Short answer

The Setra Power Meter measures several electrical loads from shared voltage inputs. Over BACnet the root device holds the readings for the two voltage inputs (Vin1, Vin2): line and line-to-line voltages, phase angles, harmonic distortion, frequency and energy, plus the service type and two pulse inputs. Per-load power and energy live in separate load devices.

This page lists 35 BACnet objects for the Setra Power Meter (SPM) - root device — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Setra’s own free documentation, linked below.

Manufacturer
Setra
Model
Setra Power Meter (SPM) - root device
Equipment
Multi-load power meter
Equipment type
Thermostats, sensors & meters
BACnet objects
35 (0 writable)
Transport
—
Firmware
Not stated
Also known as
SPM, Setra SPM, Setra Power Meter, Setra multi-load power meter
Source document
Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H
Download CSV 35 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.

BMS integration notes: Setra Power Meter (SPM) - root device

Integration in brief

Read the voltages, frequency and energy from the root device; read per-load power, current and energy from each load device. Nothing needs to be written for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Vin1 Line 1 Measured Line-Neutral Voltage (L1-N)Vin1 L1-N voltageRead
AI 2Vin1 Line 2 Measured Line-Neutral Voltage (L2-N)Vin1 L2-N voltageRead
AI 3Vin1 Line 3 Measured Line-Neutral Voltage (L3-N)Vin1 L3-N voltageRead
AI 13Vin1 FrequencyVin1 frequencyRead
LAV 1Vin1 Total Energy UsageVin1 total energy, kWh (double precision)Read

Network setup

Watch out for

Setra Power Meter (SPM) - root device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

35 of 35 shown
Type
AnalogMulti-state
Show
Setra Power Meter (SPM) - root device BACnet Points List
DescriptionStates
AImin1Vin1 Line 1 Measured Line-Neutral Voltage (L1-N)VRead
AImin2Vin1 Line 2 Measured Line-Neutral Voltage (L2-N)VRead
AImin3Vin1 Line 3 Measured Line-Neutral Voltage (L3-N)VRead
AI4Vin1 Line 1 - Line 2 Measured Voltage (L1-L2)VRead
AI5Vin1 Line 2 - Line 3 Measured Voltage (L2-L3)VRead
AI6Vin1 Line 3 - Line 1 Measured Voltage (L3-L1)VRead
AI7Vin1 Line 1 Phase AngleUnits can be set to radians or degrees-phase°Read
AI8Vin1 Line 2 Phase AngleUnits can be set to radians or degrees-phase°Read
AI9Vin1 Line 3 Phase AngleUnits can be set to radians or degrees-phase°Read
AI10Vin1 Line 1 Harmonic Distortion%Read
AI11Vin1 Line 2 Harmonic Distortion%Read
AI12Vin1 Line 3 Harmonic Distortion%Read
AImin13Vin1 FrequencyHzRead
AI14Vin1 Total Energy UsagekWhRead
AI21Vin2 Line 1 Measured Line-Neutral Voltage (L1-N)VRead
AI22Vin2 Line 2 Measured Line-Neutral Voltage (L2-N)VRead
AI23Vin2 Line 1 Measured Line-Neutral Voltage (L3-N)Printed "Line 1 ... (L3-N)"; Vin2 line 3 to neutralVRead
AI24Vin2 Line 1 - Line 2 Measured Voltage (L1-L2)VRead
AI25Vin2 Line 2 - Line 3 Measured Voltage (L2-L3)VRead
AI26Vin2 Line 3 - Line 1 Measured Voltage (L3-L1)VRead
AI27Vin2 Line 1 Phase AngleUnits can be set to radians or degrees-phase°Read
AI28Vin2 Line 2 Phase AngleUnits can be set to radians or degrees-phase°Read
AI29Vin2 Line 3 Phase AngleUnits can be set to radians or degrees-phase°Read
AI30Vin2 Line 1 Harmonic Distortion%Read
AI31Vin2 Line 2 Harmonic Distortion%Read
AI32Vin2 Line 3 Harmonic Distortion%Read
AI33Vin2 FrequencyHzRead
AI34Vin2 Total Energy UsagekWhRead
NC1Event Notification ClassRead
MV1Vin1 Service TypeWiring type of voltage input 1Read1=4-Wire wye, 2=3-Wire delta, 3=Reserved, 4=3-Wire single phase (split-phase), 5=2-Wire single phase
MV2Vin2 Service TypeWiring type of voltage input 2Read1=4-Wire wye, 2=3-Wire delta, 3=Reserved, 4=3-Wire single phase (split-phase), 5=2-Wire single phase
Other1Pulse Input #1Pulse Converter object, user-configurable unitsRead
Other2Pulse Input #2Pulse Converter object, user-configurable unitsRead
LAVmin1Vin1 Total Energy UsageLarge analog (double) copy of AI 14kWhRead
LAV2Vin2 Total Energy UsageLarge analog (double) copy of AI 34kWhRead
Object ID lookup: Setra Power Meter (SPM) root device point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Setra Power Meter (SPM) - root device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Setra Power Meter (SPM) - root device

How many BACnet points does the Setra Power Meter (SPM) - root device have?

This list has 35 BACnet objects: 28 analog inputs, 1 notification class, 2 multi-state values, 2 large analog values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Setra Power Meter (SPM) - root device BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Setra Power Meter (SPM) - root device BACnet documentation?

The source is Setra Power Meter Master BACnet Object List (SS-SPM-BAC-OBJ), revision Rev H, published free by Setra at https://www.setra.com/hubfs/SS-SPM-BAC-OBJ,%20print_A.pdf.

What are the minimum BACnet points to integrate the Setra Power Meter (SPM) - root device?

Start with AI 1 Vin1 Line 1 Measured Line-Neutral Voltage (L1-N) (Vin1 L1-N voltage); AI 2 Vin1 Line 2 Measured Line-Neutral Voltage (L2-N) (Vin1 L2-N voltage); AI 3 Vin1 Line 3 Measured Line-Neutral Voltage (L3-N) (Vin1 L3-N voltage); AI 13 Vin1 Frequency (Vin1 frequency); LAV 1 Vin1 Total Energy Usage (Vin1 total energy, kWh (double precision)).

How do I check these points on the real Setra Power Meter (SPM) - root device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Setra BACnet points lists

Source: Setra Power Meter Master BACnet Object List · SS-SPM-BAC-OBJ · rev. Rev H. Object names, instances and units are reproduced as published; descriptions are our own.