Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The SRH300D and SRH200D are Setra humidity and temperature transmitters that act as BACnet MS/TP smart sensors. The SRH300D exposes eight read-only Analog Inputs (temperature, RH and calculated psychrometric values); the SRH200D exposes only temperature and RH. Units follow the configured measurement units.

This page lists 8 BACnet objects for the Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Setra’s own free documentation, linked below.

Manufacturer
Setra
Model
SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)
Equipment
Humidity / temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
8 (0 writable)
Transport
BACnet MS/TP
Firmware
1.8 (PICS dated 28.10.2014)
Also known as
SRH300D, SRH200D, SRH300, SRH200, Setra SRH BACnet
Source document
PICS SRH200D & SRH300D - BACnet Protocol Implementation Conformance Statement · rev. 28.10.2014 (catalog copy dated 8/17/18)
Download CSV 8 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.

BMS integration notes: Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP communication parameters and a unique device instance, then read temperature and RH (and dew point on the SRH300D). The device can also broadcast unsolicited COV when a COV increment is set.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0TAir temperatureRead
AI 1RHRelative humidityRead
AI 3TdDew point (SRH300D only)Read

Network setup

Watch out for

Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

8 of 8 shown
Type
Analog
Show
Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TTemperature°C / °F / KRead
AImin1RHRelative humidity%RHRead
AI2eWater vapor partial pressure (SRH300D only)mbar / psiRead
AImin3TdDew point temperature (SRH300D only)°C / °F / KRead
AI4dvAbsolute humidity (SRH300D only)g/m3 / g/ft3Read
AI5rMixing ratio (SRH300D only)g/kg / gr/lbRead
AI6hEnthalpy (SRH300D only)kJ/kg / ft·lbf/lb / BTU/lbRead
AI7TfFrost point temperature (SRH300D only)°C / °F / KRead
Object ID lookup: Setra SRH300D / SRH200D humidity and temperature transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)

How many BACnet points does the Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) have?

This list has 8 BACnet objects: 8 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP) BACnet documentation?

The source is PICS SRH200D & SRH300D - BACnet Protocol Implementation Conformance Statement, revision 28.10.2014 (catalog copy dated 8/17/18), published free by Setra at https://www.bacnetinternational.net/catalog/manu/setra%20systems,%20inc./PICS_SRH200D_SRH300D%208_17_18.pdf.

What are the minimum BACnet points to integrate the Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)?

Start with AI 0 T (Air temperature); AI 1 RH (Relative humidity); AI 3 Td (Dew point (SRH300D only)).

How do I check these points on the real SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Setra BACnet points lists

Source: PICS SRH200D & SRH300D - BACnet Protocol Implementation Conformance Statement · rev. 28.10.2014 (catalog copy dated 8/17/18). Object names, instances and units are reproduced as published; descriptions are our own.