47Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)AI48Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)AI49CT# 1 Peak DemandAI50CT# 1Phase AngleAI51CT# 1 Reactive Energy Received (kvarh-)AI52CT#1 Reactive Energy Delivered (kvarh-)AI140Total Kilowatt Hours (kWh)AI141Total Kilovolt Ampere Hours (kVAh)AI142Total Kilovolt Ampere Reactive Hours (kVARh)AI143Total Export Kilowatt Hours (kWh-)AI144Total Import Kilowatt Hours (kWh+)AI145Total Export Kilovolt Ampere Hours (kVAh-)AI146Total Import Kilovolt Ampere Hours (kVAh+)AI147Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)AI148Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)AI149Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)AI150Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)AI151Total Reactive Energy Delivered (kvarh+)AI152Total Reactive Energy Received (kvarh-)BV1CT# 1 Polarity CorrectionNC1Event Notification ClassLAV1Total Kilowatt Hours (kWh)LAV2Total Kilovolt Ampere Hours (kVAh)LAV3Total Kilovolt Ampere Reactive Hours (kVARh)LAV4Total Export Kilowatt Hours (kWh-)LAV5Total Import Kilowatt Hours (kWh+)LAV6Total Export Kilovolt Ampere Hours (kVAh-)LAV7Total Import Kilovolt Ampere Hours (kVAh+)LAV8Total Reactive Energy Accumulated in Quadrant 3 (kvarh_Q3)LAV9Total Reactive Energy Accumulated in Quadrant 4 (kvarh_Q4)LAV10Total Reactive Energy Accumulated in Quadrant 2 (kvarh_Q2)LAV11Total Reactive Energy Accumulated in Quadrant 1 (kvarh_Q1)LAV12Total Reactive Energy Delivered (kvarh+)LAV13Total Reactive Energy Received (kvarh-)
Integration notes
- The meter shows up as more than one BACnet device: a root device for the voltage inputs and load device(s) with the object list below. The root and load lists are separate entries in this library.
- The list has no read/write column; all objects are shown read-only here (access inferred).
- Only the CT 1 block (AI 30-52, BV 1) is printed. The manual reserves AI 60-82 for CT 2 and AI 90-112 for CT 3 (CT 1 instance + 30 per CT), and BV 2/BV 3 for their polarity correction.
- Several unit cells look wrong in the PDF: AI 52 prints degrees-phase, AI 141/142 and LAV 2/3 swap kVAh and kvarh, and AI 43/44 and AI 145/146 print kvarh for kVAh totals. Units are kept as printed. AI 50 (phase angle) prints kvarh and is left blank here.
- AI 51 and AI 52 are both printed with "(kvarh-)"; the notes column marks them import (Q1+Q2) and export (Q3+Q4).
- The object list does not say which BACnet network the meter uses (BACnet IP or BACnet MS/TP); check Setra's SPM data sheet for the model.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Setra Power Meter (SPM) - load device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Setra Power Meter (SPM) - load device
How many BACnet points does the Setra Power Meter (SPM) - load device have?
This list has 68 BACnet objects: 53 analog inputs, 1 binary value, 1 notification class, 13 large analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Setra Power Meter (SPM) - load device BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Setra Power Meter (SPM) - load device BACnet documentation?
The source is Setra Power Meter Master BACnet Object List (SS-SPM-BAC-OBJ), revision Rev H, published free by Setra at https://www.setra.com/hubfs/SS-SPM-BAC-OBJ,%20print_A.pdf.
What are the minimum BACnet points to integrate the Setra Power Meter (SPM) - load device?
Start with AI 8 Total Real Power (kW) (Total real power, kW); AI 9 Total Amperage (A) (Total current, A); AI 11 Total Apparent Power Factor (aPF) (Total apparent power factor); AI 17 Total Power Demand (Total power demand, kW); LAV 1 Total Kilowatt Hours (kWh) (Total energy, kWh (double precision)).
How do I check these points on the real Setra Power Meter (SPM) - load device?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Setra BACnet points lists
- Room pressure monitor and controller
Setra FLEX Room Pressure Monitor
Setra FLEX wall-mounted room pressure and environmental monitors (FLEX-RM monitor-only and FLEX-RC room control) covering up to three rooms.
Also known as: SetraFLEX, Setra FLEX, FLEX-RM, FLEX-RC, Setra FLEX Environmental Monitor - Multi-load power meter
Setra Power Meter (SPM) - root device
Setra Power Meter (SPM) multi-load electrical meters; this entry covers the root device that carries the voltage inputs.
Also known as: SPM, Setra SPM, Setra Power Meter, Setra multi-load power meter - Humidity / temperature sensor
Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)
Setra SRH300 and SRH200 humidity/temperature transmitters with the RS-485 BACnet MS/TP output (SRH300D / SRH200D).
Also known as: SRH300D, SRH200D, SRH300, SRH200, Setra SRH BACnet
Source: Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H. Object names, instances and units are reproduced as published; descriptions are our own.