VRF outdoor unit (via BACnet gateway) · BACnet points list

Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) BACnet points list

Updated 7 November 2026

Short answer

Through the 40VM900052A interface, each VRF outdoor header unit appears as its own BACnet device with 20 objects: ambient and discharge temperatures, pressures, compressor and fan speeds, malfunction code, on/off, alarm and mode status, plus system-wide multistate outputs (all off, energy limit, fan speed at zero capacity, dry contact 4 settings) that act on every indoor unit of that system. Follower units show only the 13 inputs.

This page lists 20 BACnet objects for the Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Equipment
VRF outdoor unit (via BACnet gateway)
Equipment type
VRF & split air conditioners
BACnet objects
20 (7 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
NNNPAAA (virtual network number, XYE port, unit address)
Also known as
40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF
Source document
40VM Series VRF System BACnet Interface Installation and Operation Manual, Part Number 40VM900052A (Table 69, BACnet Object List of Outdoor Header Unit) · 40VM-52ASI R1 · rev. 2023-04
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)

Integration in brief

Read outdoor unit status and diagnostics from the header unit device; the SYS_MO outputs give group commands such as turning off all indoor units of the system (MO 11) or an energy limit level (MO 10).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 11SYS_MO_AllTurnOffGroup command: turn off/on all indoor unitsWrite
MO 10SYS_MO_AllEnergyLimitSystem energy limit level (No Limit, Level 1-5)Write
BI 1ODU_BI_OnOffStatusOutdoor unit on/off statusRead
MI 1ODU_MI_ModeStatusOutdoor unit mode statusRead
AI 1ODU_AI_AmbientTempOutdoor ambient temperatureRead
BI 2ODU_BI_AlarmOutdoor unit alarm indicationRead
AI 8ODU_AI_MalfunctionCodeOutdoor unit malfunction codeRead

Network setup

Watch out for

Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

20 of 20 shown
Type
AnalogBinary
Access
Show
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) BACnet Points List
DescriptionStates
AImin1ODU_AI_AmbientTempambient temperatureRead
AI2ODU_AI_CompressorSpeedcompressor speedRead
AI3ODU_AI_DischargeTemp1discharge temperature 1Read
AI4ODU_AI_DischargeTemp2discharge temperature 2Read
AI5ODU_AI_DischargeTemp3discharge temperature 3Read
AI6ODU_AI_HighPressurehigh pressureRead
AI7ODU_AI_LowPressurelow pressureRead
AImin8ODU_AI_MalfunctionCodemalfunction codeRead
AI9ODU_AI_Fan1_Speedfan 1 speedRead
AI10ODU_AI_Fan2_Speedfan 2 speedRead
BImin1ODU_BI_OnOffStatuson/off statusRead
BImin2ODU_BI_Alarmalarm indicationRead
MImin1ODU_MI_ModeStatusmode statusRead1=Turn Off, 2=Fan, 3=Cooling, 4=Heating, 5=Force to Cool, 6=Main Cooling, 7=Main Heating, 8=Force to Heat
MOmin10SYS_MO_AllEnergyLimitAll energy limitWrite1=No Limit, 2=Level-1, 3=Level-2, 4=Level-3, 5=Level-4, 6=Level-5
MOmin11SYS_MO_AllTurnOffTurn off all indoor unitsWrite1=Turn Off, 2=Turn On
MO12SYS_MO_AllCoolStopFanIndoor fan speed when cooling capacity is 0 (all units)Write1=Off, 2=Low, 3=Medium, 4=High, 5=Keep
MO13SYS_MO_AllHeatStopFanIndoor fan speed when heating capacity is 0 (all units)Write1=Off, 2=Low, 3=Medium, 4=High, 5=Keep
MO14SYS_MO_AllDryContact4OnDry contact 4 on temperature difference (all units)Write
MO15SYS_MO_AllDryContact4OffDry contact 4 off temperature difference (all units)Write
MO16SYS_MO_AllDryContact4DelayDry contact 4 delay time (all units)Write
Object ID lookup: Carrier 40VM900052A ODU point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)

How many BACnet points does the Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) have?

This list has 20 BACnet objects: 10 analog inputs, 2 binary inputs, 1 multi-state input, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) BACnet points are writable?

7 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects) BACnet documentation?

The source is 40VM Series VRF System BACnet Interface Installation and Operation Manual, Part Number 40VM900052A (Table 69, BACnet Object List of Outdoor Header Unit) (40VM-52ASI R1), revision 2023-04, published free by Carrier at https://brandportal.carrier.com/asset/e7209642-8ffc-4f1c-a298-cd0941359add/40VM-52ASI-R1.pdf.

What are the minimum BACnet points to integrate the Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)?

Start with MO 11 SYS_MO_AllTurnOff (Group command: turn off/on all indoor units); MO 10 SYS_MO_AllEnergyLimit (System energy limit level (No Limit, Level 1-5)); BI 1 ODU_BI_OnOffStatus (Outdoor unit on/off status); MI 1 ODU_MI_ModeStatus (Outdoor unit mode status); AI 1 ODU_AI_AmbientTemp (Outdoor ambient temperature); BI 2 ODU_BI_Alarm (Outdoor unit alarm indication); AI 8 ODU_AI_MalfunctionCode (Outdoor unit malfunction code).

How do I check these points on the real 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.