- 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Air-cooled split condensing unit controller · BACnet points list
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) BACnet points list
Updated 6 November 2026
On 38APS/38APD condensing units the BACnet option is a UPC Open controller in the main control box. It talks BACnet MS/TP to the BMS and CCN to the unit's ComfortLink board. The list has about 150 objects: start/stop, emergency stop, demand limit, cooling setpoints, control mode and type, compressor and fan relays, circuit pressures and temperatures, run hours and starts, thermostat inputs and spare user values.
This page lists 149 BACnet objects for the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
- Equipment
- Air-cooled split condensing unit controller
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 149 (42 writable)
- Transport
- BACnet MS/TP
- Firmware
- ComfortLink v8
- Also known as
- 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Address the UPC Open on its rotary switches and set the BAS port DIP switches for MS/TP. Set the unit control method to CCN Control (CTRL=3); the BMS then starts and stops the unit with BV 4 chil_s_s_1 and can limit capacity with AV 2 dem_lim_1. Read the control mode (AV 8), capacity, circuit pressures and the comm alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 4 | chil_s_s_1 | Start/stop command (CCN control only) | Write |
| AV 2 | dem_lim_1 | Active demand limit, % | Write |
| AV 5 | ctrl_pnt_1 | Control point | Write |
| MV 5 | control_msv_1 | Control method: must be CCN for BMS start/stop | Read |
| AV 8 | stat | Control mode (6 = On CCN, 2 = Off CCN) | Read |
| AV 3 | cap_t_1 | Percent total capacity | Read |
| AV 1008 | sa_temp_1 | Supply air temperature | Read |
| MV 1 | alm_msv_1 | Alarm state: Normal, Alert or Alarm | Read |
| BV 58 | comm_lost_alm | UPC Open lost CCN communication with the unit | Read |
Enable & remote start
Set the control method to CCN Control (Configuration > OPT2 > CTRL = 3); the manual says units run by a third-party BAS through the UPC Open must use it. The unit switch must be in Enable, or in Remote Control with the external contacts closed. The BMS then writes CHIL_S_S Start/Stop; EMSTOP (BV 6) stops all cooling until set back to Enable.
Heartbeat & communication loss
The manual says loss of CCN communication puts the unit in stand-alone mode. BV 58 comm_lost_alm and BV 2999 element_stat_1 show the UPC Open link to the unit.
Sensors & values from the BMS
Outside Air Temperature (AV 1003) and Space Temperature (AV 2007) are writable; the space temperature is used with the SPT control types.
Network setup
- Set the MAC address on the UPC Open Tens and Ones rotary switches; it reads switches, DIP switches and jumpers only at power-up.
- Device instance = network number (default 16101) followed by the MAC address, e.g. MAC 20 gives 1610120.
- BAS port: DS3 enable, DS4 E1-485, DS5-DS8 set to MSTP; baud on DS1-DS2 (9600, 19.2k, 38.4k or 76.8k, Carrier default 76.8k); 8N1 fixed. EIA-485 jumpers to EIA-485 and 2W.
- Fit a BT485 terminator on the first and last controller of the MS/TP segment.
- The UPC Open and the ComfortLink board must use the same CCN element and bus numbers (factory 1 and 0).
Watch out for
- Start/stop over BACnet only works with the control method set to CCN; monitoring alone does not need it.
- Points depend on unit size and options (number of compressors and fans, head pressure control, digital compressor).
- Thermostat inputs Y1-Y4 are read-only in this list.
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 6 | cool_ma_1 | 4-20 Cooling Demand (range 0-20) | mA | Read | |
| AV | 36 | lmt_ma_1 | 4-20 mA Demand Signal (range 0-20) | mA | Read | |
| AV | 33 | rst_ma_1 | 4-20 mA Reset Signal (range 0-20) | mA | Read | |
| AVmin | 2 | dem_lim_1 | Active Demand Limit (range 0-100) | % | Write | |
| AV | 4 | sp_1 | Active Setpoint (range -20-70) | °F | Read | |
| MVmin | 1 | alm_msv_1 | Alarm State (multistate copy of a CCN point for i-Vu/BACnet) | Read | 0=Normal, 1=Alert, 2=Alarm | |
| BVmin | 4 | chil_s_s_1 | CCN Chiller | Write | 0=Stop, 1=Start | |
| AV | 37 | dl_stat_1 | CCN Loadshed Signal (range 0-2) | Read | ||
| AV | 59 | hr_cira_1 | Circuit A Run Hours (range 0-9999) | hr | Read | |
| AV | 67 | cy_cira_1 | Circuit A Starts (range 0-9999) | Read | ||
| AV | 63 | hr_cirb_1 | Circuit B Run Hours (range 0-9999) | hr | Read | |
| AV | 71 | cy_cirb_1 | Circuit B Starts (range 0-9999) | Read | ||
| BV | 54 | cl_maint_1 | Coil Cleaning Maint.Done | Write | 0=No, 1=Yes | |
| AV | 50 | si_coil_1 | Coil Cleaning Srvc Inter (range 0-9999) | hr | Write | |
| AV | 49 | cl_cdown_1 | Coil Service Countdown (range 0-9999) | hr | Read | |
| AV | 34 | digitalp_1 | Comp A1 Load Percent (range 0-100) | % | Read | |
| AV | 20 | rgta_1 | Compr Return Gas Temp (range 0-125) | °F | Read | |
| AV | 28 | rgtb_1 | Compr Return Gas Temp (range 0-125) | °F | Read | |
| BV | 16 | k_a1_fbk_1 | Compressor A1 Feedback | Read | 0=Off, 1=On | |
| BV | 13 | k_a1_rly_1 | Compressor A1 Relay | Read | 0=Off, 1=On | |
| AV | 60 | hr_a1_1 | Compressor A1 Run Hours (range 0-9999) | hr | Read | |
| AV | 68 | cy_a1_1 | Compressor A1 Starts (range 0-9999) | Read | ||
| BV | 17 | k_a2_fbk_1 | Compressor A2 Feedback | Read | 0=Off, 1=On | |
| BV | 14 | k_a2_rly_1 | Compressor A2 Relay | Read | 0=Off, 1=On | |
| AV | 61 | hr_a2_1 | Compressor A2 Run Hours (range 0-9999) | hr | Read | |
| AV | 69 | cy_a2_1 | Compressor A2 Starts (range 0-9999) | Read | ||
| BV | 18 | k_a3_fbk_1 | Compressor A3 Feedback | Read | 0=Off, 1=On | |
| BV | 15 | k_a3_rly_1 | Compressor A3 Relay | Read | 0=Off, 1=On | |
| AV | 62 | hr_a3_1 | Compressor A3 Run Hours (range 0-9999) | hr | Read | |
| AV | 70 | cy_a3_1 | Compressor A3 Starts (range 0-9999) | Read | ||
| BV | 22 | k_b1_fbk_1 | Compressor B1 Feedback | Read | 0=Off, 1=On | |
| BV | 19 | k_b1_rly_1 | Compressor B1 Relay | Read | 0=Off, 1=On | |
| AV | 64 | hr_b1_1 | Compressor B1 Run Hours (range 0-9999) | hr | Read | |
| AV | 72 | cy_b1_1 | Compressor B1 Starts (range 0-9999) | Read | ||
| BV | 23 | k_b2_fbk_1 | Compressor B2 Feedback | Read | 0=Off, 1=On | |
| BV | 20 | k_b2_rly_1 | Compressor B2 Relay | Read | 0=Off, 1=On | |
| AV | 65 | hr_b2_1 | Compressor B2 Run Hours (range 0-9999) | hr | Read | |
| AV | 73 | cy_b2_1 | Compressor B2 Starts (range 0-9999) | Read | ||
| BV | 24 | k_b3_fbk_1 | Compressor B3 Feedback | Read | 0=Off, 1=On | |
| BV | 21 | k_b3_rly_1 | Compressor B3 Relay | Read | 0=Off, 1=On | |
| AV | 66 | hr_b3_1 | Compressor B3 Run Hours (range 0-9999) | hr | Read | |
| AV | 74 | cy_b3_1 | Compressor B3 Starts (range 0-9999) | Read | ||
| MVmin | 5 | control_msv_1 | Control Method (multistate copy of a CCN point for i-Vu/BACnet) | Read | 0=Switch, 1=Occupancy, 2=CCN | |
| AVmin | 8 | stat | Control Mode | Read | 0=Test, 1=Local Off, 2=CCN Off, 3=Clock Off, 4=Emergency Stop, 5=Local On, 6=CCN On, 7=Clock On, 8=IDF Off, 9=SPT SATS | |
| AVmin | 5 | ctrl_pnt_1 | Control Point (range -20-70) | °F | Write | |
| AV | 9006 | cool_demand_level_1 | Cooling Demand Level (range 0-3) | Read | ||
| AV | 56 | cramp_1 | Cooling Ramp Loading (range 0.2-2.0) | °F | Write | |
| MV | 7 | crst_typ1_msv_1 | Cooling Reset Type (multistate copy of a CCN point for i-Vu/BACnet) | Read | 0=No Reset, 1=4-20 mA Input, 2=Outdoor Air Temp, 3=Return Temperature, 4=Space Temperature | |
| AV | 53 | csp1_1 | Cooling Setpoint 1 (range -20-70) | °F | Write | |
| AV | 54 | csp2_1 | Cooling Setpoint 2 (range -20-70) | °F | Write | |
| AV | 80 | dmv_lvl_1_perct | Demand Level 1 (range 0-100) | Write | ||
| AV | 81 | dmv_lvl_2_perct | Demand Level 2 (range 0-100) | Write | ||
| AV | 82 | dmv_lvl_3_perct | Demand Level 3 (range 0-100) | Write | ||
| MV | 8 | dmd_ctrl_msv_1 | Demand Limit Select (multistate copy of a CCN point for i-Vu/BACnet) | Read | 0=None, 1=Ext. Sw. Input, 2=4-20 mA Input, 3=CCN Loadshed | |
| BV | 25 | dmd_sw1_1 | Demand Limit Switch 1 | Read | 0=Off, 1=On | |
| BV | 26 | dmd_sw2_1 | Demand Limit Switch 2 | Read | 0=Off, 1=On | |
| BV | 41 | mode_15_1 | Demand/Sound Limited | Read | 0=Off, 1=On | |
| AV | 7 | digcmpdt_1 | Discharge Gas Temp (range -40-245) | °F | Read | |
| AV | 13 | dp_a_1 | Discharge Pressure (range 0-999) | psig | Read | |
| AV | 23 | dp_b_1 | Discharge Pressure (range 0-999) | psig | Read | |
| BVmin | 58 | comm_lost_alm | Element Communications Alarm (BALM) | Read | 0=Comm Normal, 1=Comm Alarm | |
| BV | 2999 | element_stat_1 | Element Comm Status | Read | 0=No Comm, 1=Normal | |
| BV | 6 | emstop_1 | Emergency Stop | Write | 0=Enable, 1=Emstop | |
| BV | 60 | fan_1_1 | Fan 1 Relay | Read | 0=Off, 1=On | |
| BV | 61 | fan_2_1 | Fan 2 Relay | Read | 0=Off, 1=On | |
| BV | 62 | fan_3_1 | Fan 3 Relay | Read | 0=Off, 1=On | |
| BV | 63 | fan_4_1 | Fan 4 Relay | Read | 0=Off, 1=On | |
| BV | 64 | fan_5_1 | Fan 5 Relay | Read | 0=Off, 1=On | |
| AV | 10 | fandlttm_1 | Fan Delta Active Time (range 0-999) | sec | Write | |
| AV | 35 | fanstgea_1 | Fan Stage Circuit A (range 0-999) | sec | Read | |
| AV | 15 | fanstgeb_1 | Fan Stage Circuit B (range 0-999) | sec | Read | |
| AV | 16 | hsp_off_1 | Head Set Point OFF (range 0-150) | °F | Write | |
| AV | 18 | hsp_on_1 | Head Set Point ON (range 0-150) | °F | Write | |
| AV | 25 | dmdhcon_1 | Hi Cool On Set Point (range 0.5-20) | °F | Write | |
| BV | 47 | mode_21_1 | High SCT Circuit A | Read | 0=Off, 1=On | |
| BV | 48 | mode_22_1 | High SCT Circuit B | Read | 0=Off, 1=On | |
| BV | 44 | mode_18_1 | High Temperature Cooling | Read | 0=Off, 1=On | |
| BV | 2 | idfa_fs_1 | Indoor Fan Status-CIRA | Read | 0=Off, 1=On | |
| BV | 3 | idfb_fs_1 | Indoor Fan Status-CIRB | Read | 0=Off, 1=On | |
| AV | 43 | lead_typ_1 | Lead/Lag Circuit Select | Write | 1=Automatic, 2=Circuit A Leads, 3=Circuit B Leads | |
| BV | 8 | llsv_a_1 | Liquid Line Solenoid A | Read | 0=Off, 1=On | |
| BV | 9 | llsv_b_1 | Liquid Line Solenoid B | Read | 0=Off, 1=On | |
| AV | 30 | dmdlcoff_1 | Lo Cool Off Set Point (range 0.5-2) | °F | Write | |
| AV | 31 | dmdlcon_1 | Lo Cool On Set Point (range -1-2) | °F | Write | |
| AV | 77 | seq_type_1 | Loading Sequence Select (range 1-2) | Write | ||
| BV | 51 | mode_25_1 | Low Sound Mode | Read | 0=Off, 1=On | |
| BV | 43 | mode_17_1 | Low Temperature Cooling | Read | 0=Off, 1=On | |
| MV | 3 | ctrltype_msv_1 | Machine Control Type (multistate copy of a CCN point for i-Vu/BACnet) | Read | 1=VAV, 2=Invalid, 3=Tstat Multi, 4=Tstat 2 Stg, 5=SPT Multi, 6=Invalid, 7=PCT Cap, 8=Dual Tsat, 9=VAV Setpoint | |
| AV | 57 | mr_mach_1 | Machine Operating Hours (range 0-9999) | hr | Read | |
| AV | 58 | cy_mach_1 | Machine Starts (range 0-9999) | Read | ||
| BV | 49 | mode_23_1 | Minimum Comp. On Time | Read | 0=Off, 1=On | |
| BV | 79 | mlv_rly_1 | Minimum Load Valve Relay | Read | 0=Off, 1=On | |
| BV | 38 | mode_10_1 | Minimum OFF time active | Read | 0=Off, 1=On | |
| AV | 32 | min_left_1 | Minutes Left for Start (range 00:00-15:00) | min | Read | |
| AV | 42 | delay_1 | Minutes Off Time (range 0-15) | min | Write | |
| BV | 2008 | occ_status_1 | Occupied | Read | 0=No, 1=Yes | |
| AV | 1003 | oa_temp | Outside Air Temperature (range -40-245) | °F | Write | |
| BV | 5 | mode_1 | Override Modes in Effect | Read | 0=No, 1=Yes | |
| AV | 12 | capa_a_1 | Percent Available Cap. (range 0-100) | % | Read | |
| AV | 22 | capb_a_1 | Percent Available Cap. (range 0-100) | % | Read | |
| AVmin | 3 | cap_t_1 | Percent Total Capacity (range 0-100) | % | Read | |
| AV | 11 | capa_t_1 | Percent Total Capacity (range 0-100) | % | Read | |
| AV | 21 | capb_t_1 | Percent Total Capacity (range 0-100) | % | Read | |
| BV | 33 | mode_5_1 | Ramp Load Limited | Read | 0=Off, 1=On | |
| AV | 9 | stage_1 | Requested Stage (range 0-99) | Read | ||
| AV | 1010 | ra_temp_1 | Return Air Temperature (range 0-125) | °F | Read | |
| AV | 40 | scta_1 | Saturated Condensing Tmp (range -40-245) | °F | Read | |
| AV | 39 | sctb_1 | Saturated Condensing Tmp (range -40-245) | °F | Read | |
| AV | 17 | ssta_1 | Saturated Suction Temp (range -40-245) | °F | Read | |
| AV | 26 | sstb_1 | Saturated Suction Temp (range -40-245) | °F | Read | |
| AV | 41 | a1sctdt_1 | SCT Delta for Compressor A1 (range 0-99) | °F | Write | |
| AV | 46 | a2sctdt_1 | SCT Delta for Compressor A2 (range 0-99) | °F | Write | |
| AV | 47 | b1sctdt_1 | SCT Delta for Compressor B1 (range 0-99) | °F | Write | |
| AV | 48 | b2sctdt_1 | SCT Delta for Compressor B2 (range 0-99) | °F | Write | |
| BV | 37 | mode_9_1 | Slow Change Override | Read | 0=Off, 1=On | |
| AV | 51 | spt_sp_1 | Space T Cool Set Point (range 0-999) | °F | Write | |
| AV | 76 | spsp_po_1 | Space T SP Plus Offset (range 0-999) | °F | Write | |
| AV | 52 | sptmode_1 | Space Temp Control Mode | Read | 0=Cool Off, 1=Lo Cool, 2=Hi Cool, 3=Cool On | |
| AV | 2007 | space_temp | Space Temperature (range 0-999) | °F | Write | |
| AV | 55 | spto_1 | Space Temperature Offset (range 0-99) | °F | Write | |
| BV | 10 | sptosens_1 | Space Temperature Offset Enable | Write | 0=Disable, 1=Enable | |
| AV | 75 | spto_rng_1 | Space Temperature Offset Range (range -20-99) | °F | Write | |
| BV | 11 | sptsens_1 | Space Temperature Sensor | Read | 0=Disable, 1=Enable | |
| AV | 14 | sp_a_1 | Suction Pressure (range 0-999) | psig | Read | |
| AV | 24 | sp_b_1 | Suction Pressure (range 0-999) | psig | Read | |
| AV | 44 | sh_a_1 | Suction Superheat Temperature (range -40-245) | °F | Read | |
| AV | 45 | sh_b_1 | Suction Superheat Temperature (range -40-245) | °F | Read | |
| AV | 78 | sat_sp_1 | Supply Air Set Point (range 0-125) | °F | Read | |
| AVmin | 1008 | sa_temp_1 | Supply Air Temperature (range -40-245) | °F | Read | |
| BV | 83 | dem_lmt_act_1 | System Demand Limiting | Read | 0=Inactive, 1=Active | |
| BV | 40 | mode_14_1 | Temperature Reset | Read | 0=Off, 1=On | |
| BV | 67 | mode_tg_1 | Time Guard Active | Read | 0=Off, 1=On | |
| BV | 34 | mode_6_1 | Timed Override in effect | Read | 0=Off, 1=On | |
| AV | 2901 | user_analog_1_1 | User Defined Analog 1 | Write | ||
| AV | 2902 | user_analog_2_1 | User Defined Analog 2 | Write | ||
| AV | 2903 | user_analog_3_1 | User Defined Analog 3 | Write | ||
| AV | 2904 | user_analog_4_1 | User Defined Analog 4 | Write | ||
| AV | 2905 | user_analog_5_1 | User Defined Analog 5 | Write | ||
| BV | 2911 | user_binary_1_1 | User Defined Binary 1 | Write | 0=Off, 1=On | |
| BV | 2912 | user_binary_2_1 | User Defined Binary 2 | Write | 0=Off, 1=On | |
| BV | 2913 | user_binary_3_1 | User Defined Binary 3 | Write | 0=Off, 1=On | |
| BV | 2914 | user_binary_4_1 | User Defined Binary 4 | Write | 0=Off, 1=On | |
| BV | 2915 | user_binary_5_1 | User Defined Binary 5 | Write | 0=Off, 1=On | |
| AV | 19 | vhpa_act_1 | Var Head Press Output Circuit A (range 0-100) | % | Read | |
| AV | 83 | vhpb_act_1 | Var Head Press Output Circuit B (range 0-100) | % | Read | |
| BV | 27 | y1_1 | Y1 Thermostat Input | Read | 0=Off, 1=On | |
| BV | 28 | y2_1 | Y2 Thermostat Input | Read | 0=Off, 1=On | |
| BV | 29 | y3_1 | Y3 Thermostat Input | Read | 0=Off, 1=On | |
| BV | 30 | y4_1 | Y4 Thermostat Input | Read | 0=Off, 1=On |
No points match these filters.
Object ID lookup: Carrier 38APS/38APD Condensing Unit point IDs by name
AV6cool_ma_1AV36lmt_ma_1AV33rst_ma_1AV2dem_lim_1AV4sp_1MV1alm_msv_1BV4chil_s_s_1AV37dl_stat_1AV59hr_cira_1AV67cy_cira_1AV63hr_cirb_1AV71cy_cirb_1BV54cl_maint_1AV50si_coil_1AV49cl_cdown_1AV34digitalp_1AV20rgta_1AV28rgtb_1BV16k_a1_fbk_1BV13k_a1_rly_1AV60hr_a1_1AV68cy_a1_1BV17k_a2_fbk_1BV14k_a2_rly_1AV61hr_a2_1AV69cy_a2_1BV18k_a3_fbk_1BV15k_a3_rly_1AV62hr_a3_1AV70cy_a3_1BV22k_b1_fbk_1BV19k_b1_rly_1AV64hr_b1_1AV72cy_b1_1BV23k_b2_fbk_1BV20k_b2_rly_1AV65hr_b2_1AV73cy_b2_1BV24k_b3_fbk_1BV21k_b3_rly_1AV66hr_b3_1AV74cy_b3_1MV5control_msv_1AV8statAV5ctrl_pnt_1AV9006cool_demand_level_1AV56cramp_1MV7crst_typ1_msv_1AV53csp1_1AV54csp2_1AV80dmv_lvl_1_perctAV81dmv_lvl_2_perctAV82dmv_lvl_3_perctMV8dmd_ctrl_msv_1BV25dmd_sw1_1BV26dmd_sw2_1BV41mode_15_1AV7digcmpdt_1AV13dp_a_1AV23dp_b_1BV58comm_lost_almBV2999element_stat_1BV6emstop_1BV60fan_1_1BV61fan_2_1BV62fan_3_1BV63fan_4_1BV64fan_5_1AV10fandlttm_1AV35fanstgea_1AV15fanstgeb_1AV16hsp_off_1AV18hsp_on_1AV25dmdhcon_1BV47mode_21_1BV48mode_22_1BV44mode_18_1BV2idfa_fs_1BV3idfb_fs_1AV43lead_typ_1BV8llsv_a_1BV9llsv_b_1AV30dmdlcoff_1AV31dmdlcon_1AV77seq_type_1BV51mode_25_1BV43mode_17_1MV3ctrltype_msv_1AV57mr_mach_1AV58cy_mach_1BV49mode_23_1BV79mlv_rly_1BV38mode_10_1AV32min_left_1AV42delay_1BV2008occ_status_1AV1003oa_tempBV5mode_1AV12capa_a_1AV22capb_a_1AV3cap_t_1AV11capa_t_1AV21capb_t_1BV33mode_5_1AV9stage_1AV1010ra_temp_1AV40scta_1AV39sctb_1AV17ssta_1AV26sstb_1AV41a1sctdt_1AV46a2sctdt_1AV47b1sctdt_1AV48b2sctdt_1BV37mode_9_1AV51spt_sp_1AV76spsp_po_1AV52sptmode_1AV2007space_tempAV55spto_1BV10sptosens_1AV75spto_rng_1BV11sptsens_1AV14sp_a_1AV24sp_b_1AV44sh_a_1AV45sh_b_1AV78sat_sp_1AV1008sa_temp_1BV83dem_lmt_act_1BV40mode_14_1BV67mode_tg_1BV34mode_6_1AV2901user_analog_1_1AV2902user_analog_2_1AV2903user_analog_3_1AV2904user_analog_4_1AV2905user_analog_5_1BV2911user_binary_1_1BV2912user_binary_2_1BV2913user_binary_3_1BV2914user_binary_4_1BV2915user_binary_5_1AV19vhpa_act_1AV83vhpb_act_1BV27y1_1BV28y2_1BV29y3_1BV30y4_1
Integration notes
- Object names end in _1, except a few printed without it (stat, oa_temp, space_temp, comm_lost_alm).
- Multistate objects (MSV) are copies of CCN points made for i-Vu and BACnet; their state numbers are printed from 0, so the device may report them +1 (BACnet multistate values start at 1). Check by discovery.
- Binary states are shown as 0/1 from the printed ON_OFF, YES_NO and ENA_DIS ranges. Numeric ranges are added to descriptions.
- Rows appear for both circuits (A and B) with the same description; the object name tells them apart.
- The 5 user-defined analog and 5 binary values are spare objects with no unit function.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
How many BACnet points does the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) have?
This list has 149 BACnet objects: 88 analog values, 56 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) BACnet points are writable?
42 of the 149 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) BACnet documentation?
The source is 38APS/38APD 025-130 Air-Cooled Condensing Units with ComfortLink Controls Version 8 - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix C, Table G Network Points List) (38AP-3T), revision 2022-08 (Rev A), published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/02/38AP-3T.pdf.
What are the minimum BACnet points to integrate the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)?
Start with BV 4 chil_s_s_1 (Start/stop command (CCN control only)); AV 2 dem_lim_1 (Active demand limit, %); AV 5 ctrl_pnt_1 (Control point); MV 5 control_msv_1 (Control method: must be CCN for BMS start/stop); AV 8 stat (Control mode (6 = On CCN, 2 = Off CCN)); AV 3 cap_t_1 (Percent total capacity); AV 1008 sa_temp_1 (Supply air temperature); MV 1 alm_msv_1 (Alarm state: Normal, Alert or Alarm); BV 58 comm_lost_alm (UPC Open lost CCN communication with the unit).
How do I enable BMS control of the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)?
Set the control method to CCN Control (Configuration > OPT2 > CTRL = 3); the manual says units run by a third-party BAS through the UPC Open must use it. The unit switch must be in Enable, or in Remote Control with the external contacts closed. The BMS then writes CHIL_S_S Start/Stop; EMSTOP (BV 6) stops all cooling until set back to Enable.
Does the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option) need a BACnet heartbeat or have a communication timeout?
The manual says loss of CCN communication puts the unit in stand-alone mode. BV 58 comm_lost_alm and BV 2999 element_stat_1 show the UPC Open link to the unit.
Can the BMS supply sensor values to the Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)?
Outside Air Temperature (AV 1003) and Space Temperature (AV 2007) are writable; the space temperature is used with the SPT control types.
How do I check these points on the real 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: 38APS/38APD 025-130 Air-Cooled Condensing Units with ComfortLink Controls Version 8 - Controls, Start-Up, Operation, Service and Troubleshooting (Appendix C, Table G Network Points List) · 38AP-3T · rev. 2022-08 (Rev A). Object names, instances and units are reproduced as published; descriptions are our own.