Rooftop unit controller · BACnet points list

Carrier 48/50FE and 48/50GE Rooftop (SystemVu) BACnet points list

Updated 4 November 2026

Short answer

The SystemVu control on the R-454B 48/50FE and 48/50GE rooftops talks BACnet MS/TP (or CCN) on one RS-485 BMS port. The BACnet table holds about 760 analog, binary and multistate values: setpoints, sensor readings, network inputs, runtimes, alerts and configuration.

This page lists 759 BACnet objects for the Carrier 48/50FE and 48/50GE Rooftop (SystemVu) — 419 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.

Manufacturer
Carrier
Model
48/50FE and 48/50GE Rooftop (SystemVu)
Equipment
Rooftop unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
759 (419 writable)
Transport
BACnet MS/TP
Firmware
SystemVu controls version 3.X
Also known as
SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T
Source document
48/50FE 04-30, 48/50GE 04-28 Single Package Rooftop Units with SystemVu Controls Version 3.X, Controls, Start-Up, Operation and Troubleshooting (Appendix E: BACnet Points List) · SYSVU-FE-GE-02T · rev. 2026-01
Download CSV 759 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.

BMS integration notes: Carrier 48/50FE and 48/50GE Rooftop (SystemVu)

Integration in brief

The SystemVu control has one RS-485 BMS port. Set BAS Protocol to BACnet on the unit display (Settings > Network Settings), set the MAC address and baud rate, power-cycle and connect to the MS/TP trunk. Run occupancy from a BACnet schedule or the BMS Occupancy Request point, write the occupied setpoints, and read the system mode, temperatures and the active fault count.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 12bms_occOccupancy request from the BMS (unocc / occupied / disabled)Write
AV 288ocspOccupied cooling setpointWrite
AV 289ohspOccupied heating setpointWrite
BV 33alarm_resetResets all current alarmsWrite
MV 2002sys_modeCurrent mode (off, cool, heat, vent, test)Read
AV 35req_fan_spdIndoor fan speed the control is calling for, %Read
AV 296space_tSpace temperatureWrite
AV 1008sa_tempSupply air temperatureRead
BV 7048equip_alarmAlarm output relay stateWrite
AV 335num_active_faultsCount of active faultsRead

Enable & remote start

Set BAS Protocol Select to BACnet on the unit display (Settings > Network Settings > BAS Protocol; default None). With BACnet selected the local occupancy schedule is reset and scheduling comes from the BACnet side: a BACnet schedule, or the BMS Occupancy Request (MV 12; the display tables list Unocc, Occupied and Disabled). Unit Control Type (MV 2) decides whether the unit runs from thermostat inputs or a space sensor.

Heartbeat & communication loss

Network Input Timeout (AV 9089, default 30 min per the display tables) applies to the network input values. The guide does not say what the unit does when it expires, so keep any written network value refreshed well inside that time.

Sensors & values from the BMS

Writable network inputs exist for space temperature (Network Space Temp Value, AV 7006), outdoor air temperature (AV 7007), return air temperature (AV 7005), space RH (AV 376), outdoor RH (AV 7003), IAQ and OAQ CO2 (AV 7001, AV 7002) and OA cfm (AV 371). The guide doesn't explain how the unit picks a network value over a local sensor; check the sensor channel settings on the display. The 'BACnet device for ...' and 'Object instance for ...' AVs let the unit read a sensor from another BACnet device.

Network setup

Watch out for

Carrier 48/50FE and 48/50GE Rooftop (SystemVu) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

759 of 759 shown
Type
AnalogBinaryMulti-state
Access
Show
Carrier 48/50FE and 48/50GE Rooftop (SystemVu) BACnet Points List
DescriptionStates
AV2cch_max_tCCH Max Temperature (40 to 90)°FWrite
AV4dmpr_cmdEcono Commanded Position (0 to 100)%Write
AV5mp_uspd2Min Pos - User Speed 2 (0 to 100)%Write
AV6sf_vfd_feedbackCommanded IDF Speed (-200 to 200)%Read
AV8ucspUnoccupied Cool Setpoint (65 to 95)°FWrite
AV10idf_sa_tempFan Supply Air Temp (-40 to 245)°FRead
AV12iaq_20maIAQ Sensor Value at 20mA (0 to 5000)PPMWrite
AV13iaq_4maIAQ Sensor Value at 4mA (0 to 5000)PPMWrite
AV14alarm_infoAlarm display info (0 to 2)Read
AV15mp_spd2Min Pos Curve - Speed 2 (0 to 100)%Read
AV21oarh_4maOARH Sensor Value at 4mA (0 to 50)%Write
AV22oarh_20maOARH Sensor Val. at 20mA (60 to 100)%Write
AV30rarhRA Relative Humidity (0 to 100)%Write
AV31rarh_4maRARH Sensor Value at 4mA (0 to 100)%Write
AV32rarh_20maRARH Sensor Value @ 20mA (0 to 100)%Write
AVmin35req_fan_spdRequested IDF Speed (0 to 100)%Read
AV36speed_maxIDF Maximum Fan Speed (50 to 100)%Write
AV37sys_demandSystem Demand (0 to 255)Read
AV39prime_vValue of Prime variable (-40 to 245)Read
AV40cl_sel_timeguardCool Mode Select T.guard (0 to 65535)secRead
AV44max_enthMax Enthalpy OA limit (1.0 to 99.0)BTU_LBWrite
AV45ht_sel_timeguardHeat Mode Select T.guard (0 to 65535)secRead
AV46acthstgsActual Heat Stage Active (0 to 2)Read
AV47hour_a1Compressor A1 Run Hours (0 to 999999)hrsRead
AV48hour_a2Compressor A2 Run Hours (0 to 999999)hrsRead
AV49hour_alarmAlarm Relay Run Hours (0 to 999999)hrsRead
AV50timgd_h2Heat Stage 2 Timeguard (0 to 600)secRead
AV51hour_dampEcon Damper Run Hours (0 to 999999)hrsRead
AV52hour_full_ldUnit Full Load Run Hours (0 to 999999)hrsRead
AV53hour_free_clFree Cooling Run Hours (0 to 999999)hrsRead
AV54hour_ht_1Heat Stage 1 Run Hours (0 to 999999)hrsRead
AV55hour_ht_2Heat Stage 2 Run Hours (0 to 999999)hrsRead
AV56hour_idfIndoor Fan Run Hours (0 to 999999)hrsRead
AV57hour_max_fanMax Fan Speed Run Hours (0 to 999999)hrsRead
AV61hour_pe_1Power Exhaust1 Run Hours (0 to 999999)hrsRead
AV62hour_pe_2Power Exhaust2 Run Hours (0 to 999999)hrsRead
AV63hour_serv_tstService Test Run Hours (0 to 999999)hrsRead
AV64hour_vent_fanVent IDF Run Hours (0 to 999999)hrsRead
AV67max_free_cl_tempFree Cooling Max OAT (0 to 90)°FWrite
AV71min_free_cl_tempFree Cooling Min Temp (-30 to 70)°FWrite
AV76oa_enthOutdoor Air Enthalpy (-9.6 to 334.2)BTU_LBWrite
AV77oa_ra_diff_enthEnthalpy Cross Deadband (0 to 20)BTU_LBWrite
AV78oa_ra_diff_tempDiff. Dry Bulb Deadband (1.0 to 99.0)°FWrite
AV95ra_enthReturn Air Enthalpy (-9.6 to 334.2)BTU_LBWrite
AV97rs_a1Comp A1 Resets Count (0 to 65535)Read
AV98rs_a2Comp A2 Resets Count (0 to 65535)Read
AV99rs_almAlarm Relay Resets Count (0 to 65535)Read
AV100rs_alrstAlarm Reset Resets Count (0 to 65535)Read
AV102rs_dampEcon Damper Resets Count (0 to 65535)Read
AV103rs_floadFull Load Resets Count (0 to 65535)Read
AV104rs_freecFree Cooling Reset Count (0 to 65535)Read
AV105ufctimeUFC PreOcc Time (1 to 9999)minWrite
AV106rs_htr_1Heat Stage 1 Reset Count (0 to 65535)Read
AV107rs_htr_2Heat Stage 2 Reset Count (0 to 65535)Read
AV108rs_idfIndoor Fan Reset Count (0 to 65535)Read
AV109rs_maxfMax IDF Spd Resets Count (0 to 65535)Read
AV113rs_pe_1P.Exhaust 1 Resets Count (0 to 65535)Read
AV114rs_pe_2P.Exhaust 2 Resets Count (0 to 65535)Read
AV115rs_porPower Cycle Resets Count (0 to 65535)Read
AV116rs_stestService Test Reset Count (0 to 65535)Read
AV117rs_ventfVent IDF Resets Count (0 to 65535)Read
AV118s_damperEconomizer Position Test (0 to 100)%Write
AV119s_idfspdIndoor Fan Speed Test (0 to 100)%Write
AV124sdp_aCir.A Discharge Pressure (-67.06 to 699.63)PSIRead
AV131ssp_aCir.A Suction Pressure (-47.33 to 430.16)PSIRead
AV134st_a1Compressor A1 Starts (0 to 999999)Read
AV135st_a2Compressor A2 Starts (0 to 999999)Read
AV136st_almAlarm Relay Starts (0 to 999999)Read
AV137st_alrstAlarm Reset Counts (0 to 999999)Read
AV138mp_uspd3Min Pos - User Speed 3 (0 to 100)%Write
AV139st_dampEconomizer Damper Starts (0 to 999999)Read
AV140st_floadUnit Full Load Starts (0 to 999999)Read
AV141st_freecFree Cooling Starts (0 to 999999)Read
AV142st_htr_1Heat Stage 1 Starts (0 to 999999)Read
AV143st_htr_2Heat Stage 2 Starts (0 to 999999)Read
AV144st_idfIndoor Fan Starts (0 to 999999)Read
AV145st_maxfMax IDF Speed Starts (0 to 999999)Read
AV148st_pe_1Power Exhaust 1 Starts (0 to 999999)Read
AV149st_pe_2Power Exhaust 2 Starts (0 to 999999)Read
AV150st_porPower Cycle Counts (0 to 999999)Read
AV151st_stestService Test Starts (0 to 999999)Read
AV152st_ventfVentilation Fan Starts (0 to 999999)Read
AV153startdlyUnit Startup Delay (10 to 600)secWrite
AV157timgd_a2Compressor A2 Timeguard (0 to 600)secRead
AV159altitudeAltitude in Feet (-1000 to 60000)Write
AV161barpBarometric Pressure (10 to 35)IN OF HGWrite
AV162timgd_a1Compressor A1 Timeguard (0 to 600)secRead
AV163temp_effEffective Demand Temp (-40 to 245)°FRead
AV164timg_aldcmp Loader Timeguard (0 to 600)secRead
AV173timgd_h1Heat Stage 1 Timeguard (0 to 600)secRead
AV175mintilocMins until next occupied (-1 to 10080)minRead
AV176nxtoctimNext Occupied Time (-1 to 10080)minRead
AV177nxtuntimNext Unoccupied Time (-1 to 10079)minRead
AV178uhspUnoccupied Heat Setpoint (40 to 80)°FWrite
AV179otl_cfgTimed Override Duration (0 to 4)hrsWrite
AV180ovr_extTimed Override Hours (0 to 240)minWrite
AV181passwordUser Password (0 to 9999)Write
AV182prvuntimPrevious Unoccupied Time (-1 to 10079)minRead
AV184resetdevReset DeviceWrite
AV185dampmaxEcon Max Damper Position (0 to 100)%Write
AV186tdmd_tg2Space Demand Time Guard2 (0 to 600)secWrite
AV187tdmd_tg3Space Demand Time Guard3 (5 to 120)minWrite
AV188bac_idBACnet ID Number (0 to 4194302)Write
AV189bac_macBACnet Device Macaddress (0 to 127)Write
AV191utc_ofstLocal Std Time offset (-780 to 780)minWrite
AV192a1strikeCompressor A1 strikes (0 to 3)Read
AV193a2strikeCompressor A2 Strikes (0 to 3)Read
AV194actcstgsActual Cool Stage Active (0 to 3)Read
AV195aq_diffDifferential Air Quality (-5000 to 5000)PPMRead
AV196aq_pos1IAQ DCV Curve - Pos 1 (0 to 100)%Read
AV197aq_pos2IAQ DCV Curve - Pos 2 (0 to 100)%Read
AV198aq_pos3IAQ DCV Curve - Pos 3 (0 to 100)%Read
AV199aq_spd1IAQ DCV Curve - Speed 1 (0 to 100)%Read
AV200aq_spd2IAQ DCV Curve - Speed 2 (0 to 100)%Read
AV201aq_spd3IAQ DCV Curve - Speed 3 (0 to 100)%Read
AV202c_minoffCompressor Min Off Time (120 to 600)secWrite
AV203c_minonCompressor Min On Time (180 to 600)secWrite
AV204cira_prCircuit A Pressure Ratio (14.5 to 667.0)Read
AV205cldtrendCooling Demand Trend (-99 to 99)Read
AV206cool_dmdSpace Cooling Demand (-100 to 100)°F deltaRead
AV207cool_fodCooling Fan-Off Delay (0 to 600)secWrite
AV208csp_effCool Setpoint in Effect (55 to 95)°FRead
AV212daq_highAQ Differential High (0 to 5000)Write
AV213daq_lowAQ Differential Low (0 to 5000)Write
AV214mp_upt3User Min Pos Pnt 3 ValidRead
AV215dmdhconHigh Cool Demand On (0.5 to 20)°FWrite
AV217dmdhhonHigh Heat Demand On (0.5 to 20)°FWrite
AV218dmdlcoffLow Cool Demand Off (-1 to 2)°FWrite
AV219dmdlconLow Cool Demand On (-1 to 2)°FWrite
AV220dmdlhoffLow Heat Demand Off (-1 to 2)°FWrite
AV221dmdlhonLow Heat Demand On (-1 to 2)°FWrite
AV222mp_uspd1Min Pos - User Speed 1 (0 to 100)%Write
AV223dmdmconMedium Cool Demand On (0.5 to 20)°FWrite
AV226eceonotrvEconomizer Travel Time (5 to 999)secWrite
AV229pe2_offsP.Exhaust 2 Curve Offset (0 to 100)%Read
AV235h_minoffHeat Minimum Off Time (60 to 600)secWrite
AV236h_minonHeat Minimum On Time (60 to 600)secWrite
AV237high_cool_saspHigh FreeCool SAT Setpnt (40 to 80)°FWrite
AV238hcsp_gapHeat-Cool Setpoint Gap (2 to 10)°FWrite
AV239hadmd_lupHeat Demand Level Up (-2 to 2)°FWrite
AV240heat_dmdHeating Space Demand (-100 to 100)°F deltaRead
AV241heat_fodHeating Fan-Off Delay (10 to 600)secWrite
AV242hour_cchr1CCH1 Relay Run Hours (0 to 999999)hrsRead
AV243hsp_effHeat Setpoint in Effect (40 to 80)°FRead
AV244htdtrendHeat Space Demand Trend (-99 to 99)Read
AV245iaq_offsIAQ DCV Curve Offset (0 to 100)%Read
AV246iaqminpIAQ Position at Max Fan (0 to 100)%Write
AV248iaqp_laPreocc Purge Lockout OAT (0 to 70)°FWrite
AV252iaqptimePreocc Purge Duration (5 to 120)minWrite
AV253la_tempLow Ambient Temperature (0 to 80)°FWrite
AV254low_cool_saspLowFree Cool SAT Setpnt (40 to 80)°FWrite
AV255lnk_aoztAverage Occup. Zone Temp (-40 to 245)°FWrite
AV256lnk_aztAverage Zone Temperature (-40 to 245)°FWrite
AV257lnk_creqLinkage Cooling Required (0 to 30)°FRead
AV258lnk_dposLinkage Damper Position (0 to 100)%Read
AV259lnk_hreqLinkage Heating Required (0 to 30)°FRead
AV260lnk_mairLinkage Maximum Airflow (0 to 5000)Read
AV261lnk_modeLinkage Equipment Mode (0 to 8)Write
AV262lnk_mzbkBlock No: in Master Zone (0 to 255)Write
AV263lnk_ocrqOcc Cooling Required (0 to 30)°FRead
AV264lnk_ocspAverage Occup. Cool Stp. (55 to 80)°FWrite
AV265lnk_ohrqOcc Heating required (0 to 30)°FRead
AV266lnk_ohspAverage Occup. Heat Stp. (55 to 80)°FWrite
AV267lnk_opstLinkage Optimal Start (0 to 180)minRead
AV268lnk_satLinkage Supply air temp (-40 to 240)°FRead
AV269lnk_sbtLinkage Start Bias time (0 to 180)minWrite
AV270lnk_siaqLinkage Space Air Qual. (0 to 2000)PPMRead
AV271lnk_sprhLinkage Space RH (0 to 100)%Read
AV272lnk_supbLinkage CCN Bus number (0 to 239)Write
AV273lnk_supeLinkage CCN element # (0 to 239)Write
AV274lnk_ucspAverage Unocc. Cool Stp. (65 to 90)°FWrite
AV275lnk_uhspAverage Unocc. Heat Stp. (40 to 80)°FWrite
AV276loch_lotLow Charge Disable Temp (-40 to 50)°FWrite
AV277lochargeLow Refrig Charge Level (0 to 150)PSIWrite
AV278max_cstgsMax Allowed Cool Stages (0 to 3)Write
AV279max_hstgsMax Allowed Heat Stages (0 to 2)Write
AV280minodftmODF High Speed Time (0 to 300)secWrite
AV281no_igctmNo IGC IFO input Timeout (0 to 60)minWrite
AV283numcstgsNumber Of Cooling Stages (0 to 2)Read
AV284numhstgsNumber Of Heating Stages (0 to 2)Write
AV286oat_locOutdoor Air Temp Sensor (-40 to 245)°FRead
AV287oatlufcUnocc Free Cool Low Temp (-30 to 70)°FWrite
AVmin288ocspOccupied Cool Setpoint (55 to 80)°FWrite
AVmin289ohspOccupied Heat Setpoint (55 to 80)°FWrite
AV290mp_dpos2Min Pos - Default Pos 2 (0 to 100)%Read
AV291rat_locReturn Air Temp Sensor (-40 to 245)°FRead
AV292req_cstgsRequested Cooling Stages (0 to 3)Read
AV293reqhstgsRequested Heating Stages (0 to 255)Read
AV294rs_cchr1CCH1 Relay Resets Count (0 to 65535)Read
AV295sdt_aCir.A Sat.Discharge Temp (-100 to 500)°FRead
AVmin296space_tSpace Temperature (-40 to 245)°FWrite
AV297spt_locSpace Temperature Sensor (-40 to 245)°FRead
AV298spto_rngSPT Offset Range (+/-) (0 to 5)°FWrite
AV300sstckdlyDelay On Low SST Check (0 to 300)secWrite
AV301st_cchr1CCH1 Relay Starts (0 to 999999)Read
AV303std_barpStd Barometric Pressure (10 to 35)IN OF HGWrite
AV305t24chdlyT24 Heat/Cool End Delay (0 to 60)minWrite
AV306t24ecstsT24Econ Min Move for SAT (10 to 20)%Write
AV307t24ratdfT24 Min Diff in RAT-OAT (5 to 20)°FWrite
AV308t24satdbDamper SAT deadband (0 to 50)°FWrite
AV309t24tstmnT24 Test Minimum Pos (0 to 100)%Write
AV310t24tstmxT24 Test Maximum Pos (0 to 100)%Write
AV311tdmd_tg1Space Demand Time Guard1 (60 to 600)secWrite
AV312link_ahu_staticLinkage static pressure (-5 to 5)IN_H2ORead
AV316pe_offdbPE Turn Off Dead band (0 to 100)%Write
AV317pe1_offsP.Exhaust 1 Curve Offset (0 to 100)%Read
AV318minp_maxEcon Min at Max Fanspeed (0 to 100)%Write
AV319mp_dpos1Min Pos - Default Pos 1 (0 to 100)%Read
AV320mp_dpos3Min Pos - Default Pos 3 (0 to 100)%Read
AV321mp_dspd1Min Pos - Default Speed1 (0 to 100)%Read
AV322mp_dspd2Min Pos - Default Speed2 (0 to 100)%Read
AV323ms_dspd3Min Pos - Default Speed3 (0 to 100)%Read
AV324mp_pos1Min Pos Curve - Pos 1 (0 to 100)%Read
AV325mp_pos2Min Pos Curve - Pos 2 (0 to 100)%Read
AV326mp_pos3Min Pos Curve - Pos 3 (0 to 100)%Read
AV327mp_spd1Min Pos Curve - Speed 1 (0 to 100)%Read
AV328mp_spd3Min Pos Curve - Speed 3 (0 to 100)%Read
AV329mp_upos1Min Pos - User Pos 1 (0 to 100)%Write
AV330mp_upos2Min Pos - User Pos 2 (0 to 100)%Write
AV331mp_upos3Min Pos - User Pos 3 (0 to 100)%Write
AV332mp_upt1User Min Pos Pnt 1 ValidRead
AV333mp_upt2User Min Pos Pnt 2 ValidRead
AV334num_active_alertsNumber of Active Alerts (0 to 100)Read
AVmin335num_active_faultsNumber of Active Faults (0 to 100)Read
AV336bkpreptmBACKUP Preparation Time (0 to 65535)Read
AV337rstcomtmRestore Completion Time (0 to 65535)Read
AV339sst_aCir.A Sat.Suction Temp (-100 to 500)°FRead
AV342sattrendSupply Air Temp Trend (-285 to 285)Read
AV343pe1_pmaxPE Stage 1 At Max Speed (0 to 100)%Write
AV344pe2_pmaxPE Stage 2 At Max Speed (0 to 100)%Write
AV345pe1_pos1Power Exhaust 1 - Pos 1 (0 to 100)%Read
AV346pe1_pos2Power Exhaust 1 - Pos 2 (0 to 100)%Read
AV347pe1_pos3Power Exhaust 1 - Pos 3 (0 to 100)%Read
AV348pe1_spd1Power Exhaust 1 - Speed1 (0 to 100)%Read
AV349pe1_spd2Power Exhaust 1 - Speed2 (0 to 100)%Read
AV350pe1_spd3Power Exhaust 1 - Speed3 (0 to 100)%Read
AV351pe2_pos1Power Exhaust 2 - Pos 1 (0 to 100)%Read
AV352pe2_pos2Power Exhaust 2 - Pos 2 (0 to 100)%Read
AV353pe2_pos3Power Exhaust 2 - Pos 3 (0 to 100)%Read
AV354pe2_spd1Power Exhaust 2 - Speed1 (0 to 100)%Read
AV355pe2_spd2Power Exhaust 2 - Speed2 (0 to 100)%Read
AV356pe2_spd3Power Exhaust 2 - Speed3 (0 to 100)%Read
AV358aqp_pos1IAQ Purge Curve - Pos 1 (0 to 100)%Read
AV359aqp_pos2IAQ Purge Curve - Pos 2 (0 to 100)%Read
AV360aqp_pos3IAQ Purge Curve - Pos 3 (0 to 100)%Read
AV361aqp_spd1IAQ Purge Curve - Speed1 (0 to 100)%Read
AV362aqp_spd2IAQ Purge Curve - Speed2 (0 to 100)%Read
AV363aqp_spd3IAQ Purge Curve - Speed3 (0 to 100)%Read
AV364aqp_offsIAQ Purge Curve Offset (0 to 100)%Read
AV367sprh_ospOccupied SPRH Setpoint (10 to 100)%Write
AV368sprh_dbSpace RH Deadband (0 to 100)%Write
AV369ocfm_4maOACFM at 4MA (0 to 5000)CFMWrite
AV371ocfm_netNetwork OACFM Value (0 to 5000)CFMWrite
AV373sprh_20maSPRH Sensor Value @ 20mA (60 to 100)%Write
AV375sprh_4maSPRH Sensor Value at 4mA (0 to 50)%Write
AV376sprh_netNetwork SPRH Value (0 to 100)%Write
AV380hour_ldv_aLDV_A Run Hours (0 to 999999)hrsRead
AV381hour_rdv_aRDV_A Run Hours (0 to 999999)hrsRead
AV382hour_rqhl1Reheat level 1 Run Hrs (0 to 999999)hrsRead
AV383hour_rqhl2Reheat level 2 Run Hrs (0 to 999999)hrsRead
AV384st_ldv_aldv_a Starts (0 to 999999)Read
AV385st_rdv_ardv_a Starts (0 to 999999)Read
AV386st_rqhl1Reheat level 1 Starts (0 to 999999)Read
AV387st_rqhl2Reheat level 2 Starts (0 to 999999)Read
AV388rs_ldv_aLDV_A Resets Count (0 to 65535)Read
AV389rs_rdv_ardv_a Resets Count (0 to 65535)Read
AV390rs_rqhl1Reheat lev 1 Rst Count (0 to 65535)Read
AV391rs_rqhl2Reheat lev 2 Rst Count (0 to 65535)Read
AV400cdlm_level1COOL DMD Offset level 1 (0 to 40)°FWrite
AV401cdlm_level2COOL DMD Offset level 2 (0 to 40)°FWrite
AV402cdlm_level3COOL DMD Offset level 3 (0 to 40)°FWrite
AV403hdlm_level1Heat DMD Offset level 1 (0 to 40)°FWrite
AV404hdlm_level2Heat DMD Offset level 2 (0 to 40)°FWrite
AV405hdlm_level3Heat DMD Offset level 3 (0 to 40)°FWrite
AV411sup_air_temp_setptSA Tempering Set point (-20 to 60)°FWrite
AV412min_posMin Position in Effect (0 to 100)%Write
AV413reqdstgsReq Compr DehumStgs (0 to 10)Write
AV414s_hmzlevHumidiMizer Level Test (0 to 2)Write
AV416oacfmOutdoor Air in CFM (0 to 5000)CFMWrite
AV417ocfm20maOACFM Value at 20mA (0 to 5000)CFMWrite
AV424oatstempOATLimitForSupAirTemp (-40 to 125)°FWrite
AV436fbdh_satFBDH SAT Min value (35 to 80)°FWrite
AV437fbdh_sstFBDH SST Min value (10 to 60)°FWrite
AV438fbdlospFBDH Low Set Point (-20 to 0)°F deltaWrite
AV441fbdsatspFBDH SAT Set Point (0 to 240)°FRead
AV442aqd_highAQ DiffHigh-IAQ OVERRIDE (0 to 5000)PPMWrite
AV443aqd_lowAQ Diff Low-IAQ OVERRIDE (0 to 5000)PPMWrite
AV455rs_clv_aCLV_A Reset Count (0 to 65535)Read
AV456rs_rlv_aRLV_A Resets Count (0 to 65535)Read
AV457hr_clv_aCLV_A Run Hours (0 to 999999)hrsRead
AV458hr_rlv_aRLV_A Run Hours (0 to 999999)hrsRead
AV459st_clv_aCLV_A Starts (0 to 999999)Read
AV460st_rlv_aRLV_A Starts (0 to 999999)Read
AV461sprh_uspUnoccupied SPRH Setpoint (10 to 100)%Write
AV617umin_satUnit's Minimum SAT (-40 to 245)°FWrite
AV618satlaclrAuto Clr SAT Limit FaultWrite
AV619satfzproSAT Freeze ProtectionWrite
AV620hour_idf2Indoor Fan2 Run Hours (0 to 999999)hrsRead
AV621st_idf2Indoor Fan2 Starts (0 to 999999)Read
AV622rs_idf2Indoor Fan2 Reset Count (0 to 65535)Read
AV623hour_ofr2ODF Relay 2 Run Hours (0 to 999999)hrsRead
AV624st_ofr2ODF Relay 2 Starts (0 to 999999)Read
AV625rs_ofr2ODF Relay2 Resets Counts (0 to 65535)Read
AV626hour_ofr3ODF Relay 3 Run Hours (0 to 999999)hrsRead
AV627st_ofr3ODF Relay 3 Starts (0 to 999999)Read
AV628rs_ofr3ODF Relay3 Resets Counts (0 to 65535)Read
AV629max_infoBACnet Device MAX Info (1 to 255)Write
AV630max_mastBACnet Device max_mast (1 to 127)Write
AV1003oa_tempOutdoor Air Temperature (-40 to 245)°FWrite
AV1006stpt_adjSpace Temperature Offset (-10 to 10)°F deltaWrite
AVmin1008sa_tempSupply Air Temperature (-40 to 245)°FRead
AV1009iaqIndoor Air Quality Level (0 to 5000)PPMWrite
AV1010ra_tempReturn Air Temperature (-40 to 245)°FWrite
AV1011space_rhSpace RH (0 to 100)%Write
AV1012oaqOA Quality Level (0 to 5000)PPMWrite
AV1022oarhOA Relative Humidity (0 to 100)%Write
AV1902EquipmentTouchSPTEquipment Touch SPT (-40 to 240)°FWrite
AV1904EquipmentTouchRHEquipment Touch RH (0 to 100)%Write
AV1905ZSZoneTempZS Zone Temp (-40 to 245)°FWrite
AV1906zszco2Zone sensor CO2 level (0 to 5000)PPMRead
AV1907ZS1TempTrimZS1 Temperature Trim (-30 to 30)°FWrite
AV1908ZS2TempTrimZS2 Temperature Trim (-30 to 30)°FWrite
AV1909ZS3TempTrimZS3 Temperature Trim (-30 to 30)°FWrite
AV1910ZS4TempTrimZS4 Temperature Trim (-30 to 30)°FWrite
AV1911ZS5TempTrimZS5 Temperature Trim (-30 to 30)°FWrite
AV1912ZS1RawTempZS1 Raw Temperature (-40 to 245)°FWrite
AV1913ZS2RawTempZS2 Raw Temperature (-40 to 245)°FWrite
AV1914ZS3RawTempZS3 Raw Temperature (-40 to 245)°FWrite
AV1915ZS4RawTempZS4 Raw Temperature (-40 to 245)°FWrite
AV1916ZS5RawTempZS5 Raw Temperature (-40 to 245)°FWrite
AV1917ZS1TempZS1Tempvalue (-40 to 245)°FWrite
AV1918ZS2TempZS2Tempvalue (-40 to 245)°FWrite
AV1919ZS3TempZS3Tempvalue (-40 to 245)°FWrite
AV1920ZS4TempZS4Tempvalue (-40 to 245)°FWrite
AV1921ZS5TempZS5Tempvalue (-40 to 245)°FWrite
AV2007space_tempSpace Temp Value (-40 to 245)°FWrite
AV2015filter_rntmFilter hour remaining (0 to 9999)hrsRead
AV2019filter_service_hrsChange Filter Timer (0 to 9999)hrsWrite
AV2022oa_dmpr_posDamper Actual Position (0 to 100)%Write
AV2027vfd_outputCommanded IDF Speed (0 to 100)%Read
AV6001zonesptSingle Zone Setpoint (55 to 80)°FWrite
AV6002ospOccupied Zone Setpoint (40 to 80)°FWrite
AV6003odbOccupied Setpoint Gap (0 to 10)Write
AV6004udbUnoccupied Setpoint Gap (0 to 55)Write
AV6005uspUnoccupiedZone Setpoint (40 to 95)°FWrite
AV6006effspEffective Zone Setpoint (55 to 90)°FWrite
AV6007effdbEffective Deadband (0 to 55)Write
AV6021setadjSetpoint adjustment°F deltaWrite
AV7001iaq_netNetwork IAQ Value (0 to 5000)PPMWrite
AV7002oaq_netNetwork OAQ Value (0 to 5000)PPMWrite
AV7003oarh_netNetwork OARH Value (0 to 100)%Write
AV7004rarh_netNetwork RARH Value (0 to 100)%Write
AV7005rat_netNetwork Return Air Temp (-40 to 245)°FWrite
AV7006spt_netNetwork Space Temp Value (-40 to 245)°FWrite
AV7007oat_netNetwork OAT Value (-40 to 245)°FWrite
AV7010hr_aldrCMP A1 Loader Run Hours (0 to 999999)hrsRead
AV7011st_aldrCMP A1 Loader Starts (0 to 999999)Read
AV7012rs_aldrA1 Loader Resets Count (0 to 65535)Read
AV8001deviaqBACnet device for IAQ (0 to 4194303)Write
AV8002devoaqBACnet device for OAQ (0 to 4194303)Write
AV8003devoatBACnet device for OAT (0 to 4194303)Write
AV8004devoarhBACnet device for OARH (0 to 4194303)Write
AV8005devrarhBACnet device for RARH (0 to 4194303)Write
AV8006devratBACnet device for RAT (0 to 4194303)Write
AV8007devsptBACnet device for SPT (0 to 4194303)Write
AV8008objiaqObject instance for IAQ (0 to 9999)Write
AV8009objoaqObject instance for OAQ (0 to 9999)Write
AV8010objoatObject instance for OAT (0 to 9999)Write
AV8011objoarhObject instance for OARH (0 to 9999)Write
AV8012objrarhObject instance for RARH (0 to 9999)Write
AV8013objratObject instance for RAT (0 to 9999)Write
AV8014objsptObject instance for SPT (0 to 9999)Write
AV8015coviaqChange of value for IAQ (0 to 60)Write
AV8016covoaqChange of value for OAQ (0 to 60)Write
AV8017covoatChange of value for OAT (0 to 60)Write
AV8018covoarhChange of value for OARH (0 to 60)Write
AV8019covrarhChange of value for RARH (0 to 60)Write
AV8020covratChange of value for RAT (0 to 60)Write
AV8021covsptChange of value for SPT (0 to 60)Write
AV8022strh_netSystem Touch RH Value (0 to 100)%Write
AV8023stst_netSystem Touch Temp Value (-40 to 245)°FWrite
AV8024devstSystem Touch Device Inst (0 to 4194303)Write
AV8025pollstSystem Touch Poll Rate (0 to 60)Write
AV8026aistsptSystem Touch AI for SPT (0 to 9999)Write
AV8027aistsprhSystem Touch AI for SPRH (0 to 9999)Write
AV8028devsprhBACnet device for SPRH (0 to 4194303)Write
AV8029objsprhObject instance for SPRH (0 to 9999)Write
AV8030covsprhChange of value for SPRH (0 to 60)Write
AV8031lclockspLow Cool lockout Temp (-20 to 60)°FWrite
AV8032mclockspMed Cool Lockout Temp (-20 to 60)°FWrite
AV8033oatlheatHeating Lockout Temp (40 to 125)°FWrite
AV8034zsaddr1Zone Sensor 1 Address (0x00 to 0xFF)Write
AV8035zsaddr2Zone Sensor 2 Address (0x00 to 0xFF)Write
AV8036zsaddr3Zone sensor 3 address (0x00 to 0xFF)Write
AV8037zsaddr4Zone sensor 4 address (0x00 to 0xFF)Write
AV8038zsaddr5Zone sensor 5 address (0x00 to 0xFF)Write
AV8043hour_ofrODF Relay Run Hours (0 to 999999)hrsRead
AV8044rs_ofrODF Relay Resets Counts (0 to 65535)Read
AV8045st_ofrODF Relay Starts (0 to 999999)Read
AV8046rs_erv2p2Position/ERV ResetCount (0 to 65535)Read
AV8047st_erv2p2Position/ERV Starts (0 to 999999)Read
AV8048fspd_rpmIDF Commanded RPM (0 to 5000)RPMRead
AV8049erv2chan2-Pos Damper/ERV Channel (0 to 2)Write
AV8050rpm_fclIDF Free Cool Speed-RPM (0 to 5000)RPMWrite
AV8051rpm_hclIDF High Cool Speed-RPM (0 to 5000)RPMWrite
AV8052rpm_heatIDF Heat Speed-RPM (0 to 5000)RPMWrite
AV8053rpm_lclIDF Low Cool Speed-RPM (0 to 5000)RPMWrite
AV8054rpm_ventIDF Vent Speed-RPM (0 to 5000)RPMWrite
AV8055hr_erv2p2Position/ERV Run Hours (0 to 999999)hrsRead
AV8056fdrpmminFBDH Min Fan Speed (0 to 5000)RPMWrite
AV8057fdrpmmaxFBDH Max Fan Speed (0 to 5000)RPMWrite
AV8075unitsizeSystem Capacity in ton (0 to 255)Write
AV9074s_ervspdERV SPEED TEST (0 to 100)%Write
AV9078FANSPED2Commanded IDF Speed2 (0 to 100)%Read
AV9079la_temp2Low Ambient Temp2 (0 to 80)°FWrite
AV9083IFM2OFSTINDOOR MOTOR2 OFFSET (0 to 100)%Write
AV9085fsp2_rpmIDF2 Commanded RPM (0 to 5000)RPMWrite
AV9087lclofsetLow Cool Offset (30 to 100)%Write
AV9089netintoNetwork Input Timeout (1 to 600)minWrite
AV9091zs_humidityZS Humidity Out (0 to 100)%Write
AV9092humzofstHumidimizer Offset Value (0 to 25)Write
AV9093zsm_tmrZSM Time Out (5 to 60)minWrite
AV9098zst_tmrZST Time Out (6 to 20)minWrite
AV9099delta_cmd_posDelta between CMD & POS (0 to 100)%Write
AV9101drsw_dlyDoor Switch Delay (0 to 99)minWrite
AV9118rpm_mclIDF Med Cool Speed-RPM (0 to 5000)RPMWrite
AV9119mclofsetMedium Cool Offset (50 to 100)%Write
AV9121la_temp3Low Ambient Temp3 (0 to 80)°FWrite
BV3cch_relayCCH Relay 1 StateRead
BV4circa_hpsCir.A High Pressure SwRead
BV5cmpa1enaCircuit A Compressor 1Read
BV6cmpa2enaCircuit A Compressor 2Read
BV7fanred10IDF Speed Reduction OnRead
BV9cmpalenaCircuit A CMP A1 LoaderRead
BV10hs1Heat Stage 1 RelayRead
BV11hs2Heat Stage 2 RelayRead
BV13igc_ifoIGC Fan On Request (IFO)Read
BV15pe1Power Exhaust 1 RelayWrite
BV16ht1_avalHeat Stage 1 AvailableRead
BV17ht2_avalHeat Stage 2 AvailableRead
BV20iaqpurgeIAQ Preoccupancy PurgeWrite
BV21dmpr_errEcono Actual PositionWrite
BV27ALARMENAlarm Reporting EnableWrite
BV28y3_inputThermostat Y3 InputWrite
BV29remoccRemote Occupancy SwitchWrite
BV32alarm_hist_clearClear Alarm HistoryWrite
BVmin33alarm_resetReset All Current AlarmsWrite
BV34locshutLocal Unit Shutdown Req.Write
BV35okpreoccOk to Preoccupancy PurgeRead
BV36oktoheatOK to Run HeatRead
BV37oktoufcOk to Unocc Free Cool?Read
BV38preocconIn Pre-Occupancy Purge?Read
BV39damp_goodEcon Damper OperationalRead
BV40db_lock_outDry Bulb LockoutWrite
BV41dif_db_enaDiff. Dry Bulb ControlWrite
BV42dif_enth_enaDiff. Enthalpy ControlWrite
BV43econ_alarmEconomizer AlertsWrite
BV44enth_lock_outEnthalpy LockoutWrite
BV45idf_alarmIndoor Fan AlertsWrite
BV46occupied_fanFan On When OccupiedWrite
BV49fst_errorFST Sensor ErrorWrite
BV50gen_statusGeneral Status SwitchWrite
BV51iaq_errIAQ Sensor ErrorWrite
BV52idf_badIDF Operation Errors?Read
BV58link_activeLinkage ActiveRead
BV60oarh_errOARH Sensor ErrorWrite
BV61oat_rel_alarmOAT Thermistor AlertsWrite
BV63sdpa_errSDPA Sensor ErrorWrite
BV64s_bmpaldCmp Bump Loader TestWrite
BV65ok_free_clOK to Use Free Cooling?Read
BV66pe2Power Exhaust 2 RelayWrite
BV67rarh_errRARH Sensor ErrorWrite
BV68rat_errRAT Sensor ErrorWrite
BV70s_alarmAlarm Output Relay TestWrite
BV71s_bmpa1Compressor Bump A1 TestWrite
BV72s_bmpa2Compressor Bump A2 TestWrite
BV73s_cchr1Crankcase Heater 1 testWrite
BV74s_coola1Cooling W/Comp.A1 TestWrite
BV75s_coola2Cooling W/Comp.A2 TestWrite
BV76s_heat1Heating Stage 1 TestWrite
BV77s_heat2Heating Stage 2 TestWrite
BV78s_idftrnIDF Manual TransitionWrite
BV79s_cola1dCooling W/Comp.ALD TestWrite
BV80purgeSmoke Purge SwitchWrite
BV82s_pe_1Power Exhaust 1 TestWrite
BV83s_pe_2Power Exhaust 2 TestWrite
BV84sat_errSAT Sensor ErrorWrite
BV89sspa_errSSPA Sensor ErrorWrite
BV92dst_actvDST currently activeRead
BV93dst_cfgDST allowed?Write
BV95loc_occLocal Sched Occ RequestWrite
BV96hol_tmrwTomorrow Is A HolidayRead
BV98holtodayToday Is A HolidayRead
BV100pass_eblUser Password ProtectionWrite
BV103space_alarmSpace Sensors AlertsWrite
BV104tstat_alThermostat AlertsWrite
BV106auidALC Auto Id SchemeWrite
BV107bac_auidBACnet ID Auto IDWrite
BV109reset_filter_timerReset Filter TimerWrite
BV110calobjstBACnetCal Object StatusRead
BV111backfileUSB Find Restore FileWrite
BV112firedownFire Shutdown SwitchWrite
BV115adptstatTstat Adaptive StagingWrite
BV122allhtlocAll Heat Stages LockoutWrite
BV123ca1_avalCompressor A1 AvailableRead
BV124ca1_lockCompressor A1 Locked OutRead
BV125ca2_avalCompressor A2 AvailableRead
BV126ca2_lockCompressor A2 Locked OutRead
BV128ciralockCircuit A Locked OutRead
BV129ddbckupMake Config Backup FileWrite
BV130ddrstreStart Config RestoreRead
BV133tcs_ActTemp Compensate Start OnRead
BV135ufc_actUnocc Free Cool ActiveRead
BV160autocoolRUN AUTO COOLING TESTWrite
BV161autoheatRUN AUTO HEATING TESTWrite
BV162autosysRUN AUTO SYSTEM TESTWrite
BV163autoindpAUTO INDEPENDENT TESTWrite
BV164iaq_ovrdIs IAQ Override Active?Read
BV167f_calochCirA low chargeRead
BV168f_caddfCirA down due to failRead
BV169a_caprCir.A Pressure RatioRead
BV170a_calspCir.A Low SuctionRead
BV171a_cahpsCir.A HPS tripRead
BV172a_cahdpCir.A High DischargeRead
BV173f_ca2ddfC.A2 down due to failRead
BV174a_ca2rrC.A2 reverse rotationRead
BV177a_ca2ftpC.A2 fail to pressureRead
BV178f_ca1ddfC.A1 down due to failRead
BV179a_ca1rrC.A1 reverse rotationRead
BV181a_caoffCir.A unexpected offRead
BV182a_ca1ftpC.A1 fail to pressureRead
BV183a_baddpaCir.A SDP sensor rangeRead
BV184a_badec1Econ feedback rangeRead
BV185a_badfstFST sensor rangeRead
BV186a_badoatOAT sensor rangeRead
BV187a_badratRAT sensor rangeRead
BV188a_badsatSAT sensor errorRead
BV189a_badspaCir.A SSP sensor rangeRead
BV190a_badsptSPT sensor rangeRead
BV191a_opndpaCir.A SDP open sensorRead
BV192a_opnec1Econ feedback openRead
BV193a_opnfstFST open sensorRead
BV194a_opniaqIAQ open sensorRead
BV195a_opnoaqOAQ open sensorRead
BV196a_opnoatOAT open sensorRead
BV197a_opnorhOARH open sensorRead
BV198a_opnratRAT open sensorRead
BV199a_opnrrhRARH open sensorRead
BV200a_opnspaCir.A SSP open sensorRead
BV201a_opnsptSPT open sensorRead
BV202a_shtdpaCir.A SDP short sensorRead
BV203a_shtec1Econ feedback shortedRead
BV204a_shtfstFST shorted sensorRead
BV205a_shtiaqIAQ shorted sensorRead
BV206a_shtoaqOAQ shorted sensorRead
BV207a_shtoatOAT shorted sensorRead
BV208a_shtorhOARH shorted sensorRead
BV209a_shtratRAT shorted sensorRead
BV210a_shtrrhRARH shorted sensorRead
BV211a_shtspaCir.A SSP short sensorRead
BV212a_shtsptSPT shorted sensorRead
BV214a_dfiltDirty FilterWrite
BV215a_dnmEcon not modulatingRead
BV216a_dnm_scEcon stuck closedRead
BV217a_dnm_soEcon stuck openRead
BV218a_dnmemdEcon mech disconnectedRead
BV219a_idfwarIndoor Fan statusRead
BV220a_impclTstat improper coolRead
BV221a_imphtTstat improper heatRead
BV222a_noignIGC ignition failureRead
BV223a_simhcTstat heat/cool callsRead
BV224a_t24encEcon not coolingRead
BV225a_t24eoaExcessive Outdoor airRead
BV226a_t24ewcEcon improper coolingRead
BV230f_idfoffIDF off when comand onRead
BV231f_idfonIDF on when comand offRead
BV235f_ronohtRollout without heatRead
BV236a_caldpCir.A Low DischargeRead
BV237a_notimeMBB Clock failureRead
BV241f_cstuckCompressor Stuck onRead
BV242f_fireFire ShutdownRead
BV243f_bad_ddSoftware ErrorRead
BV244a_genswGeneral StatusRead
BV245a_mbb0xMBB zero crossingRead
BV246a_mbb12dMBB Rnet voltage rangeRead
BV247a_mbb24dMBB 24vdc rangeRead
BV248a_mbb5dcMBB 5vdc rangeRead
BV264f_freezeFreeze protectionRead
BV265f_genswGeneral StatusRead
BV266f_hstuckRun away heat faultRead
BV267f_mbbeepMBB EEPROM FailureRead
BV268f_mbbf2MBB fuse 2 openRead
BV269f_mbbf3MBB fuse 3 openRead
BV270f_mbblovMBB low voltageRead
BV271f_mbbrefMBB reference voltageRead
BV272f_remoffRemote ShutdownRead
BV273f_cofsCondensate OverflowRead
BV274a_opnsrhSPRH open sensorRead
BV275a_shtsrhSPRH shorted sensorRead
BV276a_opnoacOACFM open sensorRead
BV277a_shtoacOACFM shorted sensorRead
BV278f_idflsmIDF Manual Limit TripRead
BV279f_phmonPhase Monitor TripRead
BV281s_ldv_aLiq Diverter Val Rly TstWrite
BV282s_rdv_aRht Dischg Valve Rly TstWrite
BV301mechcoolMechanical Cool active?Read
BV302okmechclOk to use compressors?Read
BV303perc_bacPercent Enable/DisableWrite
BV305hw_alHardware Failures AlertsWrite
BV306heat_alHeating Failure AlertsWrite
BV307co2s_alAir Quality CO2 AlertsWrite
BV308rhs_alRH sensor failure AlertRead
BV309gens_alGeneral Status AlertsWrite
BV310trans_alTransducer Sensor AlertsWrite
BV311sa_ra_alarmSAT/RAT Sensor AlertsWrite
BV312comp_alarmCompressor AlertsWrite
BV313circuit_alarmRefrig Circuit AlertsWrite
BV314oat_errorOAT Sensor ErrorWrite
BV317lc_lockLow cooling locked outRead
BV318mc_lockMedium Cooling lockoutRead
BV370heatdmdLimitHeatDemandLimitingWrite
BV371oacfm_rel_alarmOACFM Alarm RelayWrite
BV410sup_air_temp_enSupply Air Temper EnableWrite
BV415oktotempOK to SupplyAirTemperingRead
BV420oktofbdOk to fan based dehumRead
BV421oktohumzOk to use humidimizerRead
BV422oktodhumOk to Dehumidify?Read
BV423humctrlahumidity ctrl is activeRead
BV435cooldmdLimitCool Demand LimitingWrite
BV439fbdsatlofbdh sat locked outRead
BV440fbdsstloFBDH SST locked outRead
BV445iaq_override_enIAQ override enableWrite
BV449sdwn_a1Shutdown A1 FirstWrite
BV450sdwn_a2Shutdown A2 FirstWrite
BV451sdwn_aldShutdown Loader FirstWrite
BV452cmpa1_enIs comp A1 presentRead
BV453cmpa2_enIs comp A2 presentRead
BV454cmpal_enIs comp Loader presentRead
BV455s_rlv_aReheat Liq Valv Rly TestWrite
BV456s_clv_aCooling Liq Valv TestWrite
BV457s_erv2p2Position/ERV Relay TestWrite
BV469disldpalLow Discharge DiagnosticWrite
BV630doorswDoor Interlock SwitchWrite
BV631a_drlockDoor Interlock AlertRead
BV632fan_statFan Status SwitchWrite
BV1016flt_statusFilter Status SwitchWrite
BV1017w1_inputThermostat W1 InputWrite
BV1018w2_inputThermostat W2 InputWrite
BV1019y1_inputThermostat Y1 InputWrite
BV1020y2_inputThermostat Y2 InputWrite
BV1021g_inputThermostat G InputWrite
BV2008occ_statusCurrently OccupiedWrite
BV6000ofrOutdoor Fan RelayWrite
BV6001s_ofrspdODF Speed Relay TestWrite
BV6002erv_2pos2-Pos Damper/ERV relayWrite
BV7001space_errSPT Sensor ErrorWrite
BV7002stpt_errSPTO Sensor ErrorWrite
BV7008sfan_fail_alarmShut Down on IDF FailureWrite
BV7009sfan_hand_alarmIDF Speed Override FlagRead
BV7010humz_enHumidimizer StatusWrite
BV7011ldv_aLiquid Diverter Val CirAWrite
BV7012rdv_aReheat Dischg Valve CirAWrite
BV7013rdva_enReheat Dischg Valve CirARead
BV7014ldva_enLiquid Divert Valve CirARead
BV7017filter_alarmDirty Filter AlertsWrite
BV7028condensate_switchCOFS Switch StateWrite
BV7030iaqoverride_switchIAQ override sw stateWrite
BVmin7048equip_alarmAlarm Output Relay StateWrite
BV7049clva_enCooling Liq Valve CirARead
BV7050rlva_enReheat Liquid Valve CirARead
BV7051rlv_aReheat Liquid Valve CirAWrite
BV7052clv_aCooling Liq Valve CirAWrite
BV7053loambenLow Ambient EnableWrite
BV9001rem_shutRemote Shutdown SwitchWrite
BV9008s_ecocalEcon Damper CalibrationWrite
BV9009evacSmoke Evacuation SwitchWrite
BV9010pressureSmoke Pressure SwitchWrite
BV9011evacdampSmoke Evac with damperWrite
BV9076ofr2Outdoor Fan Relay 2Write
BV9077ofr3Outdoor Fan Relay 3Write
BV9080loamben2Low Ambient Enable2Write
BV9081s_ofr2ODF Relay2 TestWrite
BV9082s_ofr3ODF Relay3 TestWrite
BV9086IFM2OFENINDOOR MOTOR2 OFFSET ENWrite
BV9088zs_motionZS Motion SensorWrite
BV9090sprh_errSPRH Sensor ErrorWrite
BV9094occstdbyOccupiedStandBYWrite
BV9095leak_dtcleak detectionRead
BV9096f_leakdtLeak DetectionRead
BV9120loamben3Low Ambient Enable3Write
MV2control_typeUnit Control Type (1 to 3)Write
MV5tstat_typeThermostat Hardware Type (1 to 4)Write
MV6ventstatVentilation Status (1 to 10)Read
MV9colorOperation Status Color (1 to 16)Read
MV11bms_cfgBAS Protocol Select (1 to 3)Write
MVmin12bms_occBMS Occupancy Request (1 to 3)Write
MV13lnk_occLinkage Occupied Request (1 to 3)Write
MV14occ_ctrlActive Occupancy control (1 to 8)Read
MV16ht_typeType of Heat Installed (1 to 2)Write
MV18bac_baudBACnet BMS baud rate (1 to 6)Read
MV19fw_stateFirmware Release State (1 to 3)Read
MV24ufc_cfgWhen to Unocc Free Cool? (1 to 3)Write
MV25iaqancfgAnalog Input IAQ Control (1 to 4)Write
MV33rarh_channelRARH Assigned Channel (1 to 5)Write
MV41filter_channelFilter Status Sw Channel (1 to 8)Write
MV42filt_cfgFilter Status Swith Type (1 to 3)Write
MV43sub_modeRunning Mode Operation (1 to 35)Read
MV44bac_restBackup and Restore (1 to 3)Read
MV45rmoc_cfgRemote Occupancy Sw Type (1 to 3)Write
MV46rmocchanRemote Occupancy Channel (1 to 8)Write
MV47keepconfKeep configuration (1 to 3)Write
MV56cdlm_levelCool demand Limit Level (1 to 4)Write
MV57hdlm_levelHeat demand Limit Level (1 to 4)Write
MV58fbd_typeFan Based Dehum Type (1 to 3)Write
MV101sys_demand_enumSystem Demand (1 to 28)Read
MV156test_itoTest Inactivity Time Out (1 to 7)Write
MV365pe1_channelPE1 Relay Channel (1 to 3)Write
MV366pe2_channelPE2 Relay Channel (1 to 3)Write
MV370ocfmchanOACFM Assigned Channel (1 to 5)Write
MV372sprhchanSPRH Assigned Channel (1 to 5)Write
MV426oaq_channelOAQ Assigned Channel (1 to 5)Write
MV444iaqo_sw_chanIAQ override sw channel (1 to 8)Write
MV451fanstcfgFan Status SW Type (1 to 3)Write
MV453venttypeVentilation Method (1 to 5)Write
MV607iaq_channelIAQ Assigned Channel (1 to 5)Write
MV608oarh_channelOARH Assigned Channel (1 to 5)Write
MV629doorchanDoor Switch Channel (1 to 8)Write
MV1922zs_typeZS Sensor Type (1 to 6)Write
MVmin2002sys_modeSystem Mode (1 to 6)Read
MV2003sysvtypeComp. Framework (1 to 4)Write
MV2005odfctlODF.Control scheme (1 to 8)Write
MV9039cofschanCOFS Assigned Channel (1 to 8)Write
MV9040firechanFire Switch Channel (1 to 8)Write
MV9041humdchanHumidistat Status Chan. (1 to 8)Write
MV9042pmr_chanPhase Monitor Channel (1 to 8)Write
MV9043enthchanEnthalpy Sw Channel (1 to 8)Write
MV9044evacchanSmoke Evacuation Sw Chan (1 to 8)Write
MV9045fnstchanFan Status Channel (1 to 8)Write
MV9046gen_chanGeneral Status Channel (1 to 8)Write
MV9047preschanSmoke Pressure Sw Chan (1 to 8)Write
MV9048purgchanSmoke Purge Sw Channel (1 to 8)Write
MV9049roffchanRemote Shutdown Channel (1 to 8)Write
MV9050alm_chanALM Relay Assigned Chan (1 to 3)Write
MV9051cofs_cfgCOFS Switch Type (1 to 3)Write
MV9052fire_cfgFire Shutdown Sw Type (1 to 3)Write
MV9053humd_cfgHumidistat Switch Type (1 to 3)Write
MV9054pmr_cfgPhase Monitor SW Type (1 to 3)Write
MV9055enth_cfgEnthalpy Switch Type (1 to 3)Write
MV9056evac_cfgSmoke Evacuation Sw Type (1 to 3)Write
MV9057gens_cfgGeneral Status Sw Type (1 to 3)Write
MV9058iaqoscfgIAQ Override Switch Type (1 to 3)Write
MV9059pres_cfgSmoke Pressure Sw Type (1 to 3)Write
MV9060purg_cfgSmoke Purge Switch Type (1 to 3)Write
MV9061roff_cfgRemote Shutdown SW Type (1 to 3)Write
MV9075ervstatERV STATUS (1 to 3)Read
MV9077zsm_cfgZS motion sensor cfg (1 to 4)Write
MV9100door_cfgDoor Switch Type (1 to 3)Write
MV9116y3_chanY3 Thermostat Channel (1 to 8)Write
MV9117y3_cfgY3 Switch Type (1 to 3)Write
Object ID lookup: Carrier 48/50FE and 48/50GE Rooftop point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50FE and 48/50GE Rooftop (SystemVu) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Carrier 48/50FE and 48/50GE Rooftop (SystemVu)

How many BACnet points does the Carrier 48/50FE and 48/50GE Rooftop (SystemVu) have?

This list has 759 BACnet objects: 428 analog values, 262 binary values, 69 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Carrier 48/50FE and 48/50GE Rooftop (SystemVu) BACnet points are writable?

419 of the 759 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Carrier 48/50FE and 48/50GE Rooftop (SystemVu) BACnet documentation?

The source is 48/50FE 04-30, 48/50GE 04-28 Single Package Rooftop Units with SystemVu Controls Version 3.X, Controls, Start-Up, Operation and Troubleshooting (Appendix E: BACnet Points List) (SYSVU-FE-GE-02T), revision 2026-01, published free by Carrier at https://brandportal.carrier.com/asset/02984c32-006a-4445-8822-1aad575e945b/SYSVU-FE-GE-02T.pdf.

What are the minimum BACnet points to integrate the Carrier 48/50FE and 48/50GE Rooftop (SystemVu)?

Start with MV 12 bms_occ (Occupancy request from the BMS (unocc / occupied / disabled)); AV 288 ocsp (Occupied cooling setpoint); AV 289 ohsp (Occupied heating setpoint); BV 33 alarm_reset (Resets all current alarms); MV 2002 sys_mode (Current mode (off, cool, heat, vent, test)); AV 35 req_fan_spd (Indoor fan speed the control is calling for, %); AV 296 space_t (Space temperature); AV 1008 sa_temp (Supply air temperature); BV 7048 equip_alarm (Alarm output relay state); AV 335 num_active_faults (Count of active faults).

How do I enable BMS control of the Carrier 48/50FE and 48/50GE Rooftop (SystemVu)?

Set BAS Protocol Select to BACnet on the unit display (Settings > Network Settings > BAS Protocol; default None). With BACnet selected the local occupancy schedule is reset and scheduling comes from the BACnet side: a BACnet schedule, or the BMS Occupancy Request (MV 12; the display tables list Unocc, Occupied and Disabled). Unit Control Type (MV 2) decides whether the unit runs from thermostat inputs or a space sensor.

Does the Carrier 48/50FE and 48/50GE Rooftop (SystemVu) need a BACnet heartbeat or have a communication timeout?

Network Input Timeout (AV 9089, default 30 min per the display tables) applies to the network input values. The guide does not say what the unit does when it expires, so keep any written network value refreshed well inside that time.

Can the BMS supply sensor values to the Carrier 48/50FE and 48/50GE Rooftop (SystemVu)?

Writable network inputs exist for space temperature (Network Space Temp Value, AV 7006), outdoor air temperature (AV 7007), return air temperature (AV 7005), space RH (AV 376), outdoor RH (AV 7003), IAQ and OAQ CO2 (AV 7001, AV 7002) and OA cfm (AV 371). The guide doesn't explain how the unit picks a network value over a local sensor; check the sensor channel settings on the display. The 'BACnet device for ...' and 'Object instance for ...' AVs let the unit read a sensor from another BACnet device.

How do I check these points on the real 48/50FE and 48/50GE Rooftop (SystemVu)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Carrier BACnet points lists

Source: 48/50FE 04-30, 48/50GE 04-28 Single Package Rooftop Units with SystemVu Controls Version 3.X, Controls, Start-Up, Operation and Troubleshooting (Appendix E: BACnet Points List) · SYSVU-FE-GE-02T · rev. 2026-01. Object names, instances and units are reproduced as published; descriptions are our own.